Loading...
HomeMy WebLinkAboutE16-0257 load calc.pdf ----- ( 6) - 6 1170 BLUE SAGE DRIVE STEAMBOAT SPRINGS.CO 80487 WILDER ENGINEERING T:970 819 7848 INC S DESIGN WILDER-ENC COM Client Name: J H Construction Project Name: Timber Falls Condo Remodel Unit#906 Project No: 201717 Date: February 3,2017 4524 Meadow Dr.$906 SQ.FT. I 1395 VA/S.F.OR QTY. VA TOTAL NOTES GENERAL LIGHTING LOAD GENERAL LIGHTING 3 4,185 4,185 Per NEC 220.12 SMALL APPLIANCE 2 1,500 3,000 Per NEC 220.52.A LAUNDRY 1 1,500 1,500 Per NEC 220.52.8 TOTAL 8,685 DEMAND FACTOR NOTES 3000 VA @ 100% 3000 Per NEC 220.42 3001 VA TO 120,000 VA @ 35% 1990 Per NEC 220.42 REMAINDER OVER 120,000 VA©25% 0 Per NEC 220.42 TOTAL 4,990 APPLIANCE LOADS Per NEC 220.53 REFRIGERATOR 1 1,200 1,200 DISHWASHER 1 1,200 1,200 DISPOSAL 1 986 986 MICROWAVE 1 1,200 1,200 HOOD 1 250 250 WATER HEATER 1 2,000 2,000 TOTAL 6,836 DEMAND FACTOR NOTES 75%OF APPLIANCE LOAD 5127 Per NEC 220.53 TOTAL 5,127 APPLIANCE LOADS @ 100% DRYER 1 5.000 5.000 Per NEC 220.54 RANGE 1 8,000 8,000 Per NEC 220.55 TOTAL 13,000 UNIT TOTAL 23,117 I 96 AMPS @ 240V,1-PH o��p-- ---DO /.te4., ill iQ 490„ ..,,,,;d.08 o;' g. 1„1,\ONAL E_-