HomeMy WebLinkAboutAssembly HW D -312.pdfSystem No. HW-D-0312 Assembly Ratings -2 and 3 Hr (See Item 38) Nominal Joint Width -1 in. 111 111 11111 Class II Movement Capabilities -12.5 % Compression or Extension L Rating At Ambient -Less Than 1 CFM/Lin Ft L Rating At 400 F -Less Than 1 CFM/Lin Ft 1 ":i II' II' '<l '<l II'. .q I? II' '<;] 1. Floor Assembly -Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) structural concrete. 2. Wall Assembly-Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) structural concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers. 3. Joint System -Max separation between bottom of floor and top of wall (at time of installation of joint system) is 1 in. (25 mm). The joint system is designed to accommodate a max 12.5 percent compression or extension from its installed width. The joint system shall consist of the following: ~ ---== --- STI A. Packing Material -Open or closed cell polyethylene or polyurethane foam backer rod used as a form to prevent the leakage of fill material. Packing material to be recessed from both surfaces of the wall to accommodate the required thickness of fill material. B. Fill, Void or Cavity Material* -Sealant -Fill material applied within the joint, flush with both surfaces of wall. Min 1/2 in. (13 mm) thickness required for 2 hr assembly rating. Min 1-1/2 in. (38 mm) thickness required for 3 hr assembly rating. SPECIFIED TECHNOLOGIES INC -Pensil 300 Sealant or SpecSeal Series SIL300 Sealant *Bearing the UL Classification Mark Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 Reproduced courtesy of Underwriters Laboratories, Inc. Created or Revised: November 26, 2008 (800)992-1180 • (908)526-8000 •FAX (908)231-8415 • E-Mail:techserv@stifirestop.com • Website:www.stifirestop.com ®HW-0-0312 PAGE 1OF1