HomeMy WebLinkAboutB16-0092_A1.0_1478906445.pdfRADON MITIGATION SYSTEM
CONNECT TO EXISTING RADON MITIGATION SYSTEM.
PROVIDE DESIGN-BUILD ENGINEERING AND CONSTRUCTION OF A PASSIVE RADON MITIGATION SYSTEM FOR THE PROJECT TO WHICH AN
INLINE FAN COULD BE ADDED LATER IF REQUIRED PER THE FOLLOWING CRITERIA AND AS REQUIRED TO MAINTAIN RADON LEVELS AT THE
MECHANICAL ROOM, LOWER LEVEL AND HOUSE BELOW EPA AND OTHER GOVERNMENT STANDARDS. THE RADON MITIGATION
SUBCONTRACTOR WILL BE RESPONSIBLE FOR COORDINATING HIS WORK WITH THE VAPOR BARRIER INSTALLATION AND THE ELECTRICIAN FOR
AN ELECTRICAL JUNCTION BOXES AT THE LOCATIONS DETERMINED BY THE RADON MITIGATION SUBCONTRACTOR FOR THE POTENTIAL FUTURE
FANS.
AT A MINIMUM, THE FOLLOWING SYSTEMS/SERVICES WILL BE PROVIDED AS PART OF THE BASE BID BY THE RADON MITIGATION SUB
CONTRACTOR.
- SEALING OF THE LOWER LEVEL CONCRETE SLAB TO THE FOUNDATION WALLS
- SEALING OF ALL PLUMBING AND OTHER PENETRATIONS THROUGH THE CONCRETE SLABS AND THROUGH THE BELOW GRADE PORTIONS OF
THE FOUNDATION WALL
- LOCATIONS & INSTALLATION OF PIPES, PORTS, AND OPENINGS IN THE SLAB FOR SLAB DEPRESSURIZATION SYSTEM.
- PROVIDE PASSIVE VENT PIPE SYSTEM WHICH RUNS FROM THE SLAB PENETRATION LOCATIONS(S) TO THE OUTSIDE IN ACCORDANCE WITH
THE EPA STANDARDS. THE VENTS SHALL BE RUN WITHIN THE INTERIOR OR EXTERIOR WALLS TO A LOCATION(S) HIGH ON THE ROOF.
COORDINATE VENT LOCATIONS WITH ARCHITECT AND/OR OWNER
- PROVIDE POWER ADJACENT TO SLAB VENT PENETRATIONS FOR POTENTIAL FUTURE INLINE FAN LOCATION INCLUDING ALL REQUIRED ROUGH
IN WIRING AND JUNCTION BOXES, IN THE EVENT THAT A FAN IS REQUIRED TO BE INSTALLED
- PROVIDE PROVISIONS FOR A SYSTEM FAILURE INDICATOR, INCLUDING ALL REQUIRED ROUGH-IN WIRING, AND JUNCTION BOXES, IN THE
EVENT THAT A FAN IS REQUIRED TO BE INSTALLED.
- PERFORM RADON TESTING AFTER THE HOME/PASSIVE SYSTEM IS COMPLETE TO DETERMINE IF THE HOME PASSES OR IF AN ACTIVE
SYSTEM IS REQUIRED IN ORDER TO MAINTAIN RADON BELOW EPA AND OTHER GOVERNMENTAL STANDARDS.
- IF AN ACTIVE SYSTEM IS REQUIRED, PERFORM FOLLOW UP RADON TESTING AFTER THE SYSTEM IS COMPLETE TO DETERMINE IF RADON
HAS BEEN MITIGATED
- PROVIDE AND INLINE FAN IF ACTIVE SYSTEM IS REQUIRED. PROVIDE OTHER EQUIPMENT AND SYSTEM AS REQUIRED TO PROVIDE A
FUNCTIONAL RADON MITIGATION SYSTEM FOR THE UNITS.
CONTRACTOR TO COORDINATE INSTALLATION OF THE 10 MIL VAPOR BARRIER UNDER THE SLAB INCUDING THE SEALING OF ALL JOINTS, ALL
PLUMBING OR MECHANICAL OR OTHER PENETRATIONS AND THE SEALING AND MECHANICAL FASTENING OF THE VAPOR BARRIER TO THE
EXTERIOR CONCRETE FOUNDATION WALLS.
RE: OUTLINE SPEC FOR MORE DETAILS
Scale
Date
Drawn by
Checked by
US Mail Only: P. O. Box 2378
Physical / Fedex: 210 Edwards
Village Blvd, Bldg A Suite A103
Edwards, Colorado 81632-2378
(970) 926 4301, Fax: 926 4364
hans@berglundarchitects.com
www . berglundarchitects.com
4
1
A5.1
A
3.2
PROJECT DIRECTORY
1
2
3
4
A9.1
A6.1
1
A6.1
1
100
LIVING
1
A4.1
SIM.
SYMBOL LEGEND
ABBREVIATIONS
MATERIAL LEGEND
DRAWING LIST:
VICINITY MAP
100
A
BUILDING
SECTION NO.
SECTION CUT
SHEET NO.
DETAIL NO.
DETAIL CUT
SHEET NO.
ROOM NUMBER
EXTERIOR ELEVATION
DOOR MARK
DETAIL CUT
REFERENCE GRID LINE
SPOT ELEVATION
DRAWING REVISION
INTERIOR ELEVATION
WINDOW MARK
Galvanized
Laminated Wood Beam
General Contractor
Hardware
Gypsum Wallboard
Grade
Gypsum
RW
RO
SEW
SECT
SAN
SHLV
Cpt Carpet
Ceramic
CER
SIM
SHT
W/
Reinforce (d)
REINF
FD Floor Drain
With (comb. form)
Required
Round Head Sheet Metal Screw
GA
FDN
FTG
Room
RM
RHSM
REQD
Gauge
Foundation
Footing
WD
W/O
Wood
Without
and Air Conditioning
Heating, Ventilating,
Lavatory
Manufacturer
Laminate
Inside Diameter
Miscellaneous
Mechanical
Not In Contract
Medicine Cabinet
Masonry Opening
Horizontal
On Center
Not to Scale
Oriented Strand Board
Opposite
Outside Diameter
Property
Plywood
Perforated (d)
Prefinished Sheet Metal
Penny (nails, etc.)
Refrigerator
Radius or Riser
Not Applicable
AAD
ADD
AGG
ADJ
AOR
BM
ARCH
ALT
BD
BS
BET
BRG
AFF
CL
BLDG
CAB
CLOS
CMU
CJ
CONC
COL
DP
DIA
DET
CONT
BO
DR
DN
DW
EL
EA
DRWG
DS
EQ
EJ
EXIST
EXT
FE CABT
FOC
FOS
FP
FL
FIN
DIM
GC
GALV
Glass
GLB
GR
GL
Head
HD
HDW
GWB
Highway
Height
HWY
HT
HVAC
GYP
Addendum
Attic Access Door
Aggregate
Adjacent
Area of Refuge
Alternate
Beam
Architectural
Board
Between
Both Sides
Bearing
Above Finished Floor
Interior
Joint
JT
INT
ID
MO
MFG
LAV
LAM
Maximum
Material
MAX
MC
MTL
Minimum
NIC
MISC
MIN
MECH
Cabinet
Building
Centerline
Closet
Concrete
Column
Construction Joint
Detail
Diameter
Damproofing
Continuous
Concrete Masonry Unit
HOR
Bottom Of
Opening
OPG
OC
NTS
d
OD
OSB
OPP
Plate
PL
PFSM
PLWD
PERF
Project
Product
PROD
PROP
PROJ
Drain
Dishwasher
Down
Elevation
Each
Drawing
Downspout
Equal
Existing
Exterior
Expansion Joint
Face Of Concrete
Face Of Stud
Fire Extinguisher Cabinet
Refer
REF
REFR
Floor
Fireproof R
Finish
NA
Dimension
Tounge and Groove
Toilet Paper Holder
Sound- Transmission Class
Vinyl Asbestos Tile
United States Gage
Unless Noted Otherwise
Uniform Building Code
SL
SQ
SPEC
STC
SM
SUB
STRUCT
STL
TV
TEL
SUSP
SUPPL
IE
THK
TEMP
TO
T&B
T&G
TPH
STD
Roof Window
Sewer
Sanitary
Section
Rough Opening
Sliding
Shelves
Similar
Square
Specification
Sheet Metal
Sheet
Steel
Substitute
Structure (al)
Television
Telephone
Suspend (ed)
Supplement (al)
That Is
Thick
Tempered
Top Of
Top and Bottom
Standard
UG
TYP
TS
USG
UBC
UNFIN
U.N.O.
VENT
VIF
VERT
VAR
VAT
WC
V
WT
WIN
WP
Typical
Underground
Tube Steel
Unfinished
Variable
Vertical
Ventilate
Verify In Field
Voltage
Water Closet
Weight
Window
Waterproof
T Tread
FINISHED WOOD
ROUGH FRAMING OR
ROUGH SAWN TRIM
WOOD BLOCKING
CONCRETE
STONE
TILE
GLAZING
FRAME WALL
CONCRETE MASONRY
PARTICLE BD. OR
GLU-LAM WOOD
WOOD FIBER BD.
RIGID INSULATION
CARPET
ACOUSTICAL CEILING
STEEL
PLYWOOD
SHEET METAL
BATT INSULATION
GYP. WALL BOARD/
STUCCO/ PLASTER
ALUMINUM OR
SECTION PLAN
SECTION PLAN
ROCK/
SOIL/ COMPACTED FILL
SAND
NON-COMPACTED FILL
Issue Date:
ELEV. 100'-0"
T.O. PWD.
SITE ELEV. = 116'-0"
Power Actuated Fastened
PAF
Issue
Date
CODE: 2015 IRC, 2015 IECC OCCUPANCY TYPE: SINGLE FAMILY HOME
ENERGY CONSERVATION: THE BUILDING COMPLIES WITH THE ENERGY CONSERVATION REQUIREMENT FROM CHAPTER 4 OF THE 2015
INTERNATIONAL ENERGY CODE PER ZONE 6B ADOPTED BY THE TOWN OF VAIL, AND AS DEMONSTRATED BY PRESCRIPTIVE BUILDING THERMAL
ENVELOPE, AS FOLLOWS:
The following is a summary for the climate zone 6B of Table R402.1.2 requirements of the IECC and as adopted by The Town of Vail, and an outline of the
proposed R values of the assemblies of the building which are defined in the Construction Document Drawings and Specifications:
Maximum Glazing U-Factor of .30 for new single family dwelling units per Town of Vail amendments, this can be a weighted average.
The Sierra Pacific windows and doors with dual glazed Low E glazing (Low E on two surfaces) exceeds this requiremnt - Average U-Value = __.
See 8.5 x 11 window proposal from manufacture for summary of U-values.
Basement Walls Insulation - Requires R-15 of continuous insulation or R-19 cavity insulation : Provide R24.4 with the following assembly: R-10 exterior
insulation/drainage medium over the typical 8" concrete wall and R-14.4 at 2x4 wood furring with 4" blown in cellulose insulation with R-3.6 per inch and 5/8"
drywall exceeds the requirement.
Garage Roof at Deck Above - Requires R-49: Provide 7 1/2 inches of spray foam insulation with an R value of 6.6 per inch at underside of existing slab equaling
R-49.5
Exterior Walls Insulation - Requires R-20: Exterior walls with 5.5” cavity: Provide R25.8 with 2” minimum of spray foam insulation @ inside of sheathing with an R
value of 6.6 per inch equaling R13.2 and 3.5” of blown in cellulose insulation with R3.6 per inch equaling R12.6 or approved equal.
Basement Slab - Requires R-15 for 4' horizontally under slab (since the slab is heated). Provide R20 with continuous 2" R10 rigid insulation under the slab and
2" R-10 continuous rigid insulation @ exterior of foundation.
ADDITIONAL REQUIREMENTS PER TOWN OF VAIL CODE AMENDMENTS:
ROOF COVERING: Meets Section 1505.6 of the Town of Vail Code- Standing seam roofing will be installed to meet the required Class A roof or Class A roof
assembly.
FIRE SPRINKLER SYSTEM: Building is to be equipped throughout with an automatic sprinkler system installed in accordance with NFPA 13 and the Town of Vail.
A monitored fire alarm system will also be provided.
PLUMBING: See plumbing documents from Plumbing Contractor
MECHANICAL: See mechanical drawings and documents from Mechanical Contractor
ELECTRICAL: See load calculations from electrical contractor for service and electric panel sizing
CODE INFORMATION
PROJECT INFORMATION
ARCHITECT
BERGLUND ARCHITECTS, LLC
P.O. Box 2378
210 Edwards Village Blvd
Suite A103
Edwards, CO 81632
Phone: (970) 926-4301
Fax: (970) 926-4364
hans@berglundarchitects.com
STRUCTURAL
ENGINEER
LANDSCAPE
ARCHITECT
CLIENTS
CONTRACTOR SURVEYOR
SOILS ENGINEER
KRM Consultants Inc.
Contact: Tim Hennum
P.O. Box 4572
Vail, CO 81658
Office: (970) 949-9391
Fax: (970 949-0839
krm@krmconsultants.com
PETRUS MANAGEMENT CORP.
Contact: Thomas Doskocil
2300 West Plano Parkway
Plano, TX 75075
MECHANICAL
ENGINEER
Shaeffer Hyde Construction
Contact: Rob Fawcett
Email: robf@shaefferhyde.com
P.O. Box 373
Vail, Colorado 81658
Phone: (970) 845-5656
As indicated
4/6/2016
4:18:29 PM
A1.0
COVER
SHEET
4-05-2016
CWF
HB
84 BEAVER DAM REMODEL
4-05-2016
PERMIT SET
4-05-2016
PERMIT SET
84 BEAVER
DAM
REMODEL
VAIL, CO
A1.0 COVER SHEET
ARCHITECTURAL DRAWINGS
A2.2 AREA CALCULATIONS
A3.1 EXISTING LOWER LEVEL FLOOR PLAN
A3.1A ENLARGED LOWER LEVEL FLOOR PLAN - WEST
A3.1B ENLARGED LOWER LEVEL PLAN - EAST
A3.2 EXISTING MAIN LEVEL FLOOR PLAN
A3.2A ENLARGED MAIN LEVEL FLOOR PLANS
A3.3 ROOF PLAN
A4.1 ELEVATIONS
A5.1 SECTIONS
A5.2 SECTIONS
A5.3 SECTIONS
A5.4 SECTIONS
A6.1 DETAILS
A6.2 DETAILS
A6.3 DETAILS
A6.4 DETAILS
A8.0 WINDOW SCHEDULE
STRUCTURAL DRAWINGS
S1 SPEC
S2 FOUNDATION PLAN
S3 LOWER LEVEL FRAMING PLAN
S4 MAIN LEVEL FRAMING PLAN
S5 ROOF FRAMING PLAN
STONE CALCULATIONS
STONE VENEER REMOVED AND REPLACED AT EAST DECK - APPROX. 550 SF
STONE VENEER REMOVED AND REPLACED AT WEST DECK - APPROX. 500 SF
TOTAL STONE VENEER TO BE REPLACED - APPROX. 1,050 SF
STONE VENEER REMOVED AND TO BE REUSED AT EAST DECK - APPROX. 210 SF
TOTAL FLAGSTONE TO BE REPLACED - APPROX. 1,470 SF
GENERAL NOTES:
1.) SEE EXISTING DRAWINGS INCLUDED WITH THIS SET FOR ADDITIONAL INFORMATION
2.) VERIFY IN FIELD ALL EXISTING CONDITIONS & HEIGHTS SHOWN IN DRAWINGS. MANY
ASSUMPTIONS WERE MADE ABOUT EXISTING CONDITIONS SINCE MANY CONDITIONS ARE
CONCEALED AND NOT SHOWN IN EXISTING DRAWINGS.
REVISION SCHEDULE
# DESCRIPTION DATE
05/12/16