Loading...
HomeMy WebLinkAboutB16-0502_Conductor sizing_1489511700.pdfPage 3 of 4 11/20/2016 P.O. Box 7627, Avon, CO 81620 | P: 970.306.4233 | F: 866.403.3485 | www.activeenergies.com Conductor Sizing Pass Thru Box to AC Disconnect (for an 9 panel circuit): Nameplate maximum continuous output current: 1A Maximum Output Power 250 Watts AC 250 W ÷ 240 V = 1A 1A x 9 inverters = 9A 8A x 125% = 10A #10 THWN-2 Table 310.16 40A (90ºC column, see note 240.4(D)) Conduit fill adjustment Table 310.15 (B)(2)(a) Use .8 for 4-6 current carrying conductors 40A *.8 = 32A Temperature correction factor Table 310.16 32A x .77 = 24.6A Overcurrent Protection Device per circuit 1 - 20A two pole breaker Per Manufacturer Specification 03/14/17