HomeMy WebLinkAboutB17-0053_A6.4_1493402457.pdfINTERIOR OF GARAGE
EXTERIOR
2X TRIM BOARD AT GARAGE DOOR JAMB
BEYOND
RE: STRUCT.
RE:
STRUCT.
4" CONC. SLAB SLOPE TO DRAIN
RE: STRUCT AND FLOOR PLANS
SLOPE
GRID
LINE
SLOPE GARAGE SLAB AT THRESHOLD
1"
GARAGE DOOR
PROVIDE GASKET AT B.O. GARAGE DOOR
3" ASPHALT RE: SPEC
W.P. EPOXY LIQUID GRANITE FLOORING OVER
CONC. SLAB AND TURNS UP WALLS MIN. 6"
T.O. CONRETE SLAB
RE: FLOOR PLANS
2" 1/2"
2" 2# CLOSED CELL SPRAY FOAM
INSULATION BETWEEN 2X FURRING
P.T. BOTTOM PLATE
5/8" GWB
LINE OF 2X P.T. FURRING HELD 1" OFF
OF CONC. FOUNDATION WALL. SHIM
AND SECURE TO CONC. WALL AS REQ'D
SEE DETAIL 1/A6.1 FOR TYP. FOUNDATION NOTES
FILL JOIST CAVITY W/ BLOWN-IN
INSULATION RE: SPEC
LVL FLOOR JOISTS W/ TOPS RIPPED @ 1/8" PER 1'-0"
RE: STRUCT.
RE: STRUCT. 1" 1 1/2"
SLOPE
T.O. CONRETE WALL
RE: STRUCT
3"4"4"
4" ROAD BASE RE: SPEC
4" GRAVEL OVER COMPACTED FILL
RE: SPEC & SOILS REPORT
HOT FLUID APPLIED WATERPROOF MEMBRANE
RE: SPEC
8 1/2"
DRAINAGE MEDIUM RE: SPEC
WATERPROOF MEMBRANE RE: SPEC
LAP B.O. 36" BITUTHANE SHEET OVER
FOUNDATION WATERPROOFING
6" MIN.
FOUNDATION WATERPROOF MEMBRANE
RE: SPEC
W.P. EPOXY LIQUID GRANITE FLOORING OVER
CONC. SLAB AND TURNS UP WALLS MIN. 6"
2 1/2"
TYPICAL GARAGE FOUNDATION NOTES:
PRESSURE TREATED WOOD
LEDGER RE: STRUCT.
JOIST HANGER RE: STRUCT.
T.O. CONRETE SLAB
RE: FLOOR PLANS
T.O. PLYWOOD
RE: FLOOR PLANS
RE: STRUCT RE:
STRUCT.
GRID
LINE
1"
SEE 1/A6.2 FOR TYP. STONE
PATIO ASSEMBLY
2 1/2" 5 1/2"
SLOPE RE: PLANS
SEE DETAIL 1/A6.1 FOR
TYP. FOUNDATION NOTES
INTERIOR EXTERIOR
MECHANICAL ROOM
FILL JOIST CAVITY W/ BLOWN-IN
INSULATION RE: SPEC
TJI FLOOR JOISTS RE: STRUCT.
PAINTED EPOXY FINISH
@ MECH ROOM FLOOR
PFSM FLASHING RE: SPEC - TURN UP
WALL AND UNDER WINDOW SILL
3/4" T&G PLYWOOD RE: STRUCT.
4 3/8" FLOOR ASSEMBLY
2 1/4"
2 1/8"
LINE OF PLYWOOD @ TYP.
FLOOR ASSEMBLY
DROP STRUCTURE 2 1/8"
@ ENTRY STONE
APPROX. 1 1/2" THICK FLAGSTONE
2 7/8" THICKENED GROUT BED W/
IN-FLOOR RADIANT HEAT
1 1/2"
2 7/8"
AIR AND WATER INFILTRATION
BARRIER RE: SPEC
3 1/4"
B.O.
SILL
@ 2 1/2"
A.F.F.
TYPICAL WINDOW SILL NOTES
RE: DETAIL 1/A8.1
2" 2# CLOSED CELL SPRAY FOAM
INSULATION BETWEEN 2X FURRING
P.T. BOTTOM PLATE
5/8" GWB
LINE OF 2X P.T. FURRING HELD 1" OFF
OF CONC. FOUNDATION WALL. SHIM
AND SECURE TO CONC. WALL AS REQ'D
1 1/2" 1"
1/2" 2"
2 1/2"
WINDOW SET IN BED OF SEALANT OVER W.P.
MEMBRANE WHICH IS CONTINUOUS UNDER
WINDOW SILL, EXTENDS DOWN OVER
WATERPROOFING @ FOUNDATION MIN. 6"
US Mail Only: P. O. Box 2378
Physical / Fedex: 210 Edwards
Village Blvd, Bldg A Suite A103
Edwards, Colorado 81632-2378
(970) 926 4301, Fax: 926 4364
hans@berglundarchitects.com
www . berglundarchitects.com
Scale
Date
Drawn by
Checked by
Issue Date 3/23/2017 1:07:44 PM
3" = 1'-0"
LILES RESIDENCE
2440 CHAMONIX LANE
VAIL, CO 81657
A6.4
FOUNDATION
DETAILS
3-23-2017
CPM
HB
3-23-2017
PERMIT SET
3" = 1'-0"
1
FOUNDATION DETAIL @ MAIN LEVEL
GARAGE DOOR THRESHOLD
3" = 1'-0"
2
FOUNDATION DETAIL @ FRONT ENTRY
SIDELITE WINDOWS
REVISION SCHEDULE
# DESCRIPTION DATE
04/28/17