Technical Data Sheet for CU-1
Job Number: Y2Z08K Page Prepared Date: 5/19/2014
Job Name: CLINK Vail 2 of 11 www.DaikinApplied.com
Job Information Technical Data Sheet
Job Name CLINK Vail
Date 5/19/2014
Submitted By James Murphy
Software Version 03.30
Unit Tag CU-1
Unit Overview
Model Number Voltage
V/Hz/Phase
Total Refrigeration
Effect
Btu/hr
Total Unit Power
kW
EER
RCS045D 208/60/3 449802 49.3 9.1
Unit
Model Number: RCS045D
Type: Applied
Approval: ETL - USA
Refrigerant Type: No. of Refrigeration Circuits Refrigerant Weight
R410A 2 24.4 lb
Refrigerant Type: No. of Refrigeration Circuits Refrigerant Weight, CKT #1 Refrigerant Weight, CKT #2
R410A 2 12.6 13.0
Condensing Section
Temperature Altitude Refrigeration Effect Power EER
Suction Ambient
45.0 °F 95.0 °F 8120 ft 449802 Btu/hr 49.3 kW 9.1
Compressor
Quantity Type Capacity Control Compressor Isolation
4 Scroll 4 steps Resilient
Full Load Current:
Circuit 1, Compressor 1 42.2 A
Circuit 2, Compressor 2 42.2 A
Circuit 1, Compressor 3 42.2 A
Circuit 2, Compressor 4 42.2 A
Condenser
Coil Fans Fan Motors
Type Number of Rows Fins per Inch Condenser
Fan Type
Quantity Full Load Current
Aluminum tube
micro channel 1 18 Quiet 4 3.40 A
Sound
Casing Radiated Sound Power (db)
63 Hz 125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz
0 86 80 83 85 82 75 71
Physical
Dimensions and Weight
Length Height Width Operating Weight
80.0 in 73.0 in 99.0 in 2570 lb
Technical Data Sheet for CU-1
Job Number: Y2Z08K Page Prepared Date: 5/19/2014
Job Name: CLINK Vail 3 of 11 www.DaikinApplied.com
Refrigeration Connections
Connection Type Number of Connections Connection Size
Suction Line 2 1.62
Liquid Line 2 .88
Hot Gas Bypass 2 .88
Refrigeration Connections
Connection Type Number of Connections Connection Size
Suction Line Ckt. 1 1 1.62 in
Suction Line Ckt. 1 1 1.37 in
Liquid Line 2 0.88 in
Hot Gas Bypass 2 0.88 in
Electrical
Voltage MROPD Field Power
Connection MCA SCCR Field Outlet
Connection
208/60/3
V/Hz/Phase 225 A Single power block 195.7 A 10 kAIC 115V, 20 amp
service
Options
Unit
Isolation Valves Per Circuit: Refrigeration Service Valves
Hot Gas Bypass: HGBP Tee (See Accessory Tab)
Condenser Coil Options: Condenser with hail protection, vandal grd
Electrical
Wiring Options Sealtite conduit
GFI Receptacle Field powered
Unit Control
Temperature Controls: No temp control, 115 V transformer
Low Ambient Control: Fantrol, Low ambient control to 45 degrees
Warranty
Parts: Standard one year parts
Compressor: Extended four year compressor, five year total
Notes
Accessories
Mandatory
Part Number Description
193330721 Hot gas bypass kit, one circuit
193330711 Liquid line kit, replace core filter drier
RCS045D_Drawing for CU-1
Job Number: Y2Z08K Page Prepared Date: 5/19/2014
Job Name: CLINK Vail 7 of 11 www.DaikinApplied.com
RCS045D_Drawing for CU-1
Product Drawing Unit Tag: CU-1
13600 Industrial Park Blvd. Minneapolis, MN 55441
www.DaikinApplied.com Software Version: 03.30
Product: Project Name: CLINK Vail
Model: RCS045D Sales Office: Long Building Technologies
Sales Engineer: May 19, 2014 Ver/Rev: Sheet 1 of 1 Scale: NTS Tolerance: +/-0.25” Dwg Units: in [mm]
RCS Piping_Drawing for CU-1
Job Number: Y2Z08K Page Prepared Date: 5/19/2014
Job Name: CLINK Vail 9 of 11 www.DaikinApplied.com
RCS Piping_Drawing for CU-1
Product Drawing Unit Tag: CU-1
13600 Industrial Park Blvd. Minneapolis, MN 55441
www.DaikinApplied.com Software Version: 03.30
Product: Project Name: CLINK Vail
Model: RCS045D Sales Office: Long Building Technologies
Sales Engineer: May 19, 2014 Ver/Rev: Sheet 1 of 1 Scale: NTS Tolerance: +/-0.25” Dwg Units: in [mm]