HomeMy WebLinkAboutDRB150160_Galatyn Lodge cutsheets_1430853780.pdfUnit Report For 25T CH 4.23.15
Project: ~Untitled1 04/23/2015
Prepared By: Darryl Merkle 10:43AM
Unit Information
Tag Name:25T CH 4.23.15
Model Number:30RAP025
Condenser Type:Air Cooled
Compressor Type:Scroll
Nameplate Voltage:208/230-3-60 V-Ph-Hz
Quantity:1
Manufacturing Source:Charlotte, NC USA
Refrigerant:R410A
Independent Refrigerant Circuits:1
Capacity Control Steps:22
Minimum Capacity:17.0 %
Shipping Weight:1328 lb
Operating Weight:1242 lb
Unit Length:89 in
Unit Width:41 in
Unit Height:79 in
Accessories and Installed Options
Cooler Heater
Micro Channel, E-Coat
Low Sound
Digital Compressor
Single Point
Wind Baffle
Security Grilles/Hail Guards
Motormaster® V Low Ambient Kit. Operation down to -20° F (-
29° C).
Low Sound Compressor Blankets
Vibration Isolation Package
Chiller Warranty Information (Note: for US & Canada only)
First Year - Parts Only (Standard)
Complete Unit Less Hydronic System Years 2-5 Parts Only
Ordering Information
Part Number Description Quantity
30RAP0255F-02100 Packaged Chiller 1
Base Unit
Cooler Heater
Micro Channel, E-Coat
Low Sound
Digital Compressor
Single Point
30RA-900---066 Wind Baffle 1
38AP-900---003 Security Grilles/Hail Guards 1
38AP-900---020 Motormaster® V Low Ambient Kit. Operation down to -20° F (-29° C). 1
38AP-900---009 Low Sound Compressor Blankets 2
30RA-900---005 Vibration Isolation Package 1
Packaged Chiller Builder NACO 3.49j Page 1 of 10
Certified Drawing for 25T CH 4.23.15
Project: ~Untitled1 04/23/2015
Prepared By: Darryl Merkle 10:43AM
Packaged Chiller Builder NACO 3.49j Page 2 of 10
Field Wiring Diagram for 25T CH 4.23.15
Project: ~Untitled1 04/23/2015
Prepared By: Darryl Merkle 10:43AM
Packaged Chiller Builder NACO 3.49j Page 3 of 10
Summary Performance Report For 25T CH 4.23.15
Project: ~Untitled1 04/23/2015
Prepared By: Darryl Merkle 10:43AM
PackagedChillerReport:DoNotEdit;
AquaSnapTM Air-Cooled Scroll Chiller
Unit Information
Tag Name:25T CH 4.23.15
Model Number:30RAP025
Quantity:1
Manufacturing Source:Charlotte, NC USA
Refrigerant:R410A
Independent Refrigerant Circuits:1
Shipping Weight:1328 lb
Operating Weight:1242 lb
Unit Length:89 in
Unit Width:41 in
Unit Height:79 in
Chiller Pressure Drop*:28.6 ft wg
*Use Chiller Pressure Drop for sizing pumps. This value
includes losses due to chiller piping, fittings, 40 mesh factory
supplied strainer and BPHX.
Evaporator Information
Fluid Type:Propylene Glycol
Brine Concentration:50.0 %
Fouling Factor:0.00010 (hr-sqft-F)/BTU
Leaving Temperature:44.0 °F
Entering Temperature:54.0 °F
Fluid Flow:57.0 gpm
Evaporator Pressure Drop*:20.7 ft wg
*Refer to Chiller Pressure Drop for sizing pumps.
Condenser Information
Altitude:8500 ft
Number of Fans:2
Total Condenser Fan Air Flow:19400 CFM
Entering Air Temperature:95.0 °F
Integrated Pump Information
No Pump Selected
Performance Information
Cooling Capacity:21.0 Tons
Total Compressor Power:25.2 kW
Total Fan Motor Power:2.04 kW
Total Unit Power (without pump):27.3 kW
Efficiency (without pump):9.26 EER
IPLV:15.14 EER
Accessories and Installed Options
Cooler Heater
Micro Channel, E-Coat
Low Sound
Digital Compressor
Single Point
Wind Baffle
Security Grilles/Hail Guards
Motormaster® V Low Ambient Kit. Operation down to -20° F (-
29° C).
Low Sound Compressor Blankets
Vibration Isolation Package
Electrical Information
Unit Voltage:208/230-3-60 V-Ph-Hz
Connection Type:Single Point
Electrical Electrical
Amps Circuit 1 Circuit 2
MCA 127.4 ---
MOCP 175.0 ---
ICF 363.3 ---
Rec Fuse Size 150.0 ---
Sound power measured in accordance with ANSI/AHRI Standard 370-2001.
Packaged Chiller Builder NACO 3.49j Page 4 of 10
Summary Performance Report For 25T CH 4.23.15
Project: ~Untitled1 04/23/2015
Prepared By: Darryl Merkle 10:43AM
Evaporator contains a glycol or other secondary coolants for freeze protection with a leaving chilled fluid temperature above 32°F and is
certified in accordance with the AHRI Air-Cooled Water Chilling Packages Using Vapor Compression Cycle Certification Program, which is based on
AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI) when tested with water at Standard Rating Conditions. Certified units may be found in
the AHRI Directory at www.ahridirectory.org.
Packaged Chiller Builder NACO 3.49j Page 5 of 10
Summary Performance Report For 25T CH 4.23.15
Project: ~Untitled1 04/23/2015
Prepared By: Darryl Merkle 10:43AM
Unit Parameters
Tag Name:25T CH 4.23.15
Model Number:30RAP025
Condenser Type:Air Cooled
Compressor Type:Scroll
Chiller Nameplate Voltage:208/230-3-60 V-Ph-Hz
Quantity:1
Manufacturing Source:Charlotte, NC USA
Refrigerant:R410A
Shipping Weight:1328 lb
Operating Weight:1242 lb
Unit Length:89 in
Unit Width:41 in
Unit Height:79 in
1 - Chiller Height Above Ground
2 - Horizontal Distance From Chiller to Receiver
3 - Receiver Height Above Ground
(See Note 3)
Accessories and Installed Options
Cooler Heater
Micro Channel, E-Coat
Low Sound
Digital Compressor
Single Point
Wind Baffle
Security Grilles/Hail Guards
Motormaster® V Low Ambient Kit. Operation down to -20° F (-
29° C).
Low Sound Compressor Blankets
Vibration Isolation Package
Acoustic Information
Table 1. A-Weighted Sound Power Levels (dB re 1 picowatt). See note #1.
Octave Band Center Frequency, Hz 31 63 125 250 500 1k 2k 4k 8k Overall
100% Load 37 58 68 78 83 84 83 77 67 89
75% Load 37 58 68 78 83 84 83 77 67 89
50% Load 37 58 68 78 83 84 82 77 67 88
25% Load 34 55 65 75 80 81 80 74 64 86
Table 2. A-Weighted Sound Pressure Levels (dB re 20 micropascals) calculated based upon user defined input for
dimensions 1, 2 and 3 as shown in above diagram. See note #2 and #3.
Octave Band Center Frequency, Hz 31 63 125 250 500 1k 2k 4k 8k Overall
100% Load 10 31 40 50 55 56 55 49 40 61
75% Load 10 31 40 50 55 56 55 49 40 61
50% Load 10 30 40 50 55 56 55 49 40 61
25% Load 7 28 37 47 52 53 52 46 37 58
Notes: (1) Measurements performed in accordance with AHRI Standard 370 for air cooled Chillers.
(2) Chiller is assumed to be a point source on a reflecting plane.
(3) Without user defined input, the default dimensions used to construct Table 2 are as follows:
1 - Chiller Height Above Ground = 0.0 ft
2 - Horizontal Distance From Chiller to Receiver = 30.0 ft
3 - Receiver Height Above Ground = 3.0 ft
Packaged Chiller Builder NACO 3.49j Page 6 of 10
Acoustic Summary For 25T CH 4.23.15
Project: ~Untitled1 04/23/2015
Prepared By: Darryl Merkle 10:43AM
PackagedChillerReport:DoNotEdit;
Please refer to Performance Output Summary or Detailed
Performance Report for Acoustic information
Packaged Chiller Builder NACO 3.49j Page 7 of 10
Detailed Performance Summary For 25T CH 4.23.15
Project: ~Untitled1 04/23/2015
Prepared By: Darryl Merkle 10:43AM
PackagedChillerReport:DoNotEdit;
Unit Information
Tag Name:25T CH 4.23.15
Model Number:30RAP025
Condenser Type:Air Cooled
Compressor Type:Scroll
Nameplate Voltage:208/230-3-60 V-Ph-Hz
Quantity:1
Manufacturing Source:Charlotte, NC USA
Refrigerant:R410A
Capacity Control Steps:22
Minimum Capacity:17.0 %
Shipping Weight:1328 lb
Operating Weight:1242 lb
Unit Length:89 in
Unit Width:41 in
Unit Height:79 in
Minimum Outdoor Operating Temp:45 °F
Chiller Pressure Drop*:28.6 ft wg
*Use Chiller Pressure Drop for sizing pumps. This value
includes losses due to chiller piping, fittings, 40 mesh factory
supplied strainer and BPHX.
Performance Information
Cooling Capacity:21.0 Tons
Total Compressor Power:25.2 kW
Total Fan Motor Power:2.04 kW
Total Unit Power (without pump):27.3 kW
Efficiency (without pump):9.26 EER
Evaporator Information
Fluid Type:Propylene Glycol
Brine Concentration:50.0 %
Fouling Factor:0.00010 (hr-sqft-F)/BTU
Leaving Temperature:44.0 °F
Entering Temperature:54.0 °F
Fluid Flow:57.0 gpm
Evaporator Pressure Drop*:20.7 ft wg
*Refer to Chiller Pressure Drop for sizing pumps.
Condenser Information
Altitude:8500 ft
Number of Fans:2
Total Condenser Fan Air Flow:19400 CFM
Entering Air Temperature:95.0 °F
Integrated Pump Information
No Pump Selected
Accessories and Installed Options
Cooler Heater
Micro Channel, E-Coat
Low Sound
Digital Compressor
Single Point
Wind Baffle
Security Grilles/Hail Guards
Motormaster® V Low Ambient Kit. Operation down to -20° F (-
29° C).
Low Sound Compressor Blankets
Vibration Isolation Package
Electrical Information
Unit Voltage:208/230-3-60 V-Ph-Hz
Connection Type:Single Point
Electrical Electrical
Amps Circuit 1 Circuit 2
MCA 127.4 ---
MOCP 175.0 ---
ICF 363.3 ---
Rec Fuse Size 150.0 ---
Packaged Chiller Builder NACO 3.49j Page 8 of 10
Detailed Performance Summary For 25T CH 4.23.15
Project: ~Untitled1 04/23/2015
Prepared By: Darryl Merkle 10:43AM
Integrated Part Load Value (AHRI)
IPLV:15.14 EER
Unit Performance
Percent of Full Load Capacity, %100 75 50 25
Percent of Full Load Power, %100.0 55.7 31.1 14.9
Unloading Sequence A A A A
Cooling Capacity, Tons 23.3 17.5 11.6 5.8
Total Unit Power, kW 27.7 15.4 8.6 4.1
Efficiency, EER 10.08 13.58 16.23 16.91
Evaporator Data
Fluid Entering Temperature, °F 54.0 51.5 49.0 46.5
Fluid Leaving Temperature, °F 44.0 44.0 44.0 44.0
Fluid Flow Rate, gpm 55.9 55.9 55.9 55.9
Fouling Factor, (hr-sqft-F)/BTU 0.0001 0.0001 0.0001 0.0001
Condenser Data
Entering Air Temperature, °F 95.0 80.0 65.0 55.0
For some 75% operating points, the efficiency may be calculated at a condenser inlet air operating temperature as much as 0.8
degrees higher.
Sound power measured in accordance with ANSI/AHRI 370-2001.
Evaporator contains a glycol or other secondary coolants for freeze protection with a leaving chilled fluid temperature above
32°F and is certified in accordance with the AHRI Air-Cooled Water Chilling Packages Using Vapor Compression Cycle Certification
Program, which is based on AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI) when tested with water at Standard Rating
Conditions. Certified units may be found in the AHRI Directory at www.ahridirectory.org.
Packaged Chiller Builder NACO 3.49j Page 9 of 10
Detailed Performance Summary For 25T CH 4.23.15
Project: ~Untitled1 04/23/2015
Prepared By: Darryl Merkle 10:43AM
Unit Parameters
Tag Name:25T CH 4.23.15
Model Number:30RAP025
Condenser Type:Air Cooled
Compressor Type:Scroll
Chiller Nameplate Voltage:208/230-3-60 V-Ph-Hz
Quantity:1
Manufacturing Source:Charlotte, NC USA
Refrigerant:R410A
Shipping Weight:1328 lb
Operating Weight:1242 lb
Unit Length:89 in
Unit Width:41 in
Unit Height:79 in
1 - Chiller Height Above Ground
2 - Horizontal Distance From Chiller to Receiver
3 - Receiver Height Above Ground
(See Note 3)
Accessories and Installed Options
Cooler Heater
Micro Channel, E-Coat
Low Sound
Digital Compressor
Single Point
Wind Baffle
Security Grilles/Hail Guards
Motormaster® V Low Ambient Kit. Operation down to -20° F (-
29° C).
Low Sound Compressor Blankets
Vibration Isolation Package
Acoustic Information
Table 1. A-Weighted Sound Power Levels (dB re 1 picowatt). See note #1.
Octave Band Center Frequency, Hz 31 63 125 250 500 1k 2k 4k 8k Overall
100% Load 37 58 68 78 83 84 83 77 67 89
75% Load 37 58 68 78 83 84 83 77 67 89
50% Load 37 58 68 78 83 84 82 77 67 88
25% Load 34 55 65 75 80 81 80 74 64 86
Table 2. A-Weighted Sound Pressure Levels (dB re 20 micropascals) calculated based upon user defined input for
dimensions 1, 2 and 3 as shown in above diagram. See note #2 and #3.
Octave Band Center Frequency, Hz 31 63 125 250 500 1k 2k 4k 8k Overall
100% Load 10 31 40 50 55 56 55 49 40 61
75% Load 10 31 40 50 55 56 55 49 40 61
50% Load 10 30 40 50 55 56 55 49 40 61
25% Load 7 28 37 47 52 53 52 46 37 58
Notes: (1) Measurements performed in accordance with AHRI Standard 370 for air cooled Chillers.
(2) Chiller is assumed to be a point source on a reflecting plane.
(3) Without user defined input, the default dimensions used to construct Table 2 are as follows:
1 - Chiller Height Above Ground = 0.0 ft
2 - Horizontal Distance From Chiller to Receiver = 30.0 ft
3 - Receiver Height Above Ground = 3.0 ft
Packaged Chiller Builder NACO 3.49j Page 10 of 10