HomeMy WebLinkAboutDRB150279_cut sheets_1436545860.pdfSummary Performance Report For CH-1
Project: ~Untitled4 03/03/2015
Prepared By: 11:37AM
PackagedChillerReport:DoNotEdit;
30RB with Greenspeed®Intelligence
Unit Information
Tag Name:CH-1
Model Number:30RB080
Quantity:1
Manufacturing Source:Charlotte, NC USA
Refrigerant:R410A
Independent Refrigerant Circuits:2
Shipping Weight:4002 lb
Operating Weight:4267 lb
Unit Length:95 in
Unit Width:89 in
Unit Height:90 in
Chiller Pressure Drop:6.6 ft wg
Evaporator Information
Fluid Type:Fresh Water
Fouling Factor:0.00010 (hr-sqft-F)/BTU
Leaving Temperature:44.0 °F
Entering Temperature:54.0 °F
Fluid Flow:175.7 gpm
Condenser Information
Altitude:8200 ft
Number of Fans:4
Total Condenser Fan Air Flow:49600 CFM
Entering Air Temperature:95.0 °F
Integrated Pump Information
No Pump Selected
Performance Information
Cooling Capacity:73.5 Tons
Total Compressor Power:88.2 kW
Total Fan Motor Power:7.45 kW
Total Unit Power (without pump):95.6 kW
Efficiency (without pump):9.22 EER
A-Weighted Sound Power Level:99 dbA
Accessories and Installed Options
Freeze Protection
Non-Fused Disconnect
Micro Channel
Ultra Low Sound Option
Single Point
BACnet Communications
Coil Trim Panels
High-Efficiency Variable Condenser Fans
Dual Chiller Accessory Kit
Convenience Outlet
Security Grille Package
Electrical Information
Unit Voltage:208/230-3-60 V-Ph-Hz
Connection Type:Single Point
Minimum Voltage:187 Volts
Maximum Voltage:253 Volts
Electrical Electrical
Amps Circuit 1 Circuit 2
MCA 366.5 ---
MOCP 400.0 ---
ICF 757.8 ---
Rec Fuse Size 400.0 ---
An uncoated Novation condenser coil was selected for this product. This is based on an installed location with postal code 81657 and
a non-corrosive localized environment.
Sound power measured in accordance with ANSI/AHRI Standard 370-2001.
Packaged Chiller Builder NACO 3.49h Page 4 of 7
Summary Performance Report For CH-1
Project: ~Untitled4 03/03/2015
Prepared By: 11:37AM
Certified in accordance with the AHRI Air-Cooled Water Chilling Packages Using Vapor Compression Cycle Certification Program, which is
based on AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI). Certified units may be found in the AHRI Directory at www.ahridirectory.org
Packaged Chiller Builder NACO 3.49h Page 5 of 7
Acoustic Summary For CH-1
Project: ~Untitled4 03/03/2015
Prepared By: 11:37AM
PackagedChillerReport:DoNotEdit;
Unit Parameters
Tag Name:CH-1
Model Number:30RB080
Condenser Type:Air Cooled
Compressor Type:Scroll
Chiller Nameplate Voltage:208/230-3-60 V-Ph-Hz
Quantity:1
Manufacturing Source:Charlotte, NC USA
Refrigerant:R410A
Shipping Weight:4002 lb
Operating Weight:4267 lb
Unit Length:95 in
Unit Width:89 in
Unit Height:90 in
1 - Chiller Height Above Ground
2 - Horizontal Distance From Chiller to Receiver
3 - Receiver Height Above Ground
Accessories and Installed Options
Freeze Protection
Non-Fused Disconnect
Micro Channel
Ultra Low Sound Option
Single Point
BACnet Communications
Coil Trim Panels
High-Efficiency Variable Condenser Fans
Dual Chiller Accessory Kit
Convenience Outlet
Security Grille Package
Acoustic Information (Full Load)
Octave Band Center Frequency, Hz 31 63 125 250 500 1k 2k 4k 8k Total
Sound pressure at specified distance in a free field, dB 50 67 68 67 67 67 62 58 52 74
A-Weighted Sound Pressure Level, dBA 11 41 52 58 64 67 63 59 51 70
Sound Power at Chiller Acoustic Center, dB 79 95 96 95 95 95 90 86 80 103
A-Weighted Sound Power, dBA 39 69 80 86 92 95 91 87 79 99
Notes
1 - Chiller Height Above Ground = 0.0 ft
2 - Horizontal Distance From Chiller to Receiver = 30.0 ft
3 - Receiver Height Above Ground = 3.0 ft
Estimated Sound Power levels - dB re: 1 picowatt
Estimated Sound Pressure levels - dB re: 20 micropascal
Estimated sound levels given above are assumed to originate at the acoustic center of the chiller.
Sound pressure level data used to develop this program was determined in accordance with AHRI Standard 575 for water chillers in a
free field and ANSI/AHRI Standard 370 for air cooled chillers.
Calculation methods used in this program are patterned after the ASHRAE Guide; other ASHRAE Publications and the AHRI
Acoustical Standards. While a very significant effort has been made to insure the technical accuracy of this program, it is assumed
that the user is knowledgeable in the art of system sound estimation and is aware of the tolerances involved in real world acoustical
estimation. This program makes certain assumptions as to the dominant sound sources and sound paths which may not always be
appropriate to the real system being estimated. Because of this, no assurances can be offered that this software will always generate
an accurate sound prediction from user supplied input data. If in doubt about the estimation of expected sound levels in a space, an
Acoustical Engineer or a person with sound prediction expertise should be consulted.
Packaged Chiller Builder NACO 3.49h Page 6 of 7
Detailed Performance Summary For CH-1
Project: ~Untitled4 03/03/2015
Prepared By: 11:37AM
PackagedChillerReport:DoNotEdit;
Unit Information
Tag Name:CH-1
Model Number:30RB080
Condenser Type:Air Cooled
Compressor Type:Scroll
Nameplate Voltage:208/230-3-60 V-Ph-Hz
Quantity:1
Manufacturing Source:Charlotte, NC USA
Refrigerant:R410A
Capacity Control Steps:4
Minimum Capacity:25.0 %
Shipping Weight:4002 lb
Operating Weight:4267 lb
Unit Length:95 in
Unit Width:89 in
Unit Height:90 in
Minimum Outdoor Operating Temp:-20 °F
Chiller Pressure Drop:6.6 ft wg
Performance Information
Cooling Capacity:73.5 Tons
Total Compressor Power:88.2 kW
Total Fan Motor Power:7.45 kW
Total Unit Power (without pump):95.6 kW
Efficiency (without pump):9.22 EER
Acoustics Information
A-Weighted Sound Power Level:99 dbA
Evaporator Information
Fluid Type:Fresh Water
Fouling Factor:0.00010 (hr-sqft-F)/BTU
Leaving Temperature:44.0 °F
Entering Temperature:54.0 °F
Fluid Flow:175.7 gpm
Condenser Information
Altitude:8200 ft
Number of Fans:4
Total Condenser Fan Air Flow:49600 CFM
Entering Air Temperature:95.0 °F
Integrated Pump Information
No Pump Selected
Accessories and Installed Options
Freeze Protection
Non-Fused Disconnect
Micro Channel
Ultra Low Sound Option
Single Point
BACnet Communications
Coil Trim Panels
High-Efficiency Variable Condenser Fans
Dual Chiller Accessory Kit
Convenience Outlet
Security Grille Package
Electrical Information
Unit Voltage:208/230-3-60 V-Ph-Hz
Connection Type:Single Point
Minimum Voltage:187 Volts
Maximum Voltage:253 Volts
Electrical Electrical
Amps Circuit 1 Circuit 2
MCA 366.5 ---
MOCP 400.0 ---
ICF 757.8 ---
Rec Fuse Size 400.0 ---
An uncoated Novation condenser coil was selected for this product. This is based on an installed location with postal code 81657 and
a non-corrosive localized environment.
Sound power measured in accordance with ANSI/AHRI 370-2001.
Certified in accordance with the AHRI Air-Cooled Water Chilling Packages Using Vapor Compression Cycle Certification
Program, which is based on AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI). Certified units may be found in the AHRI
Directory at www.ahridirectory.org
Packaged Chiller Builder NACO 3.49h Page 7 of 7