HomeMy WebLinkAboutDRB150337_A4.4_1438727460.pdfREMOVE DECKS
REMOVE RAILING
R @ 7 3/16"
5
EXTERIOR COMP.
WOOD STAIRS
STUCCO
VENEER
REMOVE STAIRS
SMALL CONC. PAD
2' - 6"
2X12
NEW METAL ROOFING
R-49 BIBS INSULATION (14" DEEP)
EXTRA INSULATION
SOFFIT TO MATCH EXIST.
2X8 FASCIA
NEW CEILING
BEAM TO SUPPORT HEADER
REMOVE DOOR
REMOVE WINDOW, CREATE OPENING
NEW SLIDER DOOR
2' - 6"
NEW FLOOR JOISTS
R-30 BIBS INSULATION
NEW BEAM
NEW LEDGER
2"
12"
REMOVE EXIST. ROOF
2X12
R @ 6"
4
EXTERIOR COMP.
WOOD STAIRS
STUCCO
VENEER
STUCCO
VENEER
NEW
PATIO
DOOR
7' - 0"
2' - 6"
CONTRACTOR TO VERIFY SEWER LINE LOCATION
2. MAIN LEVEL
41' - 0 3/8"
3. ENTRY LEVEL
50' - 2 1/2"
1. BASEMENT
31' - 10 3/4"
EXISTING SONOTUBE
FOUNDATION PIERS
EXISTING NON-
BEARING WALL
EXISTING
RIM BEAM
EXISTING
SLAB
REMOVE WALL
AFTER NEW
EXTERIOR WALL
PLACED TO PICK
UP CANTILEVER.
NEW BEARING EXTERIOR WALL
28' - 10 3/4"
2' - 4" 9"
2' - 4"
2' - 6"
MAX
WITHOUT
RAILING
BOULDER RETAINING WALL
CONTRACTOR TO VERIFY HEIGHT
5' - 2 13/16"
BLOCKING
CANTILEVER
WATERPROOF DECK:
3" CONC SLAB (COLOR & PATTERN)
OVER W.P.MEMBRANE (NO PENTETRATIONS)
OVER SHEATHING OVER SLOPING JOISTS (1/8" / FT.)
BEAM RE:
STRUCT.
WRAP POST W/
STONE VENEER
SPIRAL STAIR - CENTER POLE
DRIP-THRU DECK - COMPOSITE
DECKING OVER JOISTS
3' - 0"
NEW HOT TUB SLAB
BUILD-UP GRADE
2X12
2X12
UNCONDITIONED
SPACE
6' - 6"
R-22 BIBS INSULATION
R-30 BIBS INSULATION
CONTRACTOR TO VERIFY SEWER LINE LOCATION
HOT TUB
CONDITIONED
SPACE
EXISTING SPACE
CLIMATE
ZONE
FENESTRATION
U-FACTOR
SKYLIGHT
U-FACTOR
GLAZED
FENESTRATION
SHGC
CEILING
R-VALUE
WOOD FRAME
WALL R-VALUE
MASS WALL
R-VALUE
FLOOR
R-VALUE
BASEMENT
WALL R-VALUE
SLAB R-VALUE
& DEPTH
CRAWLSPACE
WALL R-VALUE
6 .32 .55 NOT
REQUIRED
49 20 + 5
(OR 13 + 10)
15 / 20 30 15 / 19 10 , 4 ft. 15 / 19
FROM TABLE R402.1.1 - IRC 2012
FROM TABLE N1102.1.1 - IECC 2012
INSULATION MINIMAL VALUES BY CODE
a
b
c
d e f e
a. Eagle County lies in climate zone 6B.
b. This is a prescriptive maximum u-factor for all windows and doors for a project considered an "addition".
c. This means R-20 for cavity insulation + R-5 for exterior continuous insulation. The Town of Vail has not adopted
the additional R-5 at this time per amendment to section 101.1.
d. The second R-value applies when more than half the insulation is on the interior of the mass wall.
e. "15/19" means R-15 continuous insulation on the interior or exterior of the basement wall -or- R-19 cavity
insulation at the interior of the basement wall (a combination cavity and continuous must equal R-19 as well).
f. R-5 shall be added for heated slabs. The R-values and depth dimension can be spread between perimeter and
under-slab locations.
970.328.5151 OFFICEPO Box 1587, Eagle, CO 81631
www.martinmanleyarchitects.com
Project number Date REVISIONS
7/23/2015 11:22:58 AM
A4.4 WALL SECTIONS xxxx
BRIAR PATCH IMPROVEMENTS
PERMIT SET 7-23-15 7-23-15 BRIAR PATCH UNITS 1390 Briar Patch Ln, Vail, CO
UNITS 1, 2, & 3 No. Description Date
1/2" = 1'-0"
1
2. ADDITION WALL SECTION 1
1/2" = 1'-0" 2
2. ADDITION WALL SECTION 2
Door Schedule
Mark Family and Type Width Height Comments
01 3_Panel_Glass_Slider NO MULLIONS:
108" x 84"
9' - 0" 8' - 0"
02 Single-Glass 1: 30" x 84" 2' - 6" 7' - 0"
03 Single-Flush: 28" x 84" 2' - 4" 7' - 0"
Window Schedule
Mark Type Mark Window Type Width Height
Head
Height Comments
101 A Awning 3' - 4" 2' - 0" 3' - 3"
102 B Picture 2' - 8" 3' - 6" 6' - 9"
103 C Casement 3' - 4" 3' - 6" 6' - 9"
INSULATION SUMMARY
ALL MINIMUM INSULATION VALUES FROM IRC 2012
ROOF JOIST CAVITY = R-56 (NON-VENTED) (MIN. R-49)
EXTERIOR WALL INSULATION = R-22 (MIN. R-20)
BASEMENT WALL INSULATION = R-24 / R-19 (MIN. R-19)
SLAB PERIMETER INSULATION = R-10 (MIN. R-10)
UNDER-SLAB INSULATION = R-10/ R-15 (MIN. R-10)
FLOOR OVER UNCONDITIONED = R-30 (MIN. R-30)
WINDOWS U-VALUE MAX. = U-.32 (MAX. U-.32)
INSULATION SUBCONTRACTOR MUST VERIFY THAT R-VALUES OF
PROPRIETARY PRODUCTS MEET OR EXCEED THE R-VALUES LISTED ABOVE
AND THAT INSTALLATION PERFORMED PER MANUFACTURER'S
SPECIFICATIONS. ALL INSULATION SHALL COMPLETELY FILL STUD/JOIST
SPACES AND HAVE PROPER AIR-BARRIER SHEATHING ON BOTH SIDES OF
THE STUD/JOIST SPACES.
WINDOW NOTES:
1. ALL NEW WINDOWS SHALL BE DOUBLE-PANED WOOD WINDOWS W/ ALUM. CLADDING OR
FIBERGLASS AND SHALL MATCH THE WHITE CLADDING COLOR OF THE ORIGINAL WINDOWS.
2. U-VALUE OF .32 MAXIMUM (SEE INSULATION SUMMARY THIS SHEET).
3. ALL WINDOWS TO RECEIVE LOW-E TREATMENT.
4. ALL SIZES SHOWN ARE NOMINAL. CONTRACTOR TO VERIFY ROUGH-OPENING SIZES WITH
CHOSEN WINDOW MANUFACTURER.
5. WINDOWS MUST DISPLAY MANUFACTURER SPECS INCLUDING R-VALUES PRIOR TO T.O.VAIL
INSPECTIONS.
DOOR NOTES:
1. ALL NEW GLASS DOORS SHALL BE WOOD W/ ALUM. CLADDING OR FIBERGLASS AND SHALL
MATCH THE WHITE CLADDING COLOR OF THE ORIGINAL WINDOWS.
2. U-VALUE OF .32 MAXIMUM (SEE INSULATION SUMMARY THIS SHEET).
3. ALL GLASS DOORS TO RECEIVE LOW-E TREATMENT.
4. ALL SIZES SHOWN ARE NOMINAL. CONTRACTOR TO VERIFY ROUGH-OPENING SIZES WITH
CHOSEN WINDOW MANUFACTURER.
5. WINDOWS MUST DISPLAY MANUFACTURER SPECS INCLUDING R-VALUES PRIOR TO T.O.VAIL
INSPECTIONS.
1/4" = 1'-0"
3
2012 Energy Table
DRB
APPROVED
8/4/2015 12:00:00
AM