HomeMy WebLinkAboutA17-0028_26_reversal_module_cut_sheet_1495850460.pdf INSTALLATION AND MAINTENANCE INSTRUCTIONS SYSTEM o $ SENSOR® (6 Series 3825 Ohio Avenue,St.Charles,Illinois 60174 1-800-SENSOR2,FAX:630-377-6495 RRS-MOD Reversing Relay/Synchronization Module www.systemsensor.com SPECIFICATIONS NOTE:In an alarm condition,a wiring-fault Operating Voltage Range: 8.5 to 35 VDC Maximum Operating Current: 25mA trouble state may also register at the panel Relay Contacts: 2A at 35 VDC when the RRS-MOD is used. Operating Temperature Range: 32°to 131°F(0°to 55°C) Operating Humidity Range: 5%to 93%non-condensing Dimensions: 21/2"x 21/2"x 1" Wire connections: 18 AWG stranded,tinned,16"long GENERAL DESCRIPTION WIRING The RRS-MOD polarity reversing relay/synchronization module is intended IMPORTANT:All polarities must be observed! for use with 2-wire and 4-wire i3 series detectors equipped with a built-in 1.Connect the RRS-MOD module trigger wire to the fire alarm output terminals. sounder,models 2WTA-B,4WTA-B,4WTAR-B, and 4WITAR-B. It is designed to allow all the detectors in the same loop to sound when one of the detectors A. Alarm/Bell output: (Figures 1 and 2) goes into alarm,and to synchronize their audible output.The RRS-MOD also Connect the purple wire to the Alarm or Bell output. allows the silencing of the detector sounders from the alarm control panel. B.Alarm relay,normally open contact: (Figures 3 and 4) 1. Connect one end of the alarm relay contact output to positive The RRS-MOD may be used with an alarm zone that provides coded output for auxiliary or detector power fire alarm output. fire and continuous output for burglary. By default the RRS-MOD's switch is 2. Connect the purple wire to the other end of the alarm relay set to"off".Therefore,the RRS-MOD will only trigger when the alarm output contact output. is coded.In this manner,smoke detectors will only sound from the result of a 2.Connect the red and black wires to the panel auxiliary or detector power fire,and not from a burglary alarm.In this mode,the detectors will provide a (red to positive,black to negative). synchronized,coded output.The RRS-MOD contains a relay that is meant for zone applications,per UL 864. 3.2-wire models Connect the yellow and orange wires to the panel initiating circuit (yel- The RRS-MOD can also be set to only trigger on continuous alarm zone sig- low to positive,orange to negative). nals by selecting the switch to"on".In this mode,the detectors will provide a synchronized,coded output. 4-wire models Connect the yellow and orange wires to the panel detector power circuit NOTICE:This manual shall be left with the owner/user of this equipment (yellow to positive,orange to negative). INSTALLATION Install in a dry indoor location. Choose a mounting location in the control 4.2-wire models panel within reach of the provided wire leads.Use a water/isopropyl alcohol Connect the brown and white wires to the smoke detector power supply mixture (50/50) to clean the mounting surface. Allow surface to dry and re- input(brown to positive,white to negative). move paper backing from the Velcro and catch. Stick the Velcro in the panel 4-wire models and the catch on the back of the module,then mount the module inside the Connect the brown and white wires to the smoke detector power circuit control panel.Route terminals to the appropriate terminals as noted below. (brown to positive,white to negative). AWARNING When calculating total current draw of the control panel, remember to add current consumption (25mA) for the polarity reversal relay module (RRS- MOD).IMPORTANT:If the fire alarm output signal is coded,set the switch on the RRS-MOD to "OFF". If the fire alarm output signal is continuous,set the switch to"ON". D500-44-00 1 I56-2203-005 NOTE:Please refer to Figures 5 and 6 for Ademco Vista panels and Figures 7 and 8 for DSC Power 832 panels. FIGURE 1.2-WIRE SYSTEM TRIGGERED FROM ALARM/BELL OUTPUT: UL LISTED ALARM CONTROL PANEL ACAUTION BELL/ I ALARM PURPLE - _ When using the RRS-MOD with model CIRCUIT T+ k 2WTA-B, do not mix the 2WTA-B with (positive signal in alarm state) _ _EOL other model smoke detectors and dry contact closure devices, including me- -41 chanical heat detectors, manual pull ------. BROWN OUT+ rli+I" p '+I" stations and waterflow switches. Such 2-WIRE + YELLOW INITIATING IN+ 2+OUT 0 2+OUT mixing can cause a direct short on the DEVICE _ ORANGE 3-IN/OUT 0 3-IN/OUT auxiliary power terminals,damaging the • CIRCUIT IN- �. OUT- 4 RA+ , O 4 RA+ control panel's internal circuitry and/or • 5 RA- 5 RA- damaging devices connected to the initi- ating device circuit. + RED PWR+ AUX POWER OPTIONAL OPTIONAL - BLACK PWR- REMOTE REMOTE ANNUNCIATOR ANNUNCIATOR (RA400Z/RA100Z) (RA400Z/RA100Z) 50101-01 FIGURE 2.4-WIRE SYSTEM TRIGGERED FROM ALARM/BELL OUTPUT: UL LISTED ALARM CONTROL PANEL BELUALARM CIRCUIT PURPLE (nositi m state ) T+ EOL RELAY (SHOWN ENERGIZED) BROWN —• OUT+ L3 1+IN 4 1+IN • + YELLOW IN+ 0 2+our M2+OUT DETECTOR POWER- ORANGE . I 0 3-IN/OUT M 3-IN/OUT IN- WRITE ���� _� OUT- 4 N.O. LW 4 N.O. v 5C filo'' 5C AUX POWER+ RED OR PWR+ DETECTOR BLACK J POWER- PWR- t EOL + INITIATING DEVICE CIRCUIT S0102-00 FIGURE 3.2-WIRE SYSTEM TRIGGERED FROM ALARM RELAY CONTACT: UL LISTED ALARM CONTROL PANEL ALARM PURPLE RELAY . T+ (NO Contact) litl EOL —40 `0 BROW v 1+IN 4 1+IN 2-WIRE + YE Now -0 INITIATING 0 2+OUT CI 2+OUT DEVICE _ ORANGE —00 3-IN/OUT 0 3-IN/OUT CIRCUIT IN- `� WHITE OUT- 0 4 RA+ 0 4 RA+ • 4 5 RA- PIV 5 RA- RED PWR+ AUX POWER OPTIONAL OPTIONAL BLACK REMOTE REMOTE PWR- ANNUNCIATOR ANNUNCIATOR (RA400Z/RA100Z) (RA400Z/RA100Z) S0103-01 D500-44-00 2 I56-2203-005 FIGURE 4.4-WIRE SYSTEM TRIGGERED FROM ALARM RELAY CONTACT: UL LISTED ALARM CONTROL PANEL ALARM • PURPLE RELAY \ T. (NO Contact) EOL RELAY (SHOWN ENERGIZED) BROWNIS `• OUT+ 1+IN 1+IN • + YELLOW a 2+OUT 2+OUT DETECTOR IN+ POWER ORANGE 0 3-IN/OUT 3-IN/OUT IN- `• WHITE OUT- a 4 N.O. a 4 N.O. OR v SC SC AUX POWER+ • REO PWR+ DETECTOR BLACK POWER- PWR- `E�EOL + INITIATING DEVICE CIRCUIT S0104-00 CONNECTION DIAGRAMS WITH ADEMCO VISTA PANELS The connection diagrams enclosed show how to connect the 2WTA-B model smoke detector to the Vista panels using the System Sensor polarity reversal relay module(RRS-MOD).Please make sure that the smoke detectors are connected properly to the zones specified in the wiring diagrams for proper operation of the smoke detectors. FIGURE 5.CONNECTING 2WTA-B SMOKE DETECTORS TO ADEMCO CONTROLS USING RRS-MOD MODULE TRIGGERED FROM BELL/ALARM CIRCUIT: SYSTEM SENSOR REVERSING UL LISTED RELAY/SYNCHRONIZATION ALARM MODULE(RRS-MOD) CONTROL (MOUNT INSIDE CONTROL ENCLOSURE) PANEL BELL/ ALARM PURPLE CIRCUIT '+ (positive signal Programming information: in alarm state) _EOL L�2K OHMS • The supervisory feature for the bell cir- ADEMCO CONTROLMit must be turned off. See applicable PANEL ��• BROWN R 1+IN O 1+IN control manual for procedure. APPCLICABLE YELLOW CONTROLS: 2-WIRE 0 2+OUT 0 2+OUT VISTA-20 INITIATING VISTA-40 CIRCUIT_ ORANGE • A O 3.IWOUT 3-IN/OUT RRS-MOD Configuration: VISTA-50P 1 �. •WHITE 4N.0. O 4RA+ • Set switch on RRS-MOD to"OFF". VISTA-32FB VISTA-100 + 5 C + 5 C VISTA-126F6 1 + RED AUX POWER s5A( OPTIONAL SYSTEM SENSOR OPTIONAL BLACK - 4700 REMOTE 2WTA-B SMOKE REMOTE 1/2 WATT' ANNUNCIATOR DETECTORS ANNUNCIATOR S0105-02 (RA400Z/RA100Z)(UP TO 16 DETECTORS (RA400Z/RA100Z) PER ZONE) '4700 1/2 WATT RESISTOR NEEDED FOR PANEL TO RESET FIGURE 6.CONNECTING 2WTA-B SMOKE DETECTORS TO ADEMCO CONTROLS USING RRS-MOD MODULE TRIGGERED FROM AUXILIARY RELAY: NOT REQUIRED ON 5110XM SYSTEM SENSOR REVERSING UL LISTED WHEN 5100XM JUMPER W3 INTACT RELAY/SYNCHRONIZATION MODULE(RRS-MOD) ALARM (MOUNT INSIDE CONTROL ENCLOSURE) CONTROL PANEL AUXILIARY r0 Programming information: RELAY PURPLE to activate on fo T+ ; •oProgram Auxiliary relay EOL alarms 1_, 2K OHMS ADEMCO —0 • Assign Auxiliary relay as an output for CONTROL -----• BROWN 1+IN ill 1 1+IN PANEL zones programmed for fire alarm re- APPCLICABLE + YELLOW 2-WIRE O 2+oDT O 2+OUT sponse only(Types 9, 16,or 17) CONTROLS: SMOKE 5110XM ORANGE O 3-IN/OUT ZONE • • O 3-IN/OUT 5140XM - _• •WHITE -� RRS-MOD Configuration: VISTA-32FB 4RA+ /�OIJ 4RA+ V VISTA-100 5 RA- 'TJI 5 RA- • Set switch on RRS-MOD to"ON". AUXILIARY A • RED POWER 'N1 OPTIONAL SYSTEM SENSOR OPTIONAL OUTPUT BLACK - 4700 REMOTE 2WTA-B SMOKE REMOTE 1/2 WATT' ANNUNCIATOR DETECTORS ANNUNCIATOR (RA400Z/RA100Z) (UP TO 16 PER ZONE)DETECTORS (RA400Z/RA100Z) TAKE POWER FROM CONTROLS AUXILIARY POWER OUTPUT ONLY S0106-02 "4700 1/2 WATT RESISTOR NEEDED FOR PANEL TO RESET D500-44-00 3 I56-2203-005 CONNECTION DIAGRAMS WITH DSC POWER 832 PANELS FIGURE 7.CONNECTING 4WTA-B,4WTAR-B,AND 4WITAR-B SMOKE DETECTORS TO DSC All smoke detectors on the 4-wire fire zone will POWER 832 CONTROLS USING RRS-MOD MODULE WITH PGM OUTPUT: be synchronized in alarm and will sound 1 sec ON,1 sec OFF only from a fire alarm event. UL LISTED CONTROLO ALARM NOTE: PANEL DSC POWER 832 • Program zone section attributes for bell PGM 1 • PURPLE [ output to be pulsing. EOL RELAY (SHOWN ENERGIZED) • PGM2 must be programmed for sensor reset. �• BROWN / 1 S • • +IN 1+IN PGM1 must be programmed as Burglary AUX(+) YELLOW 0 2+ouT 2+OUT and Fire Bell Output (01) with ON, ON, PGM2 ORANGE • '3 3-muVA 3-IN/OUT OFF attributes. . WHITE a V 4N.O. .1 4N.O. WV Q 5C tig5C • RRS-MOD switch must be set to OFF (fac- tory default setting). AUX + RED AUX — BLACK EOL ZONE + S0107-02 ZONE(COM)— 'NOTE:5.61(0 resistor must be rated for 1/4W or greater.Must be present for panel to reset. FIGURE 8.CONNECTING 2WTA-B SMOKE DETECTORS TO DSC POWER 832 CONTROLS US- All smoke detectors on the 2-wire fire zone will ING RRS-MOD MODULE WITH PGM OUTPUT: be synchronized in alarm,and will sound 1 sec UL LISTED ON,1 sec OFF only from a fire alarm event. ALARM CONTROL NOTE: PANEL DSC POWER 832 i • Program zone section attributes for bell PGM 1 PURPLE EOL output to be pulsing. • PGM2 must be programmed for 2-wire smoke zone (04). Jumper J1 on the main board must be removed. -----... BROWN 01+IN 13 1+IN AUX(+) YELLOW • PGM1 must be programmed as Burglary PGM 2 MIN 2+our 0 3 IN/OUT -s 3-IN/OUT OUT and Fire Bell Output (01) with ON, ON, OFF attributes. - WHITE I v 4 N.O. 0.......:y N.O. 0 5 c s c • RRS-MOD switch must be set to OFF (fac- ��,541. tory default setting). AUX + RED S0108-02 AUX — BLACK *NOTE:5.6K0 resistor must be rated for 1/4W or greater.Must be present for panel to reset. TESTING Before testing, notify the proper authorities that the system is undergoing 3. Reset the system from the control panel. All smoke detector sounders maintenance and will temporarily be out of service. should be silent. Test in accordance with NFPA 72 test methods,inspections,and testing frequency. 4. If the fire alarm panel also functions in burglary,initiate a burglary alarm 1. Confirm that all smoke detectors connected to the RRS-MOD module(s) and ensure the smoke detectors do not sound. contain a sounder and the sounders are activated upon power reversal. 2. Initiate an alarm with one of the smoke detectors connected to the RRS- MOD module using any approved test method.In the alarm state,all the detectors connected to the RRS-MOD module must be sounding their sounders. THREE-YEAR LIMITED WARRANTY System Sensor warrants its enclosed product to be free from defects in materials and tt ,3825 Ohio Avenue,St.Charles,IL 60174.Please include a note describing workmanship under normal use and service for a period of three years from date of the malfunction and suspected cause of failure.The Company shall not be obligated to manufacture.System Sensor makes no other express warranty for the enclosed product. replace units which are found to be defective because of damage,unreasonable use, No agent,representative,dealer,or employee of the Company has the authority to in- modifications,or alterations occurring after the date of manufacture.In no case shall the crease or alter the obligations or limitations of this Warranty.The Company's obligation Company be liable for any consequential or incidental damages for breach of this or any of this Warranty shall be limited to the replacement of any part of the product which other Warranty,expressed or implied whatsoever,even if the loss or damage is caused by is found to be defective in materials or workmanship under normal use and service the Company's negligence or fault.Some states do not allow the exclusion or limitation of during the three year period commencing with the date of manufacture.After phoning incidental or consequential damages,so the above limitation or exclusion may not apply System Sensor's toll free number 800-SENSOR2 (736-7672) for a Return Authorization to you.This Warranty gives you specific legal rights,and you may also have other rights number,send defective units postage prepaid to:System Sensor,Returns Department,RA which vary from state to state. D500-44-00 4 I56-2203-005 ©System Sensor 2009