HomeMy WebLinkAboutB16-0087 Tab report.pdfTEST, ADJUST AND BALANCE REPORT PROJECT TOV FIRE STATION #1 #1263 PREPARED FOR R&H MECHANICAL REPORT ISSUE DATE 2/6/2017 PREPARED BY HVAC TAB lie P.O. BOX 1926 VAIL, CO 81658 PHONE: 970-376-5198 E-MAIL: mrichardson@hvactab.co ,.. . HVAC TAB lie TEST, ADJUST AND BALANCE REPORT THE DATA PRESENTED IN THIS REPORT IS AN EXACT RECORD OF SYSTEM PERFORMANCE AND WAS OBTAINED IN COMPLIANCE WITH NBC PROCEDURAL STANDARDS. ANY VARIANCES FROM THE DESIGN REQUIREMENTS ARE NOTED THROUGHOUT THIS REPORT. THE RESULTS SHOWN AND INFORMATION PRESENTED IN THIS REPORT IS CERTIFIED TO BE ACCURATE AND COMPLETE, TO THE EXTENT POSSIBLE BY EQUIPMENT AND PROCEDURES USED THROUGH- OUT THIS SURVEY. THE FINAL AIR DISTRIBUTION SYSTEM MEASUREMENTS ARE IN COMPLIANCE WITH NBC PROCEDURAL STANDARDS FOR TESTING, ADJUSTING AND BALANCING OF ENVIRONMENT AL SYSTEMS AND THE PROJECT SPECIFICATIONS. CERTIFIEDBY: ~~ DATE: 2./6/20J7 THE FINAL HYDRONIC DISTRIBUTION SYSTEM MEASUREMENTS ARE IN COMPLIANCE WITH NBC PROCEDURAL STANDARDS FOR TESTING, ADU STING AND BALANCING. OF ENVIRONMENT AL SYSTEMS AND THE PROJECT SPECIFICATIONS. HVAC TAB lie WARRANTS THAT THE AIR AND HYDRONIC SYSTEM EVALUATED DURING THIS SURVEY IS OPERATING AT THE SPECIFIED LEVELS AS SHOWN WITHIN THIS REPORT, AT AND ONLY AT THIS TIME. HVAC TAB lie MAKES NO OTHER WARRANTIES, STATED OR IMPLIED, CONCERNING THE CONTINUED PERFORMANCE, OPERATION OR SAFETY IN THE USE OF THIS EQUIPMENT PASS THIS TIME. CERTIFIED Page: I I 13-004-03 Expires 2/22/2017 NATIONAl. BAIA"'10NG (OUNQL HVAC TAB lie DATE: 2/3/2017 PROJECT: TOY FIRE STATION #1 PROJECT ALTITUDE: "HG INSTRUMENT/ SERIAL# APPLICATION DATE OF USE SHORTRIDGE ADM-870C I #M0921 l AIR FLOW READINGS 2/3/2017 ANEMOMETER #T57251515001 AIR FLOW READINGS 2/3/2017 SHORTRIDGE FLOW HOOD AIF FLOW READINGS NOT USED TH-720 HYGROMETER/ #TH7200950003 AIR TEMP I HUMIDITY NOT USED PITOT TUBE 18" PRES. READINGS 2/3/2017 PITOT TUBE 24" PRES. READINGS NOT USED PITOT TUBE 36" PRES. READINGS NOT USED PITOT TUBE 48" PRES. READINGS NOT USED SHIMPO TACHOMETER I #Cl05B0010 RPM READINGS NOT USED FLUKE 375 I #21290229 VOLT I AMP 2/3/2017 SHORTRIDGE HDM-250/ #W08162 WATER PRES. READINGS 2/3/2017 A SCRO FT I 0-100 PSI I #D068332-06 WATER PRES. READINGS NOT USED FLUKE 52 II THERMOMETER I 99780167 TEMP. READINGS NOT USED REFRACTOMETER RHA-100 I #RHA-GLYCOL% READINGS NOT USED 100 INSTRUMENT CALIBRATION REPORT CALIBRATION CALIBRATION DATE DUE DATE 06/02/2016 0610212017 05/06/2016 0510612017 * * 0610312016 06/03/2017 NIA NIA NIA NIA NIA NIA NA NA 0610212016 0610212017 06/02/2016 0610212017 0610212016 06/02/2017 * * 0610312016 0610312017 NIA NIA *CHECKED TO CALIBRATED METER REMARKS: ALL READINGS WITH SHORTRIDGE INSTRUMENTS ARE CORRECTED FOR TEMPERATURE AND ALTITUDE. PAGE: HVACTAB lie ERV FAN TEST REPORT DATE: 2/3/2017 PROJECT: TOV FIRE STATION #1 SYSTEM: ERV-1 I HRV-1 FAN NUMBER ERV-1 HRV-1 UNIT DATA UNIT DATA UNIT DATA MANUFACTURER RENEW AIRE ALOES MODEL HE1XIN H650-FI SERIAL G162545C H650-FI 1609002 SCHEDULE RATING/OUTLET TOTAL 800CFM@0.5"ESP 31 OCFM@0.8"ESP MOTOR DATA MOTOR DATA MOTOR DATA MANUFACTURER ---- MOTOR HP RPM 2X 0.75 --- PHASE FRAME ---- S.F. TYPE ---- VOLTS AMPS 115 9.0 120 5.5 DRIVE DATA DRIVE DATA DRIVE DATA MOTOR DRIVE BORE DD DD DD DD FAN DRIVE BORE DD DD DD DD NO. BELTS SIZE DD DD DD DD DRIVE CHANGE ROTATION DD CORRECT DD CORRECT ST ARTER DAT A STARTER DATA STARTER DATA MFG. MODEL NONE NONE NONE NONE RANGE SET AT (AMPS) NONE NONWE NONE NONE SET AT HERTZ REQ. THERM NONE NONE NONE NONE THERMAL PROTECTION NONE NONE NONE NONE TEST DATA TEST DATA TEST DATA CFM VOLTS 837 S / 868 R 123 320 S / 330 R 122 FAN RPM AMPS DD NA DD 5.1 RETURN -0.36" I EXHAUST 0.15" RETURN -0.16" I EXHAUST 0.15" @/ @/ OUTSIDE AIR-0.36" I I SUPPLY 0.08" OUTSIDE AIR-0.03" I SUPPLY 0.25" NOTES: PAGE: HVACTAB lie DATE: 2/3/2017 PROJECT: TOV FIRE STATION #1 SYSTEM TERMINAL NO TYPE SIZE AK ERV-I SUPPLY I SR 919 2 SR 919 3 SR 23/5 4 SR 9.5/9.5 5 SR 919 6 SR 919 7 SR 919 8 SR 23/5 ERV-I-RETURN I ER 919 2 ER 919 3 ER 919 4 ER 919 5 ER 919 6 ER 919 NOTES: SYSTEM: ERV-1 DESIGN INITIAL VEL CFM VEL CFM 50 0 IOO 35 200 I22 IOO NF 50 44 50 I04 50 67 200 98 800 470 IOO 0 50 0 100 0 50 0 IOO 0 200 66 600 66 AIR TERMINAL TEST REPORT FINAL NOTES VEL CFM 54 II6 2I7 I02 52 53 48 I95 837 TOTAL I49 77 I57 75 I37 273 868 TOTAL PAGE: HVACTAB lie DATE: 2/3/2017 PROJECT: TOV FIRE STATION #1 SYSTEM TERMINAL NO TYPE SIZE AK HRV-1 SUPPLY 1 SR 23/5 2 SR 919 3 SR 23/5 4 SR 23/5 5 SR 23/5 6 SR 23/5 HRV-1 RETURN 1 ER 5"R 2 ER 919 3 ER 919 4 ER 919 5 ER 919 EF-2 1 ER 10/10 NOTES: DESIGN VEL CFM 50 50 50 50 60 50 310 50 70 100 50 50 320 145 AIR TERMINAL TEST REPORT SYSTEM: HRV-1 I EF-2 INITIAL FINAL NOTES VEL CFM VEL CFM 62 53 66 50 40 52 165 48 147 65 58 52 538 320 TOTAL 54 53 146 66 44 109 128 54 104 48 476 330 TOTAL 248 248 TOTAL PAGE: HVACTAB lie ERV FAN TEST REPORT DATE: 2/3/2017 PROJECT: TOV FIRE STATION #1 SYSTEM: HRV-2 I HRV-3 FAN NUMBER HRV-2 HRV-3 UNIT DATA UNIT DATA UNIT DATA MANUFACTURER ALOES AL DES MODEL H 650-FI H 650-FI SERIAL H650-FI 1608002 H650-FI 1608003 SCHEDULE RATING/OUTLET TOTAL 31 OCFM@0.8"ESP 31 OCFM@0.8"ESP MOTOR DATA MOTOR DATA MOTOR DATA MANUFACTURER ---- MOTOR HP RPM ---- PHASE FRAME ---- S.F. TYPE ---- VOLTS AMPS 120 5.5 120 5.5 DRIVE DATA DRIVE DATA DRIVE DATA MOTOR DRIVE BORE DD DD DD DD FAN DRIVE BORE DD DD DD DD NO. BELTS SIZE DD DD DD DD DRIVE CHANGE ROTATION DD CORRECT DD CORRECT STARTER DATA STARTER DATA STARTER DATA MFG. MODEL NONE NONE NONE NONE RANGE SET AT (AMPS) NONE NONE NONE NONE SET AT HERTZ REQ. THERM NONE NONE NONE NONE THERMAL PROTECTION NONE NONE NONE NONE TEST DATA TEST DATA TEST DATA CFM VOLTS 301S/318R 121 296 SI 281 R 121 FAN RPM AMPS DD 4.8 DD 5.4 RETURN -0.21" I EXHAUST 0.15" RETURN -0.22" I EXHAUST 0.31" @7 @/ OUTSIDE AIR -0.09" I I SUPPLY 0.23" OUTSIDE AIR-0.19" I SUPPLY 0.25" NOTES: PAGE: HVACTAB lie DATE: 2/3/2017 PROJECT: TOV FIRE STATION #1 SYSTEM TERMINAL NO TYPE SIZE AK HRV-2 SUPPLY 1 SR 1315 2 SR 1315 HRV-2-RETURN 1 ER 919 2 ER 13/5 HRV-3-SUPPL Y I SR 1315 2 SR 13/3.5 3 SR 13/5 HRV-3-RETURN I ER 919 2 ER 919 3 ER 13/5 NOTES: DESIGN VEL CFM 50 250 300 100 200 300 50 50 200 300 100 100 100 300 AIR TERMINAL TEST REPORT SYSTEM: HRV-2 I HRV-3 INITIAL FINAL NOTES VEL CFM VEL CFM 151 50 209 251 360 301 TOTAL 108 108 410 210 518 318 TOTAL 0 48 0 52 205 196 205 296 TOTAL 81 94 40 94 ill 93 233 281 TOTAL PAGE: HVACTAB lie DATE: 2/3/2017 PROJECT: TOV FIRE STATION #1 FLOW METER LOCATION TYPE SIZE HX BL SIDE TACO 2" HX SM SIDE TACO 2" HC-1-ERV-1 TACO 3/4 HC-2-HRV-1 TACO 3/4 HC-3-HRV-2 TACO 3/4 HC-4-HRV-3 TACO 3/4 P-4 TACO 2" P-5 TACO 1 1/4" NOTES: BALANCE VALVE TEST REPORT SYSTEM: HX-1 I HC-1-4 / P-4 / P-5 DESIGN MEASURED DESIGN DESIGN VALVE ,6p GPM FINAL.6 P POSITION FINALGPM %OPEN 37.9 17.6 100% 37.9 33.6 12.5 100% 32.0 4.8 29.4 100% 3.3 1.4 5.3 50% 1.4 1.4 5.4 94% 1.45 1.4 5.0 100% 1.37 26.0 7.3 100% 25.0 10.2 8.6 100% 7.5 PAGE: HVACTAB lie PUMP TEST REPORT DATE: 2/3/2017 PROJECT: TOV FIRE STATION #1 SYSTEM: P-1 I P-2 PUMP IDENTIFICATION P-1 P-2 MANUFACTURER GRUNDFOS GRUNDFOS Ii. MODEL NUMBER I TYPE UP 26-96F/VS UP 26-96F/VS ::!: ::::> SERIAL NUMBER PC-1622 PC-1622 Ii. RATING GPM RATING Ft. Hd. 26.5 GPM Ft. Hd. 26.5 GPM Ft. Hd. MANUFACTURER -- MOTOR HP RPM ix: (KW) ---- 0 I-PHASE FRAME 1 -1 -0 ::!: S.F. TYPE ---- VOLTS AMPS 115 1.7 115 1.7 MANUFACTURER NONE NONE MODEL NONE NONE ix: SIZE NONE NONE w I-RANGE NONE NONE ix: <( I-SETTING (AMPS) NONE NONE en REQUIRED THERMAL NONE NONE RATING AMPS NONE NONE PUMP OFF PRESSURE P1 PSI FT. HD. PSI FT. HD. VALVE SHUT DIFFERENTIAL PSI FT. HD. PSI FT. HD. c INDICATED/ACTUAL IMPELLER DIAMETER w ix: VALVE OPEN DIFFERENTIAL PSI 3.8 FT. HD. PSI 4.38 FT. HD. ::::> en VALVE OPEN GPM 27.0 26.5 <( w ::!: DISCHARGE PRESSURE PSl/Ft.Hd P1 39.8 34.7 SUCTION PRESSURE PSl/Ft.Hd P2 36.0 30.3 [:.. P PSI I Ft. Hd. 3.8 4.38 DISCHARGE PRESSURE PSI I Ft. Hd. P1 PSI 39.8 FT. HD. PSI 34.7 FT. HD. SUCTION PRESSURE PSI I Ft. Hd. P2 PSI 36.0 FT. HD. PSI 30.3 FT. HD. .J Dp PSI I Ft. Hd. PSI 3.8 FT. HD. PSI 4.38 FT. HD. <( z u::: GPM 27.0 26.5 VOLTS NA NA AMPS NA NA NOTES: NA DENOTES NO ACCESS PAGE: HVACTAB lie DATE: PROJECT: TOV FIRE STATION #1 PUMP IDENTIFICATION MANUFACTURER D.. MODEL NUMBER I TYPE ~ :::J SERIAL NUMBER D.. RATINGGPM RATING Ft. Hd. MANUFACTURER MOTOR HP RPM 0:: (KW) 0 I-PHASE FRAME 0 ~ S.F. TYPE VOLTS AMPS MANUFACTURER MODEL 0:: SIZE w I-RANGE 0:: <C I-SETTING (AMPS) en REQUIRED THERMAL RATING AMPS PUMP OFF PRESSURE P1 VALVE SHUT DIFFERENTIAL c INDICATED/ACTUAL IMPELLER DIAMETER w 0:: :::J VALVE OPEN DIFFERENTIAL en VALVE OPEN GPM <C w ~ DISCHARGE PRESSURE PSl/Ft.Hd P1 SUCTION PRESSURE PSl/Ft.Hd P2 6. P PSI I Ft. Hd. DISCHARGE PRESSURE PSI I Ft. Hd. P1 SUCTION PRESSURE PSI I Ft. Hd. ....I D. P PSI I Ft. Hd. <C z u:::: GPM VOLTS AMPS NOTES: *3 DENOTES NO PETES PORTS NA DENOTES NO ACCESS P2 PUMP TEST REPORT SYSTEM: P-3 I P-4 P-3 I P-4 I GRUNDFOS GRUNDFOS UP 26-96FNS UPS 43-100 PC-1629 PC-1634 28 GPM Ft. Hd. 26 GPM Ft. Hd. -- ---- 1 -1 - ---- 115 1.7 115 2.5/3.1/3.5 NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE PSI FT. HD. PSI FT. HD. PSI FT. HD. PSI FT. HD. PSI 3.2 FT. HD. PSI FT. HD. 28.5 *3 36.2 33.0 3.2 PSI 36.2 FT. HD. PSI FT. HD. PSI 33.0 FT. HD. PSI FT. HD. PSI 3.2 FT. HD. PSI FT. HD . 28.5 25.0 (SPD-3) NA NA NA NA PAGE: HVACTAB lie PUMP TEST REPORT DATE: 2/3/2017 PROJECT: TOV FIRE STATION #1 SYSTEM: P-5 I P-6 PUMP IDENTIFICATION P-5 P-6 MANUFACTURER GRUNDFOS GRUNDFOS ll.. MODEL NUMBER I TYPE UPS 26-64 F UPS 50-60 F :!:: => SERIAL NUMBER PC-1604 PC-1631 ll.. RATINGGPM RATING Ft. Hd. 10.2 GPM Ft. Hd. 37.9 GPM Ft. Hd. MANUFACTURER -- MOTOR HP RPM 0:.:: (KW) ---- 0 I-PHASE FRAME 1 -1 -0 :!:: S.F. TYPE ---- VOLTS AMPS 115 1.7 115 2.7/3.4/3.6 MANUFACTURER NONE NONE MODEL NONE NONE 0:.:: SIZE NONE NONE w I-RANGE NONE NONE 0:.:: <( I-SETTING (AMPS) NONE NONE (/) REQUIRED THERMAL NONE NONE RATING AMPS NONE NONE PUMP OFF PRESSURE P1 PSI FT. HD. PSI FT. HD. VALVE SHUT DIFFERENTIAL PSI FT. HD. PSI FT. HD. c INDICATED/ACTUAL IMPELLER DIAMETER w 0:.:: VALVE OPEN DIFFERENTIAL PSI 20.9 FT. HD. PSI FT. HD. => (/) VALVE OPEN GPM 7.5 *3 <( w :!:: DISCHARGE PRESSURE PSl/Ft.Hd P1 67.6 SUCTION PRESSURE PSl/Ft.Hd P2 46.7 !:::,. P PSI I Ft. Hd. 20.9 DISCHARGE PRESSURE PSI I Ft. Hd. P1 PSI FT. HD. PSI FT. HD. SUCTION PRESSURE PSI I Ft. Hd. P2 PSI FT. HD. PSI FT. HD. ...J ID P PSI I Ft. Hd. PSI FT. HD. PSI FT. HD. <( z u:::: GPM 7.5 37.9 ( SPD-3) VOLTS NA NA AMPS NA NA NOTES: NA DENOTES NO ACCESS PAGE: I HVACTAB lie PUMP TEST REPORT DATE: 2/3/2017 PROJECT: TOV FIRE STATION #1 SYSTEM: P-7 I DHWP PUMP IDENTIFICATION I P-7 DHWP MANUFACTURER GRUNDFOS GRUNDFOS a.. MODEL NUMBER I TYPE UPS 32-160F UP 50-75F :::!!: ::::> SERIAL NUMBER a.. RATING GPM RATING Ft. Hd. 33.6 MANUFACTURER MOTOR HP RPM 0::: {KW) - 0 I-PHASE FRAME 1 0 :::!!: S.F. TYPE - VOLTS AMPS 115 MANUFACTURER MODEL 0::: SIZE w I-RANGE 0::: <( I-SETTING {AMPS) en REQUIRED THERMAL RATING AMPS PUMP OFF PRESSURE P1 VALVE SHUT DIFFERENTIAL 0 INDICATED/ACTUAL IMPELLER DIAMETER w 0::: ::::> VALVE OPEN DIFFERENTIAL en VALVE OPEN GPM <( w :::!!: DISCHARGE PRESSURE PSl/Ft.Hd P1 SUCTION PRESSURE PSl/Ft.Hd P2 6 P PSI I Ft. Hd. DISCHARGE PRESSURE PSI I Ft. Hd. P1 SUCTION PRESSURE PSI I Ft. Hd. P2 ...I ID P PSI I Ft. Hd . <( z u: GPM VOLTS AMPS NOTES: *1 DENOTES NO PETES PORTS I NO CIRCUIT SETTER *3 DENOTES NO PETES PORTS NA DENOTES NO ACCESS PC 1622 PC-1616 GPM Ft. Hd. GPM -- -- -1 -- 5.5/5.8/5.8 115 NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE NONE PSI FT. HD. PSI PSI FT. HD. PSI PSI FT. HD. PSI *3 *1 PSI FT. HD. PSI PSI FT. HD. PSI PSI FT. HD. PSI 32.0 (SPD-3) *1 NA NA NA NA PAGE: Ft. Hd. - - - 2.15 FT. HD. FT. HD. FT. HD. FT. HD. FT. HD. FT. HD. NORTH DIAN ~ l TI' 11 ©~ ~ 11 II 1· II II \:© 0 @G'.l~ II I TI' 11 ©~ ~ GENERAL NOTES: , ALL DUCT\'\'ORK DIMENSIONS ARE SHOW'\; INSIDE ro INSIDE. DIMENSIONS 1\1 i 1 INJ!CATE OUTER SIZES WlTH l'JSULATION. TrlESE SIZES MJl.Y DIFFER BASE:J ON THE SELECTED lNSt.:LATION. VERIFY IN FIELD PRIOR T 0 INST ALL.i\ TION. 2. ALL IN1E~l0R SUPPL V A~D RETURN DUCTWORK StiALL INCLUDE , .. !.lt-..ER UNLESS OTt-IERVVISE NOTED. ALL OUTSICE AJR IN"! AKE MD ROL!t·,:J DVCl\VORK SHALL BE WHAPPEO \-Vi-t-i 1 S THICK lt'-.S.JLATION Ur-.LESS QTHERi'VJSE:. NOTED :i All FNA:... DUCTWORK CO!'.NECTIO~S TC SUPPLY GRL..LES (OR PLENUVS SMALL BE GJMPLEl E:D WI rH ACOUSTICAL f-LEXl5LE DUCT UNLESS OTHERWISE NOTED ANO A MAXJMUfi.1 LENGTH OF FIVE FE:E T ·1 All ROUND DUCT CONNECTIONS TO ROUND DUCTVJORK S~1ALL BE CONICAL TEtS. S Al L SQUARE 90 DEGREE ELBOWS $'-!All HAVE TURNING VANES 6 ALL DUCTWORK S--IAll BE RUN TIG'"IT TO UNOE'~SIOE OF S1R'-1CTL.RE WHERE IT EXISTS UNLESS OTHERWISE NCH CO. 7, t~LL DUCTWORK PASSING THROUGH nRE+RATE:J f,SsEMBLIES SH,!>,LL J\.!CLUDE FIRE DAMPERS RATED TO MATCH TH!~T OF THE ASSl.:WL v 8. All SUPPLY GRILLES SHALL HAVE INC~VDE A BALANCING Dft.t .• i;;i.ER UNLESS OTl-!ER'.\rlSE NOTED (::.VEr>. THOUGH THEY MAY NUT BE :5H0Vfr~ EVERYWHERE). I"° THE DAMPER IS '-OCATEO IN .\N INACCESSISU:. LOCATION, CASU:·ST'ILE DAMPERS (ROTOTVVIST OR EQJ!VALH. T,i SHi\lL BE INSTALLED A\10 SHALL BE ADJUSTABLE FROM THE G~1\.LE FACE MUL TlPLE RETURN DIFFUS!:RS IF SERVED SY A cor .. 1~.~0N HE_ 1 i...;RN CVCH'',ORK SHALL BE EQUIPPED \>VITH 13ALANCING DAMPERS 9 COOROll\ATE All ACCFSS PA'>!El LOCATIONS 'l/JTH THE AR.CrlJTEC--:-- SHEET DETAIL NOTES: 011\'STALL HRV-2 IN HQRIZONlAL POSITION {00° ROTATEOj, VERIFY \'\1TH IVANUFAClURER PRIOR TO ORDERING. INSTALL eoo ON EXHAUST A."'10 MOTORIZED DA\.!PER ON OA INTAKE DUCH'.'ORK. COORDINATE ACCESS PANEL (MIN. 3fo:48 OR ECUIVALE"'T'WITH ARCHITCCT AND G.C. IN F!ELD. 0 lNSrA;,,,L ~C.3, INTERLOCK VNAY MODULATING VALVE WITH THE DUCT MOUNTED SENSOR (IN TH;;; l-'RV·2 DISCHARGE DUCT,. VERIFY COL Dl~JE"JSIONS AND SPAC~ REOUIF\.EMENTS IN FIELD PRIOR TO COIL f.'Uf'(Ct1ASE:. AOJUS r SIZE AND CONNECTION SIDE PER FIELD MEASUREMENTS. CONTACT ENGINEER FOR ASSIST Af•CL If-REOUIR~D 0 VERIFY STATE AND ADEQl.;ACY OF THE EXISTING EF-1. IF ACCEPTA3LE RHJSE AND RELOCATE TO TH1S LOCATION JN THE HALLV/AY VO!O SPACE. G.C, TO PROVIDE ACCESS PANL !MIN. 36x36 OR EQUIVALENT) FOR SERVICE ANO MAlNfENANCE. IF THE FAt\ CANN:JT EE REUSED REPLACE 'v\'ITH TYE NE'N ONE. 0 ;iRO'JlDE NH\' SlLENCFR IF REQUIRED VERIFY WI',... TH[ ~~ANUFACTURER. GTHERWISE OMlT. 0 G.C.10 PROVIDE SH.1.r.'" FOR THE EXHAUSTS, MAINTAIN MN.;~ C:LEAR.ANCE 10R AS PER MANUFACTURER) :o COMBUSTIBLES COCR;Jl~ATS JN FIELD PRIOR TO INSTALLATIOI\_ VE'RIFY VFN1S SIZES WITt1 r,1f'.NLIFACTURER PR.OR TO INSTALLATION. 30C-EX LEVEL 2 HVAC PLAN NORTH L 300-0/i 10 ~&x12 T66S:71, __ 72 ,- l 10 BB..69 7J Jil t_ TOBB~73~75 NORTH =L 5 (EHU LOFT) HVAC PLAN ~