Loading...
HomeMy WebLinkAboutB16-0087_A0-09_1465941540.pdf2X6 DIMENSIONAL LUMBER 5/8" GYPSUM WALL BOARD INTERIOR SELF FURRING LATH EXTERIOR 1 LAYER ASPHALTIC BUILDING PAPER STRUCTURAL SHEATHING, RE: STRUCTURE W1-2 5/8" GYP. = 40 MIN. 2x6 FRAMING @ 16" O.C.= 20 MIN. BATT INSULATION = 15 MIN. FIRE RATING (1-HOUR MIN.) : SHEATHING = 20 MIN. 3 COAT STUCCO SYSTEM CLOSED CELL SPRAY-IN INSULATION, R-21 MIN. 2X6 DIMENSIONAL LUMBER 5/8" GYPSUM WALL BOARD INTERIOR EXTERIOR CLOSED CELL SPRAY-IN INSULATION, R-21 MIN. BUILDING WRAP STRUCTURAL SHEATHING, RE: STRUCTURE W1-1 5/8" GYP. = 40 MIN. 2x8 FRAMING @ 16" O.C.= 20 MIN. BATT INSULATION = 15 MIN. FIRE RATING (1-HOUR MIN.) : SHEATHING = 20 MIN. CEMENTITIOUS SIDING 5/8" GYPSUM WALL BOARD 5 1/2" W2-6 2X6 DIMENSIONAL LUMBER, SEE PLANS AND WALL TAG FOR STUD SIZE, TYP. SOUND BATTS 5/8" GYPSUM WALL BOARD 3 1/2" W2-4 2X4 DIMENSIONAL LUMBER, SEE PLANS AND WALL TAG FOR STUD SIZE, TYP. SOUND BATTS GENERAL ASSEMBLY AND FINISH SYSTEMS Note: Reference structural drawings and specifications for all fasteners within all building assemblies including but not limited to nails, screws & bolts for size (length, diameter & shank), type, style & spacing. Contact Architect with any discrepancies prior to ordering and installation of product in assembly. All products are to be installed in strict conformance with product specifications, requirements and warranties. Contact Architect with any discrepancies prior to ordering product. Refer to both architectural and structural drawings for assembly information. Structural drawings shall govern over architectural drawings regarding framing. Architectural drawings shall govern over structural drawings regarding wall location dimensions, fire, sound and weather proofing related details. Contact Architect immediately with any discrepancy prior to installation of the work. Install all fire rated assemblies per their listings as referenced with options shown. The following assembly narratives are general. WALL SYSTEMS: FLOOR ASSEMBLIES: F1-W VINYL PLANK ON EXISTING FLOOR ASSEMBLY Vinyl plank installed per manufacturer's specifications,over 1/4" AcoustiMat II underlayment on 3/4" T & G APA rated (exposure 1) wood structural panels over Pre-Manufactured floor trusses at 16" o.c. maximum spacing (Re: Structural Drawings.) Install (1) layer 5/8" Type "x"gypsum board ceiling on Resilient Channels 7/8" deep, 26 gauge galvanized steel @ 16"o.c. on U/S of trusses. F1-C CARPET ON EXISTING FLOOR ASSEMBLY Carpet and pad, installed per manufacturer's specifications, over 1/4" AcoustiMat II underlayment on 3/4" T & G APA rated (exposure 1) wood structural panels over Pre-Manufactured floor trusses at 24" o.c. maximum spacing (Re: Structural Drawings.) Install (1) layer 5/8" Type "X" gypsum board ceiling on Resilient Channels 7/8" deep, 26 gauge galvanized steel @ 16"o.c. on U/S of trusses. C1 GYPSUM BOARD CEILING CONSTRUCTION (1Hr-Rated) UL DESIGN NO. L521 & UL P533 5/8" Gypsum board on 7/8" furring channels attached to underside of floor trusses or joists. (TYPICAL FOR ALL CEILINGS) Note: Typical ceiling system included in floor assemblies. Re: floor assemblies. CEILING SYSTEMS: FLOOR SYSTEMS: Note: Reference structural drawings and specifications for all fasteners within all building assemblies including but not limited to nails, screws & bolts for size (length, diameter & shank), type, style & spacing. Contact Architect with any discrepancies prior to ordering and installation of product in assembly. All products are to be installed in strict conformance with product specifications, requirements and warranties. Contact Architect with any discrepancies prior to ordering product. Refer to both architectural and structural drawings for assembly information. Structural drawings shall govern over architectural drawings regarding framing. Architectural drawings shall govern over structural drawings regarding wall location dimensions, fire, sound and weather proofing related details. Contact Architect immediately with any discrepancy prior to installation of the work. Install all fire rated assemblies per their listings as referenced with options shown. The following assembly narratives are general. NOTES ** Interior Walls Studs: 4 - 2x4 Wood Studs 6 - 2x6 Wood Studs 8 - 2x8 Wood Studs RE: See wall tags for stud sizes. **** Use water and mold resistant non-paper-faced substrate at shower walls and plumbing walls; moisture resistant non-paper-faced substrate at all other bathroom and restroom walls; water, mold, and indentation resistant non-paper-faced underlayment for all carpet, vinyl, and tile interior floor covering over slab on grade where recommended by manufacturer. Maintain required fire-rating. Refer to Structural Drawings for Bearing Walls and Shear Walls. RATED ASSEMBLIES (EXTERIOR): W1-1 CEMENTITIOUS SIDING @ RATED EXTERIOR WALLS Cementitious siding over (1) layer of Tyvek building wrap on structural sheathing (per structural design) @ exterior face of 2x6 dimensional lumber studs w/ min. R-21 closed cell spray-in foam insulation between studs. (1) layer 5/8" gypsum board @ interior face of studs. Interior finish will be paint or FRP panels, see room finish schedule for finish. (Re: Structural for size and spacing of studs and sheathing). W1-2 STUCCO @ RATED EXTERIOR WALLS 3 coat stucco system over self-furring metal lathe over 15 lb asphaltic building paper, 2x6 dimensional lumber studs w/ R-21 closed cell spray-in foam insulation between studs. (1) layer 5/8" gypsum board @ interior face of studs. (Re: Structural for size and spacing of studs and sheathing). W1-3 CEMENTITIOUS SIDING ON BOTH SIDES @ EXTERIOR WALLS Cementitious siding over (1) layer of Tyvek building wrap on structural sheathing (per structural design) @ both exterior faces of 2x6 dimensional lumber studs w/ min. R-21 closed cell spray-in foam insulation between studs. (Re: Structural for size and spacing of studs and sheathing). W1-4 STUCCO ON CMU @ RATED EXTERIOR WALLS 3 coat stucco system over self-furring metal lathe over 15 lb asphaltic building paper, on structural sheathing (per structural design) over 2x4 dimensional lumber studs w/ R-21 closed cell spray-in foam insulation between studs. Stud wall over 8" CMU wall, interior CMU face to be painted and recieve vinyl base. (Re: Structural for size and spacing of studs and sheathing). NON-RATED ASSEMBLIES (INTERIOR): W4-*** GYPSUM BOARD PARTITION ON 2X DIMENSIONAL LUMBER STUDS (Non-Rated) (1) Layer 5/8" gypsum board**** on each side of 2x dimensional lumber studs at non-bearing walls, demising bedrooms and living areas. Sound batt insulation. (Re. Structural for size and spacing). W5- GYPSUM BOARD OVER FURRING (Non-Rated) (1) Layer 5/8" gypsum board**** over 1 1/2" metal furring strips @ 16" O.C. with 1 1/2" rigid insulation. (Re. Structural for size and spacing). (1Hr-Rated), R-50 R1 NEW METAL ROOF CONSTRUCTION: New metal roof to match existing metal roof. Install over Vycor ice and water shield. Note: Install ice and water 24" up at vertical wall interface. Typical. Note: Install snow retention system and heat tape in accordance with manufacturer's instructions. 110 MPH Wind resistance (ASTM D 3161), Class 4 impact resistance (UL 2218), ICC-ES (ESR-2119), Miami Dade Code Approval ROOF SYSTEMS: 8" CMU BLOCK W4-8 INTERIOR PAINT 7 5/8" 4" CMU BLOCK W4-6 6" METAL STUD BATT INSULATION SPACE FOR PLUMBING 5/8" GYPSUM WALL BOARD 2X6 DIMENSIONAL LUMBER 5/8" GYPSUM WALL BOARD EXTERIOR CLOSED CELL SPRAY-IN INSULATION, R-21 MIN. BUILDING WRAP STRUCTURAL SHEATHING, RE: STRUCTURE W1-3 CEMENTITIOUS SIDING BOTH SIDES EXTERIOR 8" CMU BLOCK W4-9 INTERIOR PAINT 7 5/8" FULL GROUT, FULL HEIGHT OF WALL 2X4 DIMENSIONAL LUMBER FRAMING 8" CMU BLOCK INTERIOR EXTERIOR RIGID INSULATION, R-21 MIN. SHEATHING W1-4 SELF FURRING LATH 1 LAYER ASPHALTIC BUILDING PAPER 3 COAT STUCCO SYSTEM 1650 Fallridge Road, Suite C-1 Vail, Colorado 81657 f.(970) 476-4901 p.(970)476-6342 LOT 15 BIGHORN SUBDIVISION 4116 COLUMBINE DRIVE VAIL, CO 81657 A0.09 ASSEMBLIES VAIL FIRE STATION # 1 Project Number - 1547 04.29.2016 PERMIT SUBMITTAL 3" = 1'-0" 2 WALL ASSEMBLY W1-2 - 3-COAT STUCCO SYSTEM 3" = 1'-0" 1 WALL ASSEMBLY W1-1 - CEMENTITOUS SIDING 1 1/2" = 1'-0" 8a WALL ASSEMBLY W2-6 - 2X6 DIMENSIONAL LUMBER INTERIOR PARTITION 1 1/2" = 1'-0" 4 WALL ASSEMBLY W4-4 - 2X4 DIMENSIONAL LUMBER INTERIOR PARTITION 1 1/2" = 1'-0" 13a WALL ASSEMBLY W4-8 - 8" CMU INTERIOR WALL 1 1/2" = 1'-0" 12a WALL ASSEMBLY W4-6 - 4" CMU / PLUMBING WALL INTERIOR WALL 3" = 1'-0" 3 WALL ASSEMBLY W1-3 - CEMENTITOUS SIDING - BOTH SIDES 1 1/2" = 1'-0" 5 WALL ASSEMBLY W4-8 - 8" CMU INTERIOR WALL (FULL GROUT / FULL HEIGHT) 3" = 1'-0" 6 WALL ASSEMBLY W1-6 - CMU W/ 3 COAT STUCCO SYSTEM 06/14/16