HomeMy WebLinkAboutB16-0087_E1.0_1478901749.pdfH/P HEAT/PHOTOELECTRIC SMOKE DETECTOR
ELECTRICAL LEGEND
(NOT ALL SYMBOLS REQUIRED FOR THIS PROJECT)
RECESSED OR SURFACE DOWNLIGHT
WALL MOUNTED LIGHT FIXTURE
RECESSED FLUOR. LIGHT FIXTURE
SURFACE FLUOR. LIGHT FIXTURE
Aa
Aa
FIXTURE DESIGNATIONS:
UPPER CASE - FIXTURE TYPE
LOWER CASE - SWITCH DESIGNATION
SHADING ON FIXTURE INDICATES EMERG. BATTERY BACKUP
FLUORESCENT STRIP FIXTURE
TRACK LIGHT AS NOTED OR SCHEDULED
WALL WASHER
POLE-MOUNTED FIXTURE
POST (BOLLARD) FIXTURE
CEILING OR WALL MOUNTED EXIT LIGHT
EMERGENCY BATTERY LIGHTS
DUPLEX RECEPTACLE @ 18" UNLESS NOTED
DOUBLE DUPLEX RECEPTACLE @ 18" UNLESS NOTED
SPECIAL OUTLET AS NOTED
FLUSH FLOOR DUPLEX RECEPTACLE
DUPLEX RECEPTACLE HALF-SWITCHED @ 18" UNLESS NOTED
TELE-POWER POLE
JUNCTION BOX IN FLOOR, CEILING OR IN WALL
MULTI-OUTLET PLUG STRIP
COMPUTER/TELEPHONE OUTLET IN FLOOR OR WALL
CONDUIT RUN CONCEALED IN WALL OR ABOVE CEILING
TELEPHONE BACKBOARD
CIRCUIT HOMERUN
CONDUIT RUN BELOW FLOOR OR GRADE
CONDUIT STUB-UP - CAP & MARK
LIGHT SWITCH AT 46" UNLESS NOTED
SUBSCRIPTS:
2 = 2-POLE SWITCH
3 = 3-WAY SWITCH
4 = 4-WAY SWITCH
K = KEY-OPERATED SWITCH
TO = THERMAL OVERLOAD SWITCH
P = SWITCH WITH PILOT LIGHT
DIMMER SWITCH W/ WATTAGE
MAGNETIC MOTOR STARTER
DISCONNECT SWITCH
PANELBOARD OR LOAD CENTER, FLUSH OR SURFACE MOUNTED
SWITCHBOARD, MOTOR CONTROL CENTER OR DISTRIBUTION BD
TRANSFORMER
GROUND
PUSHBUTTON CONTROL STATION
PHOTOELECTRIC CELL
TIME SWITCH
THERMOSTAT AT 60" UNLESS NOTED
DIVISION 15 EQUIPMENT
CIRCUIT BREAKER
MOTOR OUTLET
AUTOMATIC TRANSFER SWITCH
FOOD SERVICE EQUIPMENT
PC
TS
T
ABBREVIATIONS
- ABOVE COUNTER
AC
AFF - ABOVE FINISHED FLOOR
- ABOVE FINISHED GRADE
AFG
- ALUMINUM
AL
- EMERGENCY
EM
- GROUND
GND
- GROUND FAULT INTERRUPTER
GFI
NIC - NOT IN CONTRACT
NL - NIGHT LIGHT
NTS - NOT TO SCALE
UG - UNDERGROUND
WP - WEATHER PROOF
XFMR - TRANSFORMER
+18" - MOUNTING HEIGHT TO CENTERLINE
OF DEVICE AFF OR AFG
FIRE ALARM SYSTEM
FIRE ALARM CONTROL PANEL
FIRE ALARM ANNUNCIATOR PANEL
FIRE ALARM PULL STATION
ALARM HORN OR SPEAKER
COMBINATION HORN/STROBE OR SPEAKER/STROBE
THERMAL HEAT DETECTOR
H
SMOKE/IONIZATION DETECTOR
I
PHOTOELECTRIC SMOKE DETECTOR
P
DUCT DETECTOR
SPRINKLER SYSTEM FLOW SWITCH
SPRINKLER SYSTEM TAMPER SWITCH
STROBE
SMOKE/FIRE DAMPER CONNECTION
REMOTE INDICATOR LIGHT
COMMUNICATION SYSTEM
SPEAKER IN CEILING OR WALL
VOLUME CONTROL AT 60" UNLESS NOTED
MICROPHONE OUTLET IN FLOOR BOX OR WALL
CALL-IN SWITCH
PROGRAM BELL
INTERCOM
CLOCK
AMPLIFIER
TELEVISION OUTLET
CONTACT DOOR SWITCH IN JAMB OR HINGE
SECURITY SYSTEM
INTRUSION MOTION DETECTOR AS SPECIFIED, CORRIDOR/ROOM
KEY-OPERATED ACCESS SWITCH
SURVEILLANCE CAMERA
DISTRIBUTION EQUIPMENT SYMBOLS
DISCONNECT SWITCH
FUSES
CIRCUIT BREAKER
CURRENT TRANSFORMER
TRANSFORMER
METER
CU - COPPER
STEP LIGHT
FACP
M = MOTION-OPERATED SWITCH
POP-UP RECEPTACLE
- ELECTRICAL CONTRACTOR
EC
- AUTHORITY HAVING JURISDICTION
AHJ
- MECHANICAL CONTRACTOR
MC
- PLUMBING CONTRACTOR
PC
UTP - UNSHIELDED TWISTED PAIR
- GENERAL CONTRACTOR
GC
- REFERENCE
REF
THE ELECTRICAL CONTRACTOR WILL PROVIDE A WALK THROUGH WITH
THE OWNER/ARCHITECT PRIOR TO FINAL ROUGH-IN AS FOLLOWS:
x
CONFIRM ALL LOCATIONS FOR LIGHT SWITCHES;
ADD THREE WAYS IF FOUND NECESSARY.
x
REVIEW RECEPTACLE LOCATIONS; MOVE AS REQUIRED.
PROVIDE UNIT PRICING IF ADDITIONAL RECEPTACLES ARE REQUIRED.
x
REVIEW RECEPTACLE LOCATIONS AT COUNTERS AND CONFIRM
IF THOSE RECEPTACLES SHOULD BE ABOVE COUNTER OR BELOW.
MOVE AS REQUIRED.
PROVIDE WALK THROUGH WITH THE OWNER PRIOR TO ROUGH INTO
CONFIRM ALL LOW VOLTAGE ROUGH IN AND RECEPTACLE LOCATIONS.
IN GENERAL CONFIRM POWER AND LIGHTING REQUIREMENTS.
THE ELECTRICIAN SHOULD BE PREPARED TO REWORK SOME
DEVICE LOCATIONS. SIGNIFICANT REWORK SHOULD BE FLAGGED AND
UNIT PRICING PROVIDED AND WRITTEN AUTHORIZATION FOR
ADDITIONAL COSTS APPROVED PRIOR TO PROCEEDING.
UNO - UNLESS NOTED OTHERWISE
14. All cabling shall be bundled and properly secured and terminated.
The warranty period shall begin at the point of system acceptance
system during this warranty period at no additional cost to the owner.
free of defects of workmanship or products and will inspect and repair the
from the date of project completion. The contractor warrants the system to be
15. The warranty set forth for this system shall consist of a full three (3) years
or beneficial use, whichever comes later.
Coordinate numbering scheme with owner.
13. No exposed wiring will be accepted unless approved in writing by the Engineer.
Care must be taken to ensure cables are not kinked, bent beyond limit,
including NEC, EIA/TIA 568,569 and 606, and federal, state and local codes.
familiar and install in accordance with all applicable codes and standards,
12. All cable hangers shall be no more than 48" apart. Contractor shall be
11. Cable bends shall be no less than eight times the cable diameter or 1.00".
termination. No more than .5 inches of exposed untwisted pairs shall be
the extent in which each twisted pair is unraveled at the point of its physical
10. All connections of twisted wiring shall be made in such a way as to minimize
length of the run. Splices and bridge taps with cabling are strictly prohibited.
Cabling shall be free from tension at both ends, as well as through out the
9. All wiring shall be protected from moving mechanical or physical contacts.
Bidder will identify any cable runs exceeding 90 meters
8. Route cables so as not to exceed 90 meters in length.
In the case of "hard" drywall ceilings, adequate support shall be accomplished
independent hangers. Cable "draped" across ceiling tiles is unacceptable.
7. All cable above the ceiling must be tied and properly supported with
6. Provide plenum rated cable when required by article NEC 300-22.
overloaded, over-cinched, crushed, improperly untwisted, etc.
present at these locations.
Wiring is to be run in cable tray and conduit where specified.
and provide solution to meet the 90 meter requirement.
where reasonably possible.
patch panel location, and each wall/floor faceplate that has wiring installed.
5. All cables will be labeled with self-laminating labels at each cable end, at each
match faceplates to power, color coded for voice and data, match to cable
modular RJ-45, 8 pin, 8 conductor, Hubbell, Leviton, or lucent or equivalent jacks,
3. The terminations at the station locations must be Category 6, T568B (AT&T)
2. Data cable will be colored blue. Voice cable will be colored white.
manufacturers include: Berk-Tek, Belden, Lucent or equivalent.
500 Mhz or better category 6, 4 pair UTP as applicable. Acceptable
1. The cabling for voice and data must be continuous, home run, non-spliced,
4. Wall mounted patch panels will be provided.
Outlets will be securely held in place.
B. Cat 6 Wiring Requirements
enclosed within cable trays, raceways or conduit, as specified.
Cabling shall be in the wall, above the ceiling or where exposed,
1. WALL ASSEMBLY - THE 1, 2, 3 OR 4 HR FIRE-RATED GYPSUM WALLBOARD/STUD WALL ASSEMBLY
SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER DESCRIBED IN THE INDIVIDUAL
U300 OR U400 SERIES WALL OR PARTITION DESIGNS IN THE UL FIRE RESISTANCE DIRECTORY AND
SHALL INCLUDE THE FOLLOWING CONSTRUCTION FEATURES:
A. STUDS - WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS (MAX 2 HR FIRE RATED
ASSEMBLIES) OR STEEL CHANNEL STUDS. WOOD STUDS TO CONSIST OF NOM 2 BY 4 IN. (51 BY 102
MM) LUMBER SPACED 16 IN. (406 MM) OC WITH NOM 2 BY 4 IN. (51 BY 102 MM) LUMBER END PLATES
AND CROSS BRACES. STEEL STUDS TO BE MIN 3-5/8 IN. (92 MM) WIDE BY 1-3/8 IN. (35 MM) DEEP
CHANNELS SPACED MAX 24 IN. (610 MM) OC.
B. GYPSUM BOARD* - NOM 1/2 OR 5/8 IN. (13 OR 16 MM) THICK, 4 FT. (122 CM) WIDE WITH SQUARE
OR TAPERED EDGES. THE GYPSUM WALLBOARD TYPE, THICKNESS, NUMBER OF LAYERS, FASTENER
TYPE AND SHEET ORIENTATION SHALL BE AS SPECIFIED IN THE INDIVIDUAL U300 OR U400 SERIES
DESIGN IN THE UL FIRE RESISTANCE DIRECTORY. MAX DIAM OF OPENING IS 26 IN. (660 MM).
2. THROUGH PENETRANT - ONE CONDUIT INSTALLED EITHER CONCENTRICALLY OR
ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. THE ANNULAR SPACE BETWEEN PIPE, CONDUIT OR
TUBING AND PERIPHERY OF OPENING SHALL BE MIN OF 0 IN. (0 MM) (POINT CONTACT) TO MAX 2 IN. (51
MM). PIPE, CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY.
THE FOLLOWING TYPES AND SIZES OF METALLIC PIPES, CONDUITS OR TUBING MAY BE USED:
A. CONDUIT - NOM 6 IN. (152 MM) DIAM (OR SMALLER) STEEL CONDUIT OR NOM 4 IN. (102 MM) DIAM
(OR SMALLER) STEEL ELECTRICAL METALLIC TUBING
3. FILL,VOID OR CAVITY MATERIAL* - CAULK OR SEALANT - MIN 5/8. 1-1/4,1-7/8 AND 2-1/2 IN.
(16, 32, 48 AND 64 MM) THICKNESS OF CAULK FOR 1, 2, 3 AND 4 HR RATED ASSEMBLIES,
RESPECTIVELY, APPLIED WITHIN ANNULUS, FLUSH WITH BOTH SURFACES OF WALL. MIN 1/4 IN. (6 MM)
DIAM BEAD OF CAULK APPLIED TO GYPSUM BOARD/PENETRANT INTERFACE AT POINT CONTACT
LOCATION ON BOTH SIDES OF WALL.
THE HOURLY F RATING OF THE FIRESTOP SYSTEM IS DEPENDENT UPON THE HOURLY FIRE RATING
OF THE WALL ASSEMBLY IN WHICH IT IS INSTALLED, AS SHOWN IN THE FOLLOWING TABLE.
THE HOURLY T RATING OF THE FIRESTOP SYSTEM IS DEPENDENT UPON THE TYPE OR SIZE OF THE
PIPE OR CONDUIT AND THE HOURLY FIRE RATING OF THE WALL ASSEMBLY IN WHICH IT IS INSTALLED,
AS TABULATED TO THE LEFT.
3M COMPANY - CP 25WB+ CAULK OR FB-3000 WT SEALANT,
*BEARING THE UL CLASSIFICATION MARKING
PENETRATION THROUGH A FIRE-RATED WALL
NOT TO SCALE
equipment, etc. furnish by mechanical - refer to both electrical and
electrical apparatus as shown on single line diagram and drawings.
and mechanical drawing for scope and work and additional information.
Complete connection of HVAC/Plumbing motor(s), water heater(s),
Fire alarm system will be by electrical contractor.
Complete provision, installation and connection of lighting fixtures,
exit signs and lamps as specified and as shown on drawings.
Complete branch circuit wiring required for the connection of
emergency lighting and exit signs to existing emergency stand
Complete feeder(s) installation as required for new and/or
new control devices, etc. for a complete lighting and power system.
including new panelboards, new conduits, new wires, new wiring devices,
Complete wiring system for new lighting and power as shown,
Electrical work shall include, but not limited to, these major items:
indicated on drawing and as specified, as necessary to complete the contract.
SCOPE:
I.
E.
F.
H.
G.
Provide grounding and bonding Facilities.
Complete all electrical demolition as required.
B.
ELECTRICAL SPECIFICATIONS
1.
by power system.
D.
C.
A. Contractor shall submit shop drawings for engineer review and approval.
MC cable permitted per local codes. Run hard pipe from panel to local
Lighting fixtures.
Shop drawing submittal shall include:
Panelboard(s).
CONDUIT AND WIRE:
B.
5.
A.
B.
b.
a.
and contractor shall have written approvals from building owner prior
Core drilling and patching of existing building structure required for
Operating, Maintenance and identification instructions manuals, if any.
electrical work. Core drilling shall follow Building Standard procedures
Applicable codes: National Electric Code (2014)
PERMITS AND FEES:
requirements of Federal, State or other City agencies having jurisdiction.
Local Electrical Code, pertinent NFPA publications and to the
Conform to the prevailing edition and amendments thereto of the
SHOP DRAWINGS AND SUBMITTAL:
to start of any work.
Test of entire system and work.
REGULATIONS AND CODES:
4.
A.
2.
J.
3.
A. General Requirements
6.
Finish per owner or architect.
Convenience receptacles will be 15 A, decora style.
Light switches will be 20 amp, commercial grade, decora style.
B.
ELECTRICAL DEVICES:
A.
Finish per owner or architect.
Finish per owner or architect.
Dimming switches will be a minimum of 600w or as noted, provide decora style.
C.
7.
All mounting heights will conform to ADA guidelines. D.
Typical receptacle heights will be +18"AFF and switch heights will be +46"AFF
unless noted otherwise.
Provide GFI type receptacles at kitchens, bathrooms, garages, exterior etc.
as required by code.
E.
junction box, and run MC cable from junction box to device.
CONDUCTOR SIZES AND TYPES: For sizes #1/0 AWG and larger, use
coppper THW or aluminum XHHW. For sizes #1 AWG and smaller, use only
copper wire with 600V insulation, types TW, THHN, or THW - stranded in
sizes #8 and larger, solid in sizes #10 and smaller. Control wiring shall be #14,
stranded. Use type THHN for wires entering or passing through fluorescent
lighting fixtures. All motors shall be wired with copper conductors only.
Support all electrical equipment independent of accessible ceilings as
required by NEC.
SUPPORT:
A.
A. Obtain and pay for all necessary permits, inspections, examinations and fees
or charges necessary for execution and completion of electrical work.
A. Furnish all materials and labor required to execute this work as
and contractor shall have written approvals from building owner prior
Core drilling and patching of existing building structure required for
electrical work. Core drilling shall follow Building Standard procedures
K.
L.
Provide tamper proof receptacles at all residential areas
as required by code.
F.
Test of entire system and work.
+80"AFF
P
+80"AFF
TELEPHONE ONE-
LINE DIAGRAM
TELEPHONE/
COMPUTER ROUGHIN
#6 CU G
ROUTE WIRE AT CEILING PARALLEL OR
PERPENDICULAR TO STRUCTURE.
SECURE TO STRUCTURE AT 4' INTERVALS OR LESS.
STUB UP TO ABOVE
ACCESSIBLE CEILNG
STRUCTURED CABLE
DISTRIBUTION PANEL
3/4"C
DOUBLE GANG BOX
W/ PULLWIRE
AT 12" AFF UNO
COLD WATER PIPE
MAIN TELE/DATA ROOM
NO SCALE
T
12" (1'-0")
46" (3'-10")
48" (4'-0")
80" (6'-8")
TYPICAL DEVICE
MOUNTING HEIGHTS
MAIN CIRCUIT BREAKER &
BRANCH CIRCUIT BREAKERS
MAXIMUM MOUNTING HEIGHT
IS 79", MINIMUM IS 18".
NOT TO SCALE
NOTES:
1. HEIGHTS SHOWN ARE TYPICAL TO CENTERLINE OF BOX
UNLESS NOTED OTHERWISE.
2. DEVICES ABOVE DOORS SHALL BE CENTERED BETWEEN
TOP OF DOOR TRIM AND CEILING LINE.
3. MOUNTING HEIGHTS SHOWN ON ARCHITECTURAL ELEVATIONS
AND NOTED ON ELECTRICAL FLOOR PLANS SHALL GOVERN
OVER THOSE SHOWN ABOVE.
4. FOR CEILING HEIGHTS HIGHER THAN 7'2", INSTALL FIRE ALARM
NOTIFICATION AUDIO AND VISUAL APPLIANCES AT
80"AFF OTHERWISE INSTALL AT 6" BELOW CEILING.
5. MOUNTING HEIGHTS PER IBC 2009 AND ADA CODES
FINISHED FLOOR
TYPICAL 8'-0" CEILING
2"C PVC WITH PULLWIRE
BURIED 20" BELOW GRADE
CATV
PEDESTAL
COAX RECEPTACLE IN SINGLE
GANG BOX @ 12" A.F.F. UNO
QUANTITIES PER FLOOR PLANS
(RG6 QUAD SHIELDED CABLE) 3/4"C
CONDUIT STUBBED TO ACCESSIBLE
CEILING, PLENUM RATED WIRE, WHEN
REQUIRED, RAN TO BACK BOARD
STRUCTURED CABLE
DISTRIBUTION PANEL
#6 CU G
METALLIC COLDWATER PIPE
NO SCALE
(3) 2" C
W/ PULLWIRE
R3-37
R3-35
x
4/ 51*
.')'0&
5%*'&7.'5
'
of
Drawn By: Checked By:
DATE: ISSUE:
02-22-16 DD SET
AEC PROJECT #: TOV FIRE STATION #1
RENOVATION
VAIL, COLORADO 81657
16001.00
www.aec-vail.com
CMechanical, Electrical & Lighting Design Services
Architectural Engineering Consultants
Telephone:
970-748-8520
E
G$Q 2IILFH ZLWK /((' $FFUHGLWHG 3URIHVVLRQDOV
03-14-16
PROGRESS
03-22-16
PERMIT
04-01-16
CD SET
06/14/16