NOTE:
PROVIDE #3/0 CU CONDUCTORS TO ALL GROUNDING ELECTRODES.
WATER SERVICE
INCOMING PIPE
(3) 3/4"x10'
DRIVEN GROUND RODS
IF REQUIRED
BY LOCAL AHJ
BONDING JUMPER
(#3/0 CU G) 3/4"C
#6 TO TELEPHONE/TV
WATER
METER
BUILDING
STEEL
GAS SERVICE
N
G
N
G
INCOMING PIPE
CONCRETE- ENCASED ELECTRODE
REQUIRED IN FOOTING/FOUNDATION
PER NEC 250-50. MINIMUM 20' #4 REBAR
OR MINIMUM 20' #4 BARE COPPER.
MUST BE INSTALLED AT
FOOTING INSPECTION.
T
UTILITY
PAD MOUNTED
TRANSFORMER
CT & METER
PANEL "P1"
600/2
600A
FRN-R
DISCONNECT
X
<10K AIC
X
59,600 AIC
38,600 AIC
X
NO SCALE
NOTE:
PROVIDE SHORT CIRCUIT BRACING TO MEET REQUIREMENTS NOTED AT ONE-LINE,
NOTED AS "AIC AVAILABLE". SERIES RATED COMBINATION ACCEPTABLE,
SUBMIT MANUFACTURER'S SERIES RATINGS WITH SHOP DRAWING REVIEW.
PANEL
"R1"
NO SCALE
NOTE:
PROVIDE #3/0 CU CONDUCTORS TO ALL GROUNDING ELECTRODES.
WATER SERVICE
INCOMING PIPE
(3) 3/4"x10'
DRIVEN GROUND RODS
IF REQUIRED
BY LOCAL AHJ
BONDING JUMPER
(#3/0 CU G) 3/4"C
#6 TO TELEPHONE/TV
WATER
METER
BUILDING
STEEL
GAS SERVICE
N
G
N
G
INCOMING PIPE
CONCRETE- ENCASED ELECTRODE
REQUIRED IN FOOTING/FOUNDATION
PER NEC 250-50.
MINIMUM 20' #4 REBAR
OR MINIMUM 20' #4 BARE COPPER.
MUST BE INSTALLED AT
FOOTING INSPECTION.
PANEL
"R2"
PANEL
"R3"
E G 600/2
PANEL
"B"
300/2
125/2
125/2
125/2
2[(3 #250 MCM CU - 1 #1 CU G) 2-1/2"C]
OR
2[(3 #500 MCM AL - 1 # 2/0 AL G) 3"C]
ATS
(3 #350 MCM CU - 1 #4 CU G) 2 1/2"C]
OR
(3 #500 MCM AL - 1 # 2 AL G) 3"C]
(3 #1 CU - 1 #6 CU G) 1 1/2"C
OR
(3 #1/0 AL - 1 # 6 AL G) 2"C
120 KVA
120/240V, 1P, 3W
DIESEL GENERATOR,
DERATE FOR 9,600 FT. ALTITUDE,
SUB BASE FUEL TANKS
NOTE:
OWNER TO SUPPLY THE GENERATOR
EQUIPMENT, CONTRACTOR TO INSTALL.
2[(3 #250 MCM CU) 2-1/2"C]
OR
2[(3 #500 MCM AL) 3"C]
PANEL
"B2"
PROVIDE ENCLOSED
EMERGENCY OFF, CONNECT TO
AUXILIARY CONTACTS FOR
GENERATOR SHUT DOWN.
PROVIDE PLAQUE TO READ
"EMERGENCY GENERATOR BACK UP,
EMERGENCY GENERATOR SHUT OFF
LOCATED NEXT TO DISCONNECT"
X
<10K AIC
4/ 51*
'.'%64+%#.
10'Ä.+0'
5%*'&7.'5
'
of
Drawn By: Checked By:
DATE: ISSUE:
02-22-16 DD SET
AEC PROJECT #: TOV FIRE STATION #1
RENOVATION
VAIL, COLORADO 81657
16001.00
www.aec-vail.com
CMechanical, Electrical & Lighting Design Services
Architectural Engineering Consultants
Telephone:
970-748-8520
E
G$Q 2IILFH ZLWK /((' $FFUHGLWHG 3URIHVVLRQDOV
03-14-16
PROGRESS
03-22-16
PERMIT
04-01-16
CD SET
06/14/16