HomeMy WebLinkAboutB16-0087_E1.1_1478903613.pdfNO SCALE NOTE: PROVIDE #3/0 CU CONDUCTORS TO ALL GROUNDING ELECTRODES. WATER SERVICE INCOMING PIPE (3) 3/4"x10' DRIVEN GROUND RODS IF REQUIRED BY LOCAL AHJ BONDING JUMPER (#3/0 CU G) 3/4"C #6 TO TELEPHONE/TV WATER METER BUILDING STEEL GAS SERVICE N G N G INCOMING PIPE CONCRETE- ENCASED ELECTRODE REQUIRED IN FOOTING/FOUNDATION PER NEC 250-50. MINIMUM 20' #4 REBAR OR MINIMUM 20' #4 BARE COPPER. MUST BE INSTALLED AT FOOTING INSPECTION. T UTILITY PAD MOUNTED TRANSFORMER CT & METER PANEL "P1" 600/2 600A FRN-R DISCONNECT X <10K AIC X 59,600 AIC 38,600 AIC X NO SCALE NOTE: PROVIDE SHORT CIRCUIT BRACING TO MEET REQUIREMENTS NOTED AT ONE-LINE, NOTED AS "AIC AVAILABLE". SERIES RATED COMBINATION ACCEPTABLE, SUBMIT MANUFACTURER'S SERIES RATINGS WITH SHOP DRAWING REVIEW. PANEL "R1" NO SCALE NOTE: PROVIDE #3/0 CU CONDUCTORS TO ALL GROUNDING ELECTRODES. WATER SERVICE INCOMING PIPE (3) 3/4"x10' DRIVEN GROUND RODS IF REQUIRED BY LOCAL AHJ BONDING JUMPER (#3/0 CU G) 3/4"C #6 TO TELEPHONE/TV WATER METER BUILDING STEEL GAS SERVICE N G N G INCOMING PIPE CONCRETE- ENCASED ELECTRODE REQUIRED IN FOOTING/FOUNDATION PER NEC 250-50. MINIMUM 20' #4 REBAR OR MINIMUM 20' #4 BARE COPPER. MUST BE INSTALLED AT FOOTING INSPECTION. PANEL "R2" PANEL "R3" E G 600/2 PANEL "B" 300/2 125/2 125/2 125/2 2[(3 #250 MCM CU - 1 #1 CU G) 2-1/2"C] OR 2[(3 #500 MCM AL - 1 # 2/0 AL G) 3"C] ATS (3 #350 MCM CU - 1 #4 CU G) 2 1/2"C] OR (3 #500 MCM AL - 1 # 2 AL G) 3"C] (3 #1 CU - 1 #6 CU G) 1 1/2"C OR (3 #1/0 AL - 1 # 6 AL G) 2"C 120 KVA 120/240V, 1P, 3W DIESEL GENERATOR, DERATE FOR 9,600 FT. ALTITUDE, SUB BASE FUEL TANKS NOTE: OWNER TO SUPPLY THE GENERATOR EQUIPMENT, CONTRACTOR TO INSTALL. 2[(3 #250 MCM CU) 2-1/2"C] OR 2[(3 #500 MCM AL) 3"C] PANEL "B2" PROVIDE ENCLOSED EMERGENCY OFF, CONNECT TO AUXILIARY CONTACTS FOR GENERATOR SHUT DOWN. PROVIDE PLAQUE TO READ "EMERGENCY GENERATOR BACK UP, EMERGENCY GENERATOR SHUT OFF LOCATED NEXT TO DISCONNECT" X <10K AIC 4/ 51* '.'%64+%#. 10'Ä.+0'  5%*'&7.'5 '   of Drawn By: Checked By: DATE: ISSUE: 02-22-16 DD SET AEC PROJECT #: TOV FIRE STATION #1 RENOVATION VAIL, COLORADO 81657 16001.00 www.aec-vail.com CMechanical, Electrical & Lighting Design Services Architectural Engineering Consultants Telephone: 970-748-8520 E G$Q 2IILFH ZLWK /(('Œ $FFUHGLWHG 3URIHVVLRQDOV 03-14-16 PROGRESS 03-22-16 PERMIT 04-01-16 CD SET 06/14/16