HomeMy WebLinkAboutB16-0087_M1.3_1478903650.pdfBOILER PIPING NOTES: 1. ALL EQUIPMENT SHOWN IN THESE DIAGRAMS SHALL BE LOCATED IN THE MECHANICAL ROOM. 2. LOCATE ALL FLOOR MOUNTED EQUIPMENT ON 4" EQUIPMENT PADS. 3. ROUTE BOILER CONDENSATE TO FLOOR DRAIN VIA NEUTRALIZATION BASIN. 4. ALL REQUIRED VALVES AND APPURTENANCES NOT NECESSARILY SHOWN. 5. FILL HEATING SYSTEM WITH 30% PROPYLENE GLYCOL. FILL SNOWMELT SYSTEM WITH 50% PROPYLENE GLYCOL. CONFIRM WATER QUALITY MEETS MINIMUM BOILER STANDARDS IN MANUFACTURER'S I&O MANUAL PRIOR TO FILL. 6. PROVIDE AIR VENTS AT ALL HIGH POINTS OF THE HYDRONIC SYSTEMS. 7. PROVIDE DRAIN DOWNS AT ALL LOW POINTS OF THE HYDRONIC SYSTEM. BOILER PIPING DIAGRAM NO SCALE S B 1 S B 2 P 1 P 2 S SPIROVENT VDX 300 HYDRAULIC SEPARATOR PIPE TO FLOOR DRAIN HEATING SUPPLY WATER TEMPERATURE SENSOR GF 1 ET 1 WH 1 S P 3 P 6 HX 1 P 7 AIR & DIRT SEPARATOR SPIROVENT VDR 200 ET 2 MANUAL FILL GF 2 TO/FROM SNOWMELT MANIFOLDS S 30 PSI PRESSURE RELIEF VALVE P 4 TO/FROM BASEBOARD LOOPS WALL MOUNTED BOILERS PIPE TO FLOOR DRAIN (TYP.2) REVERSE RETURN LAYOUT 2" HIGH DENSITY RIGID EDGE INSULATION AT DRIVEWAYS, 2" STANDARD RIGID INSULATION AT WALKWAYS & DECKS 5 8" HePEX TUBING SPACED 9" 0.C. 3' 2" HIGH DENSITY RIGID INSULATION UNDER DRIVEWAY. 2" STANDARD RIGID INSULATION UNDER WALKWAYS AND DECKS. COORDINATE COMPRESSION REQUIREMENTS WITH CIVIL ENGINEER. 9" O.C. SNOWMELT TUBING DETAIL NO SCALE 7" CONCRETE COVER COMPACTED SUBGRADE PROVIDE ARMIFLEX INSULATION SLEEVES AT ALL EXPANSION JOINTS IN THE CONCRETE PRESSURIZE SNOW MELT TUBING TO 100 PSI AIR TO PREVENT CRUSHING OF TUBE WHEN THE CONCRETE IS POURED TIE WRAP TO CONCRETE REINFORCING 3' TYP. WIRE TIE 3' O.C. SEE FIGURE 2 STEEL REINFORCING RE: STRUCTURAL NOTES: PLACE TUBING WITH MAX. 3" CONCRETE ON TOP OF THE TUBING AND NOT LESS THAN 2". BUBBLE FOIL INSULATION IS PROHIBITED. 2" FOAMULAR 1000 BY OWENS CORNING OR EQUIVALENT RIGID INSULATION SHALL BE USED WITH MIN. COMPRESSIVE STRENGTH 100 PSI, ASTM C578 TYPE V FOR HEAVY LOAD TRAFFIC AREAS. FOR STANDARD RIGID INSULATION UNDER WALKWAYS OR DECKS FOAMULAR 150 (15 PSI) OR 250 (25 PSI) SHALL BE USED. COORDINATE LOAD REQUIREMENTS WITH THE CIVIL ENGINEER. BALL VALVE HWR HWS NEAR ENCLOSED GRILLE MANUAL AIR VENT UNION (TYP) DRAIN VALVE FINNED ELEMENT FIN-TUBE RADIATION PIPING NO SCALE P 5 TO/FROM HC-1 ~ 4 FIG. 2 FIG. 1 3" MIN. CONCRETE ABOVE TUBING (COORD. WITH GEOTECH & STRUCTURAL, IF TUBING CANNOT BE PLACED AS SHOWN, LOCATE ON TOP OF THE INSULATION) REINFORCING (RE: STRUCTURAL) 4" AGGREGATE BASE COURSE (CDOT CLASS 6) 2" 2" 2-1/2" 2" 2" 2" 1-1/4" 2" 3" 3" PUMP IN-LINE PROVIDE VIBRATION ISOLATING TYPE PUMP SUPPORTING HANGERS AT INLET AND DISCHARGE OF THE PUMP. DO NOT SUPPORT THE PUMP FROM ITS MOTOR. CHECK VALVE OMIT ON SINGLE PUMP INSTALLATIONS METAL BRAIDED FLEXIBLE CONNECTOR PRESSURE GAUGE W/ GAUGE COCKS & SNUBBER COMBINATION ISOLATION VALVE & CIRCUIT SETTER SHUTOFF VALVE BALL VALVE UP TO 2" BUTTERFLY VALVE 2 1 2" AND LARGER STRAINER W/ BLOW DOWN VALVE UNION OR FLANGE CONNECTION IN-LINE PUMP DIAGRAM NO SCALE SNOWMELT MANIFOLD DETAIL NO SCALE ‘ /223 SUPPLY FITTING (TYP) ‘ /223 5(7851 PIPING (TYP) END CAP W/ VENT MANIFOLD SUPPORT BRACKET (TYP.) VALVE CAP ANGLE VALVES(TYP) RETURN MANIFOLD RETURN MAIN DRAIN DOWN HOSE BIB DRAIN DOWN HOSE BIB BALL VALVE SUPPLY MANIFOLD COMPRESSION FITTING (TYP) SUPPLY MAIN COMPRESSION FITTING (TYP) PROVIDE A MEANS FOR BALANCING INDIVIDUAL LOOPS SHUTOFF/BALANCING VALVE BALANCING VALVE NOT REQUIRED IF VISUAL FLOW DISPLAYS PROVIDED ON INDIVIDUAL LOOPS. PROVIDE PRESSURE / TEMPERATURE PORTS ACROSS MANIFOLD SNOWMELT REVERSE RETURN LAYOUT NO SCALE INSTALL SNOWMELT TUBING IN REVERSE-RETURN PATTERN TO ALLOW EQUAL HEAT UP OF THE SNOWMELTED SURFACE. THIS LAYOUT IS AN EXAMPLE AND NOT THE ACTUAL TUBING LAYOUT . SNOWMELT LAYOUT WHERE PASSING JOINTS NO SCALE INSTALL SNOWMELT TUBING IN REVERSE-RETURN PATTERN TO ALLOW EQUAL HEAT UP OF THE SNOWMELTED SURFACE. THIS LAYOUT IS AN EXAMPLE AND NOT THE ACTUAL TUBING LAYOUT . 1/4 OF "W" OR A IR FLOWRET URN/EXHAUST ƒ 6" MINIMUM. SUPPLY AIR FLOW WSEAL AIRTIGHT AROUND ENTIRE TAKE-OFF. ƒ '8&7 7$.(2)) NO SCALE: 1/4 OF "W" OR AIR FLOWRET URN/EXHA UST ƒ 6" MINIMUM. S UPPLY AIR FLOW W SEAL AIRTIGHT AROUND ENTIRE TAKE-OFF. ƒ '8&7 7$.(2)) NO SCALE: INSULATED RIGID DUCT AIR FLOW CLAMP MANUAL DAMPER, HANDLE, & LOCK NUT WORM DRIVE S.S. ‘ 7:,67,1 ),77,1* : ROUND DUCT TAKE-OFF NO SCALE INSULATED RIGID DUCT AIR FLOW CLAMP MANUAL DAMPER, HANDLE, & LOCK NUT WORM DRIVE S.S. ‘ 7:,67,1 ),77,1* : ROUND DUCT TAKE-OFF NO SCALE R=W W RADIUS ELBOW DETAIL NO SCALE R=W W RADIUS ELBOW DETAIL NO SCALE 3/4" TEKMAR 667 OUTDOOR AIR SENSOR TO BOILER CONTROLS TO P-6, P-7 090 SNOW / ICE SENSOR AND 091 SOCKET/CAP 3/4" 2" TO/FROM INDIVIDUAL ZONE TO/FROM INDIVIDUAL ZONE TO/FROM INDIVIDUAL ZONE TO/FROM INDIVIDUAL ZONE TO/FROM INDIVIDUAL ZONE TO/FROM INDIVIDUAL ZONE TO/FROM INDIVIDUAL ZONE TO/FROM INDIVIDUAL ZONE TO/FROM INDIVIDUAL ZONE TO/FROM INDIVIDUAL ZONE 1-1/4" 1-1/4" 1-1/4" BALANCING VALVE (TYP.) DIFFERENTIAL PRESSURE BY-PASS VALVE I.E. CALEFFI 519600 A BALANCING VALVE (TYP.) DIFFERENTIAL PRESSURE BY-PASS VALVE I.E. CALEFFI 519600 A NOTE: FOR EXACT PIPING ROUTING, SIZES AND NUMBER OF ZONE VALVES REFER TO FLOOR PLANS. CONTRACTOR TO PROVIDE ADD-ALTERNATE PRICING FOR P-4 VFD PUMP AND NO BY-PASS VALVE 1-1/2" 1-1/2" ZONE VALVE (TYP.) ZONE VALVE (TYP.) VFD VFD PROVIDE SLAB PROTECTION FEATURE EACH BASEBOARD LOOP SHALL BE EQUIPPED WITH A ZONE VALVE AND ISOLATING VALVES IN BASEBOARD ENCLOSURE. INSTALL BASEBOARDS AND BASEBOARDS LOOPS SO THEY CAN BE EASILY DRAINED. of Drawn By: Checked By: DATE: ISSUE: 02-22-16 DD SET AEC PROJECT #: TOV FIRE STATION #1 RENOVATION VAIL, COLORADO 81657 16001.00 www.aec-vail.com CMechanical, Electrical & Lighting Design Services Architectural Engineering Consultants Telephone: 970-748-8520 E G$Q 2IILFH ZLWK /(('Œ $FFUHGLWHG 3URIHVVLRQDOV 03-14-16 PROGRESS 03-22-16 PERMIT 04-01-16 CD SET ') 61% /'%*#0+%#. &'6#+.5  &+#)4#/ /   06/14/16