HomeMy WebLinkAboutB16-0087_M3.0_1465941600.pdfMECH
ROOM
BUNKER GEAR
1ST FLR HALLWAY
STAIRS
PUBLIC
RESTROOM
UP
WDD
E
C
5
6
4
1
3
2
7
A
B
8
F.1 F.2
F.3 F.4
7.5
A1
4.9
7A
7B
7C
UP
GYM
CONFERENCE
ROOM
OFFICE
A
OFFICE
B
OFFICE
HALLWAY
ENTRY
APPARATUS BAY
CLEAN
ROOM
STORAGE
HALLWAY
STORAGE
ROOM 2
STORAGE
ROOM 1
EPO
HRV
1
EMG-1
L
3
12400-OA
60x66
L
4
12400-EX
60x66
M
M
12x8 [15x11]
L
5
310-OA
24x12
L
6
310-EX
24x12
12x8
12x8
HC
2
12x8 [14x10]
A
60-S
24x6
A
50-S
24x6
12x8
12x8 [14x10]
SHEET DETAIL NOTES:
INSTALL HRV-3 ,1 +25,=217$/ 326,7,21 527$7(' 9(5,)< :,7+
MANUFACTURER PRIOR TO ORDERING. INSTALL BDD ON EXHAUST AND
M.O.D. ON INTAKE DUCTWORK (NOT SHOWN). COORDINATE ACCESS
PANEL (MIN. 36x48 OR EQUIVALENT) WITH ARCHITECT AND G.C. IN FIELD.
INSTALL HC-2, INTERLOCK 2-WAY MODULATING VALVE WITH THE DUCT
MOUNTED SENSOR (IN THE HRV-2 DISCHARGE DUCT). VERIFY COIL
DIMENSIONS AND SPACE REQUIREMENTS IN FIELD PRIOR TO COIL
PURCHASE. ADJUST SIZE AND CONNECTION SIDE PER FIELD
MEASUREMENTS. CONTACT ENGINEER FOR ASSISTANCE IF REQUIRED.
VERIFY STATE AND ADEQUACY OF THE EXISTING EF-1. IF ACCEPTABLE
REUSE AND RELOCATE TO THIS LOCATION IN THE HALLWAY VOID
SPACE. G.C. TO PROVIDE ACCESS PANEL (MIN. 36x36 OR EQUIVALENT)
FOR SERVICE AND MAINTENANCE. IF THE FAN CANNOT BE REUSED,
REPLACE WITH THE NEW ONE.
DELETED.
DELETED.
VERIFY STATE AND ADEQUACY OF THE EXISTING RADIANT HEATERS
AND CAPACITY FOR REUSING WITH RELOCATED EXHAUST AS INDICATED
ON THE PLANS PRIOR TO ANY WORK. IF THE EXISTING SYSTEM CANNOT
BE REUSED AS IS, REPLACE BURNERS WITH CORAYVAC CRV-B-2
(VERIFY SIZES PRIOR TO PURCHASING) AND A NEW VACUUM PUMP
CORAYVAC EP100, INSTALL CONDENSATE TEE ON THE BOTTOM OF THE
VERTICAL VENT AND ROUTE DRAIN INTO THE NEAREST FLOOR DRAIN.
TERMINATE VIA AIR GAP. COORDINATE DRAIN INSTALLATION WITH THE
RADIANT HEATERS MANUFACTURER. PORCELAIN COATED RADIANT
TUBING.
DEMO EXISTING RADIANT AND PLYMOVENT DUCT AND EQUIPMENT.
RELOCATE INTO THE NEW LOCATIONS (OR PROVIDE NEW EQUIPMENT IF
EXISTING CANNOT BE REUSED).
PLYMOVENT DUCT UP TO THE (E) EF-1.
EXISTING PLYMOVENT TO REMAIN.
TERMINATE DRYER VENT THRU THE WALL, 10' FROM PROPERTY LINE, 10'
FROM ANY MECHANICAL AIR INTAKE OR 3' ABOVE IT, 3' FROM NATURAL
AIR INTAKE, AND 5' ABOVE GRADE.
TERMINATE LOUVERS MIN. 5' ABOVE GRADE, 10' FROM THE PROPERTY
LINE, EXHAUST 10' FROM ANY MECHANICAL AIR INTAKE OR 3' ABOVE IT,
AND 3' FROM NATURAL AIR INTAKE INTO THE BUILDING.
TERMINATE LOUVERS MIN. 3' ABOVE GRADE (OR AS AVAILABLE IF
SNOWMELT IS PROVIDED), 10' FROM THE PROPERTY LINE, EXHAUST 10'
FROM ANY MECHANICAL AIR INTAKE OR 3' ABOVE IT, AND 3' FROM
NATURAL AIR INTAKE INTO THE BUILDING.
TERMINATE BOILER INTAKE & EXHAUST MIN. 3' ABOVE GRADE, 10' FROM
THE PROPERTY LINE, EXHAUST 10' FROM ANY MECHANICAL AIR INTAKE
OR 3' ABOVE IT, AND 12" FROM NATURAL AIR INTAKE INTO THE BUILDING.
BOILER FLUE MUST UTILIZE CPVC OR PP. PVC IS NOT ALLOWED.
EXISTING T-STAT FOR RADIANT HEATERS TO BE REUSED. IF THE
SYSTEM IS REPLACED AND NEW T-STAT IS NEEDED REPLACE WITH NEW
T-STAT. COORDINATE IN FIELD WITH THE EQUIPMENT MANUFACTURER.
7(50,1$7( (;+$867 0,1 $:$< )520 3523(57< /,1(
FROM MECHANICAL AIR INTAKE, 3' FROM ANY NATURAL AIR INTAKE AND
5' ABOVE GROUND.
ELECTRICAL CONTRACTOR TO PROVIDE 120 V POWER FOR MOTORIZED
DAMPERS IN THIS LOCATION. INTERLOCK WITH THE GENERATOR.
ALLOW GENERATOR TO OPERATE AFTER DAMPERS ARE FULLY OPEN
(MECHANICAL CONTRACTOR TO PROVIDE DAMPER POSITION SWITCHES
TO INDICATE THE POSITION TO THE GENERATOR, COORDINATE WITH
THE ELECTRICAL CONTRACTOR).
ELECTRICAL CONTRACTOR TO PROVIDE HEAT MATS (SNOWMELT) MIN. 3'
IN FRONT OF THE LOUVERS TO ALLOW LOWERED HEIGHT ABOVE GRADE
INSTALLATION.
5287( 0$.(83 $,5 '8&7 83 7+58 7+( 522) 7(50,1$7( :,7+ $
GOOSENECK, MIN. 36" ABOVE THE ROOF, 10' FROM PROPERTY LINE.
PROVIDE MOTORIZED DAMPER AND INTERLOCK WITH EF-2.
1
2
GENERAL NOTES:
1. ALL DUCTWORK DIMENSIONS ARE SHOWN INSIDE TO INSIDE. DIMENSIONS
IN [ ] INDICATE OUTER SIZES WITH INSULATION. THESE SIZES MAY
DIFFER BASED ON THE SELECTED INSULATION. VERIFY IN FIELD PRIOR
TO INSTALLATION.
2. ALL INTERIOR SUPPLY AND RETURN DUCTWORK SHALL INCLUDE 1" LINER
UNLESS OTHERWISE NOTED. ALL OUTSIDE AIR INTAKE AND ROUND
DUCTWORK SHALL BE WRAPPED WITH 1.5" THICK INSULATION UNLESS
OTHERWISE NOTED.
3. ALL FINAL DUCTWORK CONNECTIONS TO SUPPLY GRILLES (OR PLENUMS)
SHALL BE COMPLETED WITH ACOUSTICAL FLEXIBLE DUCT UNLESS
OTHERWISE NOTED AND A MAXIMUM LENGTH OF FIVE FEET.
4. ALL ROUND DUCT CONNECTIONS TO ROUND DUCTWORK SHALL BE
CONICAL TEES.
5. ALL SQUARE 90 DEGREE ELBOWS SHALL HAVE TURNING VANES.
6. ALL DUCTWORK SHALL BE RUN TIGHT TO UNDERSIDE OF STRUCTURE
WHERE IT EXISTS UNLESS OTHERWISE NOTED.
7. ALL DUCTWORK PASSING THROUGH FIRE-RATED ASSEMBLIES SHALL
INCLUDE FIRE DAMPERS RATED TO MATCH THAT OF THE ASSEMBLY.
8. ALL SUPPLY GRILLES SHALL HAVE INCLUDE A BALANCING DAMPER
UNLESS OTHERWISE NOTED (EVEN THOUGH THEY MAY NOT BE SHOWN
EVERYWHERE). IF THE DAMPER IS LOCATED IN AN INACCESSIBLE
LOCATION, CABLE-STYLE DAMPERS (ROTOTWIST OR EQUIVALENT) SHALL
BE INSTALLED AND SHALL BE ADJUSTABLE FROM THE GRILLE FACE.
MULTIPLE RETURN DIFFUSERS IF SERVED BY A COMMON RETURN
DUCTWORK SHALL BE EQUIPPED WITH BALANCING DAMPERS.
9. COORDINATE ALL ACCESS PANEL LOCATIONS WITH THE ARCHITECT.
3
4
5
B
50-EX
10x10
B
70-EX
10x10
B-2
B-1
GF-1
WH-1
HX-1
GF-2
A
50-S
24x6
A
50-S
24x6
A 50-S
24x6
B
50-EX
10x10
6
6 6
6
6
6
6
RELOCATED OR
NEW VACUUM
PUMP
7
7
7
7
8
8
DRAIN TEE
RE: NOTE #6
9
9
9
10
10
11
11
11
12
12
12
T
T
T
T
T
T
T
T
T
T
H
PB
PB
PB
13
13
13
B
100-EX
10x10
A
50-S
10x10
B
50-EX
10x10
TO BB-14, 15
TO BB-13
TO BB-6
TO HRV-1
TO BB-10
TO LIGHTS
& HRV-1
TO BB-1 - 5
T
TO BB-6 - 12
T
14
14
TO HRV-1
T
TO BB-23,24
TO EF-2
TO BB-21,22
TO HRV-1
TO BB-16 - 20
TO BB-25 - 26
TO HRV-1
EF
2
15
15
M
16
16
16
17
17
17
BDD
M
18
18
1
2
3
of
Drawn By: Checked By:
DATE: ISSUE:
02-22-16 DD SET
AEC PROJECT #: TOV FIRE STATION #1
RENOVATION
VAIL, COLORADO 81657
16001.00
www.aec-vail.com
CMechanical, Electrical & Lighting Design Services
Architectural Engineering Consultants
Telephone:
970-748-8520
E
G$Q 2IILFH ZLWK /((' $FFUHGLWHG 3URIHVVLRQDOV
03-14-16
PROGRESS
03-22-16
PERMIT
04-01-16
CD SET
/< 61%
.'8'.
*8#%
2.#0
5%#.' Ä
/
NORTH
LEVEL 1 HVAC PLAN
SCALE: 3/16" = 1'0"
06/14/16