SHEET DETAIL NOTES:
TERMINATE RELOCATED PLYMOVENT DUCT MIN. 36" ABOVE THE ROOF
(PROVIDE HEAT TRACE FOR SNOWMELT TO REDUCE THE HEIGHT), 24"
ABOVE THE HIGHEST POINT OF THE ROOF WITHIN 10', 10' FROM
PROPERTY LINE, 10' FROM ANY AIR INTAKE INTO THE BUILDING OR 3'
ABOVE IT, AND 10' FROM ANY NATURAL AIR INTAKE INTO THE BUILDING.
TERMINATE NEW RADIANT HEATERS VENT MIN. 36" ABOVE THE ROOF
(PROVIDE HEAT TRACE FOR SNOWMELT TO REDUCE THE HEIGHT), 24"
ABOVE THE HIGHEST POINT OF THE ROOF WITHIN 10', 10' FROM
PROPERTY LINE, 10' FROM ANY AIR INTAKE INTO THE BUILDING OR 3'
ABOVE IT, 3' FROM ANY NATURAL AIR INTAKE INTO THE BUILDING, AND
12" FROM THE PLYMOVENT TERMINATION OR 12" ABOVE IT.
TERMINATE DRYER VENT MIN. 3' ABOVE THE ROOF, 10' FROM PROPERTY
LINE, 10' FROM ANY MECHANICAL INTAKE OR 3' ABOVE IT, AND 3' FROM
ANY NATURAL INTAKE INTO THE BUILDING. TOTAL DESIGNED LENGTH:
VERTICAL RUN = 15 FT
HORIZONTAL RUN = 7 FT
(/%2:6 [ = 5 FT
TOTAL LENGTH = 27 FT
G.C. TO PROVIDE DRYER ALLOWING THIS LENGTH OR INSTALL DRYER
ALLOWING LONG VENT INSTALLATION. CONTACT MECHANICAL
ENGINEER FOR ASSISTANCE.
1
GENERAL NOTES:
1. ALL DUCTWORK DIMENSIONS ARE SHOWN INSIDE TO INSIDE. DIMENSIONS
IN [ ] INDICATE OUTER SIZES WITH INSULATION. THESE SIZES MAY
DIFFER BASED ON THE SELECTED INSULATION. VERIFY IN FIELD PRIOR
TO INSTALLATION.
2. ALL INTERIOR SUPPLY AND RETURN DUCTWORK SHALL INCLUDE 1" LINER
UNLESS OTHERWISE NOTED. ALL OUTSIDE AIR INTAKE AND ROUND
DUCTWORK SHALL BE WRAPPED WITH 1.5" THICK INSULATION UNLESS
OTHERWISE NOTED.
3. ALL FINAL DUCTWORK CONNECTIONS TO SUPPLY GRILLES (OR PLENUMS)
SHALL BE COMPLETED WITH ACOUSTICAL FLEXIBLE DUCT UNLESS
OTHERWISE NOTED AND A MAXIMUM LENGTH OF FIVE FEET.
4. ALL ROUND DUCT CONNECTIONS TO ROUND DUCTWORK SHALL BE
CONICAL TEES.
5. ALL SQUARE 90 DEGREE ELBOWS SHALL HAVE TURNING VANES.
6. ALL DUCTWORK SHALL BE RUN TIGHT TO UNDERSIDE OF STRUCTURE
WHERE IT EXISTS UNLESS OTHERWISE NOTED.
7. ALL DUCTWORK PASSING THROUGH FIRE-RATED ASSEMBLIES SHALL
INCLUDE FIRE DAMPERS RATED TO MATCH THAT OF THE ASSEMBLY.
8. ALL SUPPLY GRILLES SHALL HAVE INCLUDE A BALANCING DAMPER
UNLESS OTHERWISE NOTED (EVEN THOUGH THEY MAY NOT BE SHOWN
EVERYWHERE). IF THE DAMPER IS LOCATED IN AN INACCESSIBLE
LOCATION, CABLE-STYLE DAMPERS (ROTOTWIST OR EQUIVALENT) SHALL
BE INSTALLED AND SHALL BE ADJUSTABLE FROM THE GRILLE FACE.
MULTIPLE RETURN DIFFUSERS IF SERVED BY A COMMON RETURN
DUCTWORK SHALL BE EQUIPPED WITH BALANCING DAMPERS.
9. COORDINATE ALL ACCESS PANEL LOCATIONS WITH THE ARCHITECT.
1
2
2
83 7+58 7+(
ROOF & DN
3
3
T
T
T
TO BB-73 - 75
TO BB-71, 72
TO BB-69, 70
of
Drawn By: Checked By:
DATE: ISSUE:
02-22-16 DD SET
AEC PROJECT #: TOV FIRE STATION #1
RENOVATION
VAIL, COLORADO 81657
16001.00
www.aec-vail.com
CMechanical, Electrical & Lighting Design Services
Architectural Engineering Consultants
Telephone:
970-748-8520
E
G$Q 2IILFH ZLWK /((' $FFUHGLWHG 3URIHVVLRQDOV
03-14-16
PROGRESS
03-22-16
PERMIT
04-01-16
CD SET
/< 61%
.'8'.
'*7 .1(6
*8#% 2.#0
5%#.' Ä
/
NORTH
LEVEL 5 (EHU LOFT) HVAC PLAN
SCALE: 3/16" = 1'0"
06/14/16