SHEET DETAIL NOTES:
PROPOSED LOCATION OF SM-1 MANIFOLD. VERIFY LOCATION WITH THE
G.C. AND/OR OWNER PRIOR TO INSTALLATION. CONNECT 1-1/2" SMS/R
TO SM-1.
PROPOSED LOCATION OF SM-2 MANIFOLD. VERIFY LOCATION WITH THE
G.C. AND/OR OWNER PRIOR TO INSTALLATION. CONNECT 1-1/2" SMS/R
TO SM-2.
ROUTE 2" SMS/R TO THE MECHANICAL ROOM. CONNECT TO THE MAIN
BOILER PIPING. RE: BOILER PIPING DIAGRAM ON M1.3.
CONFIRM EXACT LOCATION OF SNOW / ICE SENSOR W/ G.C. LOCATE
EQUIDISTANT BETWEEN TUBING & DO NOT LOCATE UNDER AN
OVERHANG.
EPO
SZ
1
SZ
2
1445 SQFT
1445 SQFT
SM
2
SM
1
P
6
B-2
B-1
GF-1
WH-1
2" SMS/R
2" SMS/R
2" SMS/R
1-1/2" SMS/R
1-1/2" SMS/R
GENERAL NOTES:
1. OFFSET PIPING AS REQUIRED TO AVOID ALL DUCTWORK, LIGHTS, AND
STRUCTURE. COORDINATE ALL STRUCTURAL PENETRATIONS WITH THE
STRUCTURAL ENGINEER.
2. ALL PIPING PASSING THROUGH FIRE-RATED ASSEMBLIES SHALL INCLUDE
A FIRE-RATED PIPE SEALANT RATED TO MATCH THAT OF THE ASSEMBLY.
3. ALL MECHANICAL PIPING SHOWN DASHED SHALL BE LOCATED BELOW
THE FLOOR DECK.
4. VERIFY FINAL LOCATIONS OF ALL MANIFOLDS WITH THE G.C. CONTACT
ENGINEER IF MANIFOLDS MOVE MORE THAN 5' (OR AS QUOTED IN THE
SNOWMELT SCHEDULE ON M1.1) FROM LOCATIONS SHOWN ON PLANS.
5. LOCATION OF ALL THERMOSTATS AND SENSORS ARE APPROXIMATE,
COORDINATE EXACT LOCATIONS WITH THE ARCHITECT. LOCATE SM
SENSOR EQUIDISTANT BETWEEN LOOPS, AND DO NOT LOCATE WHERE IT
MAY LIKELY BE COVERED BY OVERHANGS, TREES, OR ANY OTHER
OBSTACLES .
6. ALL PIPING SIZED FOR TYPE L COPPER, SNOWMELT TUBING SIZED FOR
APPROPRIATE aPEX WITH OXYGEN BARRIER. CONTACT ENGINEER FOR
ANY CHANGE TO PEX FOR NECESSARY PIPE SIZING AND/OR PUMP
CHANGES.
1
2
2
3
3
7B C 7C D F.3 F.4 E F.1 F.2
S
SNOWMELT
SENSOR 090/091
TO SNOWMELT
CONTROLLER
RE: BOILER PIPING
DIAGRAM ON M1.3
GF-2
HX-1
4
4
of
Drawn By: Checked By:
DATE: ISSUE:
02-22-16 DD SET
AEC PROJECT #: TOV FIRE STATION #1
RENOVATION
VAIL, COLORADO 81657
16001.00
www.aec-vail.com
CMechanical, Electrical & Lighting Design Services
Architectural Engineering Consultants
Telephone:
970-748-8520
E
G$Q 2IILFH ZLWK /((' $FFUHGLWHG 3URIHVVLRQDOV
03-14-16
PROGRESS
03-22-16
PERMIT
04-01-16
CD SET
/< 61%
.'8'.
5019/'.6
2.#0
5%#.' Ä
/
NORTH
LEVEL 1 SNOWMELT PLAN
SCALE: 3/16" = 1'0"
06/14/16