HomeMy WebLinkAboutinspector_summary_28471_01-24-2017-5120.pdfInspection Result:Fail
Inspector:Charlie Davis
Permit Type Inspection Type Address
Construction Mechanical Final 4116 COLUMBINE DR (210112215009) (21011221500915)
Inspection Date:01/24/2017
Permit #:B16-0087.002
TMK:21011221500915
Applicant name:Town Of Vail - John King
Email:jking@vailgov.com
Phone:
Comments:
1. 1st level tube heaters originally was to use existing but has since been replaced with new appliances
including gas piping. Revised drawings provide to me did not have mechanical revisions. Be sure Town
approval obtained.
2. Equipment/clothes dryer must be vented to exterior see IMC 504
3. Inspector Signature
4. Applicant Signature
5. Balance report required
6. Cover plates required on all heat lines
7. Provide listing for gas regulator allowed to be in vented IFGC chapter 4
8. Complete labeling of all valves
Inspection Summary