HomeMy WebLinkAboutinspector_summary_28471_01-24-2017-5120.pdfInspection Result:Fail Inspector:Charlie Davis Permit Type Inspection Type Address Construction Mechanical Final 4116 COLUMBINE DR (210112215009) (21011221500915) Inspection Date:01/24/2017 Permit #:B16-0087.002 TMK:21011221500915 Applicant name:Town Of Vail - John King Email:jking@vailgov.com Phone: Comments: 1. 1st level tube heaters originally was to use existing but has since been replaced with new appliances including gas piping. Revised drawings provide to me did not have mechanical revisions. Be sure Town approval obtained. 2. Equipment/clothes dryer must be vented to exterior see IMC 504 3. Inspector Signature 4. Applicant Signature 5. Balance report required 6. Cover plates required on all heat lines 7. Provide listing for gas regulator allowed to be in vented IFGC chapter 4 8. Complete labeling of all valves Inspection Summary