HomeMy WebLinkAboutinspector_summary_28472_01-24-2017-5122.pdfInspection Result:Fail
Inspector:Charlie Davis
Permit Type Inspection Type Address
Construction Building Final 4116 COLUMBINE DR (210112215009) (21011221500915)
Inspection Date:01/24/2017
Permit #:B16-0087.002
TMK:21011221500915
Applicant name:Town Of Vail - John King
Email:jking@vailgov.com
Phone:
Comments:
1. Single user restroom lavatory encroaches upon 60" clearance from toilet wall see ICC A117.1 section
604
2. Vertical grab bar is installed less than 39" from rear wall see A117.1 section 604.
3. Inspector Signature
4. Applicant Signature
5. Raised letter signs/exit signs required at all exit discharge doors. IBC 1011
6. Signs greater than 60" from Braille ICC A117.
7. Final clean removal of all constructive n materials and equipment required.
8. Generator commissioning and final start up required.
9. Electrical final required
10. Emergency shut off sign for boiler required
11. Slope paving from garage to main entry appears to be greater than 5%. Confirm that less than this or
Inspection Summary
provide required handrails for ramp.
12. Confirm with Building that hand rail extension on main stairs not required.
13. Rated access panel required at under stair storage access to valves located in space and patch
penetration
14. Spray foam insulation requires ignition barrier in attic/mech space
15. Guard rail gaps greater than 4" at balusters EHU 2
16. Finish exterior trim EHU 2
17. Deck at EHU 1 not complete more than 4" spacing at joists
18. Window limiters are required at all windows with sill heights less than 36" and grade greater than 6' IBC
1013.8
19. Inspection discontinued.