Loading...
HomeMy WebLinkAboutinspector_summary_28472_01-24-2017-5122.pdfInspection Result:Fail Inspector:Charlie Davis Permit Type Inspection Type Address Construction Building Final 4116 COLUMBINE DR (210112215009) (21011221500915) Inspection Date:01/24/2017 Permit #:B16-0087.002 TMK:21011221500915 Applicant name:Town Of Vail - John King Email:jking@vailgov.com Phone: Comments: 1. Single user restroom lavatory encroaches upon 60" clearance from toilet wall see ICC A117.1 section 604 2. Vertical grab bar is installed less than 39" from rear wall see A117.1 section 604. 3. Inspector Signature 4. Applicant Signature 5. Raised letter signs/exit signs required at all exit discharge doors. IBC 1011 6. Signs greater than 60" from Braille ICC A117. 7. Final clean removal of all constructive n materials and equipment required. 8. Generator commissioning and final start up required. 9. Electrical final required 10. Emergency shut off sign for boiler required 11. Slope paving from garage to main entry appears to be greater than 5%. Confirm that less than this or Inspection Summary provide required handrails for ramp. 12. Confirm with Building that hand rail extension on main stairs not required. 13. Rated access panel required at under stair storage access to valves located in space and patch penetration 14. Spray foam insulation requires ignition barrier in attic/mech space 15. Guard rail gaps greater than 4" at balusters EHU 2 16. Finish exterior trim EHU 2 17. Deck at EHU 1 not complete more than 4" spacing at joists 18. Window limiters are required at all windows with sill heights less than 36" and grade greater than 6' IBC 1013.8 19. Inspection discontinued.