HomeMy WebLinkAboutB17-0154_M0.3_1497476280.pdfSUPPORT SYSTEM. WHERE OVERHEAD STRUCTURE DOES NOT PERMIT DIRECT FASTENING OF
SUPPORTS, FURNISH ADDITIONAL FRAMING AND SUPPLEMENTARY STEEL AS REQUIRED
FASTENED SECURELY TO THE BUILDING STRUCTURAL.
10. COORDINATE THE MECHANICAL WORK WITH THE WORK OF THE OTHER SECTIONS AND
DIVISIONS. PROVIDE TIME AND MATERIALS TO MAKE ALL APPROPRIATE AND PROPER
INSTALLATIONS AND CONNECTIONS. REVIEW SPACE REQUIREMENTS, INCLUDING SERVICE AND
MAINTENANCE CLEARANCES FOR THE EQUIPMENT SUPPLIED FOR THIS PROJECT WITH THE
ACTUAL FIELD CONDITIONS TO ENSURE THAT EQUIPMENT AND MATERIALS CAN BE INSTALLED
INTO THE SPACE ALLOTED.
11. PREPARE WORKING DRAWINGS, ATTEND MEETINGS, PREPARE CRITICAL ENVIRONMENT WORK
AUTHORIZATION (CEWA) REQUESTS, OBTAIN ALL APPROVALS BY ALL AHJ, CONDUCT REQUIRED
TESTS AND OBTAIN REQUIRED PERMITS.
3.01 BUILDING SURFACE PENETRATIONS
1. SLEEVES SHALL NOT BE INSTALLED IN STRUCTURAL MEMBERS EXCEPT WHERE INDICATED OR
APPROVED. SLEEVES IN NONLOAD BEARING SURFACES SHALL BE GALVANIZED SHEET METAL,
CONFORMING TO ASTM A 653, COATING CLASS G-90, 20 GAUGE. SLEEVES IN LOAD BEARING
SURFACES SHALL BE UNCOATED CARBON STEEL PIPE, CONFORMING TO ASTM A 53, STANDARD
WEIGHT. SEALANTS SHALL BE APPLIED TO MOISTURE AND OIL-FREE SURFACES AND
ELASTOMERS TO NOT LESS THAN 1/2 INCH DEPTH.
2. EACH SLEEVE SHALL EXTEND THROUGH ITS RESPECTIVE WALL AND SHALL BE CUT FLUSH WITH
EACH SURFACE. PIPES PASSING THROUGH CONCRETE OR MASONRY WALL SHALL BE PROVIDED
WITH PIPE SLEEVES FITTED INTO PLACE AS REQUIRED. SLEEVES SHALL BE OF SUCH SIZE AS TO
PROVIDE A MINIMUM OF 1/4 INCH ALL-AROUND CLEARANCE BETWEEN BARE PIPE AND SLEEVES
OR BETWEEN JACKETED-INSULATION AND SLEEVES. EXCEPT IN PIPE CHASES OR INTERIOR
WALLS, THE ANNULAR SPACE BETWEEN PIPE AND SLEEVE OR BETWEEN JACKET
OVER-INSULATION AND SLEEVE SHALL BE SEALED WITH APPROPRIATE JOINT SEALANTS.
3. ESCUTCHEONS: FINISHED SURFACES WHERE EXPOSED PIPING, BARE OR INSULATED, PASS
THROUGH WALLS EXCEPT IN UTILITY OR EQUIPMENT ROOMS, SHALL BE PROVIDED WITH
ESCUTCHEONS. WHERE SLEEVES PROJECT SLIGHTLY FROM FLOORS, SPECIAL DEEP-TYPE
ESCUTCHEONS SHALL BE USED. ESCUTCHEON SHALL BE SECURED TO PIPE OR PIPE COVERING.
3.02 CLEANING
1. REMOVE DEBRIS FROM INSIDE AND OUTSIDE OF ALL DUCTWORK AND EQUIPMENT. CLEAN
INTERIOR OF EXISTING WSHP UNIT WITH A DAMP CLOTH TO REMOVE ALL DIRT AND METAL
SHAVINGS.
2. BRUSH OR CLEAN WORK, WHICH WILL BE CONCEALED, PRIOR TO FINAL ACCEPTANCE AND
BEFORE CONCEALING.
3. CLEAN SURFACES WHICH HAVE BEEN SOILED AND REPAIR SURFACES WHICH HAVE BEEN
DAMAGED TO MATCH ADJACENT SURFACES BEFORE FINAL ACCEPTANCE.
3.03 PAINTING: PROVIDE ALL PAINTING REQUIRED
FOR THE MECHANICAL WORK.
1. PAINT SHALL BE THE BEST GRADE FOR ITS PURPOSE, DELIVERED IN ORIGINAL SEALED
CONTAINERS, APPLIED IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS, WITH COLORS
TO MATCH THE EXISTING OR ADJACENT SURFACES.
2. PROVIDE HOT-DIPPED GALVANIZED OR ZINC CHROMATE PRIMER ON ALL UNFINISHED IRON
SURFACES.
3.04 TESTING, ADJUSTING AND BALANCING
1. GENERAL:
A. ADJUSTMENT: BEFORE TEST AND BALANCE WORK IS INITIATED, EACH PIECE OF HVAC
EQUIPMENT AND EACH HVAC SYSTEM SHALL BE ADJUSTED TO THE APPROXIMATE DESIGN
CAPACITY TO ENSURE PROPER FUNCTIONING OF ALL CONTROLS.
1) PRELIMINARY OPERATION: THE OWNER RESERVES THE RIGHT TO OPERATE ANY
SYSTEMS OR EQUIPMENT PRIOR TO FINAL COMPLETION AND ACCEPTANCE OF THE
WORK. SUCH PRELIMINARY OPERATION SHALL NOT BE CONSTRUED AS AN
CONTRACTUAL ACCEPTANCE OF THE MECHANICAL WORK.
2. AIR DISTRIBUTION SYSTEMS:
A. BALANCE AND ADJUST AIR DISTRIBUTION SYSTEM TO QUANTITIES INDICATED ON THE
DRAWINGS IN ACCORDANCE WITH THE ASSOCIATED AIR BALANCE COUNCIL (AABC)
MANUAL, LATEST EDITION; OR THE NATIONAL ENVIRONMENTAL BALANCING BUREAU (NEBB)
MANUAL, LATEST EDITION.
B. BALANCING AND TESTING SHALL BE PERFORMED BY A CERTIFIED INDEPENDENT FIRM
SPECIALIZING IN TESTING AND BALANCING (AABC); OR BY A CONTRACTOR CERTIFIED IN
TEST AND BALANCING (NEBB). FIRM SHALL BE A MEMBER OF AABC OR NEBB. TEST
REPORTS SHALL BE TYPEWRITTEN AND SUBMITTED IN BOUND FOLDERS AND ON THE AABC
OR NEBB TEST AND BALANCE REPORT FORMS. ALL GRILLES, REGISTERS, AND DIFFUSERS
TESTED SHALL BE IDENTIFIED IN THE REPORT BY DESIGNATIONS AS INDICATED ON THE
DRAWINGS.
C. THE HVAC SYSTEMS AND THE INDIVIDUAL DAMPERS AND AIR BALANCING DEVICES SHALL
BE ADJUSTED TO PROVIDE DIFFUSER AIR FLOW DELIVERY NOT BE LESS THAN NOR MORE
THAN TEN (10) PERCENT OF THE AIR DELIVERY INDICATED ON THE DRAWINGS.
D. UPON COMPLETION OF THE INSTALLATION, CONTRACTOR SHALL REBALANCE ANY AIR
DISTRIBUTION SYSTEM AFFECTED BY THE TENANT IMPROVEMENT WORK AND RENOVATION,
INCLUDING AIR TERMINAL UNITS AND AIR OUTLETS.
3.05 INSTRUCTION OF OWNER'S OPERATING PERSONNEL
1. THE CONTRACTOR SHALL INCLUDE THE COST OF THE SERVICES OF QUALIFIED INSTRUCTOR(S)
TO INSTRUCT THE OWNER'S OPERATING PERSONNEL IN THE OPERATION, ADJUSTMENT, CARE
AND MAINTENANCE OF ALL EQUIPMENT AND SYSTEMS.
2. INSTRUCTION SHALL BE PERFORMED AT A TIME APPROVED BY THE OWNER AFTER ALL
EQUIPMENT AND SYSTEMS ARE INSTALLED, COMPLETED, ADJUSTED AND OPERATING TO
SPECIFIED REQUIREMENTS. CONTRACTOR SHALL NOTIFY THE ENGINEER 7 DAYS PRIOR TO THE
SCHEDULED TIME WHEN INSTRUCTIONS WILL BE GIVEN.
3. QUALIFICATION OF INSTRUCTOR(S) SHALL BE SUBJECT TO APPROVAL OF THE OWNER AND
EQUIPMENT MANUFACTURER.
4. THE BASIS OF THE INSTRUCTION AND TRAINING OF THE OPERATORS FOR HVAC EQUIPMENT
SHALL BE THE CONTRACTOR'S OPERATION AND MAINTENANCE MANUALS PROVIDED FOR THE
MECHANICAL, FIRE PROTECTION AND PLUMBING EQUIPMENT AND SYSTEMS SUPPLIED FOR THIS
PROJECT.
5. TWO COPIES OF ACKNOWLEDGEMENT OF ALL REQUIRED INSTRUCTIONS TO OWNER'S
OPERATING PERSONNEL, SIGNED BY THE OWNER OR HIS AUTHORIZED REPRESENTATIVE, SHALL
BE SUBMITTED TO THE ENGINEER PRIOR TO SUBMITTING APPLICATION FOR FINAL PAYMENT. AN
ADDITIONAL COPY OF THIS ACKNOWLEDGEMENT SHALL BE PLACED IN EACH COPY OF THE
OPERATION AND MAINTENANCE MANUALS BEFORE THEY ARE TURNED OVER TO THE OWNER
AND/OR THE OWNER'S REPRESENTATIVE.
3.06 PROJECT CLOSEOUT
1. AFTER FINAL COMMISSIONING OPERATIONS FOR INSPECTION AND ACCEPTANCE, DELIVER ALL
COPIES OF THE FOLLOWING INFORMATION TO THE ENGINEER:
2. OPERATION AND MAINTENANCE (O&M) MANUALS.
3. RECOMMENDED SPARE PARTS LISTS, TO BE INCLUDED IN A SECTION OF THE O&M MANUAL.
4. EQUIPMENT STARTUP REPORTS (PREPARED BY FACTORY-AUTHORIZED START-UP PERSONNEL).
5. RECORD (AS-BUILT) DRAWINGS.
6. CONTRACTOR'S WRITTEN WARRANTY.
7. EXTENDED WARRANTIES, TO BE INCLUDED IN A SECTION OF THE O&M MANUAL.
8. HVAC TEST AND BALANCE REPORT.
9. CONTROLS COMMISSIONING REPORT.
10. HVAC COMMISSIONING REPORT.
11. PREVENTIVE MAINTENANCE CEWA'S FOR HVAC EQUIPMENT.
12. ALL TOOLS SUPPLIED WITH THE EQUIPMENT FOR MAINTENANCE SHALL BE TAGGED AND
TEMPORARILY SECURED TO THE UNIT, OR TURNED OVER TO THE BUILDING ENGINEER OR THE
OWNER'S AUTHORIZED AGENT FOR THIS PROJECT.
13. ALL SPARE PARTS AND AN EXTRA SET OF HVAC FILTERS SHALL BE TURNED OVER TO THE
BUILDING ENGINEER OR THE OWNER'S AUTHORIZED AGENT FOR THIS PROJECT.
2.05 INSULATION MATERIALS
1. MATERIALS: INSULATION, JACKETS, FACINGS, ADHESIVES, COATINGS, AND ACCESSORIES SHALL
BE UL LISTED AND IN COMPLIANCE WITH NFPA STANDARD 90A FIRE HAZARD RATING: "FIRE
HAZARD CLASSIFICATION OF BUILDING MATERIALS"; UL 723, ASTM E84, NFPA 225.
A. FLAME SPREAD: 25, MAXIMUM.
B. FUEL CONTRIBUTED: 50, MAXIMUM.
C. SMOKE DEVELOPED: 50, MAXIMUM.
2. INSULATION SHALL BE MANUFACTURED BY MANVILLE OR APPROVED EQUAL.
3. INSULATION SHALL BE LABELED AS REQUIRED BY CODE.
4. INSULATION SHALL BE APPLIED IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS.
5. NOISE CONTROL:
A. UNLESS OTHERWISE NOTED, ALL ROOM NC LEVELS SHALL BE 35 OR LESS.
B. DUCTS LINED AS REQUIRED.
6. INSULATE ALL EXISTING AND NEW DUCTWORK AND EQUIPMENT, EXCEPT AS FOLLOWS:
A. VENTS, OVERFLOW AND RELIEF PIPING.
B. RETURN AIR DUCTS IN CONDITIONED SPACES AND EXHAUST AIR DUCTS, EXCEPT WHERE
INDICATED.
C. WHERE SOUND LINING IS OF MINIMUM THICKNESS SPECIFIED FOR INSULATION.
7. TYPE OF INSULATION:
A. DUCT INSULATION: 2-INCH THICK, 3/4 PCF LB. DENSITY, DUCT WRAP GLASS FIBER
INSULATION WITH ALUMINUM FOIL FACING. 6.0 R-VALUE. MANVILLE R-SERIES MICROLITE
OR APPROVED EQUAL.
B. DUCT LINING: 2-INCH THICK, 1-1/2 PCF DENSITY, COATED ON AIR SIDE WITH BLACK
NEOPRENE, FIRE-RESISTANT, ANTI-MICROBIAL COATING. 6.0 R-VALUE. MANVILLE
LINACOUSTIC OR APPROVED EQUAL. FOR THE FOLLOWING DUCTWORK:
1) ALL DUCTWORK WITHIN MECHANICAL ROOMS AND NOT LESS THAN 25 FEET FROM FAN
FOR SUPPLY AND 20 FEET FROM FAN FOR RETURN DUCTWORK.
2) AIR TRANSFER DUCTS.
3) DOWNSTREAM OF ALL VARIABLE AIR VOLUME AND CONSTANT VOLUME BOXES FOR A
MINIMUM OF 10 FEET.
4) MINIMUM OF 2 INCHES THICK FOR ALL MIXED AIR PLENUMS, EXCEPT WHERE
MOISTURE CARRY-OVER FROM OUTDOOR AIR LOUVER WILL OCCUR
2.06 ROOM TEMPERATURE SENSORS
1. ROOM TEMPERATURE SENSORS
C. PUSH BUTTON TIMED OVERRIDE
D. SET POINT ADJUSTMENT
E. DIGITAL READOUT DISPLAY
F. FULLY COMPATIBLE WITH EXISTING BMS.
2.07 IDENTIFICATION:
TAGS, CHARTS, PIPE LABELING AND STENCILING
1. TAGS:
A. MINIMUM 2 INCH DIAMETER
B. NO. 18 GAGE ALUMINUM WITH STAMPED NUMBERS AND LETTERS FILLED IN WITH BLACK
PAINT.
C. IDENTIFYING NUMBER AND SYSTEM LETTER.
D. FASTENED BY HEAVY ALUMINUM HOOK OR CHAIN.
E. DIFFERENT PATTERN THAN THOSE USED FOR PLUMBING AND SPRINKLER WORK.
F. PROVIDE ON VALVES AND CONTROLS.
G. LABELING PER OWNER'S REQUIREMENTS.
2. CHARTS:
A. SCHEMATIC FLOW DIAGRAMS FOR EACH PIPING SYSTEM INDICATING:
B. LOCATION AND FUNCTION OF EACH TAGGED VALVE.
C. SUBMIT FOR REVIEW.
D. BOUND IN O&M MANUALS.
3. STENCILING:
A. BY HVAC CONTRACTOR.
B. MARK PIPING WITH SIZE, PURPOSE AND DIRECTION OF FLOW WITH CORRECT
2.08 IDENTIFICATION OF EQUIPMENT AND CONTROLS
1. ALL EQUIPMENT SHALL BE STENCILED OR LABELED WITH LAMACOID PLATES SCREWED THEREON
WHICH SHALL INDICATE SYSTEMS SERVICE.
2. AN IDENTIFICATION LABEL SHALL BE PROVIDED FOR THE FOLLOWING TYPES OF EQUIPMENT:
A. AIR HANDLING UNITS.
B. EXHAUST FANS.
C. VALVES.
D. AS REQUESTED BY THE OWNER.
1) IDENTIFICATION LABELS
SHALL BE BY SETON, OR EQUIVALENT.
2) THE ARRANGEMENT OF THE INFORMATION, LETTERING SIZES, ETC. FOR
IDENTIFICATION LABELS SHALL CONFORM TO THE BUILDING STANDARD.
2.09 EQUIPMENT OPERATING AND MAINTENANCE MANUALS
1. ON COMPLETION AND ACCEPTANCE OF WORK, THIS CONTRACTOR SHALL FURNISH WRITTEN
INSTRUCTIONS TO THE OWNER ON THE PROPER OPERATION AND MAINTENANCE (O&M) OF ALL
EQUIPMENT AND APPARATUS FURNISHED UNDER THIS CONTRACT.
2. THESE INSTRUCTIONS SHALL BE TYPED ON 8½ BY 11 INCH PAPER AND BOUND IN THREE-RING
BINDERS WITH CLEAR ACETATE COVERS. ALSO AN ELECTRONIC COPY ON A DVD SHALL BE
PROVIDED. THE CONTRACTOR SHALL GIVE THREE HARD AND TWO DVD COPIES OF THE
INSTRUCTIONS TO THE OWNER AND ONE COPY OF BOTH TO THE ENGINEER.
3. THE INSTRUCTION BOOKLET SHALL BE ORGANIZED IN SECTIONS WITH ONE SECTION PER
SYSTEM. THE COVER OF THE INSTRUCTION BOOKLET SHALL BEAR THE NAME, ADDRESS AND
PHONE NUMBER OF THE PROJECT, ARCHITECT, ENGINEER, MECHANICAL CONTRACTOR AND
SUBCONTRACTOR'S NAME.
2.10 ACCESS DOORS
1. PROVIDE EQUIPMENT AND CONCEALED VALVE ACCESS, EXCEPT IN REMOVABLE TILE CEILINGS
AND APPROVED BY LOCAL CODE, WITH ADEQUATE SIZE (MINIMUM 18 INCHES BY 18 INCHES)
ACCESS DOORS FOR INSPECTION AND MAINTENANCE.
3.00 INSTALLATION
1. HVAC EQUIPMENT AND THE INSTALLATION THEREOF SHALL CONFORM TO ASHRAE 15.
NECESSARY SUPPORTS SHALL BE PROVIDED FOR ALL EQUIPMENT AND APPURTENANCES.
2. THE DRAWINGS ARE DIAGRAMMATIC AND DO NOT INDICATE ALL NECESSARY OFFSETS,
OBSTRUCTIONS, OR STRUCTURAL CONDITIONS. IT IS THE RESPONSIBILITY OF THE CONTRACTOR
TO FIELD VERIFY ALL EXISTING CONDITIONS WHICH AFFECT THE ARRANGEMENT AND LAYOUT OF
THE WORK.
3. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO INSTALL THE WORK AT THE HIGHEST
ELEVATION POSSIBLE AND IN SUCH A MANNER AS TO CONFORM TO THE STRUCTURE, AVOID
OBSTRUCTIONS, MAINTAIN HEADROOM, AND LEAVE ADEQUATE CLEARANCES FOR LIGHT
FIXTURES, MAINTENANCE ACCESS, AND FOR OTHER CLEARANCES AS REQUIRED BY THE LOCAL
AHJ. ALL WORK TO PROVIDE MAXIMUM POSSIBLE CLEARANCES IS A PROJECT REQUIREMENT AND
SHALL BE PERFORMED AND PROVIDED AT NO ADDITIONAL COST TO THE PROJECT.
4. PROCEED WITH THE INSTALLATION AS RAPIDLY AS THE BUILDING CONSTRUCTION AND
RENOVATION WILL PERMIT. THOROUGHLY CLEAN ITEMS BEFORE INSTALLATION. CAP OPENINGS
IN DUCTWORK TO EXCLUDE DIRT UNTIL FINAL CONNECTIONS HAVE BEEN MADE.
5. WELDING AND BRAZING SHALL BE ACCOMPLISHED IN ACCORDANCE WITH THE QUALIFIED
PROCEDURES USING PERFORMANCE QUALIFIED WELDERS, AND BRAZING OPERATORS.
6. FOR DIRECTIONS AND DETAILS NOT SHOWN ON THE DRAWINGS, THE MANUFACTURER'S
CERTIFIED DRAWINGS AND WRITTEN OR PUBLISHED INSTRUCTIONS SHALL BE FOLLOWED IN ALL
CASES WHERE THE MAKERS OF DEVICES AND EQUIPMENT FURNISHED PROVIDE SUCH
INFORMATION.
7. DRAWINGS ARE NOT INTENDED TO BE SCALED, BUT SHALL BE FOLLOWED WITH SUFFICIENT
ACCURACY TO COORDINATE WITH OTHER WORK AND STRUCTURAL LIMITATIONS.
8. ALL EQUIPMENT SHALL BE SECURELY FASTENED TO THE BUILDING CONSTRUCTION BY AN
APPROVED SUPPORTING SYSTEM. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL
ANCHORS, SUPPORTS, AND CONNECTIONS OF THE MECHANICAL WORK TO THE BUILDING
STRUCTURE TO PREVENT DAMAGE TO THE STRUCTURE OR TO MECHANICAL EQUIPMENT,
INCLUDING THE CONNECTION AND INTEGRITY OF SHOP-FABRICATED AND FIELD-FABRICATED
MATERIALS AND EQUIPMENT. ALL SUPPORTS, EQUIPMENT AND CONNECTIONS THERETO SHALL
BE DESIGNED TO CONFORM TO THE REQUIREMENTS OF THE STATE OF NORTH CAROLINA
BUILDING CODES, OR TO THE OTHER GOVERNING CODES.
9. ALL MECHANICAL WORK SHALL BE PROPERLY SUPPORTED FROM THE BUILDING STRUCTURE
AND/OR FRAMING IN AN APPROVED MANNER, AND SHALL BE INDEPENDENT OF THE CEILING
2.04 SUPPORTS AND ANCHORS
1. GENERAL: SUPPORT HORIZONTAL DUCTS WITH HANGERS OF SIZE AND SPACING AS REQUIRED
BY THE SMACNA DUCT MANUAL. PROVIDE ADDITIONAL SUPPLEMENTARY STRUCTURAL STEEL AS
REQUIRED.
2. HORIZONTAL DUCT SUPPORTS:
A. INSTALL HANGERS AT EACH CHANGE IN DIRECTION OF DUCT.
B. STRAP HANGERS:
1) EXTEND STRAP AND FASTEN TO DUCT DOWN BOTH SIDES OF DUCT.
2) TURN STRAPS UNDER BOTTOM OF DUCT ONE INCH, MINIMUM.
3) PROVIDE SHEET METAL SCREWS AT 12-INCHES ON CENTER.
4) SEAL AROUND SCREW HEADS "AIR TIGHT".
C. ANGLE HANGERS: PROVIDE ANGLE HANGERS FORMED BY EXTENDING VERTICAL
BRACING ANGLES TO STRUCTURE.
2.11 AIR DISTRIBUTION DEVICES
1. EXISTING CEILING DIFFUSERS MAY BE REUSED AND RELOCATED AS NECESSARY UNLESS OTHERWISE OR
SIZE PROHIBITS USE.
2. NEW CEILING DIFFUSERS TO BE PRICE, TITUS, METALAIRE OR KRUEGER AND EQUAL TO PRICE MODEL AS
SCHEDULED AND SUIT THE SPECIFIED SERVICE AND CEILING TYPE UNLESS NOTED OTHERWISE ON PLANS.
COORDINATE WITH ARCHITECTURAL PLANS.
3. CEILING RETURN AIR GRILLES SHALL BE PRICE, TITUS, NAILOR, METALAIRE OR KRUEGER AND EQUAL TO
PRICE MODEL AS SCHEDULED.
4. EXHAUST REGISTERS SHALL BE PRICE, TITUS, NAILOR, METALAIRE OR KRUEGER AND EQUAL TO PRICE
MODEL AS SCHEDULED.
5. ALL DIFFUSERS SHALL BE FURNISHED WITH SPIN-IN COLLAR. VOLUME DAMPER AND 6' OF FLEXIBLE DUCT.
2.12 INSTALLATION
1. PIPING SHALL BE COMPLETE WITH: PIPE, FITTINGS, COUPLINGS, HANGERS, ANCHORS, SUPPORTS,
CLEANOUTS, SLEEVES AND ACCESSORIES.
2. ALL ITEMS SHALL BE FURNISHED AND INSTALLED IN ACCORDANCE WITH THE LATEST EDITIONS OF THE
FOLLOWING CODES AND STANDARDS:
A. AMERICAN SOCIETY OF MECHANICAL ENGINEERS (ASME).
B. AMERICAN SOCIETY OF TESTING AND MATERIALS (ASTM).
C. AMERICAN NATIONAL STANDARDS INSTITUTES (ANSI).
D. MANUFACTURERS STANDARDIZATION SOCIETY OF THE VALVE AND FITTING INDUSTRY (MSS).
3. FOR JOINTS OF DISSIMILIAR METALS, PROVIDE DIELECTRIC UNION OR FLANGE.
4. TESTING: ALL PRESSURIZED PIPING TO BE TESTED HYDR-STATICALLY TO 150.
5. PIPING:
A. HOT WATER PIPING: SEAMLESS COPPER TUBING, TYPE L, COLD DRAWN, HARD TEMPER. ASTM B88.
6. PIPE FITTINGS:
A. WROUGHT COPPER SOLDER SWEAT TYPE. ANSI B16.22 OR BRASS CASTING, ANSI B16.18.
7. JOINTS:
A. 95-5 (TIN AND ANTIMONY) SOLDER. BRASS CASTING, ANSI B16.18.
8. PIPE SUPPORT:
A. PROVIDE ADEQUATE SUPPORT FOR PIPE AND CONTENTS TO PREVENT SAGGING, VIBRATION OR SWAYING
AND ALLOW FOR EXPANSION AND CONTRACTION. PROVIDE SUPPLEMENTAL STEEL AS REQUIRED WHERE
STRUCTURE CANNOT SUPPORT POINT LOADS.
B. HORIZONTAL PIPING TO BE SUPPORTED BY FORGED STEEL ADJUSTABLE CLEVIS TYPE HANGER. MAXIMUM
SPACING AS FOLLOWS:
1) COPPER 3/4 IN. AND SMALLER: 5 FT.
2) COPPER 1-1-1/4 IN.: 6FT.
3) COPPER 1-1/2-3 IN.: 8FT.
4) COPPER 4 IN. AND LARGER: 10 FT.
5) ADDITIONAL SUPPORTS AT CHANGES IN DIRECTION, RUNOUTS, AND CONCENTRATED LOADS DUE TO
VALVES, ETC.
2.13 PIPE INSULATION
1. INSULATION MATERIAL:
A. HOT WATER PIPING: MOLDED FIBERGLASS, MAXIMUM 0.23 K-FACTOR AT 75 DEG F MEAN
TEMPERATURE, MINIMUM 4 LB DENSITY. SIMILAR TO OWENS CORNING FIBERGLASS MODEL 650 ASJ.
B. FOR VALVES, FLANGES AND FITTINGS, MOLDED FIBERGLASS FITTING, MAXIMUM 0.23 K-FACTOR AT 75
DEG F MEAN TEMPERATURE, MINIMUM 4 LB DENSITY. SIMILAR TO EPOLUX HAMFAB MOLDED FITTINGS.
2. HOT WATER PIPES:
A. INSULATE WITH OWENS-CORNING ASJ-SSL-II OR OPPROVED EQUAL 2" THICK PIPE INSULATION.
FITTING AND VALVES SHALL BE FINISHED WITH WHITE 25/50 PVC COVER MOLDED INSULATION
FITTINGS. ALL JOINTS AND LAPS SHALL BE VAPOR SEALED.
MARK SIZE OBD FINISH THROW NECK SIZE MANUFACTURER/MODEL NO. REMARKS NOTES
NOTES:
2. CONTRACTOR TO COORDINATE FRAME STYLE WITH ARCHITECTURAL PLANS.
3. PROVIDE INSULATION BLANKET.
EXHAUST TYPE AIR DEVICES
NECK SIZE
CFM NECK SIZE
SUPPLY TYPE DIFFUSERS
CFM NECK SIZE
UP TO 160
161 TO 250
251 TO 330
331 TO 440
441 TO 500
501 TO 800
6"Ø
8"Ø
10"Ø
12"Ø
14"Ø
16"Ø
UP TO 120
121 TO 240
241 TO 380
381 TO 680
551 TO 900
8"Ø
6"Ø
10"Ø
12"Ø
14"Ø
UP TO 290
291 TO 450
451 TO 700
701 TO 1200
1201 TO 1600
12/8
8/8
12/12
16/16
18/18
CFM
___
R-1 24x24
TITUS / PAR
NOTE 1
NO WHITE
S-1 24x24
TITUS / TMS LAY-IN CEILING SUPPLY DIFFUSER
4-WAY NOTE 1
NO
ALL
WHITE
DESIGN DEVELOPMENT /
PROGRESS
THIS DOCUMENT IS RELEASED
FOR THE PURPOSE OF DESIGN
DEVELOPMENT AND PROGRESS
UNDER THE AUTHORITY OF
JEFFREY W. MUSSER, PE #95820
ON MARCH 31, 2017. IT IS NOT TO
BE USED FOR OTHER PURPOSES.
VAIL
CASCADE + ARIA
RENOVATION
1300
WESTHAVEN
DRIVE
Vail, Colorado
04/20/2017
Revisions:
Sheet Title:
Project No:
Sheet No:
Issue Dates:
(970) 748-1470
email: tab@vail.net
fax: (970) 748-1471
Avon, CO 81620-7431
Post Office Box 7431
TAB
The Architectural Balance
Associates
www.tabassociates.com
Plotted:
4/19/2017
5:50:05 PM P:\DAL\BET\TABCO001\CAD\SHEETS\MECHANICAL\M0.3 MECHANICAL
SPECS AND SCHEDULES.DWG - snahas
A member company of SH Group, Inc.
R
Syska Hennessy Group, Inc.
1130 E. Arapaho Road
Suite #525
Richardson, TX 75081
Tel: 972.470.0704
Fax: 972.470.5851
www.syska.com
MECH
SPECS
AND SCHD
M0.3
LAY-IN CEILING RETURN DIFFUSER ALL
S-2 12x24
TITUS / TMS LAY-IN CEILING SUPPLY DIFFUSER
4-WAY NOTE 1
NO
ALL
WHITE
___
R-1 12x24
TITUS / PAR
NOTE 1
NO WHITE
LAY-IN CEILING RETURN DIFFUSER ALL
S-3 4 FT
TITUS / FL20 (1) 2" SLOT LINEAR SUPPY DIFFUSER
2-WAY NOTE 1
NO
ALL
WHITE
R-3 4 FT
TITUS / FL20 (1) 2" SLOT LINEAR RETURN DIFFUSER
NOTE 1
NO ALL
WHITE ___
06/14/17