SH-1
FIXTURE
ROUGH-IN SIZE
WASTE
2"
VENT
2"
HW
CW
1/2" 1/2"
SHOWER
NOTES:
SK-1 2"
1/2" 1/2"
SINK
1. ALL PLUMBING FIXTURES SHALL MEET LOW WATER CONSUMPTION REQUIREMENTS PER LOCAL &
STATE CODES.
2. PLUMBING CONTRACTOR SHALL PROVIDE TRAP PRIMERS AT ALL FLOOR DRAINS (WHETHER
SHOWN ON DRAWINGS OR NOT).
3. PLUMBING CONTRACTOR SHALL INSTALL FLUSH CONTROL LEVERS/HANDLES ON WIDE SIDE OF
STALL FOR ALL WATER CLOSETS TO ENSURE ADA COMPLIANCE.
4. PLUMBING CONTRACTOR SHALL INSTALL TRUEBRO PIPE (SUPPLY AND DRAIN) COVERS AND
OFFSET DRAIN CONNECTIONS FOR ALL SINKS AND LAVATORIES (IF REMOVABLE PROTECTIVE
PANEL IS NOT PROVIDED BY ARCHITECT) TO ENSURE ADA COMPLIANCE.
5. PLUMBING CONTRACTOR SHALL PROVIDE FLUSH VALVE OFFSET TUBES TO ACCOMMODATE GRAB
BARS FOR ALL WATER CLOSETS TO ENSURE ADA) COMPLIANCE.
6. PLUMBING CONTRACTOR SHALL INSTALL ALL PLUMBING FIXTURES AND ACCESSORIES
ACCORDING TO AND/OR IN COMPLIANCE WITH ADA STANDARDS.
7. PLUMBING CONTRACTOR SHALL REFERENCE AND COORDINATE ROUGH-IN DIMENSIONS AND
MOUNTING HEIGHTS WITH ARCHITECTURAL DRAWINGS BEFORE PURCHASING AND/OR INSTALLING
ANY FIXTURES AND ACCESSORIES AND BEFORE PROCEEDING WITH CONSTRUCTION.
8. ALL P-TRAPS SHALL HAVE INTEGRAL CLEANOUT PLUGS.
9. PLUMBING FIXTURE SCHEDULE IS TO ESTABLISH DESIGN INTENT. COORDINATE WITH EXISTING
FACILITY STANDARDS AND ARCHITECTURAL DRAWINGS. PROVIDE FOR AS REQUIRED.
10. REFER TO ARCHITECTURAL DRAWINGS FOR EXACT LOCATIONS OF PLUMBING FIXTURES.
2"
3.04 TESTING, ADJUSTING AND BALANCING
1. GENERAL:
A. ADJUSTMENT: BEFORE TEST AND BALANCE WORK IS INITIATED, EACH PIECE OF HVAC
EQUIPMENT AND EACH HVAC SYSTEM SHALL BE ADJUSTED TO THE APPROXIMATE DESIGN
CAPACITY TO ENSURE PROPER FUNCTIONING OF ALL CONTROLS.
1) PRELIMINARY OPERATION: THE OWNER RESERVES THE RIGHT TO OPERATE ANY
SYSTEMS OR EQUIPMENT PRIOR TO FINAL COMPLETION AND ACCEPTANCE OF THE
WORK. SUCH PRELIMINARY OPERATION SHALL NOT BE CONSTRUED AS AN
CONTRACTUAL ACCEPTANCE OF THE MECHANICAL WORK.
2. AIR DISTRIBUTION SYSTEMS:
A. BALANCE AND ADJUST AIR DISTRIBUTION SYSTEM TO QUANTITIES INDICATED ON THE
DRAWINGS IN ACCORDANCE WITH THE ASSOCIATED AIR BALANCE COUNCIL (AABC)
MANUAL, LATEST EDITION; OR THE NATIONAL ENVIRONMENTAL BALANCING BUREAU (NEBB)
MANUAL, LATEST EDITION.
B. BALANCING AND TESTING SHALL BE PERFORMED BY A CERTIFIED INDEPENDENT FIRM
SPECIALIZING IN TESTING AND BALANCING (AABC); OR BY A CONTRACTOR CERTIFIED IN
TEST AND BALANCING (NEBB). FIRM SHALL BE A MEMBER OF AABC OR NEBB. TEST
REPORTS SHALL BE TYPEWRITTEN AND SUBMITTED IN BOUND FOLDERS AND ON THE AABC
OR NEBB TEST AND BALANCE REPORT FORMS. ALL GRILLES, REGISTERS, AND DIFFUSERS
TESTED SHALL BE IDENTIFIED IN THE REPORT BY DESIGNATIONS AS INDICATED ON THE
DRAWINGS.
C. THE HVAC SYSTEMS AND THE INDIVIDUAL DAMPERS AND AIR BALANCING DEVICES SHALL
BE ADJUSTED TO PROVIDE DIFFUSER AIR FLOW DELIVERY NOT BE LESS THAN NOR MORE
THAN TEN (10) PERCENT OF THE AIR DELIVERY INDICATED ON THE DRAWINGS.
D. UPON COMPLETION OF THE INSTALLATION, CONTRACTOR SHALL REBALANCE ANY AIR
DISTRIBUTION SYSTEM AFFECTED BY THE TENANT IMPROVEMENT WORK AND RENOVATION,
INCLUDING AIR TERMINAL UNITS AND AIR OUTLETS.
4.00 SUBMITTALS
1. PRODUCT DATA FOR THE FOLLOWING:
A. PLUMBING FIXTURES
2.05 INSULATION
1. INSULATE WATER PIPING, VALVES WITH 4 LBS. DENSITY FIBERGLASS ONE PIECE MOLDED
SECTIONAL PIPE COVERING. MAXIMUM K FACTOR: 0.23 AT 75°F MEAN.
2. FIRE RETARDANT ALL SERVICE JACKET ON PIPE INSULATION. MAXIMUM FLAMESPREAD AND
SMOKE RATING 25/50.
3. VALVES AND FITTINGS: PREMOLDED FIBERGLASS FITTINGS OR RADIAL MITERED SEGMENTS OF
PIPE INSULATION TAPED ON, OR SEALED WITH, INSULATING CEMENT, FIBERGLASS REINFORCING
CLOTH, AND MASTIC. VAPOR SEAL INSULATION ON COLD WATER PIPING VALVES AND FITTING.
THICKNESS SAME AS REQUIRED ON PIPING.
4. COLD WATER PIPING: 1/2 INCH THICK FIBERGLASS SECTIONAL PIPE COVERING WITH VAPOR
BARRIER JACKET. NO STAPLES PERMITTED.
5. HOT WATER PIPING: 1 INCH FIBERGLASS SECTIONAL PIPE COVERING.
6. PROVIDE SWEATPROOFING ON DRAINAGE PIPING, AS NOTED, FOR INSULATION ON COLD WATER
PIPING, USING THE NEXT LARGER DIAMETER COVERING OVER HUBS FOR HORIZONTAL STORM
WATER DRAINS AND DRAINAGE PIPING FROM ICE MAKER FLOOR DRAINS, PROVIDE BETWEEN
FIXTURE AND STACK.
2.06 PLUMBING FIXTURES:
1.
REFERENCE STANDARDS:
A. AMERICAN NATIONAL STANDARDS INSTITUTE:
1) A117.1 "SPECIFICATIONS FOR MAKING BUILDINGS AND FACILITIES ACCESSIBLE TO AND
USABLE BY PHYSICALLY HANDICAPPED PEOPLE."
2. PROVIDE NEW, WHITE FIXTURES, EXCEPT AS NOTED, FIXTURE SHALL BE IN COMPLIANCE WITH
ASME/ANSI A112.19.2M, BEST OF THEIR KIND, WITH POLISHED CHROME PLATED TRIM UNLESS
OTHERWISE NOTED (PROVIDE ROUGH-ING FOR FIXTURES, ETC.).
A. EXPOSED PIPE, FITTINGS, TRAPS, ESCUTCHEONS, VALVES, VALVE HANDLES AND
ACCESSORIES, ABOVE AND BELOW FIXTURES:
1) CHROME PLATED BRASS.
2) SET SCREW CHROME PLATED CAST BRASS ESCUTCHEONS FOR PIPING AND TUBING.
3) COVERING TUBES NOT PERMITTED.
4) CHROME PLATED TYPE "L" TUBING SUPPLY RISERS MAY BE USED.
3. REFER TO ARCHITECTURAL PLUMBING FIXTURE SCHEDULE.
3.00 EXECUTION
3.01 INSTALLATION
1. DURING THE COURSE OF CONSTRUCTION, COVER EXPOSED FITTINGS WITH BURLAP AND COVER
PLUMBING FIXTURES WITH PROTECTIVE HOUSINGS. UNCOVER AND THOROUGHLY CLEAN
FIXTURES AND FITTINGS WHEN DIRECTED AND LEAVE FIXTURES IN PERFECT CONDITION AT
COMPLETION OF PROJECT. FIXTURES THAT ARE NOT IN PERFECT CONDITION SHALL BE
REPLACED BY THIS CONTRACTOR WITHOUT ADDITIONAL COST TO THE OWNER.
C. LAG PLUMBING FIXTURE CARRIER BASE PLATES OR FEET TO SLAB WITH LEAD EXPANSION
SHIELDS AND INSERT BOLTS IN ALL BOLT HOLES.
D. WHERE WALL HUNG WATER CLOSETS ARE SUPPORTED ADJACENT TO STUD WALLS,
PROVIDE REAR ANCHOR FOOT ASSEMBLY BOLTED TO SLAB.
E. SEAL ALL SPACES BETWEEN FIXTURES, AND WALLS OR FLOORS, WITH A NON YELLOWING
OR SHRINKING FLEXIBLE WATER SEALANT.
F. WHERE PLUMBING FIXTURES ARE REMOVED AND REPLACED PROVIDE NEW ROUGHING AS
REQUIRED FOR PROPER INSTALLATION.
3.02 TESTS
1. TEST SYSTEMS AS REQUIRED BY BUILDING CODE.
2. PLUMBING FIXTURE ROUGHING, UNDERGROUND PIPING, PIPING IN FLOOR CONSTRUCTION OR
PIPE CHASE WALLS, SHALL BE INSTALLED AND TESTED BEFORE CONCEALMENT.
3. TEST EQUIPMENT CONTROLS FOR PROPER PERFORMANCE AND MAKE NECESSARY
ADJUSTMENTS IN THE PRESENCE OF A FACTORY-AUTHORIZED REPRESENTATIVE OF THE
EQUIPMENT MANUFACTURER.
3.03 DISINFECTION
1. DISINFECT DOMESTIC WATER PIPING SYSTEMS AS REQUIRED BY BUILDING CODE.
2. DISINFECT ALL POTABLE WATER PIPING SYSTEMS AT THE COMPLETION OF THE PROJECT PRIOR
TO BUILDING OCCUPANCY AS FOLLOWS:
A. FLUSH THOROUGHLY WITH POTABLE WATER.
B. FILL SYSTEM WITH A WATER-CHLORINE SOLUTION CONTAINING 50 PARTS PER MILLION OF
CHLORINE AND ALLOW TO STAND FOR 24 HOURS.
C. FILL SYSTEM WITH A WATER-CHLORINE SOLUTION CONTAINING 200 PARTS PER MILLION OF
CHLORINE AND ALLOW TO STAND FOR THREE HOURS.
D. FLUSH SYSTEM WITH POTABLE WATER TO REMOVE ALL CHLORINE. PERFORM ANY
ADDITIONAL TESTS OR TREATMENTS AS REQUIRED BY THE LOCAL AUTHORITY.
2.00 PRODUCTS
2.01 GENERAL ITEMS
1. WATER HAMMER ARRESTORS: TYPE K HARD COPPER, PERMANENTLY LUBRICATED PISTON TYPE,
O-RING SEALS, -40˚ F TO 212˚ F, 35 TO 350 PSIG, PROVIDED ON BRANCHES WITH FAST CLOSING
VALVES, EQUAL TO PRECISION PLUMBING PRODUCTS, INC.
2. ESCUTCHEONS: PROVIDE EXPOSED PIPING BOTH BARE AND COVERED, WITH CP CAST BRASS
ESCUTCHEONS WITH SET SCREWS ON BOTH SIDES WHERE PASSING THROUGH CEILINGS, WALLS
OR PARTITIONS.
3. VALVE TAGS AND CHARTS: PROVIDE 2 INCH SQUARE, 18 GAUGE ALUMINUM WITH STAMPED
NUMBERED TAGS, FILL IN WITH BLACK PAINT. PROVIDE ON CONTROL VALVES EXCEPT THOSE
CONTROLLING A SINGLE FIXTURE AND LOCATED ADJACENT TO FIXTURES. FASTEN WITH BRASS
HOOKS. PROVIDE FRAMED CHART LISTING OPERATION, LOCATION AND PURPOSE OF VALVES.
COORDINATE WITH EXISTING BUILDING VALVE CHART.
4. SLEEVES: PROVIDE NO. 18 USSG GALVANIZED STEEL SLEEVES EXTENDED THROUGH
CONSTRUCTION IN CEILINGS, WALLS AND PARTITIONS. FOR INSULATED PIPING, SIZED TO ALLOW
INSULATION TO PASS THROUGH SLEEVE. PROVIDE 1/2 INCH SPACE BETWEEN PIPE AND/OR
INSULATION AND SLEEVE. FIREPROOF BY SEALING ALL SLEEVES IN ACCORDANCE WITH BUILDING
CODE AND FIRE DEPARTMENT REQUIREMENTS. SLEEVES EQUAL TO F&W MFG. CORP. FIG. NO.
202.
5. HANGER AND PIPING SUPPORTS
A. SUPPORT MATERIALS: COPPER OR INSULATED GALVANIZED FOR COPPER PIPING AND
GALVANIZED FOR STEEL PIPING.
B. SUPPORT PIPING AT DISTANCES AS REQUIRED BY CODE.
C. ALL PIPING SHALL BE INDEPENDENTLY SUPPORTED FROM STRUCTURE. PIPE SUPPORTED
FROM PIPE, CHAIN, STRAP, PERFORATED BAR, OR WIRE HANGERS ARE NOT PERMITTED.
D. PIPING 2 INCHES OR LESS PROVIDE ELECTROPLATED SOLID BAND HANGERS, GRINNELL
ADJUSTABLE SWIVEL RING FIG. 70.
E. FOR HORIZONTAL PIPING 3 INCHES AND LARGER, PROVIDE GALVANIZED "CLEVIS" HANGERS,
GRINNELL 260.
F. SUPPORT HORIZONTAL BRANCH PIPING IN PIPE CHASES FROM WALL BRACKETS
SUPPORTED FROM STRUCTURE.
G. TRAPEZE FOR MULTIPLE LINES, SUPPORTED BY A MINIMUM OF TWO HANGERS.
H. SUSPEND TRAPEZE AND/OR HANGERS FROM EXPANSION ANCHORS IN SOLID CONCRETE
SLABS, EQUAL TO HILTI HDI OR FROM EXISTING STRUCTURAL STEEL WITH BEAM CLAMPS
EQUAL TO GRINNELL NO. 61, 87, 131 AND 225. PROVIDE RODS SIZED FOR PIPE SUPPORTED
AND LOCK HANGER IN PLACE WITH DOUBLE NUTS. PROVIDE GALVANIZED METAL
PROTECTION SHIELDS ON INSULATED PIPING. INSTALL HANGERS OVER INSULATION AND
SHIELDS.
I. WHERE OVERHEAD CONSTRUCTION DOES NOT PERMIT FASTENING HANGER RODS IN
REQUIRED LOCATIONS, PROVIDE ADDITIONAL STEEL FRAMING AS REQUIRED AND
REVIEWED.
6. ACCESS DOORS:
A. 12 INCH X 12 INCH NO. 4 FINISH STAINLESS STEEL FLUSH TYPE, LOCATE AND SET AFTER
REVIEW. STEEL DOOR AND FRAME WITH FLANGE, CONCEALED HINGES, AND SCREWDRIVER
OPERATED STAINLESS STEEL CAM LOCK. KARP STYLE DSC 214M OR KRP-150-FR IN FIRE
RATED CONSTRUCTION.
7. LABELING:
A. PROVIDE ON ALL PIPING, 10 FEET ON CENTERS, INDICATING SYSTEM AND DIRECTION OF
FLOW.
8. DISSIMILAR METALS:
A. PROVIDE BRASS OR COPPER WATER PIPING CONNECTED TO GALVANIZED PIPE AND FOR
ANY OTHER DISSIMILAR METALS WITH DIELECTRIC FITTINGS.
2.02 PIPING AND FITTINGS
1. SANITARY DRAINAGE AND VENT PIPING:
A. SERVICE WEIGHT CAST IRON HUB AND SPIGOT SOIL PIPE AND DRAINAGE FITTINGS, OR
GALVANIZED STEEL PIPE WITH GALVANIZED THREADED CAST IRON DRAINAGE FITTINGS,
WITH GALVANIZED THREADED MALLEABLE IRON VENT FITTINGS OR CAST IRON NO-HUB
WITH 24 GAUGE, 304 STAINLESS STEEL COUPLINGS WITH NEOPRENE GASKETS, RATED FOR
15 PSI AND REQUIRING A MINIMUM OF 100 INCH/LBS. OF TORQUE.
B. HUBLESS PIPE 5 INCHES AND LARGER SHALL BE ANCHORED AT EACH SIDE OF COUPLING
(OR NO HUB CLAMP) AND AT FIVE (5) FEET INTERVALS.
C. TYPE M HARD COPPER TUBING WITH CAST BRONZE OR WROUGHT COPPER DRAINAGE
FITTINGS FOR SANITARY AND VENT, EXCEPT DO NOT USE ON URINAL WASTES UP TO
INTERSECTION OF PIPING FROM OTHER FIXTURE TYPES.
D. EXPOSED WASTE PIPING AT PLUMBING FIXTURES SHALL BE CHROME PLATED.
2. WATER PIPING:
A. BRASS PIPE WITH THREADED CAST BRASS FITTINGS OR TYPE 'L" COPPER TUBING WITH
WROUGHT COPPER OR CAST BRONZE FITTINGS WITH 95-5 SOLDERED JOINTS.
B. EXPOSED WATER PIPING AT PLUMBING FIXTURES SHALL BE CHROME PLATED.
2.03 VALVES
1. SHUT-OFF VALVES: BRONZE BODY BALL VALVE WITH STAINLESS STEEL BALL AND STEM, VIRGIN
TFE SEATS AND SEALS, 600 PSI W.O.G., THREADED ENDS, EQUAL TO COMBRACO 'APOLLO' 70-100
SERIES, SOLDER JOINT ENDS, EQUAL TO COMBRACO 'APOLLO' 70-200 SERIES.
2. CHECK VALVES: BRONZE SWING TYPE, 125 PSI WSP, THREADED ENDS, EQUAL TO STOCKHAM NO.
B 319. SOLDER JOINT ENDS, EQUAL TO STOCKHAM NO. B 309. THERMOSTATIC MIXING VALVE,
EQUAL TO MILANO AUTOFAUCET 402188
2.04 PLUMBING EQUIPMENT
1. FIXED AIR GAP:
A. CHROME PLATED BRONZE BODY WITH SET SCREW ON INLET AND THREADED OUTLET.
B. CONFORMING TO ANSI A112.1.2.
C. EQUAL TO J. R. SMITH NO. 3950 FOR UNDERCOUNTER DISHWASHERS.
2. VACUUM BREAKERS:
A. NON CONTINUOUS PRESSURE USE AND WITH NO BACK PRESSURE.
1) CAST BRASS BODY, WITH FULL SIZE ORIFICE.
2) CONFORMING TO ASSE STANDARD NO. 1011.
3) ATMOSPHERIC TYPE, EQUAL TO WATTS NO 288A.
3. TRAP PRIMERS:
A. CHROME PLATED AUTOMATIC TRAP PRIMER. EQUAL TO J. R. SMITH NO. 2699.
4. CLEANOUTS:
A. PROVIDE CAST BRONZE CLEANOUTS IN ACCORDANCE WITH ANSI A112.36.2. FULL SIZE UP
TO 4 INCH AND AT LEAST HALF SIZE FOR LARGER PIPES WITH 4 INCH MINIMUM.
B. LOCATE AT CHANGE IN DIRECTION OF MORE THAN 45 DEGREE AT BASE OF STACKS AND
WHERE INDICATED ON DRAWINGS.
C. PIPING IN OR BEHIND WALLS AND PARTITIONS EXTEND OUT TO FINISH WALL AND PROVIDE
CAST BRONZE PLUGS WITH SATIN FINISH CHROME PLATED BRASS, NICKEL BRONZE OR
STAINLESS STEEL WALL PLATES, EQUAL TO J. R. SMITH NO. 4532 IN FINISHED AREAS, IN
UNFINISHED AREAS LESS WALL PLATE.
PLUMBING SPECIFICATIONS
1.00 GENERAL REQUIREMENTS
1. DRAWINGS AND GENERAL PROVISIONS OF CONTRACT, INCLUDING DIVISION 1 SPECIFICATION
SECTIONS, APPLY TO THIS SECTION.
1.01 PRINCIPAL WORK IN THIS SECTION
1. GENERAL ITEMS.
2. PIPING, FITTINGS AND VALVES.
3. PLUMBING EQUIPMENT.
4. INSULATION
5. PLUMBING FIXTURES.
6. TESTING, FILING AND FEES.
1.02 SUBMITTALS
1. PROVIDE FOUR (4) COPIES OF SUBMITTAL MATERIAL
2. IF THIS CONTRACTOR SUBMITS SHOP DRAWINGS OF SPECIFIED ITEMS AS LISTED IN THIS
SPECIFICATION, THEN THE SHOP DRAWINGS SHALL BE SUBMITTED FOR RECORD ONLY.
3. IF THIS CONTRACTOR ELECTS TO USE MANUFACTURERS OTHER THAN THOSE LISTED IN THIS
SPECIFICATION, THE FOLLOWING IS REQUIRED:
A. BEFORE COMMENCING WORK, THE CONTRACTOR SHALL SUBMIT A LIST OF MANUFACTURE
SUBSTITUTIONS, FOR REVIEW AND ACCEPTANCE. SUBSTITUTION WILL NOT BE ACCEPTED
AT ANY OTHER TIME.
B. AFTER VERIFYING ALL FIELD CONDITIONS THIS CONTRACTOR SHALL SUBMIT SHOP
DRAWINGS FOR REVIEW AND APPROVAL.
C. AT THE TIME OF EACH SUBMISSION, THIS CONTRACTOR IS TO IDENTIFY ANY DEVIATION BY
'CLOUDING' ON SHOP DRAWINGS.
4. SUBMIT CATALOG DATA AND ILLUSTRATIONS OF THE FOLLOWING FIXTURE AND EQUIPMENT,
THEIR SIZES, MATERIAL, ROUGH-IN DIMENSIONS, UTILITY SIZES, ELECTRICAL REQUIREMENTS,
TRIM AND FINISHES.
A. SLEEVES.
B. ACCESS DOORS.
C. VALVES.
D. HANGERS AND SUPPORTS.
E. PIPE, FITTINGS AND JOINTS.
F. TRAP PRIMERS.
G. CLEANOUTS.
H. INSULATION.
I. PLUMBING FIXTURES, TRIM, TRAPS, ETC.
J. WATER FILTERS.
K. SOLDER.
L. FLOOR DRAINS.
1.03 QUALITY ASSURANCE
1. DRAWINGS ARE DIAGRAMMATIC AND INDICATE GENERAL ARRANGEMENT OF PIPING. PROVIDE
NECESSARY SUPPORTS, PIPE, FITTINGS AND VALVES THAT ARE REQUIRED FOR COORDINATION
OF THIS WORK WITH OTHER TRADES AND THE EXISTING STRUCTURE.
2. VERIFY SIZES AND LOCATIONS OF EXISTING PIPING TO BE CONNECTED TO PRIOR TO START OF
WORK.
3. CAREFULLY EXAMINE EXISTING CONDITIONS BEFORE SUBMITTING PROPOSAL. COORDINATE
WORK TO MINIMIZE INTERFERENCE WITH EXISTING AND NEW FACILITIES.
4. CONNECTIONS TO EXISTING WORK: SHALL BE AT ODD HOURS TO INSURE MINIMUM
INTERFERENCE WITH REGULAR OPERATION OF EXISTING FACILITIES. PIPING RUN IN OTHER
TENANTS' AREAS SHALL BE COORDINATED WITH THAT TENANT, INSTALLED ON OVERTIME AND AT
TIMES CONVENIENT TO TENANT AFFECTED. WORK SPACE SHALL BE CLEANED AND RESTORED TO
ITS ORIGINAL CONDITION. OBTAIN APPROVAL OF BUILDING MANAGEMENT PRIOR TO INSPECTION,
SHUTDOWN, COMMENCING WORK AND TESTING.
5. PROVIDE WORKMANSHIP OF HIGHEST QUALITY. INSTALLATION SHALL BE IN ACCORDANCE WITH
THE REQUIREMENTS OF THE CURRENT STATE AND LOCAL BUILDING CODES.
6. PROVIDE ONE YEAR GUARANTEE AGAINST DEFECTIVE WORKMANSHIP AND MATERIAL.
7. MATERIAL FOR PLUMBING WORK SHALL BE NEW AND BEST OF ITS KIND.
8. LOCATE PIPING SUCH THAT NONE PASSES THROUGH ELECTRICAL OR TELEPHONE ROOMS.
SHOULD THIS NOT BE POSSIBLE, PIPING PASSING OVER ELECTRICAL OR TELEPHONE ROOMS
SHALL BE PROVIDED WITH DRIP PANS, TO DISCHARGE INTO AN APPROVED RECEPTOR.
9. COMPLY WITH BUILDING STANDARDS.
1.04 SCOPE OF WORK
1. PROVIDE REQUIRED LABOR, MATERIALS, EQUIPMENT AND CONTRACTOR'S SERVICES
NECESSARY FOR A COMPLETE SAFE INSTALLATION OF WORK IN FULL CONFORMITY WITH THE
REQUIREMENTS OF AUTHORITIES HAVING JURISDICTION, AS INDICATED ON THE DRAWINGS
AND/OR HEREIN SPECIFIED, INCLUDING THE FOLLOWING:
A. SANITARY DRAINAGE AND VENT SYSTEM, INCLUDING CONNECTIONS TO EXISTING PIPING,
PLUMBING FIXTURES AND EQUIPMENT.
B. DOMESTIC WATER SUPPLY SYSTEM, INCLUDING CONNECTIONS TO EXISTING PIPING,
VALVES, PLUMBING FIXTURES AND EQUIPMENT.
C. PLUMBING FIXTURES.
D. INSULATION
E. CORE DRILLING, ROUGH CUTTING AND PATCHING.
F. SHOP DRAWINGS.
G. TESTING, FILING AND FEES.
H. DISINFECTION OF DOMESTIC WATER SYSTEM.
2. THE RUN AND ARRANGEMENT OF PIPES SHALL BE APPROXIMATELY AS SHOWN ON THE
DRAWINGS. ADJUST LOCATION OF RUNS, IF REQUIRED, DUE TO INTERFERENCE WITH
STRUCTURE OR OTHER TRADES AND UNNECESSARY CUTTING OF FLOORS AND WALLS.
INSTALLATION SHALL BE AS STRAIGHT AND DIRECT AS POSSIBLE, EVENLY SPACED, FORMING
RIGHT ANGLES OR PARALLEL LINE WITH BUILDING WALLS AND OTHER PIPES. RISERS SHALL BE
ERECTED PLUMB AND TRUE.
1.05 WARRANTY
1. PROVIDE ONE-YEAR WARRANTY AGAINST DEFECTIVE WORKMANSHIP AND MATERIALS.
1.06 DEMOLITION
1. IN DEMOLITION WORK, UNUSED PIPING SHALL NOT BE ABANDONED 'IN PLACE'. PIPING SHALL BE
REMOVED BACK TO SOURCE OR POINT OF DISCHARGE, AND THE RESULTING OPENINGS
PLUGGED. AS INDICATED ON THE DRAWINGS.
2. DISCONNECT, REMOVE AND CAP OR PLUG EXISTING UNUSED PIPING AS NOTED OR REQUIRED TO
PERMIT NEW INSTALLATION.
3. EXISTING PLUMBING FIXTURES, PIPING AND EQUIPMENT TO BE REMOVED SHALL REMAIN THE
PROPERTY OF THE OWNER AND SHALL BE DISPOSED OF BY THIS CONTRACTOR AS DIRECTED BY
THE OWNER.
4. DISCONNECT AND REMOVE EXISTING UNUSED PIPING AND FIXTURES WITHOUT INTERRUPTING
EXISTING REQUIRED FUNCTIONING SYSTEMS.
5. PIPING FROM FIXTURES TO BE REMOVED AND REPLACED SHALL BE PROPERLY PLUGGED OR
CAPPED, AT WALL OR FLOOR, TO AWAIT INSTALLATION OF NEW FIXTURES.
6. UNUSED PIPING AND RELATED ITEMS CONCEALED IN WALLS, FLOORS AND CEILING WITHIN THE
STRUCTURE SHALL BE ABANDONED AND REMOVED WHERE EXPOSED TO VIEW. REMOVAL OF
EXISTING PIPING SHALL BE DONE IN A SATISFACTORY MANNER TO THE ENGINEER AND BUILDING
ENGINEER.
7. WASTE AND SANITARY DRAINAGE PIPING NOT TO BE USED SHALL BE REMOVED AND PLUGGED AT
ACTIVE MAIN OR RISER.
WALL CLEANOUT
WCO
AS NOTED ON PLANS
SHOCK ARRESTORS
SA
AS NOTED ON PLANS
VAIL
CASCADE + ARIA
RENOVATION
1300
WESTHAVEN
DRIVE
Vail, Colorado
04/20/2017
Revisions:
Sheet Title:
Project No:
Sheet No:
Issue Dates:
(970) 748-1470
email: tab@vail.net
fax: (970) 748-1471
Avon, CO 81620-7431
Post Office Box 7431
TAB
The Architectural Balance
Associates
www.tabassociates.com
Plotted:
4/19/2017
6:06:38 PM P:\DAL\BET\TABCO001\CAD\SHEETS\PLUMBING\P0.2
PLUMBING