HomeMy WebLinkAboutB17-0198_E1_1497031980.pdf
This is an Electrical Load Report for the Vail Community Development for
the remodel at Manor Vail Unit 348. The address is 595 East Valley Drive
#348, Vail, CO. I am the electrician working for Foster Construction. My
company is Eagle Electric Inc. and my name is Michael Koenen.
The property has multiple units. The remodel has its own meter. The meter
has a 100 amp single phase main breaker. The feeder to the panel is a #2
THN aluminum wire from the meter.
The only power requirements we are adding: fifteen 4Órecessed cans
LED lights in the Living Room and one in the Hallway. We are replacing
16 existing recessed cans with 75 watt bulbs in the Bathrooms, Master and
Guest Bedrooms with new 4Ó recessed cans LED lights. Due to LED the
lighting load decreased.
With changes, no increase of power is needed.
1512 sq. ft.*3VA per sq ft. 4536VA
4536VA at 100% 4536VA
General LightingÉ.. 4,536VA
Small appliance load 4,536VA
Total General lighting
And small appliance 9,072VA 9,072VA
Range load 8,000VA
Dryer 5,000VA
Laundry 1,500VA
23572VA
Total Load: 23,572VA divided by 240V = 98 amps On a 100 amp panel
My name is Michael Koenen and my company is Eagle Electric
My address is Box 131, Gypsum CO. Phone # (970) 471-6155.
06/09/17