B17-0227_5185 Main Gore Drive-Load Report_1497223320.PDF
Load Report Project #:5185 Main Gore Drive Manual J8 Load Calculation Project Information June 01, 2017 Project #: Name: Location: Gordon Mason Residence 5185 Main Gore Drive Vail, CO Notes: Manual J Load Summary Outdoor Conditions Indoor Conditions Total Heating: 186,713 Btu/hr Total Sensible: 0 Btu/hr Total Latent: 0 Btu/hr Location:(User Specified) Vail,Colorado Elevation:8200 ft Latitude:40 Heating Cooling Dry Bulb:-20.0 °F 80.0 °F Daily Range:High Wet Bulb:60.0 °F Heating Cooling Room Temp:70 °F Design Temp Diff:90.0 °F 5.0 °F Humidity:35 50 Moisture Diff (Grains):-15.0 Infiltration Ventilation Method:Simple Stories:3 Construction:Semi-Tight Exposure Category:Three or Four Exposures Num Fireplaces:4 (Tight) Net Air Changes (Heat/Cool):0.26 / 0.00 Net Flow (Heat/Cool):312 cfm / 0 cfm Num Occupants:5 Heating Type:Heat Recovery ACH:0.50 Outside Air:605 cfm Sensible Eff:50 % Cooling Type:Heat Recovery Outside Air:0 cfm Sensible Eff:50 % Floorplan/Levels Garage Level 1,064 ft² Entry Level 1,328 ft² Second Level 2,378 ft² Upper Level 2,656 ft² Total Heated Area:7,426 ft² Total Cooled Area:0 ft² Created Using LoopCAD 2016 (6/7/2017) Version:16.0.0080 Length = ft Area = ft² Temperature = °F Flowrate = USGPM Heat Loss = Btu/hr Unit Heat Loss = Btu/hr·ft² Rv = hr·ft²·°F/btu Head Loss = ft water RH = Radiant Floor Heating BB = Baseboard FA = Forced Air OTH = Other Heating SM = Snowmelt N = Not Heated See end of report for important Notes and Disclaimers.Page 1 of 7 Name:Gordon Mason Residence Project #:5185 Main Gore Drive Load Report June 01, 2017 Constructions Walls Code Description U-Value Area Heating Cooling 15C19-0w Four Inch Concrete; Wood Framing; R-19 Insulation in 2 x 6 Stud Cavity; Plus Interior Finish 0.08 323 2,238 0 12F-6sw Frame Wall or Partition; Wood Framing; R-21 Insulation in 2 x 6 Stud Cavity; Stucco or Wood Siding; Plus Interior Finish 0.05 5,216 22,533 0 12F-6sw Frame Wall or Partition; Wood Framing; R-21 Insulation in 2 x 6 Stud Cavity; Stucco or Wood Siding; Plus Interior Finish 0.05 943 453 0 12F-6sw Frame Wall or Partition; Wood Framing; R-21 Insulation in 2 x 6 Stud Cavity; Stucco or Wood Siding; Plus Interior Finish 0.05 1,204 289 0 Below Grade Walls Code Description U-Value Area Heating Cooling 15C19-0w (10 ft)Four Inch Concrete; Wood Framing; R-19 Insulation in 2 x 6 Stud Cavity; Plus Interior Finish 0.08 1,663 5,961 0 15C19-0w (4 ft)Four Inch Concrete; Wood Framing; R-19 Insulation in 2 x 6 Stud Cavity; Plus Interior Finish 0.08 106 490 0 15C19-0w (8 ft)Four Inch Concrete; Wood Framing; R-19 Insulation in 2 x 6 Stud Cavity; Plus Interior Finish 0.08 153 590 0 15C19-0w (6 ft)Four Inch Concrete; Wood Framing; R-19 Insulation in 2 x 6 Stud Cavity; Plus Interior Finish 0.08 130 544 0 Doors Code Description U-Value Area Heating Cooling 11D Wood Door with Solid Core 0.39 759 26,625 0 Created Using LoopCAD 2016 (6/7/2017) Version:16.0.0080 Length = ft Area = ft² Temperature = °F Flowrate = USGPM Heat Loss = Btu/hr Unit Heat Loss = Btu/hr·ft² Rv = hr·ft²·°F/btu Head Loss = ft water RH = Radiant Floor Heating BB = Baseboard FA = Forced Air OTH = Other Heating SM = Snowmelt N = Not Heated See end of report for important Notes and Disclaimers.Page 2 of 7 Name:Gordon Mason Residence Project #:5185 Main Gore Drive Load Report June 01, 2017 Floors Code Description U-Value Area Heating Cooling 21B-24-r Embedded Slab -0.10 1,673 3,270 0 21B-24-r Embedded Slab -0.10 165 331 0 22B-10-r 22B - Vertical Board Insulation Covers Slab Edge and Extends Straight Down to Three Feet Below Grade, any Floor Cover 0.10 41 (P)2,436 0 22B-10-r 22B - Vertical Board Insulation Covers Slab Edge and Extends Straight Down to Three Feet Below Grade, any Floor Cover 0.10 6 (P)364 0 22B-10-r 22B - Vertical Board Insulation Covers Slab Edge and Extends Straight Down to Three Feet Below Grade, any Floor Cover 0.10 23 (P)1,496 0 Concrete Thin Slab-r Concrete Thin Slab -0.04 20 88 0 Concrete Thin Slab-r (Sealed Crawl) Concrete Thin Slab -0.04 909 2,016 0 Concrete Thin Slab-r (Sealed Crawl) Concrete Thin Slab -0.04 331 604 0 Concrete Thin Slab-r Concrete Thin Slab -0.04 39 186 0 Concrete Thin Slab-r Concrete Thin Slab -0.04 184 891 0 Concrete Thin Slab-r Concrete Thin Slab -0.04 21 44 0 Concrete Thin Slab-r Concrete Thin Slab -0.04 57 264 0 Concrete Thin Slab-r Concrete Thin Slab -0.04 33 44 0 Concrete Thin Slab-r Concrete Thin Slab -0.04 82 80 0 Concrete Thin Slab-r Concrete Thin Slab -0.04 110 128 0 Concrete Thin Slab-r Concrete Thin Slab -0.04 165 897 0 Concrete Thin Slab-r Concrete Thin Slab -0.04 65 98 0 Ceilings Code Description U-Value Area Heating Cooling 18A-38md No radiant barrier over ceiling or same type of air space behind an attic knee wall; Absorptivity of roofing material exceeds 0.75; Materials: Asphalt Shingles(a), Metal(m), Tar / Gravel(x), Membrane(z); Colors: Dark(d); 0.03 4,172 10,889 0 18A-38md No radiant barrier over ceiling or same type of air space behind an attic knee wall; Absorptivity of roofing material exceeds 0.75; Materials: Asphalt Shingles(a), Metal(m), Tar / Gravel(x), Membrane(z); Colors: Dark(d); 0.03 165 96 0 18A-38md No radiant barrier over ceiling or same type of air space behind an attic knee wall; Absorptivity of roofing material exceeds 0.75; Materials: Asphalt Shingles(a), Metal(m), Tar / Gravel(x), Membrane(z); Colors: Dark(d); 0.03 48 7 0 18A-38md No radiant barrier over ceiling or same type of air space behind an attic knee wall; Absorptivity of roofing material exceeds 0.75; Materials: Asphalt Shingles(a), Metal(m), Tar / Gravel(x), Membrane(z); Colors: Dark(d); 0.03 1 0 0 Created Using LoopCAD 2016 (6/7/2017) Version:16.0.0080 Length = ft Area = ft² Temperature = °F Flowrate = USGPM Heat Loss = Btu/hr Unit Heat Loss = Btu/hr·ft² Rv = hr·ft²·°F/btu Head Loss = ft water RH = Radiant Floor Heating BB = Baseboard FA = Forced Air OTH = Other Heating SM = Snowmelt N = Not Heated See end of report for important Notes and Disclaimers.Page 3 of 7 Name:Gordon Mason Residence Project #:5185 Main Gore Drive Load Report June 01, 2017 Glazing Windows Code Description Exposure U-Value SHGC Area Heating Cooling 3Bf Window with fixed sash, with Emissivity of Low-e coating = 0.40 - Insulated Fiberglass Framing, BlindsMedium45 (50%), 1', 1' above. E 0.49 0.66 195 8,591 0 3Bf Window with fixed sash, with Emissivity of Low-e coating = 0.40 - Insulated Fiberglass Framing, BlindsMedium45 (50%), 1', 1' above. NE 0.49 0.66 487 21,485 0 3Bf Window with fixed sash, with Emissivity of Low-e coating = 0.40 - Insulated Fiberglass Framing, BlindsMedium45 (50%), 1', 1' above. NW 0.49 0.66 396 17,466 0 3Bf Window with fixed sash, with Emissivity of Low-e coating = 0.40 - Insulated Fiberglass Framing, BlindsMedium45 (50%), 1', 1' above. SE 0.49 0.66 88 3,864 0 3Bf Window with fixed sash, with Emissivity of Low-e coating = 0.40 - Insulated Fiberglass Framing, BlindsMedium45 (50%), 1', 1' above. W 0.49 0.66 13 568 0 3Bf Window with fixed sash, with Emissivity of Low-e coating = 0.40 - Insulated Fiberglass Framing, BlindsMedium45 (50%), 1', 1' above. S 0.49 0.66 121 5,314 0 Created Using LoopCAD 2016 (6/7/2017) Version:16.0.0080 Length = ft Area = ft² Temperature = °F Flowrate = USGPM Heat Loss = Btu/hr Unit Heat Loss = Btu/hr·ft² Rv = hr·ft²·°F/btu Head Loss = ft water RH = Radiant Floor Heating BB = Baseboard FA = Forced Air OTH = Other Heating SM = Snowmelt N = Not Heated See end of report for important Notes and Disclaimers.Page 4 of 7 Name:Gordon Mason Residence Project #:5185 Main Gore Drive Load Report June 01, 2017 Heating Load Breakdown Windows* Ventilation Below GradeWalls Radiant Backloss Doors Walls Ceilings Infiltration Load Breakdown *Average Load Procedure Name Heating Sensible Latent Windows*57,288 0 Skylights*0 0 Doors 26,625 0 Walls 25,513 0 Below Grade Walls 7,585 Ceilings 10,992 0 Floors 0 0 Infiltration 23,107 0 0 Internal 0 0 Other 0 Duct Loads 0 0 0 Ventilation 22,367 0 0 Humidification 0 Piping Load 0 Radiant Backloss 13,237 Blower Heat 0 AED*0 Total 186,713 0 0 Total Area 7,426 ft²0 ft² Created Using LoopCAD 2016 (6/7/2017) Version:16.0.0080 Length = ft Area = ft² Temperature = °F Flowrate = USGPM Heat Loss = Btu/hr Unit Heat Loss = Btu/hr·ft² Rv = hr·ft²·°F/btu Head Loss = ft water RH = Radiant Floor Heating BB = Baseboard FA = Forced Air OTH = Other Heating SM = Snowmelt N = Not Heated See end of report for important Notes and Disclaimers.Page 5 of 7 Name:Gordon Mason Residence Project #:5185 Main Gore Drive Load Report June 01, 2017 Heating Zones Zone Area Room Temp Total Load Zone 101 1,064 70 25,046 Zone 201 555 70 16,621 Zone 202 773 70 11,068 Zone 301 499 70 15,842 Zone 302 124 70 614 Zone 303 691 70 16,395 Zone 304 556 70 8,043 Zone 305 509 70 14,204 Zone 401 596 70 20,966 Zone 402 345 70 4,101 Zone 403 765 70 25,206 Zone 404 950 70 28,608 Heating Rooms Room Area Room Temp Total Load 3 Car Garage 899 70 22,133 Bath 1 124 70 614 Bath 2 119 70 363 Bath 3 169 70 6,193 Bedroom / Closet 1 499 70 15,842 Bedroom / Closet 2 438 70 7,679 Coat Closet 144 70 4,615 Dining & Living Areas 765 70 25,206 Entry / Mud Room 361 70 10,900 Entry Level Powder 50 70 1,106 Garage Level Hall 165 70 2,912 Kitchen, Breakfast, Informal Seating 950 70 28,608 Laundry Room 228 70 2,254 Master Bath 206 70 3,074 Master Bedroom 431 70 15,159 Master Closet 1 87 70 623 Master Closet 2 165 70 5,807 Office / Bedroom 3 340 70 8,011 Second Level Hall 462 70 14,141 Created Using LoopCAD 2016 (6/7/2017) Version:16.0.0080 Length = ft Area = ft² Temperature = °F Flowrate = USGPM Heat Loss = Btu/hr Unit Heat Loss = Btu/hr·ft² Rv = hr·ft²·°F/btu Head Loss = ft water RH = Radiant Floor Heating BB = Baseboard FA = Forced Air OTH = Other Heating SM = Snowmelt N = Not Heated See end of report for important Notes and Disclaimers.Page 6 of 7 Sitting/Music, Wine, Yoga Areas 773 70 11,068 Upper Level Powder 53 70 403 Design Locaton MJ8Custom Location:Vail Province/State:Colorado Country:United States Outdoor Heating Design Temp:-20.0 °F Outdoor Cooling Design Temp:80.0 °F Altitude:8200'ft Latitude:40 Wet Bulb Temperature:60.0 °F Daily Range:High Disclaimers With the permission of the Air Conditioning Contractors of America (“ACCA”), material is reproduced from Manual J Residential Load Calculation (8th Edition) which is copyrighted by ACCA. The program and data are provided "as is" without warranty of any kind either expressed or implied. The entire risk as the quality and performance of the program and data is with you. In no event will ACCA be liable to you for any damages, including without limitation anylost profits, lost savings, or other incidental or consequential damages arising out of the use or inability to use this program or the data. © 2015 Air Conditioning Contractors of America. All Rights Reserved. www.acca.org ACCA, Manual J and Powered by ACCA Manual J are registered trademarks of the Air Conditioning Contractors of America. All rights reserved. Cold weather humidification, or some lifestyles that produce excessive moisture, may cause condensation to occur if the absolute humidity of the indoor air is too high for the momentary circumstances. Condensation can occur onsurfaces or concealed within the structure, and can lead to mold, mildew, frost damage, and moisture damage. The software does not perform calculations for the estimation or detection of possible condensation problems, and it is the designers (i.e. software users) responsibility to do so independently if required. For guidance and additional cautions refer to ACCA Manual J 8th Edition, including Section 1-11 and Section 27. The calculated values shown in this report are based on the data input by the user of the software. Inaccurate or erroneous data input will result in inaccurate or erroneous results. You are strongly advised to review all input data carefully, and to have the calculated results reviewed by an experienced heating professional to ensure reasonableness and suitability for your application. IN NO EVENT WILL AVENIR SOFTWARE INC. (“AVENIR”) OR ITS AFFILIATES BE LIABLE UNDER ANY CONTRACT, NEGLIGENCE, STRICT LIABILITY OR OTHER LEGAL OR EQUITABLE THEORY FOR ANY CONSEQUENTIAL, INCIDENTAL, INDIRECT OR SPECIAL OR PUNITIVE DAMAGES WHATSOEVER (INCLUDING, BUT NOT LIMITED TO, DAMAGES FOR LOSS OF BUSINESS PROFITS, BUSINESS INTERRUPTION, LOSS OF BUSINESS INFORMATION OR DATA AND THE LIKE), EVEN IF SUCH PARTY HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. AVENIR’S CUMULATIVE LIABILITY FROM ANY CAUSE RELATED TO OR ARISING FROM THE USE THIS REPORT, AND REGARDLESS OF THE FORM OF THE ACTION, SHALL BE LIMITED TO NO GREATER THAN THE AMOUNT OF FEES PAID TO AVENIR UNDER THE SOFTWARE LICENSE AGREEMENT. Name:Gordon Mason Residence Project #:5185 Main Gore Drive Load Report June 01, 2017 Created Using LoopCAD 2016 (6/7/2017) Version:16.0.0080 Length = ft Area = ft² Temperature = °F Flowrate = USGPM Heat Loss = Btu/hr Unit Heat Loss = Btu/hr·ft² Rv = hr·ft²·°F/btu Head Loss = ft water RH = Radiant Floor Heating BB = Baseboard FA = Forced Air OTH = Other Heating SM = Snowmelt N = Not Heated See end of report for important Notes and Disclaimers.Page 7 of 7