HomeMy WebLinkAboutB17-0227_5185 Main Gore Drive-Snow Melt Panel Schedule_1497223320.PDFSnow Melt Panel Schedule
Project #:5185 Main Gore Drive
Project Information
June 06, 2017
Project #:
Name:
Location:
Gordon Mason Residence
5185 Main Gore Drive
Vail, CO
Notes:
Design Conditions and Summary
Load Calculation Method:Manual
Fluid Type:50% Propylene Glycol
Total Flowrate:34.36 USGPM
Max. Head Loss:22.4 ft water
Design Temp. Drop:25.0 °F
Total Area:3,034 ft²
Total Snow Melt Load:380,415 Btu/hr
Radiant Panel Details
Panel Type #1 - Snow Melt - Concrete
Embedded Layer Thickness:5.0 in
Tube Depth (Embedded Layer):3.4 in
Embedded Layer R per Inch:0.14 °F•ft²•hr/Btu•in
Insulation Rv:10.0 hr·ft²·°F/btu
Spacing:9 in
Floorplans:
Bedroom 1 Patio 130 ft²
Entry / Garage 1,798 ft²
New Floorplan 1,095 ft²
Created Using LoopCAD 2016 (6/7/2017)
Version:16.0.0080
Note: Tube depth is measured from top of embedded layer to the centerline of the tubing.
See end of report for important Notes and Disclaimers.Page 1 of 2
Name:Gordon Mason Residence
Project #:5185 Main Gore Drive
Snow Melt Panel Schedule
June 06, 2017
Disclaimers
The calculated values shown in this report are based on the data input by the user of the software. Inaccurate or erroneous data input will result in inaccurate or erroneous results. You are strongly advised to review all input datacarefully, and to have the calculated results reviewed by an experienced heating professional to ensure reasonableness and suitability for your application.
IN NO EVENT WILL AVENIR SOFTWARE INC. (“AVENIR”) OR ITS AFFILIATES BE LIABLE UNDER ANY CONTRACT, NEGLIGENCE, STRICT LIABILITY OR OTHER LEGAL OR EQUITABLE THEORY FOR ANY CONSEQUENTIAL, INCIDENTAL, INDIRECT OR
SPECIAL OR PUNITIVE DAMAGES WHATSOEVER (INCLUDING, BUT NOT LIMITED TO, DAMAGES FOR LOSS OF BUSINESS PROFITS, BUSINESS INTERRUPTION, LOSS OF BUSINESS INFORMATION OR DATA AND THE LIKE), EVEN IF SUCH PARTY
HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. AVENIR’S CUMULATIVE LIABILITY FROM ANY CAUSE RELATED TO OR ARISING FROM THE USE THIS REPORT, AND REGARDLESS OF THE FORM OF THE ACTION, SHALL BE LIMITED
TO NO GREATER THAN THE AMOUNT OF FEES PAID TO AVENIR UNDER THE SOFTWARE LICENSE AGREEMENT.
Created Using LoopCAD 2016 (6/7/2017)
Version:16.0.0080
Note: Tube depth is measured from top of embedded layer to the centerline of the tubing.
See end of report for important Notes and Disclaimers.Page 2 of 2