HomeMy WebLinkAboutE16-0081 revised load calcs.pdf This is a Electrical Load report for the Vail Community
Development Office for the remodel at Manor Vail Unit
212. The address for the Wren is 595 Vail Valley Drive,
Vail CO. I am the electrician working for Foster
Construction. My company is Eagle Electric Inc. and my
name is Michael Koenen.
The property has multiple units. The remodel has its own meter. The meter
has a 100 amp single phase main breaker. The feeder to the panel is a#2
THN aluminum wire from the meter.
The only power requirements we are adding twelve L.E.D recessed
lights in living room, hallway, master bedroom, where there was four
recessed cans with 75 watt bulbs in the hallway. No change in wattage.
With changes, no increase of power needed.
1000 sq.ft.*3VA per sq ft. 3000VA
3000VA at 100% 3000VA
General Lighting..... 3000VA
Small appliance load 3000VA
Total General lighting
And small appliance 6000VA
Range load 8000VA
Dryer 5000VA
Laundry 1500VA
Total Load 22,500VA divided by 240V = 93
amps On a 100 amp panel
My name is Michael Koenen and my company is Eagle Electric
My address is Box 131, Gypsum CO. Phone # 970-471-6155.