HomeMy WebLinkAboutE17-0082 load calcs.pdf . DWI ir4
a: C
00 eft.
9'.len 961j
06/05/17
1
2014 W. Gore Creek
Demand Load Calculations
(Per NEC Article 220 Parts I-Ill, Optional calc 220.82)
Quantity Volt-Amps Demand Total (VA)
General
Dwelling unit Square footage 3200 SF X 3 X 100% = 9600
Small Appliances 12 EA X 1500 X 100% = 18000
Clothes Washer 1 EA X 1500 X 100% -- 1500
Total General & Lighting I 29100
General & Lighting (1st 3 KVA) 3000 VA 100% = 3000
General &Lighting (next 120,000' 26100 VA 35% = 9135
General &Lighting (next 117,500 0 VA 25% = 0
Kitchen
Dishwasher 6 EA X 1200 X 75% = 5400
Oven/Range 6 EA X 8000 X 43% = 20640
Microwave 6 EA X 1000 X 75% = 4500
Disposal 6 EA X 1000 X 75% = 4500
Laundry&Spa Appliances_
Clothes Dryer 1 EA X 5000 X 100% = 5000
Mechanical Equipment
Boiler and pumps 1 EA X 1500 X 100% = 1500
Heat Trace 500 L 1=X 12 X 100% = 6000
Exhaust Fans 6 EA X 21 X 100% = 126
Add' 25% Largest Mech. Load 1 LS X 21 X 25% _ 5
TOTAL 59806
For 240V, 1-Phase, 3 Wire Service ! 59806 (VA) 1 240 = 249 AMPS
!
I