HomeMy WebLinkAboutE16-0109 load calcs.pdf 1170 BLUE SAGE DRIVE STEAMBOAT SPRINGS,CO B0407 WILDER ENGINEERING x:970-S19•7848 ELECTRICAL CONSULTfNG&DESIGN WILDER-ENG.COM ELECTRIC LOAD SUMMARY Client Name: Snowdon and Hopkins Architects PC Load Tab Project Name: Unit 13 Remodel/Addition,770 Potato Patch Drive Project No: 201636 Date: June 1,2016 Creamery Ranch ISQ.FT. Residential 2025 VA/S.F.OR QTY. VA TOTAL NOTES GENERAL LIGHTING LOAD GENERAL LIGHTING 3 6,075 6,075 Per NEC 220.83(6)(1) SMALL APPLIANCE 2 1,500 3,000 Per NEC 220.83(B)(2) LAUNDRY 1 1,500 1,500 Per NEC 220.83(6)(2) TOTAL 10,575 APPLIANCE LOADS Per NEC 220.83(6)(3) REFRIGERATOR 1 1,200 1,200 _ DISHWASHER 1 1,200 1,200 DISPOSAL 1 960 960 MICROWAVE 1 1,000 1,000 DRYER 1 5,000 5,000 OVEN 1 9,600 9,600 RANGE 1 1,000 1,000 HOT WATER HEATER 1 4,500 4,500 STEAM BATH 1 4,800 4,800 HOT TUB 1 5,000 5,000 EXHAUST FAN 1 15 15 34,275 GEN.LTG AND APPLIANCE LOAdI 44,850 DEMAND FACTOR NOTES 100%FIRST 8,000 VA 8000 Per NEC 220.83(B) 40%FOR REMAINDER OF LOAD 14740 Per NEC 220.83(B) TOTAL 22,740 AIR CONDITIONING&COOLING Per NEC 220.83(B) HEAT PUMP 1 9,660 9,660 _ FAN COILS 2 1,920 3,840 BASEBOARD HEAT-1 1 400 0 Omitted per NEC 220.83(B) BASEBOARD HEAT-2 1 1,000 0 Omitted per NEC 220.83(B) BASEBOARD HEAT-3 1 1,500 0 Omitted per NEC 220.83(B) BASEBOARD HEAT-4 1 2,000 0 Omitted per NEC 220.83(B) KICKSPACE HETER 1 1,125 0 Omitted per NEC 220.83(B) HEAT MAT 1 1,440 0 Omitted per NEC 220.83(B) TOTAL 13,500 OVERALL TOTAL(VA)I 36,240 Gen.Ltg&Appl.Load+AC W -nkpfldR�C�.itf 151 AMPS @ 240V,1-PH .1 GH Ltics ,sIli fr SELECTED SINGLE PHASE 5 ,et-p r• r 200-AMPS FEEDER BASED ON NEC e• . 9 ; OPTIONAL LOAD CALCULATION Ir`y • Y!