Creamery Ranch ISQ.FT.
Residential 2025
VA/S.F.OR
QTY. VA TOTAL NOTES
GENERAL LIGHTING LOAD
GENERAL LIGHTING 3 6,075 6,075 Per NEC 220.83(6)(1)
SMALL APPLIANCE 2 1,500 3,000 Per NEC 220.83(B)(2)
LAUNDRY 1 1,500 1,500 Per NEC 220.83(6)(2)
TOTAL 10,575
APPLIANCE LOADS Per NEC 220.83(6)(3)
REFRIGERATOR 1 1,200 1,200 _
DISHWASHER 1 1,200 1,200
DISPOSAL 1 960 960
MICROWAVE 1 1,000 1,000
DRYER 1 5,000 5,000
OVEN 1 9,600 9,600
RANGE 1 1,000 1,000
HOT WATER HEATER 1 4,500 4,500
STEAM BATH 1 4,800 4,800
HOT TUB 1 5,000 5,000
EXHAUST FAN 1 15 15
34,275
GEN.LTG AND APPLIANCE LOAdI 44,850
DEMAND FACTOR NOTES
100%FIRST 8,000 VA 8000 Per NEC 220.83(B)
40%FOR REMAINDER OF LOAD 14740 Per NEC 220.83(B)
TOTAL 22,740
AIR CONDITIONING&COOLING Per NEC 220.83(B)
HEAT PUMP 1 9,660 9,660 _
FAN COILS 2 1,920 3,840
BASEBOARD HEAT-1 1 400 0 Omitted per NEC 220.83(B)
BASEBOARD HEAT-2 1 1,000 0 Omitted per NEC 220.83(B)
BASEBOARD HEAT-3 1 1,500 0 Omitted per NEC 220.83(B)
BASEBOARD HEAT-4 1 2,000 0 Omitted per NEC 220.83(B)
KICKSPACE HETER 1 1,125 0 Omitted per NEC 220.83(B)
HEAT MAT 1 1,440 0 Omitted per NEC 220.83(B)
TOTAL 13,500
OVERALL TOTAL(VA)I 36,240 Gen.Ltg&Appl.Load+AC
W -nkpfldR�C�.itf 151 AMPS @ 240V,1-PH
.1 GH Ltics ,sIli
fr SELECTED SINGLE PHASE
5 ,et-p r• r 200-AMPS FEEDER BASED ON NEC
e• . 9 ; OPTIONAL LOAD CALCULATION