HomeMy WebLinkAboutA17-0016_Battery Calcs_1491332640.pdf Vail Fire Station. 45 S Frontage Rd Vigilant VS2 FACP Battery Calculations Standby Number of Current Total Current Device Type Devices (Amps) (Amps) Base Panel 1 X 0.172 = 0.172 SA-DACT 1 X 0.3 = 0.3 GSA-CT2 Dual Monitor Module 4 X 0.000396 = 0.001584 GSA-PS - Photo Smoke Detector 4 X 0.000045 = 0.00018 V-PCOS Smoke/CO Detector 3 X 0.00007 = 0.00021 GSA-M278 Manual Pull Station 4 X 0.00025 = 0.001 SUM COLUMN FOR STANDBY LOAD 0.474974 = AMPS Alarm Load Number of Current Total Current Device Type Devices (Amps) (Amps) Base Panel 1 X 0.267 = 0.267 SA-DACT 1 X 0.3 = 0.3 GSA-CT2 Dual Monitor Module 4 X 0.00068 = 0.00272 GSA-PS - Photo Smoke Detector 4 X 0.000045 = 0.00018 V-PCOS Smoke/CO Detector 3 X 0.00007 = 0.00021 GSA-M278 Manual Pull Station 4 X 0.0004 = 0.0016 NAC 1 X 1.5 = 1.5 NAC 1 X 1.5 = 1.5 Sounder Base 9 X 0.041 = 0.369 WP A/V at FDC 1 X 0.365 = 0.365 SUM COLUMN FOR STANDBY LOAD 4.30571 = AMPS Standby Load Required Standby Time in Hours Current (Amps) 0.474974 X 24 = 11.40 Alarm Load Required Alarm Time in Hours Current (Amps) (15 minutes) 4.30571 X 0.25 = 1.08 Add Standby and Alarm Load for Required Ampere Hour Battery 12.48 Multiply by the Derating Factor of 1.2 Total Ampere Hours Required = 14.97 Batteries Provided: 17AH Batteries