HomeMy WebLinkAboutB17-0203_comCHECK Report_1495555980.pdfCOMcheck Software Version COMcheckWeb Envelope Compliance Certificate Project Title: 2015 IECC Project Type:Addition Vertical Glazing / Wall Area:29% Location:Vail, Colorado Climate Zone:6b Construction Site: 520 East Lionshead Cir. #302 Vail, Colorado 81657 Owner/Agent: NASA Properties Sydney, AUS Designer/Contractor: Heid Custom Builders PO Box 4909 Edwards, Colorado 81632 Project Information Energy Code: Pacanowski Residence Building Area Floor Area 1-Multifamily : Residential 1955 Envelope Assemblies Assembly Cavity R-Value Cont. R-Value Proposed U-Factor Budget U- Factor(a) Gross Area or Perimeter Roof: Insulation Entirely Above Deck, [Bldg. Use 1 - Multifamily]1113 ---54.4 0.018 0.032 EAST Ext. Wall: Steel-Framed, 24in. o.c., [Bldg. Use 1 - Multifamily]348 37.4 0.0 0.055 0.057 Window: Wood Frame: Fixed, Perf. Specs.: Product ID PEL-N-11- 09031-00001, SHGC 0.26, [Bldg. Use 1 - Multifamily] (b) 16 ------0.280 0.360 Window: Wood Frame: Operable, Perf. Specs.: Product ID PEL-N- 09032-0002, SHGC 0.28, [Bldg. Use 1 - Multifamily] (b) 80 ------0.260 0.430 WEST Ext. Wall: Steel-Framed, 24in. o.c., [Bldg. Use 1 - Multifamily]208 37.4 0.0 0.055 0.057 Window: Wood Frame: Fixed, Perf. Specs.: Product ID PEL-N-09031- 0001, SHGC 0.28, [Bldg. Use 1 - Multifamily] (b) 25 ------0.260 0.360 Window: Wood Frame: Operable, Perf. Specs.: Product ID PEL-N-11- 09031, SHGC 0.28, [Bldg. Use 1 - Multifamily] (b) 42 ------0.260 0.430 (a)Budget U-factors are used for software baseline calculations ONLY, and are not code requirements. (b)Fenestration product performance must be certified in accordance with NFRC and requires supporting documentation. Project Title: Data filename: Pacanowski Residence 04/10/17Report date: 131 ofPage Envelope Compliance Statement Compliance Statement: The proposed envelope design represented in this document is consistent with the building plans, specifications, and other calculations submitted with this permit application. The proposed envelope systems have been designed to meet the 2015 IECC requirements in COMcheck Version COMcheckWeb and to comply with any applicable mandatory requirements listed in the Inspection Checklist. Name - Title Signature Date Envelope PASSES: Design 28% better than code Project Title: Data filename: Pacanowski Residence 04/10/17Report date: 132 ofPage COMcheck Software Version COMcheckWeb Interior Lighting Compliance Certificate Project Title: 2015 IECC Project Type:Addition Construction Site: 520 East Lionshead Cir. #302 Vail, Colorado 81657 Owner/Agent: NASA Properties Sydney, AUS Designer/Contractor: Heid Custom Builders PO Box 4909 Edwards, Colorado 81632 Project Information Energy Code: Pacanowski Residence Allowed Interior Lighting Power A Area Category B Floor Area (ft2) C Allowed Watts / ft2 D Allowed Watts 1-Multifamily 1955 0 997.51 997Total Allowed Watts = Proposed Interior Lighting Power E (C X D) D Fixture Watt. A Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast B Lamps/ Fixture C # of Fixture 1-Multifamily LED: 3" LED Can: LED PAR 13W:1 13 13 169 Halogen: Wall Sconce: MR-11 20W:1 7 20 140 Linear Fluorescent: 48" T8 25W (Super T8): Electronic:1 6 25 150 459Total Proposed Watts = Interior Lighting Compliance Statement Compliance Statement: The proposed interior lighting design represented in this document is consistent with the building plans, specifications, and other calculations submitted with this permit application. The proposed interior lighting systems have been designed to meet the 2015 IECC requirements in COMcheck Version COMcheckWeb and to comply with any applicable mandatory requirements listed in the Inspection Checklist. Interior Lighting PASSES: Design 54% better than code Project Title: Data filename: Pacanowski Residence 04/10/17Report date: 133 ofPage COMcheck Software Version COMcheckWeb Exterior Lighting Compliance Certificate Project Title: 2015 IECC Project Type:Addition Construction Site: 520 East Lionshead Cir. #302 Vail, Colorado 81657 Owner/Agent: NASA Properties Sydney, AUS Designer/Contractor: Heid Custom Builders PO Box 4909 Edwards, Colorado 81632 Project Information Energy Code: Pacanowski Residence 2 (Residential mixed use area)Exterior Lighting Zone Allowed Exterior Lighting Power A Area/Surface Category B Quantity C Allowed Watts / D Tradable Wattage E Allowed Watts (B X C) Total Tradable Watts (a) = Total Allowed Watts = Total Allowed Supplemental Watts (b) = 200 200 600 (a)Wattage tradeoffs are only allowed between tradable areas/surfaces. (b)A supplemental allowance equal to 600 watts may be applied toward compliance of both non-tradable and tradable areas/surfaces. Proposed Exterior Lighting Power E (C X D) D Fixture Watt. A Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast B Lamps/ Fixture C # of Fixture Other door (not main entry) (10 ft of door width): Tradable Wattage 0Total Tradable Proposed Watts = Exterior Lighting TBD: No exterior fixtures are defined. Project Title: Data filename: Pacanowski Residence 04/10/17Report date: 134 ofPage COMcheck Software Version COMcheckWeb Mechanical Compliance Certificate Project Title: 2015 IECC Project Type:Addition Location:Vail, Colorado Climate Zone:6b Construction Site: 520 East Lionshead Cir. #302 Vail, Colorado 81657 Owner/Agent: NASA Properties Sydney, AUS Designer/Contractor: Heid Custom Builders PO Box 4909 Edwards, Colorado 81632 Project Information Energy Code: Pacanowski Residence Mechanical Systems List Quantity System Type & Description Mechanical Compliance Statement Compliance Statement: The proposed mechanical design represented in this document is consistent with the building plans, specifications, and other calculations submitted with this permit application. The proposed mechanical systems have been designed to meet the 2015 IECC requirements in COMcheck Version COMcheckWeb and to comply with any applicable mandatory requirements listed in the Inspection Checklist. Project Title: Data filename: Pacanowski Residence 04/10/17Report date: 135 ofPage Inspection Checklist Requirements: 0.0% were addressed directly in the COMcheck software COMcheck Software Version COMcheckWeb Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided. Energy Code: 2015 IECC Section # & Req.ID Plan Review Complies?Comments/Assumptions C103.2 [PR1]1 Plans and/or specifications provide all information with which compliance can be determined for the building envelope and document where exceptions to the standard are claimed. Complies Does Not Not Observable Not Applicable C103.2 [PR4]1 Plans, specifications, and/or calculations provide all information with which compliance can be determined for the interior lighting and electrical systems and equipment and document where exceptions to the standard are claimed. Information provided should include interior lighting power calculations, wattage of bulbs and ballasts, transformers and control devices. Complies Does Not Not Observable Not Applicable C402.4.1 [PR10]1 The vertical fenestration area <= 30 percent of the gross above-grade wall area. Complies Does Not Not Observable Not Applicable C402.4.1 [PR11]1 The skylight area <= 3 percent of the gross roof area. Complies Does Not Not Observable Not Applicable Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Data filename: Pacanowski Residence 04/10/17Report date: 136 ofPage Section # & Req.ID Footing / Foundation Inspection Complies?Comments/Assumptions C303.2.1 [FO6]1 Exterior insulation protected against damage, sunlight, moisture, wind, landscaping and equipment maintenance activities. Complies Does Not Not Observable Not Applicable Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Data filename: Pacanowski Residence 04/10/17Report date: 137 ofPage Section # & Req.ID Framing / Rough-In Inspection Complies?Comments/Assumptions C303.1.3 [FR12]2 Fenestration products rated in accordance with NFRC. Complies Does Not Not Observable Not Applicable C303.1.3 [FR13]1 Fenestration products are certified as to performance labels or certificates provided. Complies Does Not Not Observable Not Applicable C402.4.3 [FR10]1 Vertical fenestration SHGC value.Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. C402.4.3, C402.4.3. 4 [FR8]1 Vertical fenestration U-Factor.Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. C402.5.1 [FR16]1 The building envelope contains a continuous air barrier that is sealed in an approved manner and either constructed or tested in an approved manner. Air barrier penetrations are sealed in an approved manner. Complies Does Not Not Observable Not Applicable C402.5.2, C402.5.4 [FR18]3 Factory-built fenestration and doors are labeled as meeting air leakage requirements. Complies Does Not Not Observable Not Applicable Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Data filename: Pacanowski Residence 04/10/17Report date: 138 ofPage Section # & Req.ID Mechanical Rough-In Inspection Complies?Comments/Assumptions C402.5.5, C403.2.4. 3 [ME3]3 Stair and elevator shaft vents have motorized dampers that automatically close. Complies Does Not Not Observable Not Applicable C402.5.5, C403.2.4. 3 [ME58]3 Outdoor air and exhaust systems have motorized dampers that automatically shut when not in use and meet maximum leakage rates. Check gravity dampers where allowed. Complies Does Not Not Observable Not Applicable Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Data filename: Pacanowski Residence 04/10/17Report date: 139 ofPage Section # & Req.ID Rough-In Electrical Inspection Complies?Comments/Assumptions C405.2.1 [EL15]1 Lighting controls installed to uniformly reduce the lighting load by at least 50%. Complies Does Not Not Observable Not Applicable C405.2.1 [EL18]1 Occupancy sensors installed in required spaces. Complies Does Not Not Observable Not Applicable C405.2.1, C405.2.2. 3 [EL23]2 Independent lighting controls installed per approved lighting plans and all manual controls readily accessible and visible to occupants. Complies Does Not Not Observable Not Applicable C405.2.2. 1 [EL22]2 Automatic controls to shut off all building lighting installed in all buildings. Complies Does Not Not Observable Not Applicable C405.2.3 [EL16]2 Daylight zones provided with individual controls that control the lights independent of general area lighting. Complies Does Not Not Observable Not Applicable C405.2.3, C405.2.3. 1, C405.2.3. 2 [EL20]1 Primary sidelighted areas are equipped with required lighting controls. Complies Does Not Not Observable Not Applicable C405.2.3, C405.2.3. 1, C405.2.3. 3 [EL21]1 Enclosed spaces with daylight area under skylights and rooftop monitors are equipped with required lighting controls. Complies Does Not Not Observable Not Applicable C405.2.4 [EL4]1 Separate lighting control devices for specific uses installed per approved lighting plans. Complies Does Not Not Observable Not Applicable C405.2.4 [EL8]1 Additional interior lighting power allowed for special functions per the approved lighting plans and is automatically controlled and separated from general lighting. Complies Does Not Not Observable Not Applicable C405.3 [EL6]1 Exit signs do not exceed 5 watts per face. Complies Does Not Not Observable Not Applicable Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Data filename: Pacanowski Residence 04/10/17Report date: 1310 ofPage Section # & Req.ID Insulation Inspection Complies?Comments/Assumptions C303.1 [IN3]1 Roof insulation installed per manufacturer’s instructions. Blown or poured loose-fill insulation is installed only where the roof slope is <=3 in 12. Complies Does Not Not Observable Not Applicable C303.1 [IN10]2 Building envelope insulation is labeled with R-value or insulation certificate providing R-value and other relevant data. Complies Does Not Not Observable Not Applicable C303.2 [IN7]1 Above-grade wall insulation installed per manufacturer’s instructions. Complies Does Not Not Observable Not Applicable C303.2.1 [IN14]2 Exterior insulation is protected from damage with a protective material. Verification for exposed foundation insulation may need to occur during Foundation Inspection. Complies Does Not Not Observable Not Applicable C402.2.1 [IN17]3 Insulation intended to meet the roof insulation requirements cannot be installed on top of a suspended ceiling. Mark this requirement compliant if insulation is installed accordingly. Complies Does Not Not Observable Not Applicable C402.2.3 [IN6]1 Above-grade wall insulation R-value.Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. C402.2.6 [IN18]3 Radiant panels and associated components, designed for heat transfer from the panel surfaces to the occupants or indoor space are insulated with a minimum of R-3.5. Complies Does Not Not Observable Not Applicable C402.4.2. 2 [IN2]1 Roof R-value. For some ceiling systems, verification may need to occur during Framing Inspection. Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. C402.5.1. 1 [IN1]1 All sources of air leakage in the building thermal envelope are sealed, caulked, gasketed, weather stripped or wrapped with moisture vapor- permeable wrapping material to minimize air leakage. Complies Does Not Not Observable Not Applicable Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Data filename: Pacanowski Residence 04/10/17Report date: 1311 ofPage Section # & Req.ID Final Inspection Complies?Comments/Assumptions C303.3, C408.2.5. 2 [FI17]3 Furnished O&M instructions for systems and equipment to the building owner or designated representative. Complies Does Not Not Observable Not Applicable C402.5.3 [FI51]3 Where open combustion air ducts provide combustion air to open combustion fuel burning appliances, the appliances and combustion air opening are located outside the building thermal envelope or enclosed in a room, isolated from inside the thermal envelope. Such rooms are sealed and insulated. Complies Does Not Not Observable Not Applicable C402.5.8 [FI26]3 Recessed luminaires in thermal envelope to limit infiltration and be IC rated and labeled. Seal between interior finish and luminaire housing. Complies Does Not Not Observable Not Applicable C405.4.1 [FI18]1 Interior installed lamp and fixture lighting power is consistent with what is shown on the approved lighting plans, demonstrating proposed watts are less than or equal to allowed watts. Complies Does Not Not Observable Not Applicable See the Interior Lighting fixture schedule for values. C408.2.5. 1 [FI16]3 Furnished as-built drawings for electric power systems within 90 days of system acceptance. Complies Does Not Not Observable Not Applicable C408.3 [FI33]1 Lighting systems have been tested to ensure proper calibration, adjustment, programming, and operation. Complies Does Not Not Observable Not Applicable Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Data filename: Pacanowski Residence 04/10/17Report date: 1312 ofPage Project Title: Data filename: Pacanowski Residence 04/10/17Report date: 1313 ofPage