SOLAR INSTALLATION INFORMATION
Vendor: Active Energies Solar LLC
PO Box 7627
Avon, CO 81620
(970-306-423 3/info@activeenergies.corn)
Site: Crow Residence
2150 Ptarmigan Road
Vail, CO 81657
System Layout: Single Panel=5.38ft tall X 3.26ft wide
System Size= 16.4ft tall X 38ft wide(including mounting equipment)
Panel Arrangement: 3 rows of 11 panels oriented in the portrait position,mounted flush
on the south facing roof,separated around the vent and exhaust pipes
2150 Ptarmigan F uad
New Main
Service
disconnect and
PV Production
ra. Meter
• "
Holy Cross Meter 14;7, ••
lf
•
1
•
/
N •4
•
Holy Cross electric meter located on northwest side of neighbor house to the west. PV
production meter to be located next to new external main service discounnt inverter to be
mounted adjacent to the meter.
-Minimum Designed Temperature: -40°F
-Maximum Ambient Design Temperature: 140°F
-All AC wiring to be completed by project's Colorado licensed master electrician
-All DC wiring to be overseen by NABCEP certified installer
Page 1 of 4 12/4/2016
PX1751462 4034. 1600 X1209 P227):T30B.ao 014:8;:x,61.433 .5Ig3,l .40.ta ghaegiesemegies.com
ACTIVE
ENERGIES
SOLAR,.
CALCULATIONS
8.745kW System Size (STC)
• 33 Canadian Solar CS6K-265M solar panels @ 265 watts
• 33 integrated SolarEdge P300 Optimizers
• 1 SolarEdge SE7600A-US inverter(2 strings of 16/17 modules/optimizers)
• Fixed array tilt angle: 22.62°
• Array azimuth: 120° (where 180° is south)
• Estimated annual power production: 11,778kWh
Maximum PV System Voltage: 690.7
Voc = 37.7V/module
37.7V x 1 module= 37.7V
Temperature correction factor 690.7(A)
Temperature Coefficient (Voc) = -0.31/°C
(-65C° x (-.0031C°)) = .2015%
((.2015% x 37.7V)x 1 panels) + 37.7V=45.1V
Maximum PV Source Circuit (String) Current: 690.8 (A)(1)
Ise/Imax= 15A
15A x 1.25 = 18.8A
Maximum PV Output Circuit(Array) Current: 690.8 (A)(2)
Max Input for SE7600A-US =23A
Inverter Output Circuit Current: 690.8 (A)(3)
32A @ 240V
Page 2 of 4 12/4/2016
P.O.BCO3 x 162 403r1600 fi 2o9 P227)12306. 31 014:8;r,61.4Ib3Al4R15.40.tarmetOtetwegies.com
ACTIVE
ENERGIES
SOLAR,.
CONDUCTOR SIZING
Pass Thru Box from Optimizers to Inverter (combined strings):
33 panels x 265w= 8,745w/350v=25A
25A x 1.25 = 31.2A
#10 THWN-2 Table 310.16
40A
No conduit fill adjustment Table 310.15 (B)(3)(a)
No Temperature correction factor Table 310.15 (B)(2)(b)
Inverter to Disconnect to Service Panel:
Nameplate maximum continuous output current:
32A @ 240V
32A x 125% =40A 210.19 (A)(1)
#8 THWN-2 Table 310.16
50A (75°C column)
No temperature correction factor
No conduit fill adjustment
Overcurrent Protection Device
40A two pole breaker Per Manufacturer Specification
Conductors may be oversized for voltage drop