Loading...
HomeMy WebLinkAboutF14-0061_Gorsuch-Calcs&Material Data_1412694540.pdf Calculations/Product Data Submittal FOR Gorsuch Vail Village Fire Sprinkler Tenant Finish 263 East Gore Creek Drive Vail, CO 81657 Prepared By: Jason Brochu Western States Fire Protection Co. 7026 S. Tucson Way Centennial, CO 80112 Phone (303) 792-0022 Fax (303) 792-9049 Email: jason.brochu@wsfp.us WSFP #CS2505 October 2nd 2014 Hydraulic Calculations 1 Description Brand Model 1 Commercial Upright Sprinkler Reliable F1FR 2 Commerical Concealed Sprinkler Reliable G5 3 Existing Backflow Preventer Double-Check Conbraco DC 4 Existing Pressure Reducing Valve Bermad 720UL 5 Steel Pipe Various Various 6 Grooved Fittings Various Various 7 Threaded Fittings Anvil Various 8 Copper Pipe Nibco Various 9 Copper Fittings Nibco Various 10 Sammy Hangers Sammy Various 11 Beam Clamp Hangers Tolco Fig 68 12 Adjustable Ring Hanger Various Various 13 All Thread Rod Tolco Fig 100 Calculation/Product Data Index Street Level Retail Hydraulic Overview Job Number: CS2505 - STREET LVL Report Description: Ordinary Group II Node Flow(gpm)Hose Flow(gpm)Static(psi)Residual(psi)Name 6 1300.0 250.0 123.0 118.0 Identifier Pressure(psi)K-Factor(K)Flow(gpm) Job System Supplies Check Point Gauges CS2505 GORSUCH VAIL 263 EAST GORE CREEK DR VAIL, CO 81657 Street Level2 Job Name: Address 1 Address 2 Design Engineer Phone FAX State Certification/License Number AHJ Job Site/Building Most Demanding Sprinkler Data Coverage Per Sprinkler System Pressure Demand Total Demand Area of Application Hose Streams Number Of Sprinklers Calculated System Flow Demand Pressure Result Job Number 562.2 @ 108.3 Supply at Node 6 (1300.0, 250.0, 123.0, 118.0) 0.20gpm/ft² 5.6 K-Factor 26.0 at 21.6 130.00ft² 108.3 881.26ft² (Actual 947.02ft²) 250.0 11 312.2 Density +13.7 (11.2%) Address 3 © M.E.P.CAD, Inc.10/2/2014 Page 1AutoSPRINK® VR11 v11.0.30.0 4:17:36PM Hydraulic Graph Report Description: Ordinary Group II Job Number: CS2505 - STREET LVL System Demand (Including Hose Allowance at Source) System Demand 118.0 @ 1300.0 Residual: Pressure 123.0 Static: Pressure Supply at Node 6 Hydraulic Graph Supply at Node 6 108.3 @ 312.2 108.3 @ 562.2 Available Pressure at Time of Test 121.9 @ 562.2 © M.E.P.CAD, Inc.10/2/2014 Page 2AutoSPRINK® VR11 v11.0.30.0 4:17:37PM Device (gpm) Actual Flow Minimum Flow (gpm)(K) K-Factor (psi) Pressure Summary Of Outflowing Devices Report Description: Ordinary Group II Job Number: CS2505 - STREET LVL Sprinkler 101 26.0 26.0 5.6 21.6 Sprinkler 102 26.3 26.0 5.6 22.1 Sprinkler 103 26.8 26.0 5.6 22.8 Sprinkler 104 27.4 26.0 5.6 24.0 Sprinkler 105 27.9 26.0 5.6 24.8 Sprinkler 106 28.1 26.0 5.6 25.1 Sprinkler 107 28.3 26.0 5.6 25.6 Sprinkler 108 28.8 26.0 5.6 26.5 Sprinkler 109 30.8 26.0 5.6 30.2 Sprinkler 110 29.5 26.0 5.6 27.8 Most Demanding Sprinkler Data © M.E.P.CAD, Inc.10/2/2014 Page 3AutoSPRINK® VR11 v11.0.30.0 4:17:38PM Pipe Type Diameter Flow Velocity Friction Loss Length Pressure Downstream Elevation Discharge K-Factor Pt Pn Fittings Eq. Length Summary Upstream Total Length HWC Hydraulic Analysis Job Number: CS2505 - STREET LVL Report Description: Ordinary Group II • • • • • Route 1 • • • • • Pf Pe Pv AO 1.055 26.0 9.54 0.136091 4'-2-5/8 0.6 101 17'-11 26.0 5.6 21.6 102 17'-11 22.1 4'-2-5/8 150 Sprinkler Pf Pe Pv AO 1.055 52.3 19.21 0.496633 8'-9-5/8 6.4 102 17'-11 26.3 5.6 22.1 4'-0 1 17'-11 28.5 12'-9-5/8 150 Sprinkler, E(2'-0), T(2'-0) Pf Pe Pv BL 1.291 49.2 12.07 0.165853 12'-2-5/8 2.0 1 17'-11 28.5 7 17'-11 30.5 12'-2-5/8 150 Pf Pe Pv BL 1.291 78.7 19.30 0.395377 12'-3-7/8 4.9 7 17'-11 29.5 30.5 8 17'-11 35.4 12'-3-7/8 150 Flow (q) from Route 4 Pf Pe Pv BL 1.291 111.0 27.21 0.746465 17'-10-5/8 15.6 8 17'-11 32.3 35.4 3'-0 9 17'-11 51.0 20'-10-5/8 150 Flow (q) from Route 5 T(3'-0) Pf Pe Pv CM 2.009 227.6 23.03 0.326943 1'-10½0.6 9 17'-11 116.6 51.0 10 17'-11 51.6 1'-10½ 150 Flow (q) from Route 3 Pf Pe Pv CM 2.009 312.2 31.60 0.587065 2'-3 3.4 10 17'-11 84.7 51.6 3'-6 11 17'-11 55.0 5'-9 150 Flow (q) from Route 2 E(3'-6) Pf Pe Pv FR 2.635 312.2 18.37 0.236745 10'-0 4.3 11 17'-11 55.0 8'-2-7/8 4.3 12 7'-11 63.6 18'-2-7/8 120 E(8'-2-7/8) Pf Pe Pv FM 2.635 312.2 18.37 0.236745 53'-5 22.4 12 7'-11 63.6 41'-2¼ 2 7'-11 86.0 94'-7¼ 120 2T(16'-5¾), E(8'-2-7/8) Pf Pe Pv FM 2.469 312.2 20.92 0.325016 13'-0¼6.2 2 7'-11 86.0 6'-0 3 7'-11 92.2 19'-0¼ 120 E(6'-0) Pf Pe Pv FM 3.068 312.2 13.55 0.112849 12'-7¾2.2 3 7'-11 92.2 7'-0 4 7'-11 94.4 19'-7¾ 120 E(7'-0) Pf Pe Pv AO 4.026 312.2 7.87 0.030043 8'-4½11.1 4 7'-11 94.4 12'-0 2.3 5 2'-6 107.8 20'-4½ 120 2LtE(6'-0), BFP(-5.5), PRV(-5.0) Pf Pe Pv UG 4.100 312.2 7.59 0.020672 21'-10¾0.9 5 2'-6 107.8 20'-0 -0.4 6 3'-6 108.3 41'-10¾ 140 2E(10'-0), S 562.2 250.0 Hose Allowance At Source 6 • • • • • Route 2 • • • • • Pf Pe Pv AO 1.055 26.8 9.82 0.143509 8'-0 1.1 103 17'-11 26.8 5.6 22.8 104 17'-11 24.0 8'-0 150 Sprinkler Pf Pe Pv AO 1.055 54.2 19.88 0.529298 1'-7½1.9 104 17'-11 27.4 5.6 24.0 2'-0 13 17'-11 25.9 3'-7½ 150 Sprinkler, PO(2'-0) Pf Pe Pv BL 1.291 81.6 19.99 0.422225 6'-1-5/8 2.6 13 17'-11 27.4 25.9 14 17'-11 28.5 6'-1-5/8 150 Flow (q) from Route 6 Pf Pe Pv BL 1.291 84.7 20.76 0.452564 45'-0½23.1 14 17'-11 3.1 28.5 6'-0 10 17'-11 51.6 51'-0½ 150 Flow (q) from Route 7 2T(3'-0) • • • • • Route 3 • • • • • Pf Pe Pv BL 1.291 27.9 6.84 0.058060 1'-7½0.3 105 17'-11 27.9 5.6 24.8 3'-0 15 17'-11 25.1 4'-7½ 150 Sprinkler, T(3'-0) Pf Pe Pv BL 1.291 0.5 0.13 0.000036 2'-7-5/8 0.0 15 17'-11 25.1 3'-0 106 17'-11 25.1 5'-7-5/8 150 T(3'-0) Pf Pe Pv BL 1.291 28.6 7.00 0.060647 8'-0 0.5 106 17'-11 28.1 5.6 25.1 107 17'-11 25.6 8'-0 150 Sprinkler Pf Pe Pv BL 1.291 56.9 13.95 0.216902 4'-4 0.9 107 17'-11 28.3 5.6 25.6 108 17'-11 26.5 4'-4 150 Sprinkler Pf Pe Pv BL 1.291 85.8 21.02 0.463156 8'-0 3.7 108 17'-11 28.8 5.6 26.5 109 17'-11 30.2 8'-0 150 Sprinkler © M.E.P.CAD, Inc.10/2/2014 Page 4AutoSPRINK® VR11 v11.0.30.0 4:17:39PM Pipe Type Diameter Flow Velocity Friction Loss Length Pressure Downstream Elevation Discharge K-Factor Pt Pn Fittings Eq. Length Summary Upstream Total Length HWC Hydraulic Analysis Job Number: CS2505 - STREET LVL Report Description: Ordinary Group II Pf Pe Pv BL 1.291 116.6 28.57 0.817049 20'-1-7/8 18.9 109 17'-11 30.8 5.6 30.2 3'-0 16 17'-11 49.2 23'-1-7/8 150 Sprinkler, Tr(1'-0), E(2'-0) Pf Pe Pv CM 2.009 116.6 11.80 0.094830 19'-1-5/8 1.8 16 17'-11 49.2 9 17'-11 51.0 19'-1-5/8 150 • • • • • Route 4 • • • • • Pf Pe Pv AO 1.055 29.5 10.83 0.171942 10'-0½2.8 110 17'-11 29.5 5.6 27.8 6'-0 7 17'-11 30.5 16'-0½ 150 Sprinkler, 2E(2'-0), T(2'-0) • • • • • Route 5 • • • • • Pf Pe Pv AO 1.055 32.3 11.84 0.202972 6'-8-5/8 2.2 111 17'-11 32.3 5.6 33.2 4'-0 8 17'-11 35.4 10'-8-5/8 150 Sprinkler, E(2'-0), T(2'-0) • • • • • Route 6 • • • • • Pf Pe Pv BL 1.291 27.4 6.72 0.056096 13'-0 0.8 15 17'-11 25.1 1'-0 13 17'-11 25.9 14'-0 150 Tr(1'-0) • • • • • Route 7 • • • • • Pf Pe Pv BL 1.291 3.1 0.76 0.001006 0'-8¾0.0 1 17'-11 28.5 3'-0 14 17'-11 28.5 3'-8¾ 150 T(3'-0) 1.51 4.87 )(150 1.33 140 1.16 130 0.713 100 Equivalent Pipe Lengths of Valves and Fittings (C=120 only) Actual Inside Diameter Schedule 40 Steel Pipe Inside Diameter = Factor C Value Multiplier Value Of C Multiplying Factor © M.E.P.CAD, Inc.10/2/2014 Page 5AutoSPRINK® VR11 v11.0.30.0 4:17:39PM Pipe Type Diameter Flow Velocity Friction Loss Length Pressure Downstream Elevation Discharge K-Factor Pt Pn Fittings Eq. Length Summary Upstream Total Length HWC Hydraulic Analysis Job Number: CS2505 - STREET LVL Report Description: Ordinary Group II Pipe Type Legend AO Arm-Over BL Branch Line CM Cross Main DN Drain DR Drop DY Dynamic FM Feed Main FR Feed Riser MS Miscellaneous OR Outrigger RN Riser Nipple SP Sprig ST Stand Pipe UG Underground Units Legend Diameter Inch Elevation Foot Flow gpm Discharge gpm Velocity fps Pressure psi Length Foot Friction Loss psi/Foot HWC Hazen-Williams Constant Pt Total pressure at a point in a pipe Pn Normal pressure at a point in a pipe Pf Pressure loss due to friction between points Pe Pressure due to elevation difference between indicated points Pv Velocity pressure at a point in a pipe Fittings Legend ALV Alarm Valve AngV Angle Valve b Bushing BalV Ball Valve BFP Backflow Preventer BV Butterfly Valve C Cross Flow Turn 90° cplg Coupling Cr Cross Run CV Check Valve DelV Deluge Valve DPV Dry Pipe Valve E 90° Elbow EE 45° Elbow Ee1 11¼° Elbow Ee2 22½° Elbow f Flow Device fd Flex Drop FDC Fire Department Connection fE 90° FireLock(TM) Elbow fEE 45° FireLock(TM) Elbow flg Flange FN Floating Node fT FireLock(TM) Tee g Gauge GloV Globe Valve GV Gate Valve Ho Hose Hose Hose HV Hose Valve Hyd Hydrant LtE Long Turn Elbow mecT Mechanical Tee Noz Nozzle P1 Pump In P2 Pump Out PIV Post Indicating Valve PO Pipe Outlet PRV Pressure Reducing Valve PrV Pressure Relief Valve red Reducer/Adapter S Supply sCV Swing Check Valve Spr Sprinkler St Strainer T Tee Flow Turn 90° Tr Tee Run U Union WirF Wirsbo WMV Water Meter Valve Z Cap © M.E.P.CAD, Inc.10/2/2014 Page 6AutoSPRINK® VR11 v11.0.30.0 4:17:39PM Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523 Bulletin 034 Rev. DBulletin 034 Rev. D Model G5-80, Model G5-56, Model G5-42, Model G5-28 Quick Response Concealed Automatic Sprinkler UL Quick Response FM Standard Response Concealed Sprinkler With a 3/4” (19mm) Adjustment Features 1. Cover plate attachment (Plain or Perforated) with ¾” (19mm) assembly adjustment. 2. Smooth aesthetic ceiling profile. 3. Factory installed protective cap. 4. Available in Chrome and White as Standard Finish- es. Special Application Finishes are also available. 5. Ordinary and Intermediate temperature rating. For additional Sprinklers refer to Bulletin 154 for Technical Specifi cation and Approvals Approvals & Listings 1. Underwriters Laboratories Inc. and cULus - Quick Response • G5-80, G5-56 - Light Hazard and Ordinary Hazard Occupancies • G5-42 - Light Hazard Occupancies • G5-28 - Light Hazard Occupancies 2. Factory Mutual Research Corp. (FM) - Standard Response (See Page 3) • G5-56 & G5-28 only. • See the most recent FM Global Property Loss Prevention Data Sheets for installation and use guidelines. 3. Loss Prevention Council (LPCB, UK) - Standard Response • G5-56 - Light Hazard and Ordinary Hazard Occupancies 4. VdS Schadenverhütung GmbH - Standard Response 5. EC-Certificate of Conformity 0832-CPD-2062 U.S. Patent number 6,554,077. Application The Reliable Model G5-80, G5-56, G5-42 and G5-28 are the most versatile quick response concealed sprinklers avail- able. It provides the best form of fire protection while offering an attractive appearance and 3/4” (19mm) of cover adjust- ment for ease of installation. The small diameter cover plate assembly is easily attached and blends into the ceiling, con- cealing the most dependable fire protection available, an au- tomatic sprinkler system. The Model G5-80, G5-56, G5-42 and G5-28 are designed for use where aesthetic appearance is important. Offices, hos- pitals, motels and restaurants are but a few of the applications where it can be used. The Model G5-80, G5-56, G5-42 and G5-28 are UL Listed Quick Response Concealed sprinklers intended for use in accordance with NFPA 13. FM Approves the G5-56 and the G5-28 sprinkler as a standard response concealed sprinkler intended for use in accordance with FM Loss Prevention Data Sheet 2.0. Product Description The Reliable Model G5-80, G5-56, G5-42 and G5-28 uses a proven quick response fusible element in a standard style sprinkler frame with a drop-down deflector. This assembly is recessed into the ceiling and concealed by a flat cover plate assembly. The threaded engagement provides ¾” (19mm) of cover adjustment. The flat cover plate is attached to the skirt using either 135°F (57°C) or 165°F (74°C) ordinary tempera- ture classification solder. When the ceiling temperature rises, the solder holding the flat cover plate melts, the flat cover plate released thus expos- ing the sprinkler inside to the rising ambient temperature. The subsequent fusing of the element opens the waterway and causes the deflector to distribute the water. Any secure engagement between the cover plate and cup will assure that the drop-down deflector is properly located below the ceiling. Plain Cover Plate Perforated Cover Plate Installation Do not install the G5-80, G5-56, G5-42 and G5-28 in ceilings which have positive pressure in the space above. • Cut a 25/8” inch (67mm) diameter hole is cut in the ceiling, the sprinkler is easily installed with the Model FC Wrench. The wrench has a socket drive which is inserted into the body of the sprinkler. When installing a sprinkler the wrench is first positioned into the sprinkler/cup assembly until the wrench socket engages the body of the sprinkler. The sprinkler is then tightened into the pipe fitting. When inserting or remov- ing the wrench from the sprinkler/cup assembly, care should be taken to prevent damage to the sprinkler. DO NOT WRENCH ON ANY OTHER PART OF THE SPRINKLER/ CUP ASSEMBLY. Install the cover plate by hand turning the cover in the clockwise direction until it is tight against the ceil- ing. A protective cap is provided to protect the drop-down sprinkler deflector from damage which could occur during construction before the cover plate is installed. The cap is factory installed inside the sprinkler cup. Remove cap to install sprinkler, then re- install cap until the cover plate is installed. Maintenance The Model G5-80, G5-56, G5-42 and G5-28 should be in- spected and the sprinkler system maintained in accordance with NFPA 25. Do not clean sprinklers with soap and water, am- monia or any other cleaning fluids. Remove any sprinkler that has been painted (other than factory applied) or damaged in any way. Concealed sprinklers cover plates can not be painted in the field, after installation or have any other coating applied other than the factory finish. A stock of spare sprinklers should be maintained to allow quick replacement of damaged or oper- ated sprinklers. Prior to installation, sprinklers should be main- tained in the original cartons and packaging to minimize the potential for damage to sprinklers that would cause improper operation or non-operation. UL Listing Category Sprinklers, Automatic and Open Quick Response Sprinkler UL Guide Number VNIV Maximum Working Pressure 175 psi (12 bar) 100% Factory tested Hydrostatically to 500 psi (34.5 bar) Temperature Rating Classifi cation Sprinkler Cover Plate Max. Ambient Temp. Ordinary 165°F/74°C 135°F/57°C 100°F/38°C Intermediate 212°F/100°C 165°F/74°C 150°F/66°C Model FC Sprinkler Wrench Ordering Information 1. Sprinkler Model 2. Nominal Orifice 3. Flat Cover Plate Plain or Perforated 4. Flat Cover Plate Assembly Finish 5. Inlet Type Cover Plate Finishes(1) Standard Finishes Chrome White Paint Special Application Finishes(2) Bright Brass Finished Bronze Black Plating Black Paint Off White Satin Chrome (1) Other finishes and colors are available on special order. Consult factory for details. Coverplate custom paint is semi-gloss, unless specified otherwise. (2) For the perforated style cover- plate, consult factory for avail- ability on these and other cus-tom finishes. 2. Technical Data Sprinkler Model Sprinkler Inlet Total Adjustment Nominal Orifi ce Nominal K Factor Thread Approvals Sprinkler Identifi cation (SIN)US Metric G5-80 Non Adjustable ¾” (19mm) 17/32” (15mm) 8.0 115 ¾” NPT (R¾) 1 RA3412 G5-56 Non Adjustable ¾” (19mm) ½” (15mm) 5.6 80 ½” NPT (R½) 1,2,3,4,5 RA3415 G5-42 Non Adjustable ¾” (19mm) 7/16” (10mm) 4.2 60 ½” NPT (R½) 1 RA3413 G5-28 Non Adjustable ¾” (19mm) 3/8” (10mm) 2.8 40 ½” NPT (R½) 1,2 RA3411 For VdS Approval, temperature rating sprinkler 165°F/74°c and cover plate 135°F/57°C only! Notice FOR USE AS A REPLACEMENT OF MODEL G4A SPRINKLERS NOTE: 1. Testing has shown that use of a “nipple extension” will not affect the listing of the sprinkler. 2. For RETROFIT installations, per NFPA 13 (2010) section 8.15.19.4, “which allows the use of nipples as the same pipe thread size as the existing outlet when revamping existing systems”. 3. Do not exceed 8-18 ft-lbs of torque during installation. 3. Reliable Automatic Sprinkler Co., Inc. (800) 431-1588 Sales Offices(800) 848-6051 Sales Fax (914) 829-2042 Corporate Offices www.reliablesprinkler.com Internet Address Manufactured by Recycled Paper Revision lines indicate updated or new data. EG. Printed in U.S.A. 06/14 P/N 9999970421 The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Products manufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries. • Automatic sprinklers • Flush automatic sprinklers • Recessed automatic sprinklers • Concealed automatic sprinklers • Adjustable automatic sprinklers • Dry automatic sprinklers • Intermediate level sprinklers • Open sprinklers • Spray nozzles • Alarm valves • Retarding chambers • Dry pipe valves • Accelerators for dry pipe valves • Mechanical sprinkler alarms • Electrical sprinkler alarm switches • Water flow detectors • Deluge valves • Detector check valves • Check valves • Electrical system • Sprinkler emergency cabinets • Sprinkler wrenches • Sprinkler escutcheons and guards • Inspectors test connections • Sight drains • Ball drips and drum drips • Control valve seals • Air maintenance devices • Air compressors • Pressure gauges • Identification signs • Fire department connection Reliable offers a wide selection of sprinkler components. Following are some of the many precision-made Reliable products that guard life and property from fire around the clock. Reliable...For Complete Protection The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523 Model F1FR Series Quick Response Standard Spray Bulletin 014 Rev. KBulletin 014 Rev. K Model F1FR56 Sprinkler Types Standard Upright Standard Pendent Conventional Vertical Sidewall Horizontal Sidewall Model F1FR56 Recessed Sprinkler Types Standard Pendent/F1/F2/FP Horizontal Sidewall Model F1FR56 Concealed Sprinkler Types Standard Pendent Model F1FR42, F1FRXLH & F1FR28 Sprinkler Types Standard Upright Standard Pendent Model F1FR42, F1FRXLH & F1FR28 Recessed Sprinkler Types Standard Pendent Model F1FR56LL & F1FR42LL Low Lead Sprinkler Types* Standard Pendent Less than 0.25% Lead Content Listing & Approvals 1. Underwriters Laboratories Inc. and Certified for Canada (cULus). 2. Factory Mutual Approvals (FM) 3. Loss Prevention Council (LPCB, UK) 4. VdS Schadenverhütung GmbH 5. *NSF Certified to NSF/ANSi Standard 61 Annex G UL Listing Category Sprinklers, Automatic & Open (VNIV) Quick Response Sprinkler Product Description Reliable Models F1FR56, F1FR56LL, F1FR42, F1FR42LL, F1FRXLH & F1FR28 Series Sprinklers are quick response sprinklers which combine the durability of a standard sprin- kler with the attractive low profile of a decorative sprinkler. The Models F1FR56, F1FR56LL, F1FR42, F1FR42LL, F1FRXLH & F1FR28 Series Recessed automatic sprinklers utilize a 3.0 mm frangible glass bulb. These sprinklers have demonstrated response times in laboratory tests which are five to ten times faster than standard response sprinklers. This quick response enables the Model F1FR56, F1FR56LL, F1FR42, F1FR42LL, F1FRXLH & F1FR28 Series sprinklers Pendent Conventional Recessed Pendent/F1/F2 Upright Vertical Sidewall Horizontal Sidewall Recessed Horizontal Sidewall RecessedPendent/FP Concealed Pendent XLH Upright XLH Pendent XLH Recessed Pendent F1/F2 XLH Recessed Pendent FP to apply water to a fire much faster than standard sprinklers of the same tem- perature rating. The glass bulb consists of an accu- rately controlled amount of special fluid hermetically sealed inside a precisely manufactured glass capsule. This glass bulb is specially constructed to provide fast thermal response. At normal temperatures, the glass bulb contains the fluid in both the liquid and vapor phases. The vapor phase can be seen as a small bubble. As heat is applied, the liquid expands, forcing the bubble smaller and smaller as the liq- uid pressure increases. Continued heating forces the liquid to push out against the bulb, causing the glass to shatter, opening the waterway and allowing the deflector to distrib- ute the discharging water. 2. Technical data: Models Discharge Coeffi cient Response Thread Size Max. Working Pressure Min. Working Pressure Temperature Rating Finish F1FR56 **F1FR56LL(1)K 5.6 Quick Response 1/2” NPT (R1/2) 175 PSI 7 PSI See “Temperature Ratings” Table. See “Finish Table” F1FR42 **F1FR42LL(1) F1FRXLH K 4.2 F1FR28 K 2.8 (1) Low Lead Sprinklers available only with Temperature Rating 200°F/93°C Material Data: Frame Defl ector Load Screw *Pintle Cup Washer Bulb DZR Brass QM Brass **Low Lead Brass CDA Alloy 260, CDA Alloy 220 orCDA Alloy510 CDA Alloy 360 or CDA Alloy 544 CDA Alloy 360 or CDA Alloy 544 CDA Alloy 651 or CDA Alloy 693 Nickel Alloy 440 or Alloy 360 coated with PTFE Adhesive Tape Glass Application Quick response sprinklers are used in fixed fire protection systems: Wet, Dry, Deluge or Preaction. Care must be exercised that the orifice size, temperature rating, deflector style and sprinkler type are in accordance with the latest published standards of the National Fire Protection Association or the approving Authority Having Jurisdiction. Quick response sprinklers are intended for installation as specified in NFPA 13. Quick response sprinklers and standard re- sponse sprinklers should not be intermixed. Model F1FR42, F1FRXLH Upright Pendent ConventionalUpright Model F1FR56, Upright, Pendent & Conventional Sprinklers Model F1FR42, F1FRXLH & F1FR28 Upright & Pendent Sprinklers Installation Wrench: Model D Sprinkler Wrench Installation Data: Nominal Orifi ce Thread Nominal K Factor Sprinkler Approval Sprinkler Identifi cation Number (SIN) Size US Metric Height Organization Upright Pendent Standard-Upright (SSU) and Pendent Deflectors Marked to Indicate Position 1/2” (15mm) (1)1/2” NPT (R1/2) 5.6 80 2.25” (57mm) 1,2,3,4 RA1425 (1)(2)(3)(4)RA1414(1)(2)(3)(4) 7/16” (10mm) 1/2” NPT (R1/2) 4.2 60 2.25” (57mm) 1 RA1423 (1)(4)RA1413(4) 3/8” (10mm) 1/2” NPT (R1/2) 2.8 40 2.25” (57mm) 1 RA1421 (1)(4)RA1411(4) Conventional-Install in Upright or Pendent Position 15mm (1)1/2” NPT (R1/2) 5.6 80 57mm 3, 4 RA1475 (3) (1) cULus listed corrosion resistant (Polyester coated) sprinkler. (2) Polyester coated FM approved sprinkler. (3) Polyester coated LPCB & VdS approved sprinkler RA1425, RA1414 & RA1475. (4) Electroless Nickel PTFE (Teflon®)* Plated - cULus listed Corrosion Resistant 3. Model F1FR56LL & F1FR42LL Pendent Sprinklers Installation Wrench: Model D Sprinkler Wrench Installation Data: Nominal Orifi ce Thread Nominal K Factor Sprinkler Approval Sprinkler Identifi cation Number (SIN) Size US Metric Height Organization Pendent Standard-Pendent Deflectors Marked to Indicate Position 1/2” (15mm) (1)1/2” NPT (R1/2) 5.6 80 2.25” (57mm) 1,5 RA1415 7/16” (11mm) 1/2” NPT (R1/2) 4.2 60 2.25” (57mm) 1,5 RA1410 (1) cULus listed corrosion resistant (Polyester coated) sprinkler. *DuPont Registered Trademark Model F1FR56 Quick Response Vertical Sidewall Sprinkler Installation Wrench: Model D Sprinkler Wrench Installation Position: Upright or Pendent Approval Type: Light Hazard Occupancy Installation Data: Nominal Orifi ce Thread Size Nominal K Factor Sprinkler Height Approval Organizations Sprinkler Identifi cation Numbers (SIN)US Metric ½” (15mm) ½” NPT (R1/2) 5.6 80 2.25” (57mm) 1,2,3 RA1485(2)(3)15mm ½” NPT (R1/2) 5.6 80 2.25” (57mm) 3 (1) (1) LPC Approval is for pendent position only. (2) cULus Listed corrosion resistant (Polyester coated) sprinkler. (3) Electroless Nickel PTFE (Teflon®)* Plated - cULus listed Corrosion Resistant Sprinkler Type Defl ector to Ceiling Distance (Min. - Max.) Upright 4” (102mm) - 12” (305mm) Pendent 4” (102mm) - 12” (305mm) Vertical Sidewall Model F1FR56, F1FR56LL, F1FR42, F1FR42LL, F1FRXLH & F1FR28 F1 or F2 Model F1FR56, F1FR56LL, F1FR42, F1FR42LL, F1FRXLH & F1FR28 FP Model F1FR56, F1FR42, F1FRXLH & F1FR28 Quick Response Recessed Pendent Sprinkler(1) Installation Wrench: Model GFR2 Sprinkler Wrench Installation Data: Nominal Orifi ce Thread Size K Factor Sprinkler Height Sprinkler Identifi cation Number (SIN)US Metric 1/2” (15mm) 1/2” NPT(R½) 5.6 80 2.25” (57mm) RA1414 7/16” (10mm) 1/2” NPT (R1/2) 4.2 60 2.25” (57mm) RA1413 3/8” (10mm) 1/2” NPT (R1/2) 2.8 40 2.25” (57mm) RA1411 (1) Refer to escutcheon data table for approvals & dimensions Model F1FR56LL & F1FR42LL Quick Response Recessed Pendent Sprinkler(1) Installation Wrench: Model GFR2 Sprinkler Wrench Installation Data: Nominal Orifi ce Thread Size K Factor Sprinkler Height Sprinkler Identifi cation Number (SIN)US Metric 1/2” (15mm) 1/2” NPT(R½) 5.6 80 2.25” (57mm) RA1415 7/16” (10mm) 1/2” NPT (R1/2) 4.2 60 2.25” (57mm) RA1410 (1) Refer to escutcheon data table for approvals & dimensions 4.*DuPont Registered Trademark 5. Model F1FR56 Quick Response Horizontal Sidewall Sprinkler Defl ector: HSW Installation Wrench: Model D Sprinkler Wrench Installation Data: Horizontal Sidewall Nominal Orifi ce Thread Size Nominal K Factor Sprinkler Height Approval Organizations and Type of Approval Sprinkler Identifi cation Numbers (SIN)US Metric Light Hazard Ordinary Hazard ½” (15mm) ½” NPT (R1/2) 5.6 80 2.63” (67mm) 1,2 1 RA1435 (1)(2)(3) (1) cULus Listed corrosion resistant (Polyester coated) sprinkler. (2) Polyester coated FM approved sprinkler. (3) Electroless Nickel PTFE (Teflon®)* Plated - cULus listed Corrosion Resistant Horizontal Sidewall Note: For Recessed HSW Sprinklers use installation wrench GFR2. cULus permits use with F1, F2 or FP escutcheons for “Light Hazard” only. While FM limits use for the same hazard with the F2 escutcheon only. Model F1FR56 Quick Response Concealed Pendent Sprinklers Installation Wrench: Model RC1 Sprinkler Wrench Technical Data: Nominal Orifi ce “K” Factor Thread Size Model Temp. Rating Max. Ambient Temp Bulb Color Approvals Sprinkler Identifi cation Number(SIN)US Metric Sprinkler Cover ½” (15mm) 5.6 80 ½” NPT F1FR 135°F/57°C 135°F/57°C 100°F/38°C Orange 1 RA1414 ½” (15mm) 5.6 80 ½” NPT F1FR 155°F/68°C 135°F/57°C 100°F/38°C Red 1, 4 (1)RA1414 ½” (15mm) 5.6 80 ½” NPT F1FR 175°F/79°C 165°F/74°C 100°F/38°C Yellow 1 RA1414 ½” (15mm) 5.6 80 ½” NPT F1FR 200°F/93°C 165°F/74°C 150°F/65°C Green 1 RA1414 (1) For VdS only = 155°F/68°C Norbulb and 1/2” [12,7mm] adjustment. Model F1FR56LL Quick Response Concealed Pendent Sprinklers Installation Wrench: Model RC1 Sprinkler Wrench Technical Data: Nominal Orifi ce “K” Factor Thread Size Model Temp. Rating Max. Ambient Temp Bulb Color Approvals Sprinkler Identifi cation Number(SIN)US Metric Sprinkler Cover ½” (15mm) 5.6 80 ½” NPT F1FR56LL 200°F/93°C 165°F/74°C 150°F/65°C Green 1, 5 RA1414 *DuPont Registered Trademark Installation Aid A protective cap is included for use during installation. Important: The F1FR56 Sprinkler with Model CCP cover plate is not an FM Approved combination. Installation Quick response sprinklers are intended for installation as specified in NFPA 13. Quick response sprinklers and stan- dard response sprinklers should not be intermixed. The Model F1FR56, F1FR56LL, F1FR42, F1FR42LL, F1FRXLH & F1FR28 Recessed Quick Response Sprin- klers are to be installed as shown. The Model F1 or F2 Es- cutcheons illustrated are the only recessed escutcheons to be used with the Model F1FR56, F1FR56LL, F1FR42, F1FR42LL, F1FRXLH & F1FR28 Sprinklers. The use of any other recessed escutcheon will void all approvals and ne- gate all warranties. When installing Model F1FR56, F1FR56LL, F1FR42, F1FR42LL, F1FRXLH & F1FR28 Sprinklers, use the Model D Sprinkler Wrench. Use the Model GFR2 Wrench for install- ing F1FR56, F1FR56LL, F1FR42, F1FR42LL, F1FRXLH & F1FR28 Recessed Pendent Sprinklers. Any other type of wrench may damage these sprinklers. NOTE: A leak tight ½” NPT (R1/2) sprinkler joint can be obtained with a torque of 8-18 ft-lbs (10,8 - 24,4 N-m). Do not tighten sprinklers over maximum recommended torque. It may cause leakage or impairment of the sprinklers. The Models F1FR56/CCP & F1FR56LL/CCP Concealed Sprinkler use the ½” orifice, ½” NPT (R1/2), Model F1FR56 & F1FR56LL Pendent Sprinkler with a threaded Model CCP cup which is factory attached to the sprinklers. The Model F1FR56 Pndent is available in temperature rating of 135°F (57°C), 155°F (68°C), 175°F (79°C) or 200°F (93°C). The Model F1FR56LL Pendent is available only in a rating of 200°F (93°C). The concealed sprinkler assemblies are com- pleted by the installation of the attractive low profile Model CCP push on cover plate assembly, rated 135°F (57°C) or 165°F (74°C) for the F1FR56 and 165°F (74°C) for the FIFR56 LL. The cover plate and sprinkler cup assemblies are joined using a cover plate skirt with flexible tabs for threaded en- gagement. A choice of two cover plate assemblies provide either 1/2” (13mm) or 5/8” (8mm) of cover adjustment, Do not install these sprinklers in ceiling which have positive pressure in the space above. After a 25/8” (67mm) diameter hole is cut in the ceiling, the sprinkler is easily installed with the Model RC1 Wrench. A Teflon* based thread sealant should be applied to the sprin- kler threads only. The Model RC1 Wrench is then used to engage the sprinkler wrenching surfaces and to install the sprinkler in the fitting. When inserting or removing the wrench from the sprinkler/cup assembly, care should be tak- en to prevent damage to the sprinkler. DO NOT WRENCH ON ANY OTHER PART OF THE SPRINKLER. The cover plate is then pushed onto the cup. Final adjustment is made by hand turning the cover plate until the skirt flange makes full contact with the ceiling. Cover plate removal requires turning in the counter clockwise direction. After installation, inspect all sprinklers to ensure that there is a gap between the cover plate and ceiling and that the four cup slots are open and free from any air flow impedi- ment to the space above. Concealed cover plate/cup assemblies are listed only for use with specific sprinklers. The use of any other concealed cover plate/cup assembly with the Model F1FR56 Pendent Sprinkler or the use of the Model CCP Concealed cover plate assembly on any sprinkler with which it is not specifi- cally listed my prevent good fire protection and will void all guarantees, warranties, listings and approvals. Glass bulb sprinklers have orange bulb protectors to minimize bulb damage during shipping, handling and in- stallation. REMOVE THIS PROTECTION AT THE TIME THE SPRINKLER SYSTEM IS PLACED IN SERVICE FOR FIRE PROTECTION. Removal of the protectors before this time may leave the bulb vulnerable to damage. RASCO wrench- es are designed to install sprinklers when covers are in place. REMOVE PROTECTORS BY UNDOING THE CLASP BY HAND. DO NOT USE TOOLS TO REMOVE THE PRO- TECTORS. 6. *DuPont Registered Trade Mark Figure 1 Figure 2 Temperature Ratings Classifi cation Sprinkler Temperature Max. Ambient Temp.Bulb Color °C °F Ordinary Ordinary Intermediate Intermediate High (1) 57 68 79 93 141 135 155 175 200 286 100°F (38°C) 100°F (38°C) 150°F (66°C) 150°F (66°C) 225°F (107°C) Orange Red Yellow Green Blue (1) Not available for recessed sprinklers. Escutcheon Data (1) (1) SIN RA1435 – cULus permits use with F1, F2 or FP escutcheons for “light hazard” only, while FM limits use for same hazard with F2 escutcheon only. Maintenance The Model F1FR56, F1FR56LL, F1FR42, F1FR42LL, F1FRXLH and Model F1FR56, F1FR56LL, F1FR42, F1FR42LL, F1FRXLH & F1FR28 Recessed Sprinklers should be inspected and the sprinkler system maintained in accor- dance with NFPA 25. Do not clean sprinklers with soap and water, ammonia or any other cleaning fluids. Remove dust by using a soft brush or gentle vacuuming. Remove any sprinkler which has been painted (other than factory ap- plied) or damaged in any way. A stock of spare sprinklers should be maintained to allow quick replacement of dam- aged or operated sprinklers. Prior to installation, sprinklers should be maintained in the original cartons and packaging to minimize the potential for damage to sprinklers that would cause improper operation or non-operation. Sprinkler Types Standard Upright Standard Pendent Conventional Recessed Pendent Vertical Sidewall Horizontal Sidewall Recessed Horizontal sidewall Concealed pendent Maximum Working Pressure 175 psi (12 bar) 100% Factory tested hydrostatically to 500 psi (34.5 bar) Finishes (1) Standard Finishes Sprinkler Escutcheon Cover plate (1) Bronze Brass Chrome Chrome Plated Chrome White Polyester Plated Coated (4)(5)(6)White Painted Special Application Finishes Sprinkler Escutcheon Cover plate (1) Electroless Nickel PTFE(Teflon®)*(7) Electroless Nickel PTFE (Teflon®)* Bright Brass Bright Brass(3)Bright Brass Black Plating Black Plated Black Plated Black Paint Black Paint(2)(6)Black Paint Off White Off White(2)(6) Off White Satin Chrome Chrome Dull Chrome Dull (1) Other finishes and colors are available on special order. Consult the factory for details. Custom color painted sprinklers may not retain their UL Corrosion resistance listing. Coverplate custom paint is semi-gloss, unless specified otherwise. (2) cULus Listed only. (3) 200°F (93°C) maximum. (4) cULus listed “corrosion resistance” applies to SIN Numbers RA1435 (HSW), RA1485(VSW), RA1425 (Upright), RA1414 (Pendent) and RA1415 (Pendent) in standard black or white. Corrosion resistance in other polyester colors is available upon request. (5) FM Approvals finish as “Polyester coated” applies to SIN Number RA1414, RA1435 and RA1425 in standard black or white. (6) LPCB and VdS Approved finish applies only to RA1425, RA1414 and RA1475. (7) cULus listed Corrosion Resistant Ordering Information Specify: 1. Sprinkler Model 2. Sprinkler Type 3. Orifice Size 4. Deflector Type 5. Temperature Rating 6. Sprinkler Finish 7. Escutcheon Type 8. Escutcheon Finish (where applicable) 9. Cover plate Model 10. Cover plate Thread size 11. Cover plate Temperature 12. Cover plate Adjustment 13. Cover plate Finish Note: When Model F1FR56 Recessed sprinklers are ordered, the sprinklers and escutcheons are packaged separately. 7. *DuPont Registered Trademark • Automatic sprinklers • Flush automatic sprinklers • Recessed automatic sprinklers • Concealed automatic sprinklers • Adjustable automatic sprinklers • Dry automatic sprinklers • Intermediate level sprinklers • Open sprinklers • Spray nozzles • Alarm valves • Retarding chambers • Dry pipe valves • Accelerators for dry pipe valves • Mechanical sprinkler alarms • Electrical sprinkler alarm switches • Water flow detectors • Deluge valves • Detector check valves • Check valves • Electrical system • Sprinkler emergency cabinets • Sprinkler wrenches • Sprinkler escutcheons and guards • Inspectors test connections • Sight drains • Ball drips and drum drips • Control valve seals • Air maintenance devices • Air compressors • Pressure gauges • Identification signs • Fire department connection Reliable offers a wide selection of sprinkler components. Following are some of the many precision-made Reliable products that guard life and property from fire around the clock. Reliable...For Complete Protection The Reliable Automatic Sprinkler Co., Inc. (800) 431-1588 Sales Offices (800) 848-6051 Sales Fax (914) 829-2042 Corporate Offices www.reliablesprinkler.com Internet Address Manufactured by RecycledPaper Revision lines indicate updated or new data. EG. Printed in U.S.A. 04/14 P/N 9999970300 The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.Products manufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries. Model DC4SG Model DC4SGN DOUBLE CHECK VALVE Conbraco Industries, Inc. 701 Matthews Mint Hill Rd. Matthews NC 28105 USA; www.apollovalves.com; 704-841-6000 This specification is provided for reference only. Conbraco reserves the right to change any portion of this specification without notice and without incurring obligation to make such changes to Conbraco products previously or subsequently sold. SS1040 © 3/10 Page 1 of 3 DESCRIPTION The Apollo® Model DC4SG, DC4SGN Double Check Valve is designed to prevent contamination of the potable water supply due to back-siphonage or backpressure from substances that are non-health hazards. The modular check valves have replaceable seats and reversible EPDM seat discs. Grooved connections on an epoxy-coated ductile iron body allow for easy connection to butterfly valves or gate valves. Note: Model DC4SG replaces Model 4S-100 (also known as Model DC) in all sizes except 10”. FEATURES x Lightweight x Short lay length x Low pressure loss x Modular check valves x Individual access to check valves x Corrosion resistant epoxy-coated ductile iron body x US Patents #5,711,341 and #6,343,618 x MADE IN THE USA MATERIAL SPECIFICATIONS Part Name Material Body Epoxy-coated (FDA) Ductile Iron Covers (2 ½”-6”) Epoxy-coated (FDA) Steel Covers (8”) Epoxy-coated (FDA) Ductile Iron Elbows Epoxy-coated (FDA) Ductile Iron Check Valves (2 ½”-6”) Glass-Filled Noryl® Check Valves (8”) Bronze Springs Stainless Steel Seat Discs Chloramine-resistant EPDM PERFORMANCE RATING Maximum Working Pressure 175 psi Temperature Range 33 ° F – 140 ° F Hydrostatic Test Pressure 350 psi APPROVALS ASSE 1015, IAPMO, CSA B64.5, UL*, FM*, AWWA C-510, and USC’s FCCC&HR. All approvals in horizontal and vertical flow-up configurations. *UL and FM installations must include indicating-type shut- off valves. ORDERING INFORMATION 4SG – 1 X X – 0 X X Y-STRAINER ˆ 0 – None (Standard) ˆ 1 – With Y-Strainer (Flanged only, shipped loose) SIZE ˆ 9 – 2 ½” ˆ C – 6” ˆ 0 – 3” ˆ E – 8” ˆ A – 4” SHUT-OFF VALVES (Inlet x Outlet) ˆ 1 – Less Shut-off Valves (see notes) ˆ 2 – NRS Flg x NRS Flg ˆ 3 – OS&Y Flg x OS&Y Flg ˆ 4 – OS&Y Flg x Monitored (Mon.) Butterfly Vlv Grv ˆ 6 – OS&Y Flg x Post Indicator Flg (Not in 2 ½” size) ˆ 7 – OS&Y Flg x OS&Y Grv ˆ 8 – OS&Y Grv x OS&Y Grv ˆ 9 – Mon. Butterfly Vlv Grv x Mon. Butterfly Vlv Grv ˆ 10 – OS&Y Flg x Post Indicator Grv (Not in 2 ½” size) ˆ 11 – NRS Grv x NRS Grv ˆ 12 – NRS Flg x NRS Grv FLOW ˆ N – Model DC4SGN Example: 4SG-10A-07 = 4” size with OS&Y flanged x grooved shut-off valves (shown above). Job Name: Contractor: Job Location: P.O. Number: Engineer: Representative: Tag: Wholesale Distributor: STRAINER OPTION FLOW (OPTIONAL) SIZE SHUT-OFF VALVES Model DC4SG Model DC4SGN DOUBLE CHECK VALVE Conbraco Industries, Inc. 701 Matthews Mint Hill Rd. Matthews NC 28105 USA; www.apollovalves.com; 704-841-6000 This specification is provided for reference only. Conbraco reserves the right to change any portion of this specification without notice and without incurring obligation to make such changes to Conbraco products previously or subsequently sold. SS1040 © 3/10 Page 2 of 3 DIMENSIONS (in.) – WEIGHTS (lbs.) Size 2 ½” 3" 4" 6" 8" A (Butterfly Valves)* 29 29 ½ 29 ¾ 32 ½ 43 A (Gate Valves)* 32 33 34 ½ 39 50 B (Grooved-end body) 17 17 16 ½ 18 27 C (Butterfly Valves) 8 8 ½ 9 ¼ 10 ¼ 12 C (OS&Y Open) 16 Ǫ 18 Ǭ 22 ¾ 30 ǩ 37 ¾ D (Butterfly Valves) 4 ½ 4 ½ 4 ½ 4 ½ 6 ½ D (Gate Valves) 3 ½ 3 ¾ 4 ½ 5 ½ 6 ¾ E (Butterfly Valves) 9 9 9 ½ 12 15 E (Gate Valves) 9 ǫ 10 Ǫ 11 Ǭ 14 ǫ 16 ¾ F (Butterfly Valves) 18 ½ 19 ¼ 20 ¾ 22 ½ 31 F (Gate Valves) 20 21 23 26 34 ¾ G 23 23 ¾ 24 ½ 29 40 ¾ H (Post Indicator) Not Avail.12 Ǫ 14 ¾ 19 22 ½ Test Cocks (NPT) ½ ½ ½ ¾ ¾ Net Wt. (Less Valves) 53 53 53 60 375 Net Wt. (w/ Butterfly Valves) 80 83 97 128 506 Net Wt. (w/ OS&Y Gate Valves) 149 174 208 309 852 Notes: 1. Nominal dimensions are shown. Allowances must be made for manufacturers’ tolerances. 2. Internal body connections are grooved on 2 ½” – 8” sizes. C D B A H G F F G C E C D B A E Model DC4SG Model DC4SGN DOUBLE CHECK VALVE Conbraco Industries, Inc. 701 Matthews Mint Hill Rd. Matthews NC 28105 USA; www.apollovalves.com FLOW CURVES Notes: 1. Flow curves directly reflect data collected by USC’s Foundation for Cross-Connection Control and Hydraulic Research Approval curve documents. 2. Flow curves shown were recorded with butterfly shut-off valves.* 3. All data points are based on USC increasing flow data, from zero GPM to rated flow (opening curve). 4. Refer to Apollo Model DC4S (Formerly 4S-100 Series) for 10” valve information. * Flow curves with gate valves are slightly lower. Contact factory for more information. ; 704-841-6000 This specification is provided for reference only. Conbraco reserves the right to change any portion of this specification without notice and without incurring obligation to make such changes to Conbraco products previously or subsequently sold. SS1040 © 3/10 Page 3 of 3 BERMAD Fire Protection 700 Series 700E Deluge Valve Data Description BERMAD 700E Deluge Valves are Y Type globe valves with integral unitized double chamber actuator that consists of one single moving assembly, which includes a diaphragm assembly, a flat seal disk and a stainless steel removable seat. These automatic water control valves are designed for high pressure service, in vertical or horizontal installations and are available in diameter sizes from 1½” to 16”; DN40 to DN400. The BERMAD 700E valves are used for water flow control in Deluge, Pressure Control Deluge, Preaction or Water/ Foam systems, and are manufactured from materials suitable for freshwater or alternative for seawater, foam concentrate or other corrosive fluids. The 700E Deluge Valve is held closed by system water pressure trapped in the control chamber. When the releasing system operates, pressure is released from the control chamber, and the seal disc opens to allow water to flow into the system. The 700E valve body design includes a single, full bore seat with unobstructed flow path, free of any in-line ribs, supporting cage, or stem guides. The 700E “Y Type” design provides high flow capabilities with minimum head loss. The integral unitized double-chambered actuator provides a combination of positive, immediate response with smooth hammer-free, drip-tight closing. The whole actuator can be easily removed for a quick in-line inspection and servicing. Valve actuation is accomplished by one moving assembly which includes a replaceable flat diaphragm, harnessed to the diaphragm assembly, a stainless steel stem and a flat seal disk assembly. The balanced seal-disk assembly with its resilient seal enables controlled actuation, high durability and perfect drip-tight sealing, even under harsh conditions. Accessories The BERMAD 700E Deluge Valve shall be trimmed with the original components and accessories per specification and in accordance with valve functions and applications. Where additional specifications and/or signaling devices are required for a specific application, refer to system data for the system used, and to the BERMAD data sheet and Installation, Operation & Maintenance for specific model required. Main Features ■ High Pressure Construction – 400 psi (28 bar) rating available ■ Integral unitized double chamber actuator with single moving assembly ■ In-line serviceable, field replaceable internals ■ Obstacle free, full bore ■ Available in corrosion resistant materials ■ Designed to be reset without opening the valve ■ Compatible with electric/hydraulic/pneumatic release and pressure control trim systems Approvals ■ UL Listed to UL 260 from 5 to 300 psi; 0.3 to 21 bar WP, 2” through 10”; DN50 through DN250 ■ ABS Approved for 300 psi; 21 bar WP, 1½” through 12”; DN40 through DN300 ■ Lloyd’s Register Type Approval for 300 psi; 21 bar WP, 1½” through 16”; DN40 through DN400 ■ Fire Test Certified to ISO 6182 part 5, 1½” through 16”; DN40 through DN400 Notes: 1. The 700E valve shall be trimmed with specific components & accessories. 2. The 700E valve must be installed and maintained in compliance with the most recent BERMAD publications. 1 BERMAD Fire Protection 700 Series700E Materials Specifications Construction Materials The BERMAD 700E valves are available in a variety of materials to ensure optimal suitability for a wide range of applications. For operation involving exposure to internal and/or external corrosive conditions, valves are constructed from corrosion-resistant materials making them suitable for use with seawater, brackish water, or corrosive environments such as seashore, petrochemical and other industrial facilities. Standard Configurations Item Number Description Firewater Valve 1 Cover Ductile Iron 2 Cover Bolt Stainless Steel 3 Cover Nut Stainless Steel 4 Separation Partition Ductile Iron 5 Stud Z.C. Plated Steel 6 Stud Nut Z.C. Plated Steel 7 Valve Body Ductile Iron 8 Spring S.S. 302 9 Removable Seat S.S. 304 10 Seal NBR (Buna-N) 11 Upper Plug (6-20”)Brass 12 Shaft Lock Nut S.S. 303 13 Shaft Nut S.S. 303 14 Diaphragm Washers S.S. 431 15 Diaphragm NBR (Buna-N) 16 Bearing Screw S.S. 303 17 Bearing Bronze 18 Shaft S.S. 303 19 Seal Disk S.S. 431 Specifications Castings ■ Ductile Iron to ASTM A536 65-45-12 (coated) ■ Cast Steel ASTM A216 Grade WCB (coated) ■ Nickel Aluminum Bronze ASTM B148 C95800 ■ Stainless Steel 316 ASTM A351 Grade CF8M ■ Super Duplex ASTM A890 Grade 5A ■ Hastelloy C-276 Bolting: ■ External Bolting: S.S.316 to ASTM A320 Gr.B8F Internal Wetted Parts: ■ Stainless Steel 303 ASTM A582 95B S30300A ■ Stainless Steel 304 ASTM A743 Grade CF8 ■ Stainless Steel 431 ASTM A743 Grade CA15M ■ Bronze ASTM B505 Grade C83600 ■ Internal Spring - S.S. 302 Optional Internal Wetted Parts: ■ Stainless Steel 316 ASTM A351 Grade CF8M ■ Nickel Aluminum Bronze ASTM B148 C95800 ■ Monel 400 ■ Super Duplex ASTM A890 Grade 5A ■ Hastelloy C-276 ■ Internal Spring - Inconel Elastomers (Diaphragm & Seals) ■ NBR, Polyamide fabric reinforced Nitrile (Buna-N), Temperature Rating 80°C ■ EPDM, Polyamide fabric reinforced Ethylene-Propylene, Temperature Rating 90°C Coating ■ Electrostatic Powder Coating Polyester ■ High Built Epoxy Fusion-Bonded with UV Protection, Anti-Corrosion ■ Color: Fire Red to RAL 3002 Note: Internal & External coating applied on Ductile Iron or Cast Steel Castings only. Material End Connection StandardInlet & Outlet Class & Type Max. working pressure psi bar Ductile Iron Flanged ANSI B16.42 #150RF 250 17.4 Flanged ANSI B16.42 #300RF 400 28 Flanged ISO 7005-2 PN 16 235 16 Flanged ISO 7005-2 PN 25 365 25 Grooved ANSI C606 300 400 25 Threaded BSP/NPT 300/PN25 400 25 C.Steel, SS316, Duplex & Hastelloy Flanged ANSI B16.5 #150RF 250 17.4 Flanged ANSI B16.5 #300RF 400 28 Flanged ISO 7005-2 PN16 235 16 Flanged ISO 7005-2 PN25 365 25 Threaded BSP/NPT 300/PN25 400 25 Ni-Al Bronze Flanged ANSI B16.24 #150RF 250 17.4 Flanged ANSI B16.24 #300RF 400 28 Flanged ISO 7005-2 PN 16 235 16 Flanged ISO 7005-2 PN25 365 25 Notes 1. Factory pressure testing: Each valve is tested at 1.6 of pressure rating.2. Water Temperature: 0.5 - 80ºC (33 - 122ºF)3. Standard flange facing: Raised Face (RF), Serrated Finish. Flat Face (FF) flanges available on request. Pressure Rating 2 1 2 3 4 5 6 7 8 9 10 9 19 18 17 16 15 14 13 12 11 BERMAD Fire Protection 700 SeriesFP 700E Flow & Hydraulic Data gpm Flow RatePressure Loss0.1 1.0 10 100 1,000 0.5 40 65 50 500 5,000 psi 15.0 12.5 10.0 7.5 5.0 2.5 1.5 50 75 100 250 500 750 1,000 2,500 20,00015,00010,0005,000 7,500 m3/h bar 11/2”21/2” 2” 50 80 3” 100 4” 150 6” 200 8” 250 10” 300 12” 350 14” 400 16” Flow Chart Flow Properties DN 40-50 65 80 100 150 200 250 300 350 400 Inch 1½"-2”2½"3"4"6"8"10"12"14"16"“Y”-TypeKv-Y 50 55 115 200 460 815 1,250 1,850 1,990 3,310 Cv-Y 58 64 133 230 530 940 1,440 2,140 2,300 3,820 K-Y 3.9 9.2 4.9 3.9 3.7 3.8 3.9 3.7 5.9 3.7 Leq-m, Y 10.3 33.4 21.6 23 37.5 53.9 70 85.6 159.9 112.7 Leq-feet, Y 33.8 109.5 70.8 75.6 123 176.9 229.5 280.8 524.5 369.6 AngleKv-A 55 61 127 220 506 897 1,375 2,035 2,189 3,641 Cv-A 64 70 146 250 580 1,040 1,590 2,350 2,530 4,210 K-A 3.2 7.6 4.0 3.2 3.1 3.1 3.2 3.1 4.9 3.0 Leq-m, A 8.5 27.6 17.8 19.0 37.0 44.6 57.8 70.7 132.1 93.1 Leq-feet, A 28 90.5 58.5 62.5 101.6 146.2 189.7 232 433.4 305.5 Valve flow coefficient, Kv or Cv Equivalent Pipe Length, Leq Flow resistance or Head loss coefficient, Cv = 1.155 Kv Where:Kv = Valve flow coefficient (flow in m3/h at 1bar Diff. Press.)Cv = Valve flow coefficient (flow in gpm at 1psi Diff. Press.)Q = Flow rate (m3/h ; gpm) ∆P = Differential pressure (bar ; psi) Gf = Liquid specific gravity (Water = 1.0) Kv(Cv)=Q Gf ∆P Leq=Lk.D K=∆H 2g V2Where:K = Flow resistance or Head loss coefficient (dimensionless) ∆H = Head loss (m ; feet)V = Nominal size flow velocity (m/sec ; feet/sec.)g = Acceleration of gravity (9.81 m/sec2 ; 32.18 feet/sec2) Where:Leq = Equivalent nominal pipe length (m ; feet)Lk = Equivalent length coefficient for turbulent flow in clean commercial steel pipe (SCH 40)D = Nominal pipe diameter (m; feet) Note: The Leq values given are for general consideration only. Actual Leq may vary somewhat with each of the valve sizes. 3 BERMAD Fire Protection 700 SeriesFP 700E Dimensions & Weights Size DN mm (inch)40 (1½”)50 (2”)65 (2½”)80 (3”)100 (4”)150 (6”)200 (8”)250 (10”)300 (12”)350 (14”)400 (16”)ANSI #150, ISO PN 16L (mm)10 205 222 250 320 415 500 605 725 733 990 LG(4)(mm)---250 320 415 500 ---- W (mm) 165 165 178 200 223 320 390 480 550 550 740 R (mm) 78 83 95 100 115 143 172 204 242 268 300 La (mm) 124 124 149 152 190 225 265 320 396 400 450 ha (mm) 85 85 109 102 127 152 203 219 273 279 369 Hy (mm) 239 244 257 305 366 492 584 724 840 866 1,108 Ha (mm) 227 227 241 281 342 441 545 633 777 781 1,082 Weight Y (kg) 10.6 10.6 13 22 37 75 125 217 370 381 846 Weight A (kg) 10 10 12 21.5 35 71 118 205 350 370 800 ANSI #300, ISO PN 25L (mm)210 210 222 264 335 433 524 637 762 767 1,024 W (mm) 165 165 185 207 250 320 390 480 550 570 740 R (mm) 78 83 95 105 127 159 191 223 261 295 325 La (mm) 124 124 149 159 200 234 277 336 415 419 467 ha (mm) 85 85 109 109 127 165 216 236 294 299 386 Hy (mm) 239 244 257 314 378 508 602 742 859 893 1,133 Ha (mm) 227 227 251 287 650 454 558 649 796 801 1,099 Weight Y (kg) 12.2 12.2 15 25 43 85 146 245 410 434 900 Weight A (kg) 11.5 11.5 13.5 23 41 81 138 233 390 421 855 Portsa (1) (mm)½½½½½½½½½½½ b (1) (mm) ½½½½½½½½½½½ c (1) (mm) ¾¾¾¾¾2 2 2 2 2 2 d (2) (optional)(mm) ¾¾1½1½2 2 2 2 2 2 2 Control Vol. (3)(Liter) 0.125 0.125 0.125 0.3 0.45 2.15 4.5 8.5 12.4 12.4 29.9 MetricSi Flanged d L & LG R Hy a cb a La Ha a ha cb a b c W b c Y Body Type Angle Body Type (1) (a), (b), (c) are NPT thread ports (2) (d) is BSPT threaded Optional drain port (3) (Control Volume) is Control Chamber Displacement Volume of liquid pushed when valve opens (4) LG for Grooved ends (see available sizes) 4 BERMAD Fire Protection 700 SeriesFP 700E Dimensions & Weights Size (inch)1½”2”2½”3”4”6”8”10”12”14”16”ANSI #150, ISO PN 16L (inch)8.1 8.1 8.3 9.8 12.6 16.3 19.7 23.8 28.5 28.9 39.0 LG(4)(inch)---9.8 12.6 16.3 19.7 ---- W (inch) 6.1 6.1 7.0 7.9 8.8 12.6 15.4 18.9 21.7 21.7 29.1 R (inch) 3.1 3.3 3.7 3.9 4.5 5.6 6.8 8.0 9.5 10.6 11.8 La (inch) 4.9 4.9 5.9 6.0 7.5 8.9 10.4 12.6 15.6 15.7 17.7 ha (inch) 3.3 3.3 4.3 4 5 6 8 8.6 10.7 11 14.5 Hy (inch) 9.4 9.6 10.1 12 14.4 19.4 23 28.5 33.1 34.1 43.6 Ha (inch)8.9 8.9 9.9 11.1 13.5 17.4 21.5 24.9 30.6 30.7 42.6 Weight Y (Lbs.)23 23 29 49 82 165 276 478 816 840 1,865 Weight A (Lbs.) 22 22 27 47 77 157 260 452 772 216 1,764 ANSI #300, ISO PN 25L (inch)8.3 8.3 8.7 10.4 13.2 17 20.6 25.1 30 30.2 40.3 W (inch) 6.5 6.5 7.3 8.1 9.8 12.6 15.4 18.9 21.7 22.4 29.1 R (inch) 3.1 3.3 3.7 4.1 5 6.3 7.5 8.8 10.3 11.6 12.8 La (inch) 4.9 4.9 5.9 6.3 7.9 9.2 10.9 13.2 16.3 16.5 18.4 ha (inch) 3.3 3.3 4.3 4.3 5.3 6.5 8.5 9.3 11.6 11.8 15.2 Hy (inch) 9.4 9.6 10.1 12.4 14.9 20 23.7 29.2 33.8 35.2 44.6 Ha (inch)8.9 8.9 9.9 11.3 13.8 17.9 22 25.6 31.3 31.5 43.3 Weight Y (Lbs.) 27 27 33 55 95 187 322 540 904 957 1,984 Weight A (Lbs.) 25 25 30 51 90 179 304 514 860 928 1,88 Portsa (1) (inch)½½½½½½½½½½½ b (1) (inch) ½½½½½½½½½½½ c (1) (inch) ¾¾¾¾¾2 2 2 2 2 2 d (2) (optional)(inch) ¾¾1½1½2 2 2 2 2 2 2 Control Vol. (3)(Gal.) 0.04 0.04 0.04 0.08 0.12 0.57 1.19 2.25 3.28 3.28 7.88 EnglishUS Flanged d L & LG R Hy a cb a La Ha a ha cb a b c W b c Y Body Type Angle Body Type (1) (a), (b), (c) are NPT thread ports (2) (d) is BSPT threaded Optional drain port (3) (Control Volume) is Control Chamber Displacement Volume of liquid pushed when valve opens (4) LG for Grooved ends (see available sizes) 5 BERMAD Fire Protection 700 SeriesFP 700E Installation, Operation & Maintanence Electric Pneumatic Hydraulic Electric Pneumatic Hydraulic Valve Closed (Set Position) Line pressure applied to the upper control chamber of the valve creates a superior force that moves the valve to the closed position and provides drip tight sealing. Valve Open (Operating Conditions) Releasing the pressure from the upper control chamber to atmosphere or some other lower pressure zone causes the line pressure acting on the seal disc to move the valve to the open position. Proper operation of the 700E Deluge Valves depends upon their trim being installed in accordance with the appropriate trim configuration. Notes: ■ Wet pilot height should not exceed “Maximum Elevation Above Valve” (see data for specific model). ■ Any deviation in trim size or arrangement may adversely affect the proper operation of the deluge valve. ■ All the pilot system devices, must be UL Listed and compatible with the particular deluge system. Refer to current “UL Listed Fire Protection Equipment Directory”. Warning: The deluge valve and trim must be installed only in areas where they will not be subject to freezing temperatures. Installation Instructions 1. Allow enough room around the valve assembly for any adjustments and future maintenance. 2. Before the valve is installed, flush the pipeline to remove any dirt, scale, debris, etc. Not flushing the line may result in the valve’s becoming inoperable. 3. Install the valve in the pipeline so that the valve flow arrow appearing on the body casting is pointing in the desired direction. Ensure that the valve is positioned so that the actuator assembly can be easily removed for future maintenance. 4. Ensure that the Control Trim is mounted properly and all other components are positioned correctly as per illustration. 5. After installation in the main line, carefully inspect/ correct any damaged accessories, piping, tubing, or fittings. Ensure that there are no leaks. 6. Install the components comprising the Deluge Trim Package in their proper positions in compliance with all instructions, drawings, and technical specifications describing the BERMAD Deluge Valve, according to the relevant illustration. 7. All additional accessories, although not packed together with the BERMAD Deluge Valve, must be installed as shown in the relevant P&ID and other illustrations. Operation Principle of Operation The BERMAD 700E Deluge Valve (assembled with specific trim) is suitable for systems that include adequate detecting and piping systems with open nozzles. The deluge valve prevents water from entering system piping until required. The deluge valve is kept closed by pressure applied to the upper control chamber through a restricted priming line. In the SET position, the water pressure supplied through the priming line is trapped in the upper control chamber of the deluge valve by a check valve, and by the normally closed release device. The pressure trapped in the upper control chamber of the deluge valve presses the valve seal disk down, thereby sealing the valve and keeping the system piping dry. Under conditions of FIRE, when the pressure is released from the upper control chamber by the opening of the automatic releasing device or by manual release, the deluge valve opens and allows the inlet supply water to flow through the valve and into the system piping and alarm devices. Warning: Whenever the handle of the Manual Emergency Release is pulled, pressure is released from the upper control chamber, the deluge valve will open, and water will flow into system piping and alarm devices. Installation 6 BERMAD Fire Protection 700 SeriesFP 700E Installation, Operation & Maintanence Placing in Service/Resetting The deluge valve and the control trim shall be Placed in Service with accordance to the most recent IOM procedures for the specific model. After all relevant instructions are performed, slowly open the supply-isolating valve and check that no water flows into the system. The system is now operational and in stand-by mode. Maintenance Bermad Deluge Valves require no lubrication, no packing tightening, and require a minimum of maintenance. Removing the System from Service Warning: When taking a deluge system out of service, a fire patrol should be established in the system area. If automatic fire alarm signaling equipment is utilized, the proper authority should be notified that the system is being removed from service. The insuring body and owner’s representative should also be notified when the system is being taken out of service. Removal Instructions 1. Shut off the main supply-isolating valve. 2. Close the priming line valve to the deluge valve control chamber. 3. Open all drain valves. 4. Release the water pressure from the control chamber of the deluge valve by pulling the manual emergency release. 5. Place "Fire Protection System Out of Service" signs in the area protected by the system. Inspection and Testing 1. Warning:Do not turn off the water supply to make repairs without placing a roving fire patrol in the area covered by the system. The patrol should continue until the system is back in service. 2. Prior to turning off any valves or activating any alarms, notify local security guards and the central alarm station, if used, to avoid signaling a false alarm. 3. The deluge valve and the control trim shall be maintained with accordance to the most recent IOM procedures for the specific model. A periodic test schedule should be established also with accordance to the site conditions and owner regulations. 4. Take all additional measures as required by NFPA-25 “standard for the inspection, testing, and maintenance of water-based fire protection systems”. 5. The system should be checked weekly for “Normal Conditions”. 6. Clean the priming strainer prior to any resetting of the deluge valve. 7. The deluge valve must be activated at full flow at least annually. Take all necessary precautions to drain water and prevent damage in the area protected by the system. 8. After about five years of operation, replacement of diaphragm and other elastomers is recommended. Remove the actuator and disassemble it. Clean the seat area from sediments, clean the control tubing entry holes, and install a new diaphragm and other elastomers in place. Spare Parts 1. The Diaphragm and the Seals are the only spare parts needed for the main deluge valve, see attached “Valve Disassembly and Parts Breakdown” illustration. 2. It is not recommended to store spare rubber parts for long periods (rubber in improper storage conditions can harden and crack). 3. Contact your Bermad representative and order new rubber parts when required. 7 BERMAD Fire Protection 700 Series Bearing Assembly Shaft Diaphragm Washer O-Ring Diaphragm Spacer Disk Diaphragm Washer Nut Indicator Lock Nut Cover Disk Bolt Cover Plug (6” and up) O-Ring Eye Nut Bearing Screw Disk Separation Partition Bolt Stud Nut Locking Screw Seal Disk Assembly Seal Disk Wash. Screw Seal SealDisk O-Ring Spring Nut Actuator Assembly Screw Removable Seat Nut Y Body Type Angle Body Type FP 700E Parts Valve Disassembling Parts Breakdown bermadfire@bermad.com • www.bermad.com © Copyright 2007-2012 Bermad CS Ltd. All Rights Reserved. The information contained in this document is subject to change without notice. BERMAD shall not be liable for any errors contained herein. PT7PE04-DATA 09.2012 8 S 5 - 2 SCHEDULE-10/40 W ith ABF P rotection W ith AB F Pr otection S5 - 3 Galvanized Pipe Superior Coating Specifications & Approvals American Made Schedule-10/Schedule-40 product can be “hot-dip” galvanized to meet FM requirements for dry systems in accordance with the zinc coating specifications of ASTM A-123. Our advanced formula mill coating of- fers a clean, durable surface. It is also paint-ready for custom color applications without special preparation. The internal surface of all black Allied Tube & Conduit Fire Sprinkler pipe products up to 4.5000” in diameter is coated with our new Antibacterial For- mula, “ABF”. In scientific laboratory test, ABS proved to have superior resis- tance to microbial colonization of pipe walls, thereby delaying or possibly pre- venting the onset of Microbiologically Influenced corrosion (MIC) when the First Sprinkler System is first installed. When you specify Schedule-10/Schedule-40 sprinkler pipe you get a UL listed and FM approved product. Although these products do not require separate approvals, Schedule-10/Schedule-40 gives you the extra quality assurance you demand. Our Sch-10 (11⁄4"– 8") pipe and Sch-40 (1"– 21⁄2") pipe have passed the same thorough lab testing as our other listed pipe products, and receive periodic mill inspections from both UL and FM agents to ensure consistent quality. Fully Listed and FM Approved Sprinkler Pipe Schedule-10®/Schedule-40® Meets “Buy American” requirement and is available through distributors in the USA, Canada and Mexico. Schedule-10/Schedule-40 pipe are in compliance with the following: ASTM A-135, and NFPA 13. Both pipe products have a working pressure rating of 300 psi maximum and also meet the stringent requirement for the following tests: • Welded Outlets • Hydrostatic Pressure • Side Wall Rupture • Vibration Test Sch-40 Specifications NPS Nominal I.D. Wt. Wt. (H2O Filled) Pcs/ Wt/Lift (21')Wt/Lift (24')Wt/Lift (25') In; mm In; mm Lbs/Ft; Kg/m Lbs/Ft; Kg/m Lift Lbs; Kg Lbs; Kg Lbs; Kg 1" 1.049 1.680 2.05 70 2,470 2,822 2,940 25 26.6 2.5 3.05 70 1,120 1,280 1,334 11⁄4" 1.380 2.270 2.93 51 2,431 2,778 2,894 32 35.1 4.36 4.36 51 1,103 1,260 1,313 11⁄2" 1.610 2.720 3.61 44 2,513 2,872 2,992 40 40.9 4.0 5.37 44 1,140 1,303 1,357 2" 2.067 3.650 5.13 30 2,300 2,628 2,738 50 52.5 5.4 7.63 30 1,043 1,192 1,242 21⁄2" 2.469 5.790 7.86 19 2,310 2,640 2,750 65 62.7 8.6 11.73 19 1,048 1,197 1,247 Sch-10 Specifications NPS Nominal I.D. Wt. Wt. (H2O Filled) Pcs/ Wt/Lift (21')Wt/Lift (24')Wt/Lift (25') In; mm In; mm Lbs/Ft; Kg/m Lbs/Ft; Kg/m Lift Lbs; Kg Lbs; Kg Lbs; Kg 1" 1.097 1.400 1.81 91 2,675 3,053 3,185 25 27.9 2.1 2.70 91 1,213 1,385 1,445 11⁄4" 1.442 1.810 2.52 61 2,319 2,664 2,760 32 36.6 2.7 3.75 61 1,052 1,208 1,252 11⁄2" 1.682 2.080 3.04 61 2,664 3,045 3,172 40 42.7 3.1 4.52 61 1,208 1,381 1,439 2" 2.157 2.640 4.22 37 2,051 2,344 2,442 50 54.8 3.9 6.28 37 930 1,063 1,108 21⁄2" 2.635 3.530 5.89 30 2,224 2,542 2,648 65 66.9 5.3 8.77 30 1,009 1,153 1,201 3" 3.260 4.330 7.94 19 1,728 1,975 2,057 80 82.8 6.4 11.82 19 784 896 933 4" 4.260 5.610 11.78 19 2,238 2,558 2,665 90 108.2 8.3 17.53 19 1,015 1,160 1,209 5" 5.295 7.77 17.33 10 1,632 1,865 1,943 125 134.5 11.56 25.80 10 740 846 881 6" 6.357 9.290 23.03 10 1,951 2,230 2,322 150 161.5 13.8 34.27 10 885 1,012 1,053 8" 8.249 16.490 40.15 7 2,424 2,770 2,885 200 209.5 24.5 59.75 7 1,100 1,256 1,309 FM Listed Approved Listed 16100 S. Lathrop • Harvey, IL 60426 11350 Norcom Rd. • Philadelphia, PA 19154 2525 N. 27 th Ave. • Phoenix, AZ 85009 Customer Service: (800) 882-5543 Fax 708-339-1806 Eddy Flow The Cost Effective Replacement for Schedule 10 Realizing the growing need of fire protection systems in commercial and residential construction, Bull Moose Tube has added Eddy Flow to its comprehensive line of sprinkler pipe products. Eddy Flow is a specially engineered replacement for schedule 10, offering better flow characteristics while providing design flexibility. This product is FM approved, as well as UL listed (for U.S. and Canada) for roll grooving and welding for use in fire protection systems with a working pressure of 300 psi or less. Please check with appropriate sources for up-to-date listings and approval information. As an added benefit, it is more economical to use than schedule 10 due to reduced delivery costs and ease of handling. Furthermore, Eddy Flow’s larger ID provides an opportunity for downsizing and further cost savings. COMPARISON INSIDE DIAMETER C.R.R.* Nominal Pipe Size (in) O.D. (in) Eddy Flow (in) Schedule 10 (in) Schedule 40 (in) Eddy Flow Schedule 40 1 1/4 1.660 1.530 1.442 1.380 1.98 1.00 1 1/2 1.900 1.728 1.682 1.610 3.44 1.00 2 2.375 2.203 2.157 2.067 2.78 1.00 2 1/2 2.875 2.705 2.635 2.469 1.66 1.00 3 3.500 3.334 3.260 3.068 1.00 1.00 4 4.500 4.310 4.260 4.026 1.00 1.00 * Corrosion Resistance Ratio BENEFITS • Dual Certified to ASTM A135 and A795. • FM Approved for roll grooved, and welded, and plain-end application in wet systems. • UL Listed (for U.S. and Canada) for joining by welding or by listed rubber gasketed fittings for use in wet, dry, preaction, and deluge type sprinkler systems. • UL Listed (for US and Canada) and FM Approved for use with Victaulic® FIT® Fittings in plain end applications. • Lightweight - saves shipping costs, and offers easier handling. • Can be used with roll grooved couplings or welded outlets for pressures up to 300 psi. • Floor stock available in various lengths produced in Casa Grande (AZ), Gerald (MO), and Masury (OH). Also can be ordered in custom lengths.. • Can be used for wet and dry* systems. * Eddy Flow can be hot dipped galvanized to meet FM’s requirement for dry systems. PIPE PREPARATION For proper operation, all pipe surfaces should be cleaned prior to installation. In order to provide a leak-tight seat for the gasket, pipe surfaces should be free from indentations and projections from the end of the pipe to the groove. All loose paint, scale, dirt, chips, grease, and rust must be removed prior to installation. Failure to take these important steps may result in improper coupling assembly, causing leakage. Also, check the manufacturer’s instructions for the specific fitting used. A company 1819 Clarkson Road Chesterfield, MO 63017 (800) 325-4467 FAX: (636) 537-2645 www.bullmoosetube.com e-mail:sales@bullmoosetube.com For additional information, contact your salesperson today at (800) 325-4467 or (636) 537-2600 in the USA, or from Canada call (800) 882-4666 All information contained herein is accurate as known at the time of publication. Bull Moose Tube reserves the right to change product specifications without notice and without incurring obligation. 8/08 S2 - 2 DYNA-FLOW® With ABF Protection With ABF Protection S2 - 3 Additional BenefitsSpecifications & Approvals Superior Hydraulics Coatings & Fabrication • Lightweight and easy to install, resulting in more efficient use of your freight and labor dollars. • Provides stability needed to comply with standard hanger spacing (15 ft O.C.) per NFPA. • Available in Standard lengths for your convenience, or can be ordered in custom lengths upon approval. • Fast cutting and welding, as well as easy roll grooving and end preparation. • Available in Factory roll grooved form for quicker shop turnaround. • Clean, durable mill coating provides longer “shelf life” and acts as an excellent primer for custom paint applications. Dyna-Flow/Super Flo pipe is manufac- tured to meet ASTM A-795 Type E, Grade A and is in compliance with NFPA-13 and NFPA-14. All sizes of Dyna Flow/Super Flo are UL Listed, FM Approved and ULC Listed. Dyna-Flow/Super Flo is UL/ULC Listed for use with roll grooved, plain-end couplings, and welded joints for wet, dry, preaction and deluge systems. It is FM Approved for roll grooved, plain-end, and welded joints for wet systems. Refer to appropriate documentation for up-to-date listing and approval information. Dyna- Flow/Super Flo is now available “hot- dip” galvanized and has been specifically approved by FM for dry systems uses. Dyna-Flow products are coated with an environmentally approved and specially formulated modified-acrylic or water-based coating. This durable coating is paintable. The black coating acts as an excellent primer and is resistant to weathering and U.V. degradation from outdoor storage. Metallurgical properties provide excellent fabrication characteristics for end prep finishes, welding and roll grooving. There is no special process or equipment needed for fabrication and installation. The internal surface of all black Allied Tube & Conduit Fire Sprinkler pipe products up to 4.5000” in diameter is coated with our new Antibacterial Formula, “ABF”. In scientific laboratory test, ABS proved to have superior resistance to microbial colonization of pipe walls, thereby delaying or possibly preventing the onset of Microbiologically Influenced corrosion (MIC) when the First Sprinkler System is first installed. With an inside diameter of up to 11% larger than Schedule-40 and up to 7% larger than Schedule-10, Dyna-Flow pipe hydraulics are exceptional. Larger I.D.s enable Dyna-Flow, and related components, to be down-sized within the system, thus increasing the potential for job cost savings. For complete Hazen- Williams charts, refer to “Dyna-Flow Hydraulic Data Tables.” Dyna-Flow pipe is the “original” high- strength lightwall sprinkler pipe. Dyna- Flow has outstanding hydraulic capabilities and is recognized as the most popular alternative to Schedule-10 pipe. Lightweight, easy to cut and easy to handle for installation. Dyna-Flow is a valuable addition to any fire protection system. Dyna-Flow® High Strength Steel Pipe The original high-strength lightwall sprinkler pipe with hydraulics superior to Schedule-10. FM Listed Approved Listed Specifications NPS Nominal I.D. Wt. Wt. (H2O Filled) Pcs/ Wt/Lift (21')Wt/Lift (24')Wt/Lift (25') In; mm In; mm Lbs/Ft; Kg/m Lbs/Ft; Kg/m Lift Lbs; Kg Lbs; Kg Lbs; Kg 1" 1.191 0.830 1.31 91 1,586 1,812 1,888 25 30.3 1.2 1.95 91 719 822 856 11⁄4" 1.536 1.059 1.87 61 1,356 1,550 1,615 32 39.0 1.6 2.78 61 615 703 733 11⁄2" 1.728 1.667 2.71 61 2,135 2,440 2,542 40 43.9 2.5 4.03 61 968 1107 1153 2" 2.203 2.104 3.79 37 1,634 1,868 1,946 50 56.0 3.1 5.64 37 741 847 883 21⁄2" 2.703 2.564 5.10 30 1,615 1,846 1,923 65 68.7 3.8 7.59 30 733 837 872 3" 3.314 3.387 7.18 19 1,351 1,544 1,608 80 84.2 5.0 10.69 19 613 700 729 4" 4.310 4.473 10.86 19 1,784 2,039 2,124 90 109.5 6.7 16.16 19 809 925 963 16100 S. Lathrop • Harvey, IL 60426 11350 Norcom Rd. • Philadelphia, PA 19154 2525 N. 27 th Ave. • Phoenix, AZ 85009 Customer Service: (800) 882-5543 Fax 708-339-1806 FireLock® products comprise a unique system specifically designed for fire protection services. FireLock full-flow elbows and tees are a CAD-developed, hydrodynamic design that has a shorter center-to-end dimension than standard fittings. A noticeable bulge allows the water to make a smoother turn to maintain similar flow characteristics as standard full flow fittings. FireLock fittings are designed for use exclusively with Style 005 and Style 009 FireLock couplings. Use of other couplings or flange adapters may result in bolt pad interference. Victaulic FireLock fittings pressure ratings conform to the ratings of Victaulic FireLock Style 005 couplings. Fitting: Ductile iron conforming to ASTM A-536, grade 65-45-12. Fitting Coating: Orange enamel. • Optional: Hot dipped galvanized. MATERIAL SPECIFICATIONS 10.03_1 FireLock® Fittings 10.03IPS CARBON STEEL PIPE – FIRE PROTECTION PRODUCTS JOB/OWNER CONTRACTOR ENGINEER System No. __________________________Submitted By ________________________Spec Sect ____________ Para __________ Location ____________________________Date ________________________________Approved ___________________________ Date ________________________________ www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2009 VICTAULIC COMPANY. ALL RIGHTS RESERVED. REV_H See Victaulic publication 10.01 for details VNIIPO DIMENSIONS C to E Cto E NO. 001 C to E NO. 003 Cto E CtoE NO. 002 T NO. 006 Size No. 001 90° Elbow No. 003 45° Elbow No. 002 Straight Tee No. 006 Cap Nominal Size Inchesmm Actual Outside Diameter Inchesmm C to E Inchesmm Approx. Weight Each Lbs.kg C to E Inchesmm Approx. Weight Each Lbs.kg C to E Inchesmm Approx. Weight Each Lbs.kg Thickness “T” Inchesmm Approx. Weight Each Lbs.kg 1 1/4 1.660 ——————0.8 0.33242.4 21 0.1 1 1/2 1.900 ——————0.82 0.44048.3 ——————21 0.2 2 2.375 2.75 1.7 2.00 1.8 2.75 2.4 0.88 0.65060.3 70 0.8 51 0.8 70 1.1 22 0.3 2 1/2 2.875 3.00 3.1 2.25 2.2 3.00 3.6 0.88 1.06573.0 76 1.4 57 1.0 76 1.6 22 0.5 76.1 mm 3.000 3.00 3.30 2.25 2.4 ————76.1 76 1.5 57 1.1 3 3.500 3.38 4.0 2.50 3.1 3.38 5.3 0.88 1.28088.9 86 1.8 64 1.4 86 2.4 22 0.5 108 mm 4.250 4.00 5.7 3.00 5.1 4.00 7.5 ——108.0 102 2.6 76 2.3 102 3.4 4 4.500 4.00 6.7 3.00 5.6 4.00 8.7 1.00 2.4100114.3 102 3.0 76 2.5 102 3.9 25 1.1 5 5.563 4.88 12.6 3.25 8.3 4.88 15.7 1.00 4.1125141.3 124 5.7 83 3.8 124 7.1 25 1.9 159 mm 6.250 5.50 12.6 3.50 9.2 5.50 17.9 ——158.8 140 5.7 89 4.2 140 8.0 6 6.625 5.50 18.3 3.50 11.7 5.50 22.7 1.00 5.9150168.3 140 8.3 89 5.3 140 10.3 25 2.7 8 8.625 6.81 25.5 4.25 20.4 6.94 38.7 1.13 12.7200219.1 173 11.6 108 9.3 176 17.6 29 5.8 10.03_2 FireLock® Fittings 10.03IPS CARBON STEEL PIPE – FIRE PROTECTION PRODUCTS www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2009 VICTAULIC COMPANY. ALL RIGHTS RESERVED. REV_H FLOW DATA Size Frictional ResistanceEquivalent Feet/meters of Straight Pipe † Nominal Size Inchesmm Actual Outside Diameter Inchesmm Elbows No. 002 Straight Tee No. 001 90° Elbow No. 003 45° Elbow Branch Run 1 1/4 1.660 1.5 0.8 3.7 1.53242.4 0.5 0.2 1.1 0.5 1 1/2 1.900 2.2 1.1 5.5 2.24048.3 0.7 0.3 1.7 0.7 2 2.375 3.5 1.8 8.5 3.55060.3 1.1 0.5 2.6 1.1 2 1/2 2.875 4.3 2.2 10.8 4.36573.0 1.3 0.7 3.3 1.3 76.1 mm 3.000 4.5 2.3 11.0 4.576.1 1.4 0.7 3.4 1.4 3 3.500 5.0 2.6 13.0 5.08088.9 1.5 0.8 4.0 1.5 108 mm 4.250 6.4 3.2 15.3 6.4108.0 2.0 0.9 4.7 2.0 4 4.500 6.8 3.4 16.0 6.8100114.3 2.1 1.0 4.9 2.1 5 5.563 8.5 4.2 21.0 8.5125141.3 2.6 1.3 6.4 2.6 159 mm 6.250 9.4 4.9 25.0 9.6158.8 2.9 1.5 7.6 2.9 6 6.625 10.0 5.0 25.0 10.0150168.3 3.0 1.5 7.6 3.0 8 8.625 13.0 5.0 33.0 13.0200219.1 4.0 1.5 10.1 4.0 † The flow data listed is based upon the pressure drop of Schedule 40 pipe. 10.03_3 FireLock® Fittings 10.03IPS CARBON STEEL PIPE – FIRE PROTECTION PRODUCTS www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2009 VICTAULIC COMPANY. ALL RIGHTS RESERVED. REV_H WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details. This product shall be manufactured by Victaulic or to Victaulic specifications. All products to be installed in accordance with current Victaulic installation/assembly instructions. Victaulic reserves the right to change product specifications, designs and standard equipment without notice and without incurring obligations. NOTE NOTE: When assembling FireLock EZ couplings onto end caps, take additional care to make certain the end cap is fully seated against the gasket end stop. For FireLock EZ Style 009 and Style 009V couplings, use FireLock No. 006 end caps containing the “EZ” marking on the inside face or No. 60 end caps containing the “QV EZ” marking on the inside face. Non-Victaulic end cap products shall not be used with Style 009/009V couplings. GENERAL NOTES WCAS-7MX2JY 10.03 FireLock® Fittings IPS CARBON STEEL PIPE – FIRE PROTECTION PRODUCTS For complete contact information, visit www.victaulic.com 10.03 1539 REV H UPDATED 1/2009 VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2009 VICTAULIC COMPANY. ALL RIGHTS RESERVED. 10.03 FireLock® Style 005 rigid coupling has a unique, patented angle-pad design which allows the housings to offset while clamping the grooves. By permitting the housings to slide on the angled bolt pads, rigidity is obtained. Support and hanging requirements correspond to NFPA 13 Sprinkler Systems. Angle-pad design permits assembly by removing one nut/bolt and swinging the housing over the gasket. This reduces components to handle during assembly. Style 005 FireLock coupling are designed and recommended for use ONLY on fire protection systems. Vic-Plus™ Gasket System: In North America, Victaulic® offers a gasket system which requires no field lubrication on wet pipe systems that are hydrostatically tested. The Vic-Plus™ System (patented) is dry, clean, and non-toxic. It reduces assembly time substantially and eliminates the mess and chance of over- lubrication. Please refer to the latest copy of the Victaulic Field Installation Handbook (I-100) for supplemental lubrication requirements and dry pipe fire protection system notes. LISTING/APPROVALS The information provided below is based on the latest listing and approval data at the time of publication. Listings/Approvals are subject to change and/or additions by the approvals agencies. Contact Victaulic for performance on other pipe and the latest listings and approvals. Related Working Pressure – psi Related Working Pressure – psi Related Working Pressure – psi Pipe Sch. Size Inches UL ULC FM Pipe Sch. Size Inches UL ULC FM Pipe Sch. Size Inches UL ULC FM 51 ¼ – 3 175 175 175 EL 1 ¼ – 2 300 N/A N/A MT 1 ¼ – 2 300 N/A N/A 10, 40 1 ¼ – 4 350 350 350 ET 1 ¼ – 2 300 N/A N/A STF 1 ¼ – 4 N/A N/A 300 5 – 8 300 300 300 EZ 4 – 6 300# N/A 300 Steady Thd.1 ¼ – 2 N/A N/A 300 BLT 1 ¼ – 2 300 300 N/A FF 1 ¼ – 4 N/A N/A 300 TF 3 – 8 N/A N/A 300 DF 1 ¼ – 4 300 300 300 GAL - 7 1 ¼ – 2 300 N/A N/A WLS 1 ¼ – 2 300 300 N/A DT 1 ¼ – 2 300 300 N/A MLT 1 ¼ – 2 300 N/A N/A XL 1 ¼ – 3 300 300 300 EF 1 1⁄ – 4 175@ N/A 175 MF 1 ¼ – 4 300 N/A 300* * FM approved for service in 1 ½ – 4" pipe. # UL Listed for service up to 4" pipe only. @ UL Listed for service up to 3" only. 10.02_1 FireLock® Rigid Coupling STYLE 005 WITH VIC-PLUS™ GASKET SYSTEM (NORTH AMERICA ONLY) 10.02IPS CARBON STEEL PIPE - FIRE PROTECTION PRODUCTS JOB/OWNER CONTRACTOR ENGINEER System No. __________________________ Submitted By ________________________ Spec Sect ____________ Para __________ Location ____________________________ Date ________________________________ Approved ___________________________ Date ________________________________ www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2006 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA. REV_I SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS § LPC and VdS Approved, see notes on page 4 PATENTED Exaggerated for clarity DIMENSIONS Size Max. Work Pressure § * Max. End Load * Allow. Pipe End Sep. † Bolt/Nut@ No – Size Dimensions – Inches/mm Approx. Wgt. Each Nominal Size Inches/mm Actual Outside Diameter Inches/mm PSI kPa Lbs. N Inches mm Inches mm XYZ Lbs. kg 1 ¼ 1.660 350 755 0.05 2 – 3⁄8 x 2 ¼ 2.75 4.50 1.88 1.2 32 42.4 2413 3370 1.2 70 114 148 0.5 1 ½ 1.900 350 990 0.05 2 – 3⁄8 x 2 ¼ 3.00 4.75 1.88 1.2 40 48.3 2413 4415 1.2 76 121 148 0.5 22.37535015500.072 – 3⁄8 x 2 ½ 3.50 5.25 1.88 1.6 50 60.3 2413 6900 1.7 89 133 148 0.7 2 ½ 2.875 350 2270 0.07 2 – 3⁄8 x 2 ½ 4.00 5.75 1.88 1.9 65 73.0 2413 10110 1.7 102 146 148 .09 76.1 mm 3.000 350 2475 0.07 2 – 3⁄8 x 2 ½ 4.13 5.75 1.88 1.9 76.1 2413 11010 1.7 105 146 148 0.9 33.50035033650.072 – 3⁄8 x 2 ½ 4.63 6.13 1.88 2.1 80 88.9 2413 14985 1.7 118 156 148 1.0 44.50035055650.162 – 3⁄8 x 2 ½ 5.75 7.25 2.13 3.1 100 114.3 2413 24770 4.1 146 184 54 1.4 108.0 mm 4.250 300 4255 0.16 2 – 3⁄8 x 2 ½ 5.63 7.25 2.13 3.1 108.0 2068 18940 4.1 143 184 54 1.4 55.56330072900.162 – ½ x 3 6.88 9.00 2.13 4.5 125 141.3 2068 32445 4.1 175 229 54 2.0 133.0 mm 5.250 300 6495 0.16 2 – ½ x 2 ¾ 6.63 9.00 2.13 4.5 133.0 2068 28900 4.1 168 229 54 2.0 139.7 mm 5.500 300 7125 0.16 2 – ½ x 2 ¾ 6.88 9.00 2.13 4.8 139.7 2068 31715 4.1 175 229 54 2.2 66.625300103400.162 – ½ x 3 8.00 10.00 2.13 5.0 150 168.3 2068 46020 4.1 203 254 53 2.3 159.0 mm 6.250 300 9200 0.16 2 – ½ x 2 ¾ 7.63 10.00 2.13 5.5 159.0 2068 40955 4.1 194 254 54 2.5 165.1 mm 6.500 300 9955 0.16 2 – ½ x 3 8.15 10.00 2.13 5.5 165.1 2068 44295 4.1 207 254 54 2.5 8 8.625 300 17525 0.19 2 – 5⁄8 x 4 ¼ 10.50 13.14 2.63 11.3 200 219.1 2068 78000 4.8 267 334 67 5.1 * Working Pressure and End Load are total, from all internal and external loads, based on standard weight (ANSI) steel pipe, standard roll or cut grooved in accordance with Victaulic specifications. Contact Victaulic for perfor- mance on other pipe. WARNING: FOR ONE TIME FIELD TEST ONLY, the Maximum Joint Working Pressure may be increased to 1 1/2 times the figures shown. † The allowable pipe separation dimension shown is for system layout purposes only. Style 005 couplings are con- sidered rigid connections and will not accommodate expansion or contraction of the piping system. @ Number of bolts required equals number of housing segments. Metric thread size bolts are available (color coded gold) for all coupling sizes upon request. Contact Victaulic for details. § Style 005 couplings are VdS and LPC Approved to 12 Bar/175 psi. Rated for wet and dry sprinkler systems at 350 psi/2413 kPa for 1 ¼ – 4"/32 – 100 mm sizes and 300 psi /2068 kPa for 4 ¼ – 8"/108 – 200 mm sizes; Schedule 10 roll grooved or Schedule 40 cut or roll grooved steel pipe. Style 005 is rigid and does not accommodate expansion, contraction or angular deflection. X ZY 10.02_2 FireLock® Rigid Coupling STYLE 005 WITH VIC-PLUS™ GASKET SYSTEM (NORTH AMERICA ONLY) 10.02IPS CARBON STEEL PIPE - FIRE PROTECTION PRODUCTS www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2006 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA. REV_I MATERIAL SPECIFICATIONS Housing: Ductile iron conforming to ASTM A-536, grade 65-45-12. Ductile iron conforming to ASTM A-395, grade 65-45-15, is available upon special request. Housing Coating: Orange enamel (North America); red enamel (Europe) • Optional: Hot dipped galvanized Gasket: • Grade “E” EPDM – Type A Vic-Plus™ Gasket System Δ (Violet color code). FireLock products have been Listed by Underwriters Laboratories Inc. and Approved by Factory Mutual Research for wet and dry (oil free air) sprinkler services up to the rated working pressure using the Grade “E” Type A Vic-Plus™ Gasket System, requiring no field lubrication for most installation conditions. • Grade “L” Silicone Recommended for dry heat, air without hydrocarbons to +350°F and certain chemical services. For dry services, Victaulic continues to recommend the use of Grade “E” Type A FlushSeal® Gasket. Contact Victaulic for details. Bolts/Nuts: Heat-treated plated carbon steel, trackhead meeting the physical and chemical requirements of ASTM A-449 and physical requirements of ASTM A-183. Δ Standard gasket and FlushSeal gasket approved for dry pipe systems to –40°F/–40°C. Based on “typical” pipe surface conditions, supplemental lubricant is recommended for services installed below 0°F/–18°C and for all dry pipe systems or systems to be subjected to air tests prior to being filled with water. Supplemental lubrication may also be required on pipe with raised or undercut weld seams or pipe that has voids and/or cracks at the weld seams. Victaulic continues to recommend the use of FlushSeal gaskets for dry services. 10.60_3 FireLock® Rigid Coupling STYLE 005 WITH VIC-PLUS™ GASKET SYSTEM (NORTH AMERICA ONLY) 10.02IPS CARBON STEEL PIPE - FIRE PROTECTION PRODUCTS www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2006 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA. REV_I WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details. This product shall be manufactured by Victaulic or to Victaulic specifications. All products to be installed in accordance with current Victaulic installation/assembly instructions. Victaulic reserves the right to change product specifications, designs and standard equipment without notice and without incurring obligations. NOTE WARNING: Depressurize and drain the piping system before attempting to install, remove, or adjust any Victaulic piping products. GENERAL NOTES INSTALLATION Reference should always be made to the I-100 Victaulic Field Installation Handbook for the product you are installing. Handbooks are included with each shipment of Victaulic products for complete installation and assembly data, and are available in PDF format on our website at www.victaulic.com. 10.02 FireLock® Rigid Coupling STYLE 005 WITH VIC-PLUS™ GASKET SYSTEM (NORTH AMERICA ONLY) 10.02IPS CARBON STEEL PIPE - FIRE PROTECTION PRODUCTS For complete contact information, visit www.victaulic.com 10.02 1538 REV I UPDATED 9/2006 VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2006 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA. WCAS-697KR4 Victaulic Mechanical-T® Outlet provides a direct branch connection at any location a hole can be cut in pipe. The hole is cut oversize to receive a “holefinder” locating collar which secures the outlet in position permanently. A pressure responsive gasket seals on the pipe O.D. Cross-type connections can be achieved by utilizing two upper housings of the same style and size, with the same or differing branch size connections. NOTE: Style 920 and Style 920N housings cannot be mated to each other to achieve a cross connection. Style 920 and Style 920N Mechanical-T outlets are available with grooved or female threaded outlet. Specify choice on order. Units are supplied painted with plated bolts. Galvanized hous- ings are available, supplied with plated bolts. All sizes of Style 920 and 920N are rated at 500 psi/3450 kPa working pressure on Schedule 10 and 40 carbon steel pipe. They may also be used on high density polyethylene or poly- butylene (HDPE) pipe. Pressure ratings on HDPE are dependent on the pipe rating. Contact Victaulic for ratings on other pipe. Style 920 and 920N are not recommended for use on PVC plastic pipe. Standard piping practices dictate that the Mechanical-T Styles 920 and 920N must be installed so that the main and branch connections are a true 90° angle when permanently attached to the pipeline surface. Additionally, the Vic-Tap II® hole cutting tool, which allows for hole cutting capabilities on pressurized systems, utilizes the Style 920 Mechanical-T in conjunction with the Series 726 Vic-Ball Valve to create the Style 931 Vic-Tap II Mechanical-T unit. See page 8 for further information. MATERIAL SPECIFICATIONS Housing/Coating: Ductile iron conforming to ASTM A-536, grade 65-45-12, with orange enamel coating. Ductile iron conforming to ASTM A-395, grade 65-45-15, is available upon special request. • Optional: Hot dipped galvanized Gasket: (Specify choice*) • Grade “E” EPDM EPDM (Green color code). Temperature range –30°F to +230°F/–34°C to +110°C. Recommended for cold and hot water service within the specified temperature range plus a variety of dilute acids, oil-free air and many chemical services. UL Classified in accordance with ANSI/NSF 61 for cold +86°F/+30°C and hot +180°F/+82°C. NOT RECOMMENDED FOR PETROLEUM SERVICES. • Grade “T” nitrile Nitrile (Orange color code). Temperature range –20°F to +180°F/–29°C to +82°C. Recommended for petroleum products, air with oil vapors, vegetable and mineral oils within the specified temperature range. Not recommended for hot water services over +150°F/+66°C or for hot dry air over +140°F/+60°C. *Services listed are General Service Recommendations only. It should be noted that there are services for which these gaskets are not recommended. Reference should always be made to the latest Victaulic Gasket Selection Guide for specific gasket service recommendations and for a listing of services which are not recommended. Bolts/Nuts: Heat-treated plated carbon steel, trackhead meeting the physical and chemical requirements of ASTM A-449 and physical requirements of ASTM A-183. 11.02_1 Mechanical-T® Bolted Branch Outlets STYLES 920 AND 920N PATENTED 11.02IPS CARBON STEEL PIPE - HOLE CUT PRODUCTS JOB/OWNER CONTRACTOR ENGINEER System No. __________________________Submitted By ________________________Spec Sect ____________ Para __________ Location ____________________________Date ________________________________Approved ___________________________ Date ________________________________ www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2007 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA. REV_J STYLES 920 AND 920N STYLE 920 CROSS SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS DIMENSIONS GROOVED OUTLET W ZY V Size Style No.Max. Work Pressure Dimensions Approx. Weight Each Run × Branch Nominal Size Inches mm 920 or 920N psi kPa Hole Diameter +0.13 -0.00 T** Inches mm V ‡ # Thd. Inches mm V ‡ Grv. Inches mm W Inches mm Y Inches mm Z Inches mm Female Thd. Lbs. kg Grv. Lbs. kg 2 × 1/2 (a)920N 500 1.50 2.00 2.53 —1.61 5.35 2.75 3.1 —50 15 3450 38.1 51 64 41 136 70 1.5 3/4 (a)920N 500 1.50 1.97 2.53 —1.61 5.35 2.75 3.1 —20 3450 38.1 50 64 41 136 70 1.5 1 (a)920N 500 1.50 1.85 2.53 —1.61 5.35 2.75 3.0 —25 3450 38.1 47 64 41 136 70 1.4 1 1/4 (a) †920N 500 1.75 2.05 2.75 3.00 1.61 5.35 3.00 3.5 3.232345044.5 52 70 76 41 136 76 1.7 1.5 1 1/2 (a) †920N 500 1.75 2.03 2.75 3.12 1.61 5.35 3.25 3.6 3.240345044.5 52 70 79 41 136 83 1.7 1.5 2 1/2 × 1/2 (a)920N 500 1.50 2.21 2.74 —91.82 5.64 2.75 3.0 —65 15 3450 38.1 56 70 46 143 70 1.4 3/4 (a)920N 500 1.50 2.18 2.74 —1.82 5.64 2.75 3.0 —20 3450 38.1 55 70 46 143 70 1.4 1 (a)920N 500 1.50 2.06 2.74 —1.82 5.64 2.75 2.9 —25 3450 38.1 52 70 46 143 70 1.4 1 1/4 † (a)920N 500 1.75 2.30 3.00 3.25 1.82 6.29 3.00 3.5 3.232345044.5 58 76 83 46 160 76 1.7 1.5 1 1/2 † (a)920N 500 2.00 2.28 3.00 3.25 1.82 6.26 3.25 3.6 3.340345050.8 58 76 83 46 159 83 1.7 1.6 76.1 × 1/2 (a)920 300 1.50 2.22 2.75 —2.25 6.46 3.18 3.9 —15 2065 38.1 56 70 57 164 81 1.8 3/4 (a)920 300 1.50 2.19 2.75 —2.25 6.46 3.18 3.9 —20 2065 38.1 56 70 57 164 81 1.8 1 (a)920 300 1.50 2.07 2.75 —2.25 6.46 3.18 3.8 —25 2065 38.1 53 70 57 164 81 1.7 1 1/4 (a)920 500 1.75 2.30 3.00 3.31 1.92 6.29 3.00 3.5 3.232345044.5 58 76 84 49 160 76 1.6 1.5 1 1/2 (a)920 500 2.00 2.28 3.00 3.31 1.92 6.29 3.25 3.5 3.340345050.8 58 76 84 49 160 83 1.6 1.5 3 × 1/2 (a)920N 500 1.50 2.52 3.05 —2.28 6.15 2.75 3.4 —80 15 3450 38.1 64 78 58 156 70 1.6 3/4 (a)920N 500 1.50 2.49 3.05 —2.28 6.15 2.75 3.4 —20 3450 38.1 63 78 58 156 70 1.6 1 (a)920N 500 1.50 2.38 3.06 —2.28 6.15 2.75 3.3 —25 3450 38.1 61 78 58 156 70 1.6 1 1/4 (a) †)920N 500 1.75 2.55 3.25 3.56 2.28 6.15 3.00 3.8 3.732 (b 3450 44.5 65 83 90 58 156 76 1.8 1.8 1 1/2 (a) †920N 500 2.00 2.78 3.50 3.56 2.28 6.15 3.25 4.1 3.840 (b)3450 50.8 71 89 90 58 156 83 1.9 1.8 2 (a)920N 500 2.50 2.75 3.50 3.56 2.28 6.75 3.88 4.9 4.650345063.5 70 89 90 58 172 99 2.3 2.1 3 1/2 × 2 920N 500 2.50 ——3.75 2.44 6.72 3.88 —3.89050345063.5 95 62 171 99 1.8 TABLE CONTINUED ON PG. 3 FEMALE THREADED OUTLET T W ZY V Important notes: Style 920 and Style 920N housings cannot be mated to one another to achieve cross connections. • Provides a direct branch connection at any location where a hole can be cut in the pipe • A pressure responsive gasket provides the seal • Request Publication 11.03 for Mechanical-T cross assemblies • Pressure rated up to 500 psi/3450 kPa on steel pipe; also available for use with HDPE pipe • Sizes from 2 × ½"/50 × 15 mm through 8 × 4"/200 × 100 mm 11.02_2 Mechanical-T® Bolted Branch Outlets STYLES 920 AND 920N 11.02IPS CARBON STEEL PIPE - HOLE CUT PRODUCTS www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2007 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA. REV_J DIMENSIONS GROOVED OUTLET W ZY V FEMALE THREADED OUTLET T W ZY V Important notes: Style 920 and Style 920N housings cannot be mated to one another to achieve cross connections. • Provides a direct branch connection at any location where a hole can be cut in the pipe • A pressure responsive gasket provides the seal • Request Publication 11.03 for Mechanical-T cross assemblies • Pressure rated up to 500 psi/3450 kPa on steel pipe; also available for use with HDPE pipe • Sizes from 2 × ½"/50 × 15 mm through 8 × 4"/200 × 100 mm Size Style No.Max. Work Pressure Dimensions Approx. Weight Each Run × Branch Nominal Size Inches mm 920 or 920N psi kPa Hole Diameter +0.13 -0.00 T** Inches mm V ‡ # Thd. Inches mm V ‡ Grv. Inches mm W Inches mm Y Inches mm Z Inches mm Female Thd. Lbs. kg Grv. Lbs. kg TABLE CONTINUED FROM PAGE 2 4 × 1/2 (a)920N 500 1.50 3.03 3.56 —2.69 7.01 2.75 3.7 —100 15 3450 38.1 77 90 68 178 70 1.8 3/4 (a)920N 500 1.50 3.00 3.56 —2.69 7.01 2.75 3.7 —20 3450 38.1 76 90 68 178 70 1.8 1 (a)920N 500 1.50 2.88 3.56 —2.69 7.01 2.75 3.6 —25 3450 38.1 73 90 68 178 70 1.8 1 1/4 (a) †920N 500 1.75 3.08 3.78 4.00 2.69 7.01 3.00 4.0 3.632 (b)3450 44.5 78 96 102 68 178 76 1.9 1.8 1 1/2 (a) †920N 500 2.00 3.28 4.00 4.00 2.69 7.01 3.25 4.2 3.940 (b)3450 50.8 83 102 102 68 178 83 2.0 1.9 2 (a) †920N 500 2.50 3.25 4.00 4.00 2.69 7.01 3.88 5.0 4.650345063.5 83 102 102 68 178 99 2.3 2.1 2 1/2 (a) †920 500 2.75 2.88 4.00 4.00 2.69 7.34 4.63 5.8 5.065345069.9 73 102 102 68 186 118 2.6 2.3 76.1 mm 920 500 2.75 ——4.00 2.69 7.34 4.63 —6.4345069.9 102 68 186 118 2.9 3 (a) †920 500 3.50 3.31 4.50 4.12 2.69 7.73 5.12 8.4 6.480345088.9 84 114 105 68 196 130 3.8 2.9 108.0 × 1 1/4 (a)920N 500 1.75 3.08 3.78 —2.63 7.64 3.05 5.0 —32 3450 44.5 78 96 67 194 78 2.3 1 1/2 (a)920N 500 2.00 3.28 4.00 —2.63 7.64 3.25 5.0 —40 3450 50.8 83 102 67 194 83 2.3 2 (a)920N 500 2.50 3.25 4.00 —2.63 7.64 4.00 4.0 —50 3450 63.5 83 102 67 194 102 1.9 76.1 mm 920 500 2.75 2.88 4.00 4.00 2.63 7.64 4.29 8.0 —3450 69.9 73 102 102 67 194 109 3.6 3 (a)920 500 3.50 3.31 4.50 —2.63 7.63 4.88 6.8 6.580345088.9 84 114 67 194 124 3.1 3.0 5 × 1 1/2 (a) †920 500 2.00 4.03 4.75 4.75 3.16 9.70 3.69 7.4 7.612540345050.8 102 121 121 80 246 94 3.4 3.4 2 (a) †920 500 2.50 4.00 4.75 4.75 3.16 9.70 4.38 8.2 8.050345063.5 102 121 121 80 246 111 3.7 3.6 2 1/2 (a) †920 500 2.75 3.63 4.75 4.75 3.16 9.70 4.63 8.3 7.965345069.9 92 121 121 80 246 118 3.8 3.6 76.1 mm 920 500 2.75 ——4.75 3.16 9.70 4.63 —8.0345069.9 121 80 246 118 3.6 3 (a) †920 500 3.50 3.81 5.00 4.63 3.16 9.70 5.31 8.4 8.880345088.9 97 127 118 80 246 135 3.8 4.0 133.0 × 2 920N 500 2.50 3.75 4.50 —3.17 8.00 3.88 8.0 —50 3450 63.5 95 114 81 203 99 3.6 3 920 500 3.50 3.81 5.00 —3.00 9.46 5.31 8.0 —80 3450 88.9 97 127 76 240 135 3.6 TABLE CONTINUED ON PG. 4 11.02_3 Mechanical-T® Bolted Branch Outlets STYLES 920 AND 920N 11.02IPS CARBON STEEL PIPE - HOLE CUT PRODUCTS www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2007 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA. REV_J DIMENSIONS GROOVED OUTLET W ZY V FEMALE THREADED OUTLET T W ZY V Important notes: Style 920 and Style 920N housings cannot be mated to one another to achieve cross connections. • Provides a direct branch connection at any location where a hole can be cut in the pipe • A pressure responsive gasket provides the seal • Request Publication 11.03 for Mechanical-T cross assemblies • Pressure rated up to 500 psi/3450 kPa on steel pipe; also available for use with HDPE pipe • Sizes from 2 × ½"/50 × 15 mm through 8 × 4"/200 × 100 mm Size Style No.Max. Work Pressure Dimensions Approx. Weight Each Run × Branch Nominal Size Inches mm 920 or 920N psi kPa Hole Diameter +0.13 -0.00 T** Inches mm V ‡ # Thd. Inches mm V ‡ Grv. Inches mm W Inches mm Y Inches mm Z Inches mm Female Thd. Lbs. kg Grv. Lbs. kg TABLE CONTINUED FROM PAGE 3 139.7 × 1 1/2 †920N 500 2.00 3.78 4.50 —3.30 8.23 3.25 7.0 —40 3450 50.8 96 114 84 209 83 3.2 2 †920N 500 2.50 3.75 4.50 —3.30 8.23 3.88 9.0 —50 3450 63.5 95 114 84 209 99 4.1 76.1 mm 920 500 2.75 3.63 4.75 —3.13 9.85 4.63 8.8 —3450 69.9 92 121 80 250 118 4.0 76.1 mm 920 500 3.50 ——4.63 3.16 9.70 5.31 11.0 —3450 88.9 118 80 246 135 5.0 3 920 500 3.50 3.81 5.00 4.63 3.16 9.85 5.38 14.0 14.288.9 3450 88.9 96.80 127 118 80 250 137 6.4 6.4 6 × 1 1/4 (a)920N 500 1.75 4.43 ——3.79 9.15 3.25 —4.815032 (b)3450 44.5 112 96 232 83 2.2 1 1/2 (a) †920N 500 2.00 4.40 5.13 5.13 3.79 9.15 3.25 5.4 5.140 (b)3450 50.8 112 130 130 96 232 83 2.4 2.3 2 (a) †920N 500 2.50 4.38 5.13 5.13 3.79 9.15 3.88 6.0 5.650345063.5 111 130 130 96 232 99 2.7 2.5 2 1/2 (a) †920 500 2.75 4.01 5.13 5.12 3.69 10.51 4.63 8.3 7.665345069.9 110 130 130 94 267 118 3.8 3.4 76.1 mm 920 500 2.75 ——5.21 3.69 10.51 4.63 —8.4345069.9 132 94 267 118 3.8 3 (a) †920 500 3.50 4.31 5.50 5.13 3.69 10.51 5.31 9.9 8.480345088.9 110 140 130 94 267 135 4.5 3.8 4 (a) †920 500 4.50 3.81 5.75 5.38 3.69 10.51 6.25 10.1 10.11003450114.3 97 146 137 94 267 159 4.6 4.6 159.0 × 1 1/4 920N 500 1.75 4.43 5.13 —3.63 9.40 3.25 9.0 8.732345044.5 113 130 92 239 83 4.1 4.0 1 1/2 (a)920N 500 2.00 4.41 5.13 —3.63 9.40 3.25 7.8 —40 3450 50.8 112 130 92 239 83 3.5 2 (a)920N 500 2.50 4.38 5.13 —3.63 9.40 3.88 8.0 —50 3450 63.5 111 130 92 239 99 3.6 76.1 mm 920 500 2.75 4.38 5.50 5.13 3.63 9.40 4.63 9.5 9.5345069.9 111 140 130 92 239 118 4.3 4.3 3 920 500 3.50 4.31 5.50 5.13 3.63 9.40 5.31 8.1 14.080345088.9 110 140 130 92 239 135 3.7 6.4 108.1 mm 920 500 4.50 ——5.38 3.63 9.40 6.12 —10.03450114.3 137 92 239 155 4.5 4 920 500 4.50 3.81 5.75 —3.63 9.40 6.25 18.0 —100 3450 114.3 96.80 146 92 239 159 8.2 TABLE CONTINUED ON PG. 5 11.02_4 Mechanical-T® Bolted Branch Outlets STYLES 920 AND 920N 11.02IPS CARBON STEEL PIPE - HOLE CUT PRODUCTS www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2007 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA. REV_J Anvil Cast & Malleable Iron Fittings Project InformatIon:aPProval StamP: Project: Date:Phone: Architect / Engineer: Contractor: Address: Notes 1: Notes 2: Rev. 03.03.06-00 ® For the latest UL/ULC Listed and FM Approved pressure ratings, versus pipe schedule, go to www.anvilstar.com or contact your local AnvilStar representative Submittal Sheet Material SpecificationS Note: See the Technical Data section for pressure-temperature ratings. See AnvilStar Web site for the most current Listings and approvals. Anvil standard and extra heavy cast iron threaded fittings are manufactured in accordance with ASMe-B6.4 (except plugs and bushings, ASMe B6.4). Dimensions also conform to Federal Specifications, WW-P-50(except plugs and bushings WW-P-47). Anvil standard and extra heavy fittings in this section, sizes ⁄4 NPS - 2NPS (8 - 300 DN), are included in the “List of Inspected Fire Protection equipment and Materials” issued by the Underwriters’ Laboratories, Inc. A B A B figure 351 90° elbow Straight Size A B Weight black galv. NPS/DN In./mm In./mm lbs./kg lbs./kg 1⁄4 1⁄2 13⁄16 0.16 0.17813220.07 0.08 3⁄8 9⁄16 15⁄16 0.25 0.261014240.11 0.12 1⁄2 11⁄16 11⁄8 0.4 0.411517290.18 0.19 3⁄4 13⁄16 15⁄16 0.6 0.612022330.27 0.281 15⁄16 11⁄2 0.92 0.952524380.42 0.4311⁄4 11⁄8 13⁄4 1.4 1.53229440.65 0.6611⁄2 15⁄16 115⁄16 2 24033490.88 0.91219⁄16 21⁄4 3.1 3.25040571.4 1.521⁄2 113⁄16 211⁄16 4.9 5.16547682.2 2.3323⁄16 31⁄8 7.2 7.48056793.3 3.44211⁄16 313⁄16 12 1310068985.5 5.7535⁄16 41⁄2 21 —125 84 114 10 —6 37⁄8 51⁄8 31 33150981301415853⁄16 69⁄16 65 672001321672930 fig. 351 90° Elbow – Straight Cast Iron Threaded Fittings Class 125 (Standard) Anvil Cast & Malleable Iron Fittings Project InformatIon:aPProval StamP: Project: Date:Phone: Architect / Engineer: Contractor: Address: Notes 1: Notes 2: Rev. 03.03.06-005 ® For the latest UL/ULC Listed and FM Approved pressure ratings, versus pipe schedule, go to www.anvilstar.com or contact your local AnvilStar representative Submittal Sheet Material SpecificationS Note: See the Technical Data section for pressure-temperature ratings. See AnvilStar Web site for the most current Listings and approvals. Anvil standard and extra heavy cast iron threaded fittings are manufactured in accordance with ASMe-B6.4 (except plugs and bushings, ASMe B6.4). Dimensions also conform to Federal Specifications, WW-P-50(except plugs and bushings WW-P-47). Anvil standard and extra heavy fittings in this section, sizes ⁄4 NPS - 2NPS (8 - 300 DN), are included in the “List of Inspected Fire Protection equipment and Materials” issued by the Underwriters’ Laboratories, Inc. fig. 358 Straight Tee Cast Iron Threaded Fittings Class 125 (Standard) B A A B B A figure 358 Straight tee Size A B Weight black galv. NPS/DN In./mm In./mm lbs./kg lbs./kg 1⁄4 1⁄2 13⁄16 0.22 0.23 8 13 22 0.1 0.1 3⁄8 5⁄8 1 0.35 0.361016250.16 0.16 1⁄2 11⁄16 11⁄8 0.56 0.58 15 17 29 0.25 0.26 3⁄4 13⁄16 15⁄16 0.84 0.852022330.38 0.391 15⁄16 11⁄2 1.3 1.3 25 24 38 0.57 0.59 11⁄4 11⁄8 13⁄4 2 2.13229440.9 0.911⁄2 15⁄16 115⁄16 2.7 2.7 40 33 49 1.2 1.2 2 19⁄16 21⁄4 4.2 4.35040571.9 221⁄2 113⁄16 211⁄16 6.7 6.8 65 47 68 3 3.1 3 23⁄16 31⁄8 10 10 80 56 79 4.5 4.6 31⁄2 27⁄16 37⁄16 13 1490628766.34211⁄16 33⁄4 16 17 100 68 95 7.4 7.7 5 35⁄16 41⁄2 27 28125841141213637⁄8 51⁄8 41 41 150 98 130 19 19 8 53⁄16 69⁄16 79 812001321673637 Anvil Cast & Malleable Iron Fittings Project InformatIon:aPProval StamP: Project: Date:Phone: Architect / Engineer: Contractor: Address: Notes 1: Notes 2: Rev. 03.03.06-00 ® For the latest UL/ULC Listed and FM Approved pressure ratings, versus pipe schedule, go to www.anvilstar.com or contact your local AnvilStar representative Submittal Sheet Material SpecificationS Note: See the Technical Data section for pressure-temperature ratings. See AnvilStar Web site for the most current Listings and approvals. Anvil standard and extra heavy cast iron threaded fittings are manufactured in accordance with ASMe-B6.4 (except plugs and bushings, ASMe B6.4). Dimensions also conform to Federal Specifications, WW-P-50(except plugs and bushings WW-P-47). Anvil standard and extra heavy fittings in this section, sizes ⁄4 NPS - 2NPS (8 - 300 DN), are included in the “List of Inspected Fire Protection equipment and Materials” issued by the Underwriters’ Laboratories, Inc. fig. 367 Concentric Reducers Cast Iron Threaded Fittings Class 125 (Standard) AB Size A B Weight black NPS/DN NPS/DN In./mm In./mm lbs./kg 3⁄4 1⁄2 5⁄8 19⁄16 0.4 20 15 16 40 0.18 125 ■ 1⁄2 11⁄16 111⁄16 0.54 ■ 15 17 43 0.24 ■ 3⁄4 7⁄16 11⁄2 0.63 ■ 20 11 38 0.29 11⁄432 1⁄2 9⁄16 15⁄8 0.84 15 14 41 0.383⁄4 1 21⁄8 1.1 20 25 54 0.49115⁄16 21⁄8 1.1 25 24 54 0.49 11⁄240 1⁄2 1⁄2 15⁄8 1 15 13 41 0.453⁄4 1⁄2 15⁄8 1.2 20 13 41 0.5411⁄2 13⁄4 1.5 25 13 44 0.6811⁄4 1 21⁄4 1.5 32 25 57 0.66 250 1⁄2 5⁄8 2 2 15 16 51 0.913⁄4 3⁄4 2 1.9 20 19 51 0.861 3⁄4 2 1.8 25 19 51 0.83 figure 367 concentric reducerS Size A B Weight black NPS/DN NPS/DN In./mm In./mm lbs./kg 250 (cont.) 11⁄4 13⁄16 21⁄8 1.83222540.81 11⁄2 7⁄8 23⁄16 24022560.9 21⁄265 11⁄2 3⁄4 2 3.14019511.4 2 1 29⁄16 35025651.4 380 3⁄4 15⁄16 21⁄2 4.32024642 2 11⁄16 23⁄4 45027701.8 21⁄2 15⁄16 213⁄16 4.46524732 4100 2 13⁄16 215⁄16 6.55030752.9 21⁄2 13⁄16 31⁄8 7.86530793.5 3 11⁄16 31⁄8 78027793.2 5 4 11⁄16 35⁄16 1012510027844.8 6150 4 11⁄8 37⁄16 1410029876.3 5 11⁄8 39⁄16 1612529907 8 6 11⁄4 37⁄8 29200150329813 ■ hex end AHEAD OF THE FLOW ™ www.nibco.com Revision 5/14/02 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 52 U.S. customary units in this document are the standard; the metric units are provided for reference only. The values stated in each system are not exact equivalents. Copper Water Tube continued DIMENSIONAL DATA – COPPER WATER TUBE – TYPE “M” TYPE “M” Hard Drawn Only: 20-ft. (6.1m) Straight Lengths Usage: For general purpose plumbing, heating and drainage installations. Tolerances Hard Drawn (Hard Drawn Only) Outside Tubing OD Nominal Wall Weight Bursting Safe Working Nominal Diameter Thickness Per Foot Pressure A PressureB Water Tube Min. Max. Size (In Inches) Inch (mm) Inch (mm) Inch (mm) Inch (mm) Lb (kg) psi (bars) psi (bars) 1/4 0.375 (9.53) 0.373 (9.47) 0.376 (9.55) N/A N/A N/A N/A N/A N/A N/A N/A 3/8 0.500 (12.70) 0.497 (12.62) 0.501 (12.73) 0.025 (0.64) 0.145 (0.07) N/A N/A 855 (59) 1/2 0.625 (15.88) 0.622 (15.80) 0.626 (15.90) 0.028 (0.71) 0.204 (0.09) 6135 (423) 741 (51) 5/8 0.750 (19.05) 0.747 (18.97) 0.751 (19.08) N/A N/A N/A N/A N/A N/A N/A N/A 3/4 0.875 (22.23) 0.872 (22.15) 0.876 (22.25) 0.032 (0.81) 0.328 (0.15) 4717 (325) 611 (42) 1 1.125 (28.58) 1.122 (28.50) 1.127 (28.63) 0.035 (0.89) 0.465 (0.21) 3865 (266) 506 (35) 1 1/4 1.375 (34.93) 1.372 (34.85) 1.377 (34.98) 0.042 (1.07) 0.682 (0.31) 3875 (267) 507 (35) 1 1/2 1.625 (41.28) 1.621 (41.17) 1.627 (41.33) 0.049 (1.24) 0.940 (0.43) 3550 (245) 497 (34) 2 2.125 (53.98) 2.121 (53.87) 2.127 (54.03) 0.058 (1.47) 1.460 (0.66) 2935 (202) 448 (31) 2 1/2 2.625 (66.68) 2.621 (66.57) 2.627 (66.73) 0.065 (1.65) 2.030 (0.92) 2800 (193) 411 (28) 3 3.125 (79.38) 3.121 (79.27) 3.127 (79.43) 0.072 (1.83) 2.680 (1.22) 2665 (184) 380 (26) 3 1/2 3.625 (92.08) 3.621 (91.97) 3.627 (92.13) 0.083 (2.11) 3.580 (1.62) N/A N/A 378 (26) 4 4.125 (104.78) 4.121 (104.67) 4.127 (104.83) 0.095 (2.41) 4.660 (2.11) 2215 (153) 377 (26) 5 5.125 (130.18) 5.121 (130.07) 5.127 (130.23) 0.109 (2.77) 6.660 (3.02) 2490 (172) 349 (24) 6 6.125 (155.58) 6.121 (155.47) 6.127 (155.63) 0.122 (3.10) 8.920 (4.05) 2000 (138) 328 (23) 8 8.125 (206.38) 8.119 (206.22) 8.127 (206.43) 0.170 (4.32) 16.500 (7.48) 2285 (158) 344 (24) 10 10.125 (257.18) 10.119 (257.02) 10.127 (257.23) 0.212 (5.38) 25.600 (11.61) N/A N/A 344 (24) 12 12.125 (307.98) 12.119 (307.82) 12.127 (308.03) 0.254 (6.45) 36.700 (16.65) N/A N/A 345 (24) Note: Information and data contained in these charts, as taken from ASTM Specifications B 88. Rated internal pressure for copper water tube based on the strength of the tube alone and applicable to systems using suitable mechanical joints. A Based on actual laboratory test data provided by Copper Development Association, Inc. B Based upon 150°F (65.6°C) with an allowable stress of 9500 psi (668 kPa). AHEAD OF THE FLOWTM Copper Fittings CATALOG C-CF-0404 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH:1.888.446.4226 • FAX: 1.800.336.4226 • INTERNATIONAL OFFICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com NIBCO flow-control solutions are everywhere you look, including on our website. We offer a wide range of metal and plastic valves and fittings that keep residential, commercial and industrial operations flowing smoothly throughout the world. Compact Economy Ball Valves Prepackaged Pneumatic Ball Valves Circuit Balancing Valves Flanged Butterfly Valves Bronze Ball Valve Line Extension PEXlink®copper fittings for PEX applications Just Right®hot-water circulation device Carbon/Stainless Steel Ball Valves Socket Fusion Equipment TruConnect®fittings for Chem-Aire® The "New Products" page is a continuously updated showcase for new products by NIBCO. *Current highlights include: ORDER ONLINE NIBCOpartner.com makes it easy for you to order all the fittings you need right from your own computer. Its quick, easy and reliable. Place your order TODAY! Price sheets (PDF & Excel format) —also accessible from home page Downloadable catalogs (PDF format) Product drill-down capabilities to categories Wrot Copper & Cast Bronze Fittings ABS & PVC Drain, Waste, & Vent PVC Schedule 40 Fittings & Valves CPVC CTS Fittings The “Fittings” Homepage at www.nibco.com provides easy access to valuable reference tools. *Key information includes: AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 33//2299//0044 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 3 Table of Contents Cast Copper Alloy Flared Fittings . . . . . . . . . . . . . . . . . . . . . . . . . . 22-24 Copper Insert Fittings for PEXlink™ . . . . . . . . . . . . . . . . . . . . . . . . . 25-27 Copper Insert Fittings for Polybutylene . . . . . . . . . . . . . . . . . . . . . 28-29 Engineering Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41-84 Frequently-Asked Questions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90 Installation Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85-89 Numerical Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91 Wrot & Cast DWV Fittings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30-40 Wrot & Cast Pressure Fittings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-21 The manufacturing plants at South Glens Falls, NY, Stuarts Draft, VA, Nacogdoches, TX and Reynosa, Mexico manufacture products under a Quality Management System conforming to the current revision of ISO-9001 International Standards AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 55//1144//0022 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 4 All of the advantages found in copper as a metal have been capitalized to the utmost in the manufacture of NIBCO Fittings. Because of the accuracy of construction and design, copper plumbing is more efficient and less expensive. NIBCO manufactures nine general types of fittings: Wrot Pressure; Cast Pressure; Wrot Drainage; Cast Drainage; Flanges; Flared Tube; Threaded Bronze; Insert Fittings for PEX; Barbed Insert Fittings for Polybutylene. Each has its particular place and use and each offers its own advantages when used for the proper service requirement. ALLOY AND FINISH — NIBCO Fittings are made from highest quality raw materials available — Cast Fittings are made from Copper Alloy C84400 which consists of 81% Copper, 7% Lead, 3% Tin, and 9% Zinc per ASTM Specification B584. Wrot Copper Fittings are made from commercially pure copper mill products per ASTM Specifications B75 Alloy C12200. NIBCO fittings are produced to meet requirements of applicable standards wherever practicable. NIBCO brand wrot and cast fittings are manufactured in the U.S.A. and Mexico. The manufacturing plants at South Glens Falls, NY, Stuarts Draft, VA, Nacogdoches, TX and Reynosa, Mexico are registered to ISO 9002 quality standards. Following is suggested phrasing to be incorporated in your specifications or bills of material for Copper Tube Fittings. WROT SOLDER JOINT FITTINGS — “Wrot Solder Joint Fittings shall be produced to one of the following specifications: 1. Material and workmanship shall be in accordance with ASME/ANSI B16.22; Wrought Copper and Copper Alloy Solder Joint Pressure Fittings.” Specifications 2. The dimensional, material and workmanship shall meet the requirements of MSS SP-104; Wrought Copper Solder Joint Pressure Fittings.” 3. The dimensional, material and workmanship of 5"–12" copper fittings shall meet the requirements of MSS SP-109 “Welded Fabricated Copper Solder Joint Pressure Fittings.” 4. Certified to ANSI/NSF 61. CAST COPPER ALLOY SOLDER JOINT FITTINGS — “Cast Copper Alloy Solder Joint Fittings shall be in accordance with ANSI Std. B16.18.” WROT DRAINAGE FITTINGS — “Wrot Drainage Fittings shall be in accordance with ASME/ANSI Std. B16.29.” CAST COPPER ALLOY SOLDER JOINT DRAINAGE FITTINGS — “Cast Copper Alloy Solder Joint Drainage Fittings shall be in accordance with ASME Std. B16.23.” CAST COPPER ALLOY FLARED TUBE FITTINGS — “Cast Copper Alloy Flared Tube Fittings shall be in accor- dance with ASME/ANSI Std. B16.26. CAST COPPER ALLOY FLANGES AND FLANGED FITTINGS— CLASS 150 — Cast Copper Alloy Flanges and Flanged Fittings shall meet the requirements of MSS SP-106 and/or the workmanship and dimensions of Federal Specifications WW-F-406 or ASME Std. B16.24. CLASS 125 — Material, workmanship and dimensions of flanges shall be in accordance with MSS SP-106. CAST BRONZE THREADED FITTINGS — “Cast Bronze Threaded Fittings shall be in accordance with ANSI/ASME B16.15.” POLYBUTYLENE COPPER INSERT TYPE VALVES AND FITTINGS — “Wrot Copper Insert Fittings shall be manufactured per the following specifications: MSS SP-103 or ASTM F1380.” NIBCO Copper Tube Fittings are all produced to above Standards. To simplify, write your specifications to read: “Copper Tube Fittings to be in accordance with specifications as outlined in NIBCO Catalog c-cf-0602.” WROT COPPER MEDICAL MEDICAL GAS SYSTEM COMPONENTS — Wrot copper fittings that are to be installed in medical gas applications shall be prepared in accordance with NFPA 99, Health Care Facilities Gas and Vacuum Systems and the Compressed Gas Association, Pamphlet G4.1. Packaging shall be adequately protective and include labeling that identifies the preparer and states that the product has been cleaned and bagged for oxygen or med gas service. For technical information and dimensions refer to the engineering section contained in this catalog. AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 33//2299//0044 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 5 Wrot and Cast Pressure Fittings 600 Series – Wrot 700 Series – Cast Adapters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-8 Air Chambers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Bulkhead Fittings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Bushings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Caps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Couplings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-11 Crosses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Elbows . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-15 Fitting Reducers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Flanges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-16 Plugs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Return Bends . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Straps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Tees . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16-20 Traps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Unions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Venturi . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Y’s . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 The manufacturing plants at South Glens Falls, NY, Stuarts Draft, VA, Nacogdoches, TX and Reynosa, Mexico manufacture products under a Quality Management System conforming to the current revision of ISO-9001 International Standards 703-2 Fitting Adapter Ftg x F – Cast APPROX. DIM. BNOM. SIZE NET WT./LBS. INCHES 1/2 x 1/4 0.11 17/32 3/4 x 1/2 0.12 19/16 1 x 3/4 0.38 131/32 1 x 1/2 0.15 17/16 2 1/2 1.65 215/16 3 2.47 31/4 703-5 Special Drop Adapter C x F – Cast APPROX. DIM. A NOM. SIZE NET WT./LBS. INCHES 1/2 0.16 3/4 3/4 0.24 31/32 703-5B Drop Adapter C x F – Cast APPROX. DIM. A NOM. SIZE NET WT./LBS. INCHES 1/2 0.15 3/4 AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 33//2299//0044 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 6 ADAPTERS 603 Adapter C x F – Wrot APPROX. DIM. ANOM. SIZE NET WT./LBS. INCHES 1/8 0.03 13/32 1/8 x 1/4 0.03 1/2 1/4 0.03 5/8 1/4 x 3/8 0.05 21/32 3/8 0.04 11/16 3/8 x 1/2 0.09 29/32 3/8 x 1/4 0.03 9/16 1/2 0.09 27/32 1/2 x 3/4 0.14 1 1/2 x 3/8 0.04 17/32 1/2 x 1/4 0.05 1/2 5/8 x 3/4 0.12 29/32 5/8 x 1/2 0.11 3/4 3/4 0.15 29/32 3/4 x 1 0.21 11/8 3/4 x 1/2 0.10 5/8 1 0.24 31/32 1 x 1 1/4 0.28 17/32 1 x 3/4 0.19 25/32 1 x 1/2 0.24 5/8 1 1/4 0.33 13/32 1 1/4 x 1 1/2 0.40 11/4 1 1/4 x 1 0.27 31/32 1 1/2 0.44 11/8 1 1/2 x 2 0.50 11/32 2 0.63 13/32 2 x 1 1/2 0.74 13/16 2 1/2 1.13 – 3 1.94 – 703 Adapter C x F – Cast APPROX. DIM. ANOM. SIZE NET WT./LBS. INCHES 1/4 x 1/2 0.13 27/32 1/2 x 1 0.30 1 3/4 x 1 1/4 0.55 1 1/8 3/4 x 3/8 0.17 3/4 1 x 1 1/2 0.68 13/32 1 1/4 x 1 0.27 31/32 1 1/4 x 3/4 0.29 3/4 1 1/2 x 2 0.78 1 1/32 1 1/2 x 1 0.37 25/32 1 1/2 x 1 1/4 0.47 1 1/4 2 x 1 1/4 0.76 27/32 2 1/2 1.62 1 3/8 3 2.34 1 1/2 4 4.05 1 9/16 603-2Fitting Adapter Ftg x F – Wrot APPROX. DIM. B NOM. SIZE NET WT./LBS. INCHES 1/4 0.03 1 3/32 3/8 0.06 1 3/16 1/2 0.09 1 7/16 1/2 x 3/8 0.05 1 1/4 3/4 0.13 1 11/16 1 0.27 2 1/32 1 1/4 0.31 2 1/8 1 1/2 0.43 2 5/16 2 0.61 2 17/32 Consult price sheet for Made to Order items and for minimum order quantities. AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 33//2299//0044 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 7 ADAPTERS continued 604 Adapter C x M – Wrot APPROX. DIM. BNOM. SIZE NET WT./LBS. INCHES 1/8 x 1/4 0.03 7/16 1/4 0.03 23/32 3/8 0.04 15/32 3/8 x 3/4 0.15 1 5/16 3/8 x 1/2 0.09 1 1/2 0.07 5/8 1/2 x 1 0.25 1 1/2 1/2 x 3/4 0.15 13/16 1/2 x 3/8 0.05 19/32 1/2 x 1/4 0.07 5/8 5/8 x 3/4 0.16 1 1/8 5/8 x 1/2 0.08 3/4 3/4 0.14 13/16 3/4 x 1 0.26 1 7/16 3/4 x 1/2 0.10 27/32 1 0.21 31/32 1 x 1 1/2 0.54 29/32 1 x 1 1/4 0.38 1 1/2 1 x 3/4 0.18 29/32 1 x 1/2 0.18 31/32 1 1/4 0.35 15/16 1 1/4 x 1 1/2 0.51 1 19/32 1 1/4 x 1 0.27 1 5/32 1 1/2 0.44 31/32 1 1/2 x 2 0.81 1 1/8 1 1/2 x 1 1/4 0.38 1 3/16 1 1/2 x 1 0.37 1 3/32 2 0.81 1 3/32 2 x 1 1/2 0.64 1 1/8 2 1/2 1.48 1 21/32 3 1.69 – Consult price sheet for Made to Order items and for minimum order quantities. 704 Adapter C x M – Cast APPROX. DIM. BNOM. SIZE NET WT./LBS. INCHES 3/4 x 1 1/2 0.60 1 17/32 3/4 x 1 1/4 0.38 1 7/32 3/4 x 3/8 0.19 13/16 1 x 2 1.15 – 1 x 1 1/2 0.64 29/32 1 1/4 x 2 0.88 1 9/32 1 1/4 x 3/4 0.30 31/32 1 1/2 x 2 0.77 1 1/8 2 x 2 1/2 1.57 1 15/32 2 x 1 1/2 0.71 1 1/8 2 x 1 1/4 1.08 – 2 1/2 1.48 1 21/32 2 1/2 x 2 1.83 1 11/16 3 1.96 1 1/2 4 3.66 1 11/16 5 8.60 2 5/8 6 10.73 2 704-F Flush Adapter C x M – Cast APPROX. DIM. BNOM. SIZE NET WT./LBS. INCHES 1/2 0.03 9/16 3/4 0.03 19/32 704-H Hose Adapter C x Hose – Cast APPROX. DIM. ANOM. SIZE NET WT./LBS. INCHES 1/2 0.09 9/32 NOTE: Fits 1/2," 5/8" and 3/4" Garden Hose. 604-2 Fitting Adapter Ftg x M – Wrot APPROX. DIM. BNOM. SIZE NET WT./LBS. INCHES 1/8 0.02 1 1/8 3/8 0.04 1 1/4 1/2 0.09 1 15/32 1/2 x 3/4 0.16 1 13/16 1/2 x 3/8 0.04 1 11/32 3/4 0.17 1 15/16 1 0.25 2 1/4 704-2 Fitting Adapter Ftg x M – Cast APPROX. DIM. B NOM. SIZE NET WT./LBS. INCHES 3/4 x 1 0.27 1 31/32 3/4 x 1/2 0.12 1 23/32 1 x 3/4 0.24 1 15/16 1 1/4 0.43 2 27/32 1 1/2 0.54 2 13/32 2 0.89 2 3/4 2 1/2 1.55 3 3/8 3 2.21 3 23/32 750 Bulkhead Fitting C x C – Cast APPROX. DIM. A DIM. BNOM. SIZE NET WT./LBS. INCHES INCHES 1/2 0.48 11/4 1 3/4 0.77 19/32 11/4 1 1.30 11/2 15/8 1 1/2 2.87 11/2 23/8 2 3.82 21/32 25/8 750-3 Bulkhead Fitting C x F – Cast APPROX. DIM. A DIM. BNOM. SIZE NET WT./LBS. INCHES INCHES 1/2 0.48 115/16 1 3/4 0.79 21/16 11/4 1 1.43 215/32 15/8 750-4 Bulkhead Fitting C x M – Cast APPROX. DIM. A DIM. BNOM. SIZE NET WT./LBS. INCHES INCHES 1/2 0.40 131/32 1 3/4 0.79 25/32 11/4 704-2-H Hose Adapter Ftg x Hose–Cast APPROX. DIM. B NOM. SIZE NET WT./LBS. INCHES 3/4 F x 1/2 H 0.16 15/8 NOTE: Fits 1/2," 5/8" and 3/4" Garden Hose. 619 Air Chamber Ftg. – Wrot APPROX. DIM. A DIM. L NOM. SIZE NET WT./LBS. INCHES INCHES 1/2 x 6 0.21 1 6 1/2 x 12 0.41 1 12 1/2 x 14 0.78 11/8 14 3/4 x 12 0.40 1 12 620-L Air Chamber or Stub-Out Ftg – Wrot As Air Chamber, just solder one joint. When used as Stub-Out, simply pressure test system then cut off stub-out (save piece for future use) and install valve or fixture. APPROX. DIM. L NOM. SIZE NET WT./LBS. INCHES 1/2 x 6 0.14 6 1/2 x 8 0.19 8 1/2 x 10 0.24 10 1/2 x 12 0.28 12 3/4 x 12 0.46 12 AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 33//2299//0044 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 8 AIR CHAMBERS BULKHEAD FITTINGS Consult price sheet for Made to Order items and for minimum order quantities. 618 Flush Bushing Ftg x C – Wrot APPROX. DIM. C NOM. SIZE NET WT./LBS. INCHES 1/4 x 1/8 0.01 1/16 3/8 x 1/4 0.01 1/16 1/2 x 3/8 0.02 3/32 1/2 x 1/4 0.04 1/4 5/8 x 1/2 0.03 1/16 3/4 x 5/8 0.22 3/16 3/4 x 1/2 0.08 3/32 3/4 x 3/8 0.11 7/16 1 x 3/4 0.12 1/8 1 x 1/2 0.22 15/32 1 1/4 x 1 0.17 3/32 1 1/2 x 1 1/4 0.22 5/32 2 x 1 1/2 0.66 1/8 618-3 Flush Bushing Ftg x F – Wrot APPROX. DIM. B NOM. SIZE NET WT./LBS. INCHES 1/2 x 1/8 0.03 9/16 1/2 x 1/4 0.03 9/16 718-3 Flush Bushing Ftg x F – Cast APPROX. DIM. BNOM. SIZE NET WT./LBS. INCHES 3/4 x 3/8 0.06 1 31/32 1 x 1/2 0.13 31/32 1 1/4 x 3/4 0.18 1 1/32 1 1/2 x 1 0.25 1 5/32 BUSHINGSADAPTERScontinued AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 33//2299//0044 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 9 Consult price sheet for Made to Order items and for minimum order quantities. CAPS 617 Tube Cap C – Wrot APPROX. DIM. N NOM. SIZE NET WT./LBS. INCHES 1/8 0.01 1/32 1/4 0.01 3/32 3/8 0.01 3/32 1/2 0.02 3/32 5/8 0.03 1/8 3/4 0.04 1/8 1 0.07 5/32 1 1/4 0.10 3/32 1 1/2 0.16 1/8 2 0.27 5/32 2 1/2 0.50 7/32 3 0.78 7/32 4 1.66 1/4 717 Tube Cap C – Cast APPROX. DIM. N NOM. SIZE NET WT./LBS. INCHES 5 5.48 7/16 6 9.07 17/32 717-D Drain Cap – Cast APPROX. DIM. A NOM. SIZE NET WT./LBS. INCHES 1/2 0.06 21/32 COUPLINGS 600 Reducing Coupling C x C – Wrot APPROX. DIM. ANOM. SIZE NET WT./LBS. INCHES 1/8 x 3/16 O.D. 0.01 5/32 5/16 O.D. x 1/8 0.01 3/16 1/4 x 5/16 O.D. 0.01 3/16 1/4 x 1/8 0.01 3/16 3/8 x 1/4 0.02 3/16 3/8 x 5/16 O.D. 0.01 1/4 3/8 x 1/8 0.01 1/4 1/2 x 3/8 0.03 3/16 1/2 x 1/4 0.02 1/4 1/2 x 1/8 0.03 11/32 5/8 x 1/2 0.05 3/16 5/8 x 3/8 0.04 11/32 5/8 x 1/4 0.03 13/32 3/4 x 5/8 0.07 3/16 3/4 x 1/2 0.06 9/32 3/4 x 3/8 0.06 3/8 3/4 x 1/4 0.05 11/32 1 x 3/4 0.11 11/32 1 x 5/8 0.09 3/8 1 x 1/2 0.10 11/32 1 x 3/8 0.10 13/32 1 1/4 x 1 0.16 5/16 1 1/4 x 3/4 0.18 17/32 1 1/4 x 5/8 0.18 5/8 1 1/4 x 1/2 0.14 7/16 1 1/2 x 1 1/4 0.23 5/16 1 1/2 x 1 0.22 9/16 1 1/2 x 3/4 0.20 3/8 1 1/2 x 1/2 0.19 1/2 2 x 1 1/2 0.41 9/16 2 x 1 1/4 0.35 11/16 2 x 1 0.37 7/16 2 x 3/4 0.34 17/32 2 x 1/2 0.35 23/32 2 1/2 x 2 0.59 9/16 2 1/2 x 1 1/2 0.65 11/16 2 1/2 x 1 1/4 0.65 13/16 2 1/2 x 1 0.73 29/32 Continues… APPROX. DIM. A NOM. SIZE NET WT./LBS. INCHES 3 x 2 1/2 0.98 1/2 3 x 2 1.06 15/16 3 x 1 1/2 0.92 1 1/32 3 1/2 x 3 1.52 1/2 4 x 3 1/2 2.12 19/32 4 x 3 1.92 27/32 4 x 2 1/2 1.77 1 4 x 2 1.92 1 1/4 5 x 4 3.50 3 31/32 5 x 3 3.18 1 15/32 5 x 2 1/2 3.50 13/16 5 x 2 3.09 2 1/32 6 x 5 5.70 1 1/8 6 x 4 5.24 1 1/2 6 x 3 5.04 2 6 x 2 1/2 5.13 2 1/4 6 x 2 4.89 2 1/2 8 x 6 13.06 1 19/32 8 x 4 12.22 2 19/32 8 x 3 11.79 3 3/32 8 x 2 1/2 12.64 3 3/8 600-RS Coupling with Rolled Tube Stop C x C – Wrot APPROX. DIM. A NOM. SIZE NET WT./LBS. INCHES 1/8 O.D. 0.01 1/16 3/16 O.D. 0.01 3/32 1/8 0.01 1/16 5/16 O.D. 0.01 3/32 1/4 0.01 1/16 3/8 0.01 3/32 1/2 0.03 3/32 5/8 0.04 3/32 3/4 0.06 3/32 7/8 0.09 3/32 1 0.11 3/32 1 1/4 0.16 1/8 1 1/2 0.23 1/8 2 0.41 1/8 2 1/2 0.65 1/8 3 0.93 1/8 3 1/2 1.45 5/32 4 1.93 7/32 601 Coupling without Stop C x C – Wrot APPROX. DIM. BNOM. SIZE NET WT./LBS. INCHES 1/4 0.01 11/16 3/8 0.01 27/32 1/2 0.03 1 5/8 0.04 111/32 3/4 0.06 119/32 1 0.11 129/32 1 1/4 0.16 21/16 1 1/2 0.23 25/16 2 0.41 213/16 2 1/2 0.64 215/16 3 0.86 35/16 3 1/2 1.40 313/16 4 1.84 45/16 5 3.50 55/16 6 5.60 63/16 8 13.68 83/32 701 Reducing Coupling C x C – Cast APPROX. DIM. ANOM. SIZE NET WT./LBS. INCHES 3 x 1 1/4 1.35 23/32 3 x 1 1.64 27/32 AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 33//2299//0044 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 10 COUPLINGS continued Consult price sheet for Made to Order items and for minimum order quantities. 600-DS Coupling with Dimpled Tube Stop C x C – Wrot APPROX. DIM. ANOM. SIZE NET WT./LBS. INCHES 3/16 O.D. 0.01 3/32 1/8 0.01 1/16 5/16 O.D. 0.01 3/32 1/4 0.01 1/16 3/8 0.01 3/32 1/2 0.03 3/32 5/8 0.04 3/32 3/4 0.06 3/32 7/8 0.09 3/32 1 0.11 3/32 1 1/4 0.16 1/8 1 1/2 0.23 1/8 2 0.41 1/8 2 1/2 0.65 1/8 3 0.93 1/8 3 1/2 1.45 5/32 4 1.93 7/32 5 3.53 7/32 6 5.63 7/32 8 14.12 15/32 701-D Drain Coupling C x C – Cast APPROX. DIM. ANOM. SIZE NET WT./LBS. INCHES 1/2 0.08 1/4 3/4 0.14 1/4 1 0.22 1/4 702 Eccentric Coupling C x C–Cast APPROX. DIM. ANOM. SIZE NET WT./LBS. INCHES 3/4 x 1/2 0.10 17/32 1 x 3/4 0.18 1/4 1 1/4 x 1 0.25 1/4 1 1/4 x 3/4 0.24 9/32 724-5-A Hy-Set Hanger Coupling C – Cast APPROX. DIM. C DIM. DNOM. SIZE NET WT./LBS. INCHES INCHES 1/2 0.05 1 5/8 23/32 3/4 0.09 1 5/8 27/32 1 0.13 1 5/8 1 AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 33//2200//0044 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 11 736 Cross-Over Coupling C x C – Cast APPROX. DIM. A NOM. SIZE NET WT./LBS. INCHES 1/2 0.27 1 7/16 3/4 0.60 1 29/32 COUPLINGS continued 735 Cross C x C x C x C – Cast APPROX. DIM. A NOM. SIZE NET WT./LBS. INCHES 3/8 0.09 3/8 1/2 0.15 7/16 3/4 0.30 9/16 1 0.54 23/32 1 1/4 0.78 7/8 1 1/2 1.05 1 2 2.00 1 1/4 2 1/2 2.96 1 1/2 CROSSES ELBOWS 606 45°Elbow C x C – Wrot APPROX. DIM. C DIM. DNOM. SIZE NET WT./LBS. INCHES INCHES 1/8 0.01 1/4 1/4 1/4 0.02 9/32 9/32 3/8 0.03 3/16 3/16 1/2 0.04 9/32 9/32 5/8 0.09 15/32 15/32 3/4 0.10 11/32 11/32 7/8 0.20 11/16 11/16 1 0.16 3/8 3/8 1 1/4 0.25 17/32 17/32 1 1/2 0.35 19/32 19/32 2 0.65 25/32 25/32 2 1/2 1.07 29/32 29/32 3 1.58 1 1/8 11/8 4 3.35 1 7/16 17/16 5 11.05 1 9/16 19/16 6 16.95 2 2 8 23.00 2 9/32 29/32 606-2 45° Fitting Elbow Ftg x C – Wrot APPROX. DIM. B DIM. CNOM. SIZE NET WT./LBS. INCHES INCHES 1/4 0.02 9/16 1/4 1/2 0.04 3/4 7/32 5/8 0.08 1 1/8 13/32 3/4 0.10 1 1/16 5/16 1 0.16 1 7/32 15/32 1 1/4 0.25 1 19/32 17/32 1 1/2 0.35 1 25/32 19/32 2 0.65 2 3/16 25/32 2 1/2 1.07 2 3/16 29/32 3 1.55 2 19/32 15/32 Consult price sheet for Made to Order items and for minimum order quantities. AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 33//2299//0044 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 12 ELBOWS continued Consult price sheet for Made to Order items and for minimum order quantities. 706-2 45° Fitting Elbow Ftg x C – Cast APPROX. DIM. B DIM. CNOM. SIZE NET WT./LBS. INCHES INCHES 4 4.31 311/32 15/16 607 90° Elbow – Close Rough C x C – Wrot APPROX. DIM. C DIM. DNOM. SIZE NET WT./LBS. INCHES INCHES 1/8 0.01 13/32 13/32 1/4 0.02 9/32 9/32 3/8 0.03 1/2 1/2 1/2 0.04 3/8 3/8 1/2 x 3/8 0.04 9/16 21/32 3/4 0.10 17/32 17/32 3/4 x 5/8 0.12 29/32 7/8 3/4 x 1/2 0.10 17/32 3/4 1 0.21 23/32 23/32 1 x 3/4 0.16 23/32 5/8 1 1/4 0.31 11/32 11/32 1 1/4 x 1 0.31 15/8 115/32 1 1/2 0.46 17/32 17/32 1 1/2 x 1 1/4 0.35 15/32 13/32 2 0.84 11/2 11/2 2 x 1 1/2 0.58 17/16 11/4 2 1/2 1.41 127/32 127/32 3 2.07 23/32 23/32 3 1/2 2.94 23/8 23/8 4 4.23 225/32 225/32 5 7.74 27/8 27/8 6 10.95 37/16 37/16 8 29.50 423/32 423/32 707 90°Elbow – Close Rough C x C – Cast APPROX. DIM. C DIM. DNOM. SIZE NET WT./LBS. INCHES INCHES 1 1/4 x 1 0.42 1 5/8 115/32 1 1/4 x 3/4 0.34 9/16 13/16 1 1/4 x 1/2 0.28 15/32 27/32 1 1/2 x 1 0.54 11/16 1 1 1/2 x 3/4 0.42 19/32 31/32 1 1/2 x 1/2 0.40 5/8 29/32 2 x 1 1/4 0.86 7/8 11/4 2 x 1 0.78 3/4 11/4 2 x 3/4 0.69 5/8 11/4 2 1/2 x 2 2.16 1 3/16 19/32 3 x 2 1/2 2.26 1 11/16 11/2 3 x 2 2.68 1 3/8 19/16 4 x 3 5.18 1 29/32 215/32 607-I 90°Elbow – Intermediate Radius C x C – Wrot APPROX. DIM. C DIM. D NOM. SIZE NET WT./LBS. INCHES INCHES 1/2 0.06 19/32 19/32 5/8 0.09 7/8 7/8 3/4 0.14 13/16 3/16 1 0.24 1 1/16 11/16 607-LT 90°Elbow – Long Radius C x C – Wrot APPROX. DIM. C DIM. DNOM. SIZE NET WT./LBS. INCHES INCHES 3/16 O.D. 0.01 13/32 13/32 1/8 0.01 13/32 13/32 5/16 O.D. 0.02 9/16 9/16 1/4 0.02 17/32 17/32 1/4 x 1/8 0.01 19/32 1/2 3/8 0.04 23/32 23/32 1/2 0.08 7/8 7/8 1/2 x 3/8 0.06 13/16 13/16 1/2 x 1/4 0.03 25/32 21/32 5/8 0.10 1 3/32 13/32 5/8 x 1/2 0.09 1 1/16 11/16 3/4 0.16 1 1/8 11/8 3/4 x 5/8 0.13 1 1/4 13/32 3/4 x 1/2 0.10 1 1/8 11/16 7/8 0.28 1 19/32 119/32 1 0.28 1 7/16 17/16 1 x 3/4 0.20 1 1/4 11/8 1 x 5/8 0.15 1 13/32 13/32 1 1/4 0.42 1 7/8 17/8 1 1/4 x 1 0.33 1 25/32 11/2 1 1/2 0.66 2 1/4 21/4 2 1.23 2 15/16 215/16 2 1/2 1.96 3 11/16 311/16 3 2.93 4 1/32 41/32 4 5.95 5 1/4 51/4 AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 33//2299//0044 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 13 Consult price sheet for Made to Order items and for minimum order quantities. 607-2 90°Fitting Elbow–Close Rough Ftg x C – Wrot APPROX. DIM. B DIM. CNOM. SIZE NET WT./LBS. INCHES INCHES 1/4 0.02 3/4 3/8 3/8 0.03 15/16 1/2 1/2 0.04 31/32 3/8 5/8 0.07 1 7/32 17/32 3/4 0.10 1 11/32 17/32 1 0.20 1 3/4 27/32 1 1/4 0.33 2 1/8 11/32 1 1/2 0.46 2 13/32 17/32 2 0.84 2 27/32 11/2 2 1/2 1.39 3 15/32 129/32 3 2.10 3 13/16 23/32 4 4.00 4 3/4 225/32 607-2-I 90°Fitting Elbow – Intermediate Radius Ftg x C – Wrot APPROX. DIM. B DIM. CNOM. SIZE NET WT./LBS. INCHES INCHES 1/2 0.06 1 5/32 19/32 5/8 0.09 1 9/16 7/8 3/4 0.14 1 5/8 13/16 1 0.24 2 1/32 11/16 607-2-LT 90°Fitting Elbow – Long Radius Ftg x C – Wrot APPROX. DIM. B DIM. CNOM. SIZE NET WT./LBS. INCHES INCHES 1/8 0.01 13/32 1/2 1/4 0.02 1 1/8 3/4 3/8 0.05 1 1/8 7/8 1/2 0.08 1 9/16 13/32 1/2 x 3/8 0.06 1 5/16 13/16 1/2 x 1/4 0.03 1 1/4 5/8 5/8 0.10 1 25/32 13/32 3/4 0.16 1 15/16 11/8 1 0.31 2 1/2 121/32 1 1/4 0.43 2 29/32 17/8 1 1/2 0.66 2 13/32 21/4 1 1/2 x 1 1/4 0.50 3 3/8 23/32 2 1.27 4 11/32 231/32 2 1/2 2.16 5 7/32 311/16 3 3.10 5 3/4 41/32 607-2-2 90°Fitting Elbow–Close Rough Ftg x Ftg – Wrot APPROX. DIM. BNOM. SIZE NET WT./LBS. INCHES 1/2 0.04 1 1/16 3/4 0.12 1 15/32 1 0.20 1 23/32 1 1/4 0.33 2 1/8 1 1/2 0.46 2 13/32 2 0.82 2 27/32 3 2.12 3 7/8 ELBOWS continued 607-2-2-LT 90°Fitting Elbow – Long Radius Ftg x Ftg – Wrot APPROX. DIM. BNOM. SIZE NET WT./LBS. INCHES 1/4 0.02 27/32 3/8 0.04 1 1/8 1/2 0.08 1 19/32 5/8 0.10 1 11/16 3/4 0.16 1 15/16 1 0.31 2 1/2 1 1/4 0.43 2 29/32 1 1/2 0.65 3 7/16 2 1.25 4 11/32 707-2-4 90°Fitting Elbow Ftg x M – Cast APPROX. DIM. B DIM. ENOM. SIZE NET WT./LBS. INCHES INCHES 1/2 0.12 7/8 25/32 AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 33//2299//0044 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 14 ELBOWS continued Consult price sheet for Made to Order items and for minimum order quantities. 707-3 90°Elbow C x F – Cast APPROX. DIM. C DIM. ENOM. SIZE NET WT./LBS. INCHES INCHES 1/4 0.06 13/32 9/16 3/8 0.09 7/16 11/16 3/8 x 1/2 0.13 9/16 13/16 1/2 0.12 7/16 13/16 1/2 x 3/4 0.18 11/16 15/16 1/2 x 3/8 0.09 1/2 13/16 1/2 x 1/4 0.10 3/8 23/32 3/4 0.18 21/32 15/16 3/4 x 1 0.35 13/16 11/8 3/4 x 1/2 0.20 9/16 15/16 1 0.43 25/32 11/4 1 x 3/4 0.35 11/16 13/16 1 x 1/2 0.26 9/16 11/8 1 1/4 0.67 1 11/2 1 1/4 x 3/4 0.47 9/16 111/16 1 1/2 0.89 11/8 15/8 2 1.46 13/8 115/16 707-3-5 90°Drop Elbow C x F – Cast NOM. APPROX. DIM. A DIM. C DIM. E SIZE NET WT./LBS. INCHES INCHES INCHES 3/8 0.12 11/32 7/16 11/16 3/8 x 1/2 0.18 11/32 9/16 13/16 1/2 0.15 13/32 9/16 7/8 1/2 x 3/8 0.17 3/8 1/2 13/16 3/4 0.28 17/32 21/32 15/16 3/4 x 1/2 0.24 17/32 9/16 15/16 1 0.49 5/8 25/32 11/4 707-3-5-A 90°Hy-Set Elbow C x F – Cast APPROX. DIM. C DIM. ENOM. SIZE NET WT./LBS. INCHES INCHES 1/2 0.21 9/16 7/8 707-3-6 90°Union Elbow C x F – Cast APPROX. DIM. A DIM. E NOM. SIZE NET WT./LBS. INCHES INCHES 1/2 0.31 11/8 7/8 3/4 0.49 17/16 1 1 0.79 17/8 11/4 707-4 90°Elbow C x M – Cast APPROX. DIM. C DIM. ENOM. SIZE NET WT./LBS. INCHES INCHES 3/8 0.08 5/16 7/8 1/2 0.12 7/16 15/32 1/2 x 3/4 0.18 9/16 15/32 1/2 x 3/8 0.10 5/16 15/16 3/4 0.21 9/16 111/32 3/4 x 1 0.33 21/32 113/32 3/4 x 1/2 0.18 7/16 17/32 1 0.43 23/32 15/8 1 1/4 0.58 7/8 111/16 1 1/2 0.81 1 131/32 2 1.38 11/4 29/32 707-4-6 90°Union Elbow C x M – Cast APPROX. DIM. A DIM. ENOM. SIZE NET WT./LBS. INCHES INCHES 3/8 0.21 1 3/32 13/16 1/2 0.30 1 1/32 11/2 3/4 0.49 1 5/16 113/16 1 0.72 1 23/32 15/8 1 1/4 1.16 1 3/4 127/32 707-5 90°Drop Elbow C x C – Cast APPROX. DIM. A DIM. C NOM. SIZE NET WT./LBS. INCHES INCHES 1/2 0.13 13/32 7/16 3/4 0.24 17/32 9/16 707-5-A 90°Hy-Set Elbow C x C – Cast NOM. APPROX. DIM. A DIM. C DIM. DSIZE NET WT./LBS. INCHES INCHES INCHES 1/2 0.13 31/32 7/16 15/32 3/4 0.21 1 5/16 9/16 9/16 707-6 90°Union Elbow C x C – Cast APPROX. DIM. A DIM. CNOM. SIZE NET WT./LBS. INCHES INCHES 3/8 0.17 31/32 5/16 1/2 0.24 1 7/16 3/4 0.39 1 17/32 9/16 1 0.64 1 21/32 23/32 1 1/4 1.07 1 19/32 23/32 708 90°Flanged Sink Elbow C x F – Cast NOM. APPROX. DIM. A DIM. C DIM. FSIZE NET WT./LBS. INCHES INCHES INCHES 1/2 0.20 7/8 9/16 13/4 764 90°Double Elbow C x C x C – Cast APPROX. DIM. C DIM. D NOM. SIZE NET WT./LBS. INCHES INCHES 1 x 3/4 x 3/4 0.33 3/4 21/32 AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 33//2299//0044 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 15 ELBOWS continued Consult price sheet for Made to Order items and for minimum order quantities. FITTING REDUCERS APPROX. DIM. B NOM. SIZE NET WT./LBS. INCHES 4 x 3 1/2 2.09 2 5/8 4 x 3 2.00 3 1/32 4 x 2 1/2 1.56 3 1/32 4 x 2 1.76 3 13/32 5 x 4 3.30 3 9/16 5 x 3 2.97 4 1/16 5 x 2 1/2 3.30 4 11/32 5 x 2 2.88 4 11/16 6 x 5 5.56 4 3/16 6 x 4 5.09 4 9/16 6 x 3 4.67 5 1/16 6 x 2 1/2 4.47 5 11/32 6 x 2 4.51 5 19/32 8 x 6 12.33 5 15/32 8 x 5 10.35 5 15/16 8 x 4 11.10 6 7/16 8 x 3 10.63 6 15/16 8 x 2 1/2 11.41 7 3/16 8 x 2 10.86 7 7/16 741 Companion Flange C – Cast NOM. APPROX. DIM. B DIM. F DIM. G DIM. W SIZE NET WT./LBS. INCHES INCHES INCHES INCHES 1/2 0.55 1/8 31/2 3/16 23/8 3/4 0.71 1/8 37/8 3/16 23/4 1 1.26 1/8 41/4 1/4 31/8 1 1/4 1.42 1/8 45/8 1/4 31/2 1 1/2 1.82 1/8 5 5/16 37/8 2 2.76 1/8 6 3/8 43/4 2 1/2 4.29 1/8 7 3/8 51/2 3 5.26 1/8 71/2 7/16 6 4 7.60 1/8 9 7/16 71/2 5 9.04 1/8 10 7/16 81/2 6 12.68 1/8 11 1/2 91/2 NOTE:Dim. B = Tube Stop to Flange Face 600-2 Fitting Reducer Ftg x C – Wrot APPROX. DIM. BNOM. SIZE NET WT./LBS. INCHES 1/4 x 1/8 0.01 15/32 3/8 x 1/4 0.01 19/32 3/8 x 1/8 0.01 25/32 1/2 x 3/8 0.03 11/16 1/2 x 1/4 0.02 25/32 5/8 x 1/2 0.04 7/8 5/8 x 3/8 0.04 31/32 5/8 x 1/4 0.03 1 1/32 3/4 x 5/8 0.06 31/32 3/4 x 1/2 0.06 1 1/8 3/4 x 3/8 0.05 1 1/8 3/4 x 1/4 0.05 1 3/32 1 x 3/4 0.10 1 7/32 1 x 5/8 0.09 1 3/8 1 x 1/2 0.09 1 1/4 1 x 3/8 0.08 1 9/32 1 1/4 x 1 0.15 1 5/16 1 1/4 x 3/4 0.16 1 1/2 1 1/4 x 1/2 0.13 1 3/8 1 1/2 x 1 1/4 0.23 1 13/32 1 1/2 x 1 0.21 1 5/8 1 1/2 x 3/4 0.20 1 7/8 1 1/2 x 1/2 0.16 1 19/32 2 x 1 1/2 0.40 1 31/32 2 x 1 1/4 0.34 2 3/32 2 x 1 0.35 1 27/32 2 x 3/4 0.35 1 27/32 2 x 1/2 0.34 1 31/32 2 1/2 x 2 0.65 1 31/32 2 1/2 x 1 1/2 0.65 2 3/8 2 1/2 x 1 1/4 0.60 2 7/32 2 1/2 x 1 0.78 2 9/32 3 x 2 1/2 1.03 2 1/4 3 x 2 0.99 2 9/16 3 x 1 1/2 0.81 2 19/32 3 x 1 1/4 1.29 3 1/4 3 1/2 x 3 1.48 2 11/32 Continues… FLANGES – CLASS 125 AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 33//2299//0044 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 16 Consult price sheet for Made to Order items and for minimum order quantities. FLANGES – CLASS 150 771 Companion Flange C – Cast NOM. APPROX. DIM. B DIM. F DIM. G DIM. W SIZE NET WT./LBS. INCHES INCHES INCHES INCHES 3/4 1.15 1/8 37/8 11/32 23/4 1 1.59 1/8 41/4 3/8 31/8 1 1/4 1.91 1/8 45/8 13/32 31/2 1 1/2 2.59 1/8 5 7/16 37/8 2 4.10 1/8 6 1/2 43/4 2 1/2 6.22 1/8 7 9/16 51/2 3 8.03 1/8 71/2 5/8 6 4 11.85 1/8 9 11/16 71/2 5 15.69 1/8 10 3/4 81/2 6 20.32 1/8 11 13/16 91/2 NOTE:Dim. B = Tube Stop to Flange Face 775 Threaded Companion Flange F – Cast NOM. APPROX. DIM. E DIM. F DIM. W SIZE NET WT./LBS. INCHES INCHES INCHES 2 4.31 1 6 43/4 2 1/2 6.30 11/8 751/2 3 7.13 13/16 71/2 6 4 10.20 15/16 971/2 PLUGS 616 Fitted Plug Ftg - Wrot APPROX. DIM. ANOM. SIZE NET WT./LBS. INCHES 3/8 0.016 1/16 1/2 0.02 3/32 3/4 0.24 1/8 638 Return Bend C x C – Wrot APPROX. DIM. E DIM. J NOM. SIZE NET WT./LBS. INCHES INCHES 1/8 0.02 21/32 1 1/4 0.04 21/32 11/2 3/8 0.08 11/32 11/2 1/2 0.13 11/2 2 3/4 0.26 119/32 21/2 1 0.44 23/32 3 1 1/4 0.70 23/4 4 1 1/2 1.04 35/32 41/2 2 1.92 329/32 51/2 739 Return Bend – Closed C x C – Cast APPROX. DIM. E DIM. J NOM. SIZE NET WT./LBS. INCHES INCHES 3/4 0.29 15/32 15/16 RETURN BENDS STRAPS TEES 623 Copper Hanger Strap APPROX.SIZE NET WT./LBS. 3/4" Wide x 25 Ft. Roll 1.93 624 Tube Strap APPROX.NOM. SIZE NET WT./LBS. 1/8 0.01 1/4 0.01 3/8 0.01 1/2 0.01 5/8 0.02 3/4 0.02 1 0.02 1 1/4 0.03 1 1/2 0.03 2 0.04 705 Baseboard Tee C x F x C – Cast APPROX. DIMENSIONS NET WT. INCHES NOM. SIZE LBS. C D E 1/2 x 1/8 x 3/4 0.15 7/16 9/16 11/16 1/2 x 1/8 x 1/2 0.11 7/16 7/16 9/16 3/4 x 1/8 x 1 0.29 5/8 3/4 13/16 3/4 x 1/8 x 3/4 0.19 9/16 9/16 11/16 1 x 1/8 x 1 0.32 23/32 23/32 3/4 11/4x 1/8 x 11/4 0.51 7/8 7/8 15/16 AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 33//2299//0044 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 17 Consult price sheet for Made to Order items and for minimum order quantities. TEES continued 705-D Vent Elbow C x C – Cast APPROX. DIMENSIONSNET WT. INCHESNOM. SIZE LBS. C D S 1/2 0.10 7/16 7/16 25/32 3/4 0.20 9/16 9/16 29/32 1 0.31 23/32 23/32 11/32 710-3 Tee F x F x C – Cast APPROX. DIMENSIONS NET WT. INCHES NOM. SIZE LBS. C E S 1/2 0.20 9/16 7/8 7/8 3/4 0.37 11/16 11 3/4 x 3/4 x 1/2 0.31 11/16 31/32 31/32 3/4 x 1/2 x 3/4 0.29 11/16 1 15/16 3/4 x 1/2 x 1/2 0.27 11/16 31/32 7/8 710-3-4 Tee M x F x C – Cast APPROX. DIMENSIONSNET WT. INCHESNOM. SIZE LBS. C E S 3/4 0.34 11/16 111/32 1 3/4 x 3/4 x 1/2 0.33 11/16 17/32 31/32 611 Tee C x C x C – Wrot APPROX. DIMENSIONSNET WT. INCHESNOM. SIZE LBS. C F G 3/16O.D.0.01 7/32 7/32 7/32 1/8 0.02 1/4 1/4 7/32 1/8 x 1/8 x 1/4 0.02 13/32 13/32 1/4 1/8 x 1/8 x 3/16O.D.0.01 1/4 1/4 5/16 1/8 x 3/16O.D. x 1/8 0.01 1/4 11/32 7/32 5/16O.D. 0.02 3/8 3/8 5/16 5/16O.D. x 5/16O.D. x 1/4 0.02 3/8 3/8 1/4 5/16O.D. x 5/16O.D. x 1/8 0.02 3/8 3/8 13/32 5/16O.D. x 1/8 x 5/16O.D. 0.02 3/8 13/32 5/16 5/16O.D. x 1/8 x 1/8 0.02 3/8 13/32 13/32 1/4 0.02 5/16 5/16 1/4 1/4 x 1/4 x 1/2 0.06 19/32 19/32 3/8 1/4 x 1/4 x 3/8 0.04 17/32 17/32 11/32 1/4 x 1/4 x 5/16O.D.0.02 5/16 5/16 5/16 1/4 x 1/4 x 1/8 0.02 5/16 5/16 13/32 1/4 x 1/4 x 3/16O.D.0.02 5/16 5/16 7/16 1/4 x 5/16O.D. x 1/4 0.02 5/16 3/8 1/4 1/4 x 1/8 x 1/4 0.02 5/16 13/32 1/4 1/4 x 1/8 x 1/8 0.02 5/16 13/32 3/8 3/8 0.04 11/32 11/32 11/32 3/8 x 3/8 x 1/2 0.07 17/32 17/32 3/8 3/8 x 3/8 x 1/4 0.04 11/32 11/32 15/32 3/8 x 3/8 x 5/16O.D.0.04 11/32 11/32 11/32 3/8 x 3/8 x 1/8 0.04 11/32 11/32 11/32 3/8 x 1/4 x 3/8 0.04 11/32 17/32 11/32 3/8 x 1/4 x 1/4 0.04 11/32 17/32 15/32 3/8 x 1/4 x 1/8 0.04 11/32 17/32 9/16 3/8 x 1/8 x 3/8 0.04 11/32 19/32 11/32 3/8 x 1/8 x 1/8 0.04 11/32 19/32 19/32 1/2 0.06 11/32 11/32 11/32 1/2 x 1/2 x 1 0.29 1 1 21/32 1/2 x 1/2 x 3/4 0.12 17/32 17/32 11/32 1/2 x 1/2 x 5/8 0.11 5/8 5/8 7/16 1/2 x 1/2 x 3/8 0.07 5/16 5/16 13/32 1/2 x 1/2 x 1/4 0.06 5/16 5/16 9/16 1/2 x 3/8 x 1/2 0.07 7/16 17/32 3/8 1/2 x 3/8 x 3/8 0.06 5/16 17/32 13/32 1/2 x 3/8 x 1/4 0.06 5/16 17/32 17/32 1/2 x 1/4 x 3/8 0.06 5/16 5/8 9/16 Continues… APPROX. DIMENSIONSNET WT. INCHESNOM. SIZE LBS. C F G 5/8 0.12 7/16 7/16 7/16 5/8 x 5/8 x 3/4 0.15 23/32 23/32 1/2 5/8 x 5/8 x 1/2 0.11 7/16 7/16 13/32 5/8 x 5/8 x 3/8 0.09 7/16 7/16 5/8 5/8 x 5/8 x 1/4 0.09 7/16 7/16 3/4 5/8 x 1/2 x 5/8 0.10 7/16 5/8 7/16 5/8 x 1/2 x 1/2 0.09 7/16 19/32 13/32 5/8 x 3/8 x 5/8 0.10 7/16 3/4 7/16 5/8 x 3/8 x 3/8 0.09 7/16 3/4 5/8 3/4 0.15 1/2 1/2 1/2 3/4 x 3/4 x 1 0.22 23/32 23/32 1/2 3/4 x 3/4 x 5/8 0.16 17/32 17/32 11/16 3/4 x 3/4 x 1/2 0.12 7/16 7/16 17/32 3/4 x 3/4 x 3/8 0.12 7/16 7/16 21/32 3/4 x 3/4 x 1/4 0.12 13/32 13/32 23/32 3/4 x 3/4 x 1/8 0.12 7/16 7/16 13/16 3/4 x 5/8 x 3/4 0.15 17/32 11/16 1/2 3/4 x 5/8 x 5/8 0.15 17/32 23/32 11/16 3/4 x 1/2 x 3/4 0.15 17/32 25/32 1/2 3/4 x 1/2 x 1/2 0.12 13/32 19/32 1/2 3/4 x 1/2 x 3/8 0.12 7/16 21/32 21/32 3/4 x 3/8 x 3/4 0.15 17/32 17/32 1/2 3/4 x 3/8 x 1/2 0.12 7/16 23/32 17/32 3/4 x 3/8 x 3/8 0.12 7/16 23/32 21/32 7/8 0.31 23/32 23/32 23/32 1 0.30 11/16 11/16 21/32 1 x 1 x 1 1/2 0.60 1 11/32 111/32 31/32 1 x 1 x 1 1/4 0.42 1 1 29/32 1 x 1 x 3/4 0.27 9/16 9/16 21/32 1 x 1 x 5/8 0.26 9/16 9/16 7/8 1 x 1 x 1/2 0.23 15/32 15/32 23/32 1 x 1 x 3/8 0.23 15/32 15/32 29/32 1 x 1 x 1/4 0.23 15/32 15/32 1 1 x 3/4 x 1 0.29 11/16 7/8 21/32 1 x 3/4 x 3/4 0.26 9/16 23/32 3/4 1 x 3/4 x 1/2 0.22 15/32 21/32 23/32 Continues… NOTE: Tee sizes are read Run x Run x Outlet. APPROX. DIMENSIONS NET WT. INCHES NOM. SIZE LBS. C F G 1 x 1/2 x 1 0.29 11/16 1 21/32 1 x 1/2 x 3/4 0.27 9/16 13/16 3/4 1 x 1/2 x 1/2 0.22 15/32 25/32 23/32 1 1/4 0.43 13/16 3/16 13/16 1 1/4 x 1 1/4 x 2 1.13 1 30/32 130/32 13/32 1 1/4 x 1 1/4 x 1 1/2 0.60 1 3/16 13/16 29/32 1 1/4 x 1 1/4 x 1 0.45 25/32 25/32 29/32 1 1/4 x 1 1/4 x 3/4 0.37 21/32 21/32 3/4 1 1/4 x 1 1/4 x 1/2 0.30 1/2 1/2 25/32 1 1/4 x 1 1/4 x 3/8 0.34 23/32 23/32 29/32 1 1/4 x 1 x 1 1/4 0.43 13/16 11/32 13/16 1 1/4 x 1 x 1 0.47 25/32 7/8 29/32 1 1/4 x 1 x 3/4 0.35 21/32 25/32 7/8 1 1/4 x 1 x 1/2 0.30 1/2 5/8 29/32 1 1/4 x 3/4 x 1 1/4 0.42 13/16 11/8 13/16 1 1/4 x 3/4 x 1 0.45 25/32 11/32 29/32 1 1/4 x 3/4 x 3/4 0.37 21/32 15/16 7/8 1 1/4 x 3/4 x 1/2 0.30 1/2 3/4 29/32 1 1/4 x 1/2 x 1 1/4 0.41 13/16 17/32 13/16 1 1/2 0.61 31/32 31/32 29/32 1 1/2 x 1 1/2 x 2 1.11 1 25/32 125/32 13/32 1 1/2 x 1 1/2 x 1 1/4 0.62 29/32 29/32 11/16 1 1/2 x 1 1/2 x 1 0.55 11/16 11/16 7/8 1 1/2 x 1 1/2 x 3/4 0.45 11/16 11/16 11/32 1 1/2 x 1 1/2 x 1/2 0.40 1/2 1/2 11/32 1 1/2 x 1 1/4 x 1 1/2 0.62 1 1/32 13/16 29/32 1 1/2 x 1 1/4 x 1 1/4 0.62 31/32 13/32 31/32 1 1/2 x 1 1/4 x 1 0.51 25/32 111/32 1 1/2 x 1 1/4 x 3/4 0.49 11/16 13/16 11/32 1 1/2 x 1 1/4 x 1/2 0.41 1/2 25/32 11/32 1 1/2 x 1 x 1 1/2 0.59 1 1/32 111/32 29/32 1 1/2 x 1 x 1 1/4 0.63 29/32 11/8 11/16 1 1/2 x 1 x 1 0.54 25/32 11/16 11/32 1 1/2 x 1 x 3/4 0.44 11/16 31/32 15/16 1 1/2 x 1 x 1/2 0.39 1/2 25/32 11/32 1 1/2 x 3/4 x 1 1/2 0.62 11/32 17/16 11/16 1 1/2 x 3/4 x 1 1/4 0.58 29/32 111/32 11/16 1 1/2 x 3/4 x 1 0.54 25/32 11/4 11/32 1 1/2 x 3/4 x 3/4 0.47 11/16 13/32 29/32 1 1/2 x 3/4 x 1/2 0.39 1/2 29/32 31/32 1 1/2 x 1/2 x 1 1/2 0.62 1 1/32 113/32 31/32 Continues… APPROX. DIMENSIONS NET WT. INCHES NOM. SIZE LBS. C F G 2 1.30 19/32 19/32 11/32 2 x 2 x 2 1/2 2.34 2 2 121/32 2 x 2 x 1 1/2 1.17 11/4 11/4 123/32 2 x 2 x 1 1/4 1.12 9/32 9/32 17/8 2 x 2 x 1 0.90 27/32 27/32 11/4 2 x 2 x 3/4 0.88 19/32 19/32 11/4 2 x 2 x 1/2 1.17 11/4 11/4 21/4 2 x 1 1/2 x 2 1.16 19/32 17/8 111/32 2 x 1 1/2 x 1 1/2 1.15 11/4 13/4 123/32 2 x 1 1/2 x 1 1/4 1.15 7/32 13/4 111/32 2 x 1 1/2 x 3/4 0.83 21/32 15/16 17/32 2 x 1 1/2 x 1/2 1.12 11/4 125/32 21/4 2 x 1 1/4 x 2 1.58 19/32 115/32 19/32 2 x 1 1/4 x 1 1/2 1.16 11/4 131/32 123/32 2 x 1 1/4 x 1 1/4 1.19 15/16 111/32 111/32 2 x 1 1/4 x 1 0.90 27/32 19/32 111/32 2 x 1 1/4 x 3/4 0.85 21/32 118/27 2 x 1 x 2 1.11 11/8 125/32 11/4 2 x 1 x 1 0.89 27/32 19/32 111/32 2 x 3/4 x 2 1.15 19/32 23/16 11/4 2 x 1/2 x 2 1.15 19/32 23/8 11/4 2 1/2 2.40 15/8 15/8 15/8 2 1/2 x 2 1/2 x 2 1.97 15/16 15/16 121/32 2 1/2 x 2 1/2 x 1 1/2 1.53 13/32 13/32 121/32 2 1/2 x 2 1/2 x 1 1/4 1.72 13/32 13/32 127/32 2 1/2 x 2 1/2 x 1 1.34 25/32 25/32 111/16 2 1/2 x 2 1/2 x 3/4 1.34 25/32 25/32 113/16 2 1/2 x 2 1/2 x 1/2 1.34 25/32 25/32 21/8 2 1/2 x 2 x 2 1/2 1.99 121/32 23/32 121/32 2 1/2 x 2 x 2 1.95 111/32 15/8 123/32 2 1/2 x 2 x 1 1/2 1.57 13/32 213/32 121/32 2 1/2 x 2 x 1 1/4 1.57 13/32 119/32 127/32 2 1/2 x 2 x 1 1.40 25/32 19/32 13/4 2 1/2 x 2 x 3/4 1.35 25/32 19/32 127/32 2 1/2 x 1 1/2 x 1 1/2 1.76 13/32 113/32 13/8 2 1/2 x 1 1/4 x 2 1/2 2.40 121/32 27/16 121/32 2 1/2 x 1 x 2 1/2 2.04 121/32 223/32 121/32 2 1/2 x 3/4 x 2 1/2 2.00 121/32 211/16 121/32 2 1/2 x 1/2 x 2 1/2 2.46 11/2 27/32 11/2 Continues… APPROX. DIMENSIONS NET WT. INCHES NOM. SIZE LBS. C F G 3 3.15 1 7/8 17/8 21/32 3 x 3 x 2 1/2 3.55 1 29/32 129/32 23/8 3 x 3 x 2 3.19 1 15/32 115/32 131/32 3 x 3 x 1 1/2 3.08 1 15/32 115/32 29/32 3 x 3 x 1 1/4 3.10 1 15/32 115/32 27/16 3 x 3 x 1 2.12 27/32 27/32 131/32 3 x 3 x 3/4 2.39 27/32 27/32 23/16 3 x 3 x 1/2 1.82 27/32 27/32 23/8 3 x 2 1/2 x 3 3.08 1 7/8 23/8 131/32 3 x 2 1/2 x 2 1/2 3.12 1 29/32 211/32 25/32 3 x 2 1/2 x 2 2.28 1 15/32 127/32 131/32 3 x 2 x 3 3.62 1 29/32 217/32 115/16 3 x 2 x 2 1/2 3.56 1 29/32 29/16 25/16 3 x 2 x 2 3.22 1 15/32 131/32 131/32 3 x 1 1/2 x 3 3.13 1 29/32 225/32 23/32 3 x 1 1/4 x 3 3.63 1 29/32 225/32 115/16 3 x 1 x 3 3.20 1 31/32 219/32 23/16 3 x 3/4 x 3 3.55 1 31/32 229/32 23/16 3 1/2 5.20 2 17/32 217/32 217/32 4 8.12 2 13/32 213/32 217/32 4 x 4 x 3 6.70 2 1/32 21/32 221/32 4 x 4 x 2 1/2 6.65 2 1/32 21/32 35/32 4 x 4 x 2 5.82 1 15/32 115/32 27/16 4 x 4 x 1 1/2 3.94 1 11/32 111/32 217/32 4 x 4 x 1 1/4 4.04 1 11/32 111/32 229/32 4 x 4 x 1 3.72 1 1 2 9/16 4 x 4 x 3/4 3.70 1 1 2 11/16 4 x 3 x 4 7.05 2 25/32 37/32 217/32 4 x 3 x 3 5.03 2 1/32 215/32 215/32 4 x 3 x 2 1/2 5.04 2 1/32 215/32 229/32 4 x 3 x 2 5.87 1 15/32 131/32 27/16 4 x 2 1/2 x 4 7.19 2 25/32 315/32 227/32 4 x 2 x 4 7.08 2 25/32 319/32 227/32 Continued on next page. NOTE: Tee sizes are read Run x Run x Outlet. 611 Tee C x C x C – Wrot continued AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 33//2299//0044 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 18 TEES continued Consult price sheet for Made to Order items and for minimum order quantities. 611-HE Heat Exchanger Tee C x C x C – Wrot Tube slips entirely through fitting on small end of run. Sizes same as listed under 611 where tee has one or more reductions on one end of run. 711 Tee C x C x C – Cast APPROX. DIMENSIONS NET WT. INCHES NOM. SIZE LBS. C F G 1 1/4 x 1/2 x 1 0.48 3/4 3/4 7/8 1 1/4 x 1/2 x 1/2 0.50 9/16 5/8 1 1 1/2 x 1/2 x 1 1/4 0.70 7/8 31/32 1 2 x 2 x 3 3.11 121/32 121/32 15/16 2 x 1 x 1 1/2 1.23 1 11/4 11/4 2 x 3/4 x 3/4 0.84 21/32 7/8 11/4 2 1/2 x 2 1/2 x 3 2.98 13/4 13/4 117/32 2 1/2 x 1 1/2 x 2 2.02 11/4 115/32 11/2 2 1/2 x 1 1/2 x 1 1/2 1.76 13/32 113/32 13/8 2 1/2 x 1/2 x 2 1/2 2.46 11/2 27/32 11/2 3 x 3 x 4 6.96 211/32 211/32 123/32 3 x 2 1/2 x 1 1/2 2.53 1 13/32 13/4 3 x 2 x 1 1/2 2.62 1 11/4 13/4 4 x 4 x 6 16.47 37/32 37/32 29/32 4 x 2 x 2 4.64 11/4 13/4 21/4 711-A Supply and Return Tee C x C x C – Cast APPROX. DIMENSIONS NET WT. INCHES NOM. SIZE LBS. C J 1/2 0.17 13/16 1 AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 33//2299//0044 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 19 TEES continued Consult price sheet for Made to Order items and for minimum order quantities. 611 Tee C x C x C – Wrot continued APPROX. DIMENSIONSNET WT. INCHESNOM. SIZE LBS. C F G 5 8.29 227/32 227/32 313/32 5 x 5 x 4 7.09 27/32 29/32 33/16 5 x 5 x 3 5.91 125/32 125/32 33/16 5 x 5 x 2 1/2 5.90 15/16 15/16 33/16 5 x 5 x 2 5.29 11/16 11/16 33/16 5 x 5 x 1 1/2 4.87 11/32 11/32 33/16 5 x 5 x 1 1/4 4.50 11/16 11/16 33/16 5 x 5 x 1 4.20 9/16 9/16 33/16 5 x 4 x 5 8.53 227/32 429/32 313/32 5 x 4 x 4 8.17 21/4 417/32 33/8 5 x 2 x 5 9.47 23/4 51/16 31/2 6 13.50 39/32 39/32 41/32 6 x 6 x 5 11.67 225/32 225/32 41/32 6 x 6 x 4 10.17 29/32 29/32 311/16 6 x 6 x 3 8.92 125/32 125/32 311/16 6 x 6 x 2 1/2 8.11 117/32 117/32 33/4 6 x 6 x 2 7.78 19/32 19/32 311/16 6 x 6 x 1 1/2 6.86 1 1 311/16 6 x 6 x 1 1/4 6.66 29/32 29/32 311/16 6 x 6 x 1 7.19 9/16 9/16 311/16 6 x 6 x 3/4 7.18 9/16 9/16 49/16 6 x 6 x 1/2 7.17 9/16 9/16 411/16 6 x 4 x 6 16.60 33/16 51/8 41/8 6 x 4 x 1 1/2 9.62 15/16 215/16 33/4 8 36.81 41/16 41/16 51/32 8 x 8 x 6 27.86 31/16 31/16 51/8 8 x 8 x 5 24.90 225/32 225/32 415/16 8 x 8 x 4 22.26 21/16 21/16 43/4 8 x 8 x 3 20.01 19/16 19/16 43/4 8 x 8 x 2 1/2 19.02 15/16 15/16 43/4 8 x 8 x 2 18.01 11/16 11/16 43/4 NOTE: Tee sizes are read Run x Run x Outlet. 611-2 Fitting Tee C x Ftg x C – Wrot APPROX. DIMENSIONSNET WT. INCHESNOM. SIZE LBS. B C F 1/2 0.07 11/32 3/8 7/16 3/4 0.15 115/32 1/2 17/32 711-5 Drop Tee C x C x C – Cast APPROX. DIMENSIONS NET WT. INCHES NOM. SIZE LBS. A C 1/2 0.16 3/8 7/16 712 Tee C x C x F – Cast APPROX. DIMENSIONSNET WT. INCHESNOM. SIZE LBS. E F G 3/8 0.11 11/16 7/16 7/16 1/2 0.14 13/16 7/16 7/16 3/4 0.33 1 21/32 21/32 1 0.54 11/4 7/8 7/8 1 1/2 1.08 15/8 11/8 11/8 2 1.74 17/8 13/8 13/8 1/2 x 1/2 x 1/4 0.16 13/16 1/2 1/2 1/2 x 1/2 x 3/8 0.15 13/16 1/2 1/2 1/2 x 1/2 x 3/4 0.23 15/16 11/16 11/16 3/4 x 3/4 x 3/8 0.23 7/8 1/2 1/2 3/4 x 3/4 x 1/2 0.24 57/64 17/32 17/32 1 1/4 x 1 1/4 x 1/2 0.49 11/4 9/16 9/16 1 1/4 x 1 1/4 x 3/4 0.55 15/16 11/16 11/16 1 1/4 x 1 1/4 x 1 0.66 17/16 7/8 7/8 1 x 1 x 1/2 0.34 11/8 9/16 9/16 1 x 1 x 3/4 0.42 13/16 11/16 11/16 1 1/2 x 1 1/2 x 1/2 0.62 13/8 9/16 9/16 1 1/2 x 1 1/2 x 3/4 0.70 17/16 11/16 11/16 1 1/2 x 1 1/2 x 1 0.79 11/2 13/16 13/16 2 x 2 x 1/2 0.97 15/8 17/32 17/32 2 x 2 x 3/4 1.10 111/16 11/16 11/16 2 x 2 x 1 1.23 13/4 13/16 13/16 1/4 0.08 13/16 9/32 9/32 1 1/4 0.76 17/16 11 3/8 x 3/8 x 1/4 0.12 11/16 7/16 7/16 3/4 x 1/2 x 3/4 0.28 1 21/32 11/16 3/4 x 3/4 x 1 0.40 11/8 7/8 7/8 712-5 Drop Tee C x C x F – Cast APPROX. DIMENSIONSNET WT. INCHESNOM. SIZE LBS. A C E 1/2 0.25 3/8 9/16 7/8 3/4 0.38 1/2 21/32 1 713 Tee C x C x M – Cast APPROX. DIMENSIONS NET WT. INCHES NOM. SIZE LBS. E F 1/2 0.15 13/32 7/16 3/4 0.29 19/32 9/16 714 Tee C x F x C – Cast APPROX. DIMENSIONSNET WT. INCHESNOM. SIZE LBS. C E S 1/2 0.18 7/16 9/16 7/8 1/2 x 3/4 x 1/2 0.27 7/16 9/16 13/16 3/4 0.31 9/16 11/16 1 3/4 x 1/2 x 3/4 0.26 9/16 9/16 15/16 1 0.52 23/32 13/16 11/4 1 x 3/4 x 1 0.43 23/32 23/32 13/16 1 x 1/2 x 1 0.42 3/4 3/4 11/8 1 1/4 0.70 7/8 1113/32 1 1/4 x 3/4 x 1 1/4 0.62 7/8 7/8 17/32 1 1/4 x 1/2 x 1 1/4 0.56 7/8 7/8 13/16 1 1/2 1.00 1 11/8 19/16 1 1/2 x 3/4 x 1 1/2 0.88 1 1 113/16 2 1.72 11/4 13/8 17/8 2 x 3/4 x 2 1.57 11/4 11/4 2 2 x 1/2 x 2 1.58 11/4 11/4 2 AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 33//2299//0044 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 20 TEES continued Consult price sheet for Made to Order items and for minimum order quantities. TRAPS 698 Suction Line P-Trap C x C – Wrot A major application of this fitting is on the suction line of a refregeration compressor. The line is looped, by use of the Suction Line P-Trap, to the floor prior to being run vertically upwards to prevent the drainage of oil back to the compressor during shut down periods. Additional P-Traps are used for each 20' or riser pipe. this prevents high velocity build-up as the oil or liquid begins to return to the compressor during this shut down period. APPROX. DIMENSIONSNET WT. INCHESNOM. SIZE LBS. C D J K 1/2 0.36 5 3/8 336 5/8 0.45 5 3/8 27/8 36 3/4 0.58 5 3/8 23/4 36 1 0.92 5 1/4 221/32 36 1 1/4 1.16 5 3/8 27/8 33/4 61/8 1 1/2 2.32 7 5/8 35/8 59 2 3.93 8 3 5/8 697/16 621 Venturi Insert – Wrot Converts any tee into a special purpose venturi or scoop tee APPROX.NOM. SIZE NET WT./LBS. 1/2 0.01 3/4 0.02 1 0.03 1 1/4 0.04 748 90° Y C x C x C – Cast APPROX. DIM. A DIM. B NOM. SIZE NET WT./LBS. INCHES INCHES 1/2 0.11 7/32 7/16 3/4 0.25 7/16 5/8 1 0.61 1/2 13/16 749 45°Y C x C x C – Cast APPROX. DIM. A DIM. B NOM. SIZE NET WT./LBS. INCHES INCHES 1/2 0.15 13/32 7/8 3/4 0.30 117/32 17/32 1 0.55 113/16 115/32 1 1/4 0.81 21/4 17/8 1 1/2 1.14 25/8 21/8 2 2.17 35/16 23/4 AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 33//2299//0044 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 21 Consult price sheet for Made to Order items and for minimum order quantities. UNIONS 733-2 Fitting Union Ftg x C – Cast APPROX. DIM. B NOM. SIZE NET WT./LBS. INCHES 1/2 0.23 19/32 3/4 0.35 15/8 1 0.55 127/32 733-3 Fitting Union C x F – Cast APPROX. DIM. ANOM. SIZE NET WT./LBS. INCHES 1/4 0.14 15/32 3/8 0.19 13/32 1/2 0.26 11/8 3/4 0.37 15/16 1 0.61 17/16 1 1/4 0.98 119/32 1 1/2 1.21 113/16 2 1.90 25/32 733-4 Union C x M – Cast APPROX. DIM. A NOM. SIZE NET WT./LBS. INCHES 1/4 0.13 11/2 3/8 0.20 15/8 1/2 0.28 111/16 1/2 x 3/4 0.35 21/16 3/4 0.43 129/32 1 0.68 21/8 1 1/4 0.95 25/32 1 1/2 1.35 213/32 2 2.17 225/32 2 1/2 4.13 313/32 633-W Union C x C – Wrot APPROX. DIM. ANOM. SIZE NET WT./LBS. INCHES 1/8 0.10 5/8 1/4 0.15 11/16 3/8 0.22 7/16 1/2 0.31 13/32 3/4 0.33 3/8 1 0.54 1/2 733 Union C x C – Cast APPROX. DIM. A NOM. SIZE NET WT./LBS. INCHES 1/4 0.10 11/16 3/8 0.15 7/16 1/2 0.22 13/32 5/8 0.31 21/32 3/4 0.31 3/8 1 0.54 1/2 1 1/4 0.76 1/2 1 1/2 1.04 23/32 2 1.77 1/2 2 1/2 3.25 1 3 4.75 1 5/32 VENTURI Y’s Cast Copper Alloy Flared Fittings 100 Series – Heavy Flared 500 Series – Flared Adapters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Couplings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Elbows . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Nuts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Tees . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 33//2299//0044 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 22 The manufacturing plants at South Glens Falls, NY, Stuarts Draft, VA, Nacogdoches, TX and Reynosa, Mexico manufacture products under a Quality Management System conforming to the current revision of ISO-9001 International Standards AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 33//2299//0044 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 23 104 Heavy Flared Adapter FL x M – Cast APPROX. DIM. LNOM. SIZE NET WT./LBS. INCHES 3/4 0.60 21/2 1 1.24 31/4 503 Flared Adapter FL x F – Cast APPROX. DIM. BNOM. SIZE NET WT./LBS. INCHES 1/2 0.36 17/8 3/4 0.48 21/32 1 1.03 23/4 1 1/2 1.99 37/32 2 3.22 39/16 504 Flared Adapter FL x M – Cast APPROX. DIM. B NOM. SIZE NET WT./LBS. INCHES 1/2 0.29 132/32 3/4 0.58 211/16 1 0.88 33/16 1 1/2 1.89 33/4 2 2.95 415/16 101 Heavy Flared Coupling FL x FL – Cast APPROX. DIM. LNOM. SIZE NET WT./LBS. INCHES 3/4 0.98 3 13/16 1 1.70 5 5/16 501 Flared Coupling FL x FL – Cast APPROX. DIM. BNOM. SIZE NET WT./LBS. INCHES 1/2 0.45 2 3/8 3/4 0.60 2 1/2 1 1.24 3 1/4 1 1/4 2.18 3 1/2 1 1/2 2.65 3 23/32 2 4.03 4 1/4 ADAPTERS COUPLINGS Consult price sheet for Made to Order items and for minimum order quantities. 507 Flared 90°Elbow FL x FL – Cast APPROX. DIM. BNOM. SIZE NET WT./LBS. INCHES 1/2 0.54 15/8 3/4 0.77 131/32 1 1.60 29/16 2 5.39 37/8 507-3 Flared 90°Elbow FL x F – Cast APPROX. DIM. B DIM. E NOM. SIZE NET WT./LBS. INCHES INCHES 1/2 0.49 15/8 11/2 3/4 0.69 115/16 15/8 1 1.43 29/16 21/4 507-4 Flared 90°Elbow FL x M – Cast APPROX. DIM. B DIM. ENOM. SIZE NET WT./LBS. INCHES INCHES 1/2 0.34 111/16 113/32 3/4 0.55 131/32 119/32 1 1.34 23/32 2 1 1/2 2.80 35/16 21/2 ELBOWS 500 Tube Nut – Cast APPROX. DIM. B DIM. LNOM. SIZE NET WT./LBS. INCHES INCHES 3/4 0.20 11/16 11/2 1 0.31 13/8 17/8 TEES 511 Flared Tee FL x FL x FL – Cast APPROX. DIMENSIONS NET WT. INCHES NOM. SIZE LBS. B D K 1/2 0.67 15/8 15/8 15/8 3/4 1.09 2 2 2 1 2.08 25/8 25/8 25/8 AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 33//2299//0044 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 24 NUTS Consult price sheet for Made to Order items and for minimum order quantities. AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 33//2299//0044 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 25 Copper Insert Fittings for Adapters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 Brass Plug . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27 Couplings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 Crimp Rings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 Crimp Tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27 Elbows . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 Fitting Reducers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 Tees . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 Tube Cutter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27 The manufacturing plants at South Glens Falls, NY, Stuarts Draft, VA, Nacogdoches, TX and Reynosa, Mexico manufacture products under a Quality Management System conforming to the current revision of ISO-9001 International Standards PEX600-2 Fitting Reducer FtgxPEX–Wrot APPROX. DIM. ANOM. SIZE NET WT./LBS. INCHES 1/2 0.035 1 5/8 3/4 0.059 1 13/16 PEX611 Tee PEX x PEX x PEX – Wrot APPROX. DIMENSIONS NET WT. INCHES NOM. SIZE LBS. A B C D 1/2 0.070 2 1/4 11/8 11/8 – 3/4 0.097 2 1/2 11/4 11/4 – 1/2 x 1/2 x 3/4 0.112 2 3/4 13/8 11/4 – 3/4 x 1/2 x 1/2 0.097 2 1/2 13/16 115/16 3/4 x 1/2 x 3/4 0.112 2 5/8 11/4 11/4 13/8 3/4 x 3/4 x 1/2 0.099 2 3/8 13/16 1– PEX198 Crimp Rings (Black) APPROX. DIM. ANOM. SIZE NET WT./LBS. INCHES 1/2 0.013 0.325 3/4 0.017 0.325 PEX600-FA Coupling PEX x Swivel FIP – Wrot APPROX. DIM. ANOM. SIZE NET WT./LBS. INCHES 1/2 0.035 1 1/2 PEX607 Elbow PEX x PEX – Wrot APPROX. DIM. ANOM. SIZE NET WT./LBS. INCHES 1/2 0.045 1 1/4 3/4 0.084 1 7/16 PEX607-FA Faucet Elbow PEX x Swivel FIP – Wrot APPROX. DIM. ANOM. SIZE NET WT./LBS. INCHES 1/2 0.049 1 7/16 PEX707-3-5 Drop Ear Elbow PEX x FIP – Wrot APPROX. DIM. ANOM. SIZE NET WT./LBS. INCHES 1/2 0.187 2 1/4 PEX603 Adapter PEX x F – Wrot APPROX. DIM. ANOM. SIZE NET WT./LBS. INCHES 1/2 0.123 29/16 3/4 0.207 23/4 PEX604 Adapter PEX x M – Wrot APPROX. DIM. ANOM. SIZE NET WT./LBS. INCHES 1/2 0.110 21/4 3/4 0.196 29/16 PEX600-T Adapter PEX x PB – Wrot APPROX. DIM. ANOM. SIZE NET WT./LBS. INCHES 1/2 0.034 113/16 3/4 0.054 2 PEX600 Coupling PEX x PEX – Wrot APPROX. DIM. ANOM. SIZE NET WT./LBS. INCHES 1/2 0.036 2 3/4 0.056 2 FITTING REDUCERS TEES CRIMP RINGS AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 55//1144//0022 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 26 ADAPTERS COUPLINGS ELBOWS Consult price sheet for Made to Order items and for minimum order quantities. COUPLINGS continued PEX841 Crimp Tool APPROX.NOM. SIZE NET WT./LBS. 3/8 3.005 1/2 3.005 3/4 3.005 1 4.000 PEX100 Tube Cutter APPROX.NOM. SIZE NET WT./LBS. — 0.03 PEX616 Brass Plugs APPROX. NOM. SIZE NET WT./LBS. 3/8 0.0168 1/2 0.0213 3/4 0.0457 1 0.0801 AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 55//1144//0022 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 27 Consult price sheet for Made to Order items and for minimum order quantities. CRIMP TOOL Copper Insert Fittings for Polybutylene Couplings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 Crimp Rings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 Elbows . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 Faucet Connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 Tees . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 33//2299//0044 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 28 The manufacturing plants at South Glens Falls, NY, Stuarts Draft, VA, Nacogdoches, TX and Reynosa, Mexico manufacture products under a Quality Management System conforming to the current revision of ISO-9001 International Standards PB607-FA 90°Elbow Faucet Connector – Barb x Swivel FIPS APPROX. NOM. SIZE NET WT./LBS. 1/2 without nut & washer 0.04 PB611 Tee – Barb x Barb x Barb APPROX.NOM. SIZE NET WT./LBS. 1/2 0.05 1/2 x 1/2 x 3/4 0.10 3/4 0.10 3/4 x 3/4 x 1/2 0.08 3/4 x 1/2 x 3/4 0.10 3/4 x 1/2 x 1/2 0.08 CRIMP RINGS PB198 Crimp Ring – Copper APPROX. NOM. SIZE NET WT./LBS. 1/2 0.01 3/4 0.02 AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 55//1144//0022 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 29 PB600 Coupling – Barb x Barb APPROX.NOM. SIZE NET WT./LBS. 1/2 0.04 3/4 0.06 PB607 90°Elbow – Barb x Barb APPROX.NOM. SIZE NET WT./LBS. 1/2 0.04 3/4 0.06 PB600-FA Straight Faucet Connector – Barb x Swivel FIPS APPROX.NOM. SIZE NET WT./LBS. 1/2 without nut & washer 0.03 COUPLINGS Consult price sheet for Made to Order items and for minimum order quantities. ELBOWS FAUCET CONNECTORS TEES FAUCET CONNECTORS Wrot and Cast DWV Fittings Adapters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31-33 Bushings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 Cleanouts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 Closet Flanges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 Couplings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 Elbows . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35-36 Plugs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 Return Bends . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40 Tees . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 Test Caps & Tees . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37-38 Traps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39-40 T-Y’s . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 Y’s . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 33//2299//0044 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 30 The manufacturing plants at South Glens Falls, NY, Stuarts Draft, VA, Nacogdoches, TX and Reynosa, Mexico manufacture products under a Quality Management System conforming to the current revision of ISO-9001 International Standards AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 33//2299//0044 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 31 903-7 DWV Trap Adapter F x SJ – Wrot APPROX. DIM. BNOM. SIZE NET WT./LBS. INCHES 1 1/4 x 1 1/4 O.D. 0.32 17/16 1 1/2 x 1 1/2 O.D. 0.42 17/16 1 1/2 x 1 1/4 O.D. 0.43 119/32 904-7 DWV Trap Adapter M x SJ – Wrot APPROX. DIM. B NOM. SIZE NET WT./LBS. INCHES 1 1/4 x 1 1/4 O.D. 0.41 13/4 1 1/2 x 1 1/2 O.D. 0.51 125/32 1 1/2 x 1 1/4 O.D. 0.49 129/32 ADAPTERS – SLIP JOINT 801-2-7 DWV Fitting Trap Adapter Ftg x SJ – Cast APPROX. DIM. BNOM. SIZE NET WT./LBS. INCHES 1 1/4 x 1 1/4 O.D. 0.25 119/32 901-2-7 DWV Fitting Trap Adapter Ftg x SJ – Wrot APPROX. DIM. B NOM. SIZE NET WT./LBS. INCHES 1 1/2 x 1 1/2 O.D. 0.29 17/16 1 1/2 x 1 1/4 O.D. 0.24 17/16 901-7 DWV Trap Adapter C x SJ – Wrot APPROX. DIM. ANOM. SIZE NET WT./LBS. INCHES 1 1/4 x 1 1/4 O.D. 0.21 21/32 1 1/2 x 1 1/2 O.D. 0.27 3/4 1 1/2 x 1 1/4 O.D. 0.24 7/8 Consult price sheet for Made to Order items and for minimum order quantities. ADAPTERS – SOIL PIPE 805 DWV Soil Pipe Adapter C x Spigot – Cast Joins copper tube to cast iron soil pipes. APPROX. DIM. ANOM. SIZE NET WT./LBS. INCHES 1 1/4 x 2 0.93 3 9/32 2 x 4 2.52 3 7/8 3 1.56 2 3/4 3 x 4 2.78 3 13/16 4 2.23 3 905 DWV Soil Pipe Adapter C x Spigot – Wrot Joins copper tube to cast iron soil pipes. APPROX. DIM. A NOM. SIZE NET WT./LBS. INCHES 1 1/2 x 2 0.60 3 7/16 2 0.44 2 9/16 805-N DWV No Hub Soil Pipe Adapter C x No Hub – Cast APPROX. DIM. ANOM. SIZE NET WT./LBS. INCHES 1 1/2 x 2 0.42 1 7/32 2 0.40 1 3/16 3 0.75 1 3/16 4 1.23 1 7/32 801-T DWV Trap Adapter C x O.D. Tube – Cast APPROX. DIM. CNOM. SIZE NET WT./LBS. INCHES 1 1/4 x 1 1/4 O.D. 0.21 1/8 1 1/2 x 1 1/2 O.D. 0.22 7/32 1 1/2 x 1 1/4 O.D. 0.20 9/32 802 DWV Adapter C x M – Cast APPROX. DIM. B DIM. C NOM. SIZE NET WT./LBS. INCHES INCHES 1 1/4 0.23 15/16 7/16 1 1/4 x 1 1/2 0.41 1 1/2 1 1/2 0.25 1 7/16 2 0.33 11/16 7/16 3 0.92 11/2 3/4 802-C DWV Flush Adapter C x M – Cast APPROX. DIM. B DIM. C NOM. SIZE NET WT./LBS. INCHES INCHES 1 1/4 0.16 15/16 7/16 1 1/2 0.20 15/16 9/16 2 0.23 11/16 5/8 802-F DWV Threaded Piece C x M – Cast Makes slip joint connection when soldered to the end of tube and slip joint nut and washer added. APPROX. DIM. B NOM. SIZE NET WT./LBS. INCHES 1 1/4 0.05 3/8 1 1/2 0.05 3/8 2 0.05 3/8 803 DWV Adapter C x F – Cast APPROX. DIM. ANOM. SIZE NET WT./LBS. INCHES 3 1.45 113/32 4 2.31 117/32 903 DWV Adapter C x F – Wrot APPROX. DIM. ANOM. SIZE NET WT./LBS. INCHES 1 1/4 0.19 27/32 1 1/2 0.25 29/32 2 0.41 1 ADAPTERS – THREADED continued ADAPTERS – THREADED AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 33//2299//0044 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 32 ADAPTERS – SPECIAL LEAD Consult price sheet for Made to Order items and for minimum order quantities. 803-2 DWV Fitting Adapter Ftg x F – Cast APPROX. DIM. B NOM. SIZE NET WT./LBS. INCHES 1 1/2 0.39 1 15/32 2 0.56 1 19/32 3 1.44 2 7/32 903-2 DWV Fitting Adapter Ftg x F – Wrot APPROX. DIM. B NOM. SIZE NET WT./LBS. INCHES 1 1/4 0.19 1 17/32 804 DWV Adapter C x M – Cast APPROX. DIM. A NOM. SIZE NET WT./LBS. INCHES 1 1/2 0.34 1 3/64 1 1/2 x 2 0.55 1 5/16 1 1/2 x 1 1/4 0.31 27/32 2 0.43 7/8 2 x 1 1/2 0.52 15/16 3 1.35 1 25/32 4 2.59 2 1/32 AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 33//2299//0044 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 33 Consult price sheet for Made to Order items and for minimum order quantities. ADAPTERS – THREADED continued 904 DWV Adapter C x M – Wrot APPROX. DIM. ANOM. SIZE NET WT./LBS. INCHES 1 1/4 0.30 13/32 1 1/4 x 1 1/2 0.37 13/16 804-T DWV Trap Adapter O.D. Tube x M – Cast APPROX. DIM. A NOM. SIZE NET WT./LBS. INCHES 1 1/4 O.D. x 1 1/2 0.44 19/32 804-2 DWV Fitting Adapter Ftg x M – Cast APPROX. DIM. B NOM. SIZE NET WT./LBS. INCHES 1 1/2 0.50 115/16 2 0.71 21/32 801-2 DWV External Bushing Ftg x C – Cast APPROX. DIM. ANOM. SIZE NET WT./LBS. INCHES 3 x 2 0.61 111/32 3 x 1 1/2 0.60 15/16 4 x 3 1.12 121/32 4 x 2 1.16 13/4 901-2 DWV External Bushing Ftg x C – Wrot APPROX. DIM. A NOM. SIZE NET WT./LBS. INCHES 1 1/2 x 1 1/4 0.13 1 2 x 1 1/2 0.19 17/32 2 x 1 1/4 0.19 13/8 901-2-F DWV Fitting Flush Bushing Ftg x C – Wrot APPROX. DIM. B DIM. C NOM. SIZE NET WT./LBS. INCHES INCHES 2 x 1 1/2 0.37 13/16 1/8 BUSHINGS CLEANOUTS 816 DWV Fitting Cleanout Ftg x Cleanout w/Plug – Cast APPROX. DIM. BNOM. SIZE NET WT./LBS. INCHES 1 1/4 0.49 25/32 1 1/2 0.60 21/4 2 0.87 23/8 3 2.37 39/32 4 3.99 35/8 816-S DWV Flush Fitting Cleanout Ftg x Cleanout w/Plug – Cast APPROX. DIM. B NOM. SIZE NET WT./LBS. INCHES 1 1/4 x 3/4 0.20 15/32 1 1/2 x 1 0.29 11/16 2 x 1 1/2 0.42 17/32 3 x 2 1/2 0.96 113/16 4 x 3 2.25 21/8 851 DWV Closet Flange C – Cast APPROX. DIMENSIONSNET WT. INCHESNOM. SIZE LBS. B F W 4 1.45 5/8 76 4 x 3 2.18 111/16 76 951 DWV Closet Flange C – Wrot APPROX. DIMENSIONSNET WT. INCHESNOM. SIZE LBS. B F W 4 x 3 0.84 111/16 63/4 6 851-C DWV Closet Flange C – Cast APPROX. DIMENSIONS NET WT. INCHES NOM. SIZE LBS. B C F W 4 x 3 1.31 11/16 1/2 67/8 6 CLOSET FLANGES AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 33//2299//0044 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 34 Consult price sheet for Made to Order items and for minimum order quantities. COUPLINGS 801 DWV Coupling C x C – Cast APPROX. DIM. A NOM. SIZE NET WT./LBS. INCHES 3 x 2 0.70 11/16 3 x 1 1/2 0.68 15/16 4 x 3 0.98 9/32 4 x 2 1.34 1 1/4 901 DWV Coupling C x C – Wrot APPROX. DIM. A NOM. SIZE NET WT./LBS. INCHES 1 1/4 0.07 3/32 1 1/2 0.09 3/32 1 1/2 x 1 1/4 0.13 5/16 2 0.14 3/32 2 x 1 1/2 0.19 15/32 3 0.45 3/32 4 0.57 1/8 901-RP DWV Repair Coupling (No Stop) C x C – Wrot APPROX. DIM. B NOM. SIZE NET WT./LBS. INCHES 1 1/2 0.09 1 13/32 2 0.14 1 17/32 3 0.42 1 29/32 4 0.57 2 13/32 906-2 DWV 45°Fitting Elbow Ftg x C – Wrot APPROX. DIM. B DIM. CNOM. SIZE NET WT./LBS. INCHES INCHES 1 1/4 0.13 13/16 1/2 1 1/2 0.21 11/4 9/16 2 0.39 15/8 13/16 3 0.84 17/8 13/8 807 DWV 90°Elbow C x C – Cast APPROX. DIM. C DIM. DNOM. SIZE NET WT./LBS. INCHES INCHES 1 1/2 x 1 1/4 0.43 11/4 13/16 2 x 1 1/2 0.71 111/16 17/16 3 2.30 27/8 27/8 4 3.92 325/32 325/32 907 DWV 90°Elbow C x C – Wrot APPROX. DIM. C DIM. DNOM. SIZE NET WT./LBS. INCHES INCHES 1 1/4 0.18 13/16 13/16 1 1/2 0.32 17/16 17/16 2 0.58 115/16 115/16 3 1.20 211/16 211/16 AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 55//1144//0022 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 35 Consult price sheet for Made to Order items and for minimum order quantities. 806 DWV 45°Elbow C x C – Cast APPROX. DIM. CNOM. SIZE NET WT./LBS. INCHES 4 2.47 117/32 906 DWV 45°Elbow C x C – Wrot APPROX. DIM. C NOM. SIZE NET WT./LBS. INCHES 1 1/4 0.13 1/2 1 1/2 0.21 9/16 2 0.38 13/16 3 0.78 13/16 806-2 DWV 45°Fitting Elbow Ftg x C – Cast APPROX. DIM. B DIM. CNOM. SIZE NET WT./LBS. INCHES INCHES 4 2.81 219/32 117/32 ELBOWS 907-LT DWV 90°Long Radius Elbow C x C – Wrot APPROX. DIM. CNOM. SIZE NET WT./LBS. INCHES 1 1/2 0.41 25/16 2 0.62 23/4 807-2 DWV 90°Fitting Elbow Ftg x C – Cast APPROX. DIM. B DIM. C NOM. SIZE NET WT./LBS. INCHES INCHES 4 3.84 413/16 325/32 907-2 DWV 90°Fitting Elbow Ftg x C – Wrot APPROX. DIM. B DIM. C NOM. SIZE NET WT./LBS. INCHES INCHES 1 1/4 0.19 17/8 13/16 1 1/2 0.33 23/16 17/16 2 0.59 211/16 17/8 3 1.21 311/16 211/16 807-3 DWV 90°Elbow C x F – Cast APPROX. DIM. C DIM. ENOM. SIZE NET WT./LBS. INCHES INCHES 1 1/2 0.72 113/32 21/8 2 1.15 17/8 211/16 807-4 DWV 90°Elbow C x M – Cast APPROX. DIM. C DIM. ENOM. SIZE NET WT./LBS. INCHES INCHES 1 1/2 0.66 113/32 23/32 807-9 DWV 90°Elbow w/Side Inlet C x C x C – Cast APPROX. DIMENSIONS NET WT. INCHES NOM. SIZE LBS. C C1 D 3 x 3 x 2 2.55 27/8 15/8 27/8 960 DWV 60°Elbow C x C – Wrot APPROX. DIM. CNOM. SIZE NET WT./LBS. INCHES 1 1/2 0.24 13/16 2 0.44 1 1/8 3 0.95 1 7/8 861-LH DWV 90°Elbow w/Low Heel Inlet C x C x C – Cast APPROX. DIM. C DIM. E NOM. SIZE NET WT./LBS. INCHES INCHES 3 x 3 x 2 2.43 2 7/8 19/32 818 A.S.A. DWV Plug M – Cast APPROX. DIM. BNOM. SIZE NET WT./LBS. INCHES 3/4 0.08 23/32 1 0.12 29/32 1 1/4 0.19 31/32 1 1/2 0.21 1 3/32 2 0.34 15/16 ELBOWS continued AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 33//2299//0044 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 36 Consult price sheet for Made to Order items and for minimum order quantities. 837 DWV 90°Double Elbow C x C x C – Cast APPROX. DIM. C DIM. G NOM. SIZE NET WT./LBS. INCHES INCHES 11/2 0.77 113/32 113/32 2 1.31 17/8 17/8 2 x 11/2 x 11/2 0.97 15/8 11/2 808 DWV 221/2°Elbow C x C – Cast APPROX. DIM. C NOM. SIZE NET WT./LBS. INCHES 1 1/4 0.22 3/16 1 1/2 0.28 1/4 2 0.48 11/32 3 0.99 17/32 809 DWV 111/4°Elbow C x C – Cast APPROX. DIM. CNOM. SIZE NET WT./LBS. INCHES 1 1/2 0.22 5/32 2 0.38 3/16 PLUGS 811-14 DWV Tee C x C x F – Cast APPROX. DIMENSIONSNET WT. INCHESNOM. SIZE LBS. B F G 1 1/2 0.88 23/16 13/16 113/32 2 1.57 223/32 11/16 17/8 2 x 2 x 1 1/2 1.17 27/16 7/8 17/16 811-15 DWV Tee C x F x F – Cast APPROX. DIMENSIONSNET WT. INCHESNOM. SIZE LBS. B E G 1 1/4 0.73 1 25/32 11/2 15/32 835 DWV Double Tee C x C x C x C – Cast APPROX. DIMENSIONS NET WT. INCHES NOM. SIZE LBS. C F G 1 1/4 0.65 1 5/32 3/4 15/32 1 1/2 0.85 1 13/32 13/16 113/16 11/2x11/2x11/4 x11/4 0.72 1 9/32 3/4 15/32 2 1.38 1 7/8 11/16 17/8 2x2x1 1/2 x1 1/2 0.99 1 21/32 7/8 17/16 2x2x1 1/4 x1 1/4 0.93 1 17/32 25/32 15/32 2x1 1/2x1 1/2x1 1/2 0.94 1 21/32 25/32 17/16 3x3x2 x2 2.36 2 3/8 11/8 17/8 3x3x1 1/2 x1 1/2 1.51 2 5/32 31/32 115/32 AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 33//2299//0044 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 37 Consult price sheet for Made to Order items and for minimum order quantities. TEES 811 DWV Tee C x C x C – Cast APPROX. DIMENSIONSNET WT. INCHESNOM. SIZE LBS. C F G 3 2.84 253/64 125/64 253/64 3 x 3 x 2 1.82 23/8 11/8 17/8 3 x 3 x 1 1/2 1.58 25/32 15/16 17/16 4 4.92 313/16 2313/16 4 x 4 x 3 3.49 311/32 119/32 27/8 4 x 4 x 2 2.91 27/8 15/32 113/32 911 DWV Tee C x C x C – Wrot APPROX. DIMENSIONS NET WT. INCHES NOM. SIZE LBS. C F G 1 1/4 0.32 11/8 13/16 11/8 1 1/2 0.49 113/32 29/32 113/32 1 1/2 x 1 1/2 x 1 1/4 1.58 25/32 15/16 17/16 2 0.78 127/32 11/8 17/8 2 x 2 x 1 1/2 0.73 15/8 15/16 13/8 2 x 2 x 1 1/4 0.51 11/2 13/16 11/8 2 x 1 1/2 x 2 0.80 127/32 125/32 113/16 2 x 1 1/2 x 1 1/2 0.73 15/8 11/4 13/8 835-B DWV Double LT Tee C x C x C x C – Cast APPROX. DIMENSIONS NET WT. INCHES NOM. SIZE LBS. C D L M 2x 11/2x 11/2x 11/2 1.73 2 3/8 33/16 321/32 3/32 917-B Test Caps – Copper C – Wrot APPROX. DIM. B NOM. SIZE NET WT./LBS. INCHES 1/2 0.01 3/16 3/4 0.01 3/16 1 0.01 1/8 1 1/4 0.01 1/4 1 1/2 0.01 1/4 2 0.02 1/4 3 0.03 1/4 4 0.05 5/16 TEST CAPS 814 DWV Test Tee C x C x Cleanout w/Plug – Cast APPROX. DIM. E DIM. FNOM. SIZE NET WT./LBS. INCHES INCHES 1 1/2 1.00 21/16 11/8 2 1.35 211/32 13/8 3 3.78 37/16 115/16 812 DWV Long Turn T-Y C x C x C – Cast APPROX. DIMENSIONS NET WT. INCHES NOM. SIZE LBS. C D J K §1 1/4 0.93 2 27/32 127/32 23/4 13/32 1 1/2 0.87 3 5/16 21/8 35/32 7/16 2 1.84 4 1/4 23/4 41/16 1/2 2 x 2 x 1 1/2 1.07 3 5/8 23/8 37/32 7/32 3 3.49 6 7/16 41/32 61/32 3/4 3 x 3 x 2 2.78 4 7/8 35/16 45/32 3/32 836 DWV Double Long Turn T-Y C x C x C x C – Cast APPROX. DIMENSIONS NET WT. INCHES NOM. SIZE LBS. C D J K 1 1/2 1.25 3 5/16 21/8 35/32 7/32 2 0.87 3 5/16 21/8 35/32 7/16 2 x 2 x11/2 x11/2 1.96 3 5/8 23/8 37/32 7/32 2 x 2 x11/4 x11/4 2.67 3 11/16 23/8 37/32 7/32 T-Y’s AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 33//2299//0044 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 38 Consult price sheet for Made to Order items and for minimum order quantities. TEST TEES Y’s continued 810 DWV 45°Y C x C x C – Cast APPROX. DIMENSIONS NET WT. INCHES NOM. SIZE LBS. C D K L 1 1/4 0.60 2 2 3/8 – 1 1/2 0.94 2 5/16 25/16 1/2 – 2 1.26 2 7/8 27/8 17/32 – 2 x 2 x 1 1/2 1.15 2 11/16 29/16 3/16 – 2 x 2 x 1 1/4 1.01 2 9/16 211/32 1/16 – 2 x 11/2 x 2 1.16 2 17/32 25/8 17/32 – 2 x 11/2 x 11/2 0.84 2 5/32 25/32 5/16 – 3 3.19 4 1/64 41/64 45/64 – 3 x 3 x 2 2.02 3 17/32 35/16 1/8 – 3 x 3 x 1 1/2 1.69 3 1/4 215/16 –3/16 4 5.55 5 15/32 515/32 11/16 – 4 x 4 x 3 3.96 4 11/16 41/2 5/16 – 4 x 4 x 2 2.90 4 7/32 313/16 –3/8 834 DWV 45°Double Y C x C x C x C – Cast APPROX. DIMENSIONSNET WT. INCHESNOM. SIZE LBS. C D K L 2 1.90 2 7/8 27/8 17/32 – 2 x 2 x11/2 x11/2 1.26 2 11/16 29/16 3/16 – 3 4.20 4 13/32 413/32 25/32 – 3 x 3 x11/2 x11/2 2.09 3 1/4 215/16 –5/16 881 DWV P-Trap C x SJ – Cast APPROX. DIMENSIONS NET WT. INCHES NOM. SIZE LBS. A E J K 1 1/2 1.50 113/32 27/32 21/2 317/32 884 DWV P-Trap w/Cleanout C x C x Cleanout w/Plug – Cast APPROX. DIMENSIONSNET WT. INCHESNOM. SIZE LBS. A C J K 1 1/4 1.21 15/32 117/32 21/4 39/32 1 1/2 1.53 113/32 115/32 21/2 317/32 2 2.26 17/8 113/32 343/32 3 5.74 27/8 115/16 4521/32 885 DWV P-Trap C x C – Cast APPROX. DIMENSIONSNET WT. INCHESNOM. SIZE LBS. A C J K 1 1/4 1.09 15/32 117/32 21/4 39/32 1 1/2 1.45 113/32 115/32 21/2 317/32 2 2.11 17/8 113/32 343/32 3 5.17 27/8 115/16 4321/32 890 3 x 5 DWV Drum Trap w/Bottom Inlet C x F x Cleanout w/Plug – Cast APPROX. DIMENSIONSNET WT. INCHESNOM. SIZE LBS. B C E 1 1/2 1.97 3 9/32 11/2 23/8 891 3 x 6 DWV Swivel Drum Trap C x C x Cleanout w/Plug – Cast APPROX. DIMENSIONSNET WT. INCHESNOM. SIZE LBS. B C F J 1 1/2 2.90 6 21/32 11/2 137/8 880 DWV P-Trap w/Cleanout CxSJxCleanout w/Plug–Cast APPROX. DIMENSIONS NET WT. INCHES NOM. SIZE LBS. A E J K 1 1/2 1.80 1 13/32 27/32 21/2 317/32 2 2.66 1 7/8 27/16 343/16 AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 33//2299//0044 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 39 Consult price sheet for Made to Order items and for minimum order quantities. TRAPS 892 DWV P-Trap w/Union Joint C x SJ – Cast APPROX. DIMENSIONS NET WT. INCHES NOM. SIZE LBS. A E J K 1 1/2 1.86 11/8 35/32 25/8 37/16 2 2.64 115/32 313/32 31/8 329/32 892-3 DWV P-Trap w/Union Joint F x SJ – Cast APPROX. DIMENSIONS NET WT. INCHES NOM. SIZE LBS. A E J K 2 2.89 113/32 313/32 31/8 329/32 892-A DWV P-Trap w/Union Joint FxSJxCleanoutw/Plug–Cast APPROX. DIMENSIONSNET WT. INCHESNOM. SIZE LBS. A E J K 1 1/2 1.88 115/16 27/32 21/2 317/32 AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 55//1144//0022 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 40 879 DWV Return Bend C x C – Cast APPROX. DIMENSIONSNET WT. INCHESNOM. SIZE LBS. C J L 1 1/4 0.76 1 17/32 21/4 – 1 1/2 0.90 1 15/32 21/2 – 1 1/2 x 1 1/2 O.D.1.00 1 15/32 21/2 – 2 1.25 1 13/32 3– 2 x 1 1/2 O.D.1.23 1 17/32 3119/32 2x11/2 1.37 1 17/32 3119/32 3 2.77 1 15/16 4– 875-S DWV Trap Upturn M x S – Cast APPROX. DIMENSIONSNET WT. INCHESNOM. SIZE LBS. B E J 1 1/2 1.20 141/64 19/64 4 Consult price sheet for Made to Order items and for minimum order quantities. TRAPS cont.RETURN BENDS 878 DWV Return Bend w/Cleanout C x C x Cleanout w/Plug – Cast APPROX. DIMENSIONSNET WT. INCHESNOM. SIZE LBS. C J 1 1/4 0.81 1 17/32 21/4 – 1 1/2 0.98 1 15/32 21/2 – 2 1.40 1 13/32 3– 3 3.34 1 15/16 4– AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 33//2299//0044 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 41 Engineering Data continued Solder Joint Fittings Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 Friction Loss Allowances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56 Installation Techniques . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85 Tolerances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 Specifications Tolerances Fittings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44, 48-49 Tubing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50-53 Valves Friction Loss Allowances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56 Working Pressures Joints . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46-47 Tubing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50-53, 57 Installation Instructions The Fine Art of Brazing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86-87 The Fine Art of Soldering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85 Polybutylene Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89 Polyethylene (PEX) Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88 Numerical Index Numerical Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92 Engineering Data Brazing Alloy Consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 Brazing Fittings Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49 Friction Loss Allowances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56 Installation Techniques . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86-87 Tolerances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49 Copper Tube Fittings Brazing Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 Fitting Terms and Abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 Plumbing System Failures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43 Rated Internal Working Pressures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46-47 Solder and Flux Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 Solder Joint Specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 Tolerances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63 Types of Joints . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 Copper Water Tube Comparative Data with Iron Pipe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54 Dimensional Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50-53 Expansion and Contraction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55 Internal Working Pressures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57 Selection of Tube Sizes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56 Tolerances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50-53 Types, Standards, Applications, Tempers and Lengths . . . . . . . . . . . . . . . . . . 84 Water Flow and Friction Loss . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58-83 Frequently Asked Questions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90 Joints Abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 Brazing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86-87 Soldering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85 Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42 Solder and Flux Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 The manufacturing plants at South Glens Falls, NY, Stuarts Draft, VA, Nacogdoches, TX and Reynosa, Mexico manufacture products under a Quality Management System conforming to the current revision of ISO-9001 International Standards AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 55//1144//0022 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 42 TYPES OF JOINTS Flared Joint — The principle of the flared joint was first developed for copper tube plumbing in 1928 by NIBCO. The flared type joint is wholly a mechanical means of joining copper tubes. The tube nut is placed over the end of the copper tube to be joined; the tube end then is flared out at an approximate 45 degree angle by a flaring tool. The flared end is then drawn up by the tube nut so the inside surface is tightly secured against the ball seat of the fitting. This joint can be readily dismantled at any time and is, in effect, a type of union connection. Its use is generally restricted to soft (annealed) copper tubes since hard drawn tubes would be subject to splitting when flared (if the ends were not previously annealed). The flared ends of NIBCO Flared Fittings are produced to the requirements of ASME B16.26, “Cast Copper Alloy Fittings for Flared Copper Tube.” Solder Joint — NIBCO pioneered the development of the solder joint and its application to the field of copper tube piping. Today the solder joint is widely adopted, as evidenced by the majority of cities and states that have written codes to include copper tube and solder joints as desirable for general plumbing, water lines, vent, stack, waste and drain lines, as well as other uses in industry. Testing has shown that often the solder joint has greater strength than the tubes being joined, depending upon the soldering alloy selected. While the method of preparing a solder joint is an exacting art to insure a full strength joint, it can be readily mastered by skilled tradesmen. It is for this reason — to insure the public of the protection afforded by properly prepared joints — that NIBCO products are marketed through the reputable sources of supply to the piping trades. Important procedures for preparing a solder joint are graphically illustrated in this catalog on page 95. Brazed Joint — This type of joint has long been used wherever and whenever critical situations have been encountered in copper piping. The joint itself is completed much in the same manner as the solder joint; however, considerably more heat and several refinements of technique require separate procedures that are described further in this catalog on pages 96-97. Threaded Ends — To adapt copper tube to equipment having National Standard Pipe Taper (NPT) threads or to add copper tube to existing iron pipe installations or other threaded connections, NIBCO provides fittings having both external and internal NPT threads. These threaded ends are produced to the requirements of ASME B1.20.1, “Pipe Threads, General Purpose (Inch).” Flanges — To adapt copper tube to equipment having flanged connections, or to add copper tube to flanged pipe installations or other purposes, NIBCO provides flanges. The flanges are produced in two standard types widely used in this field where copper tube can serve — Class 150, comply with ASME B16.24, “Cast Copper Alloy Pipe Flanges and Flanged Fittings Class 150, 300, 400, 600, 900, 1500 and 2500”; and Class 125, which conform to MSS SP 106, “Cast Copper Alloy Flanges and Flanged Fittings Class 125, 150 and 300.” Barbed Insert Fittings for Polybutylene (PB) — NIBCO offers a complete line of copper barbed insert fittings for joining PB tube. The insert fittings are produced to the requirements of ASTM F 1380. Along with the insert fittings are copper crimp rings, which, when properly installed, provide a leak-tight mechanical joint. Transition fittings are available for adapting to new or existing threaded or solder joint ends. Barbed Insert Fittings for PEX — NIBCO offers a complete line of copper barbed insert fittings for joining PEX tube. The insert fittings are produced to the requirements of ASTM F 1807. Along with the insert fittings are copper crimp rings, which, when properly installed, provide a leak-tight mechanical joint. Transition fittings are available for adapting to new or existing threaded or solder joint ends. Fitting Terms and Abbreviations C Female solder cup Ftg Male solder end F Female NPT thread M Male NPT thread Hose Standard hose thread Hub Female end for soil pipe Spigot Male end for soil pipe No Hub Used with mechanical coupling O.D. Tube Actual tube outside diameter S Straight thread SJ Slip joint FL Flared Copper Tube Fittings AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 55//1144//0022 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 43 WHAT MAKES A PLUMBING SYSTEM FAIL? Failure in a copper plumbing system is rare, but may occur due to a variety of reasons. The most common causes of failure are: 1. Excessive fluid velocity causes erosion-corrosion or impingement (to strike or hit against) attack in the tube and/or fitting. For this reason, the copper plumbing industry has establish design velocity limits for copper plumbing systems to the following: Hot Water > 140°F (60°C) 2 to 3 feet per second (0.6 to 0.9 meters per second) Hot Water 140°F (60°C) 4 to 5 feet per second (1.2 to 1.5 meters per second) Cold Water 5 to 8 feet per second (1.5 to 2.4 meters per second) 2. Localized high velocities and/or turbulence. The presence of a dent, tube ends which are not reamed or deburred before soldering, and sudden changes in direction can all cause localized high velocity conditions. 3. Flux Corrosion is typified by pin hole leaks, generally in the bottom of a horizontal line. Fluxes are mildly corrosive liquid or petroleum-based pastes containing chlorides of zinc and ammonia. Unless the flux is flushed from the system, it will lay in the bottom of the tube and remain active. ASTM B 813, “Liquid and Paste Fluxes for Soldering Applications of Copper and Copper-Alloy Tube,” limits the corrosivity of soldering fluxes and ensures that these fluxes are flushable in cold water, which facilitates easy removal of flux residue following installation. 4. Galvanic Corrosion may be defined as the destruction of a material by electrochemical interaction between the environment and the material. Generally, it is slow but persistent in character and requires the presence of dissimilar metals. Galvanic corrosion requires the flow of an electric current between certain areas of dissimilar metal surfaces. To complete the electric circuit, there must be two electrodes, an anode and a cathode, and they must be connected by an electrolyte media (water) through which the current can pass. The amount of metal which dissolves at the anode is proportional to the number of electrons flowing, which in turn is dependent upon the potential and resistance of the two metals. The use of dissimilar metals in a plumbing system may or may not create a problem. For instance, copper and steel are perhaps the most common dissimilar metals found together in a plumbing system. In closed systems, such as a chilled or heating water piping, the use of dissimilar metals may not create a serious problem; this is because there is virtually no oxygen in the water and corrosion relations tend to be stifled. Where dissimilar metals must be used, some codes require that they should be separated by dielectric union or a similar type of fitting. The effectiveness depends upon; distance between the metals on the electromotive-force series (EMF) chart, ratio of cathode to anode area, degree of aeration, amount of agitation, temperature, presence of dissolved salts, and other factors. ABBREVIATED EMF SERIES (Electromotive-Force Series; Common Piping Materials in Sea Water) CATHODE (+) Passive GOLD – Fixtures, Faucets, Plating PLATINUM SILVER – Brazing alloys, Silver-bearing solders TITANIUM – Condenser tubes MONEL (67% Ni - 33% Cu) – Specialty piping & equipment CUPRO-NICKEL – Condensers, Marine, Nuclear COPPER – Pressure, DWV, Gases, Air, Refrigeration, etc. BRASS (85/15 - Red) – Cast fittings, Valves BRASS (70/30 - Yellow) – Gas-cocks, Fittings, Connectors LEAD – Solder, Pipe, Sheet, Coating, Lining TIN – Solders, Coating, Lining CAST IRON – Pressure, DWV WROUGHT IRON – Pressure MILD STEEL – Fire Protection ALUMINUM – Refrigeration, Irrigation, some Solar GALVANIZED STEEL – Pressure, DWV ZINC – Coatings, Linings, some Fittings MAGNESIUM – Water Heater Anodes, Cathodic protection for pipelines ANODE (-) Active; Sacrificial Material 5. Dezincification is a type of corrosion in which brass dissolves as an alloy and the copper constituent redeposits from solution onto the surface of the brass as a metal, but in the porous form. The zinc constituent may be carried away from the brass as a soluble salt, or may be deposited in place as an insoluble compound. Dezincification is normally associated with brass valves where the zinc content exceeds 15%. Generally, areas of high stress, such as valve stems and gate valve bodies, are primary targets of attack. 6. On rare occasion problems of corrosion by aggressive water, possibly aggravated by poor design or workmanship, do exist. Aggressive, hard well waters that cause pitting can be identified by chemical analysis and treated to bring their composition within acceptable limits. Typically these hard waters are found to have high total dissolved solids (t.d.s.) including sulfates and chlorides, a pH in the range of 7.2 to 7.8, a high content of carbon dioxide (CO2) gas (over 10 parts per million, ppm), and the presence of dissolved oxygen (D.O.) gas. Soft acidic waters can cause the annoying problem of green staining of fixtures or “green water”. Raising the pH of such waters to a value of about 7.2 or more usually solves the problem, but a qualified water treatment specialist should be consulted. 7. Aggressive soil conditions can be a cause for external corrosion of copper piping systems. Non-uniform soil characteristics, such as different soil aeration, resistivity, or moisture properties, between adjacent sections of tube can create galvanic corrosion cells. Soils contaminated with high concentrations of road salts or fertilizers containing ammonia, chlorides, and nitrogen are known to combine with water to form acids. Any metal pipe laid in ash or cinders is subject to attack by the acid generated when sulfur compounds combine with water to form sulfuric acid. U.S. customary units in this document are the standard; the metric units are provided for reference only. The values stated in each system are not exact equivalents. 1. Soldering Clearance (between the outside of the tube and the inside diameter of the solder cup) and the Depth of the Solder Cup (into which the tube is inserted). Chart 1 – Soldering Clearance and Solder Cup Depth Nominal Maximum Minimum Maximum Depth of Size I.D. of O.D. of Clearance Solder Cup of Fitting Fitting Tube for Soldering (Inches) Inch (mm) Inch (mm) Inch (mm) Inch (mm) 1/4 0.381 (9.66) 0.374 (9.50) 0.007 (0.18) 0.31 (7.9) 3/8 0.506 (12.85) 0.499 (12.67) 0.007 (0.18) 0.38 (9.7) 1/2 0.631 (16.03) 0.622 (15.85) 0.009 (0.18) 0.50 (12.7) 5/8 0.756 (19.20) 0.749 (19.02) 0.007 (0.18) 0.62 (15.7) 3/4 0.881 (22.38) 0.872 (22.20) 0.009 (0.18) 0.75 (19.1) 1 1.132 (28.75) 1.123 (28.54) 0.008 (0.216) 0.91 (23.1) 1 1/4 1.382 (35.10) 1.373 (34.88) 0.008 (0.216) 0.97 (24.6) 1 1/2 1.633 (41.48) 1.623 (41.22) 0.010 (0.25) 1.09 (27.7) 2 2.133 (54.18) 2.123 (53.92) 0.010 (0.25) 1.34 (34.0) 2 1/2 2.633 (66.88) 2.623 (66.62) 0.010 (0.25) 1.47 (37.3) 3 3.133 (79.58) 3.123 (79.32) 0.010 (0.25) 1.66 (42.2) 3 1/2 3.633 (92.28) 3.623 (92.02) 0.010 (0.25) 1.91 (48.5) 4 4.133 (104.98) 4.123 (104.72) 0.010 (0.25) 2.16 (54.9) 5 5.133 (130.38) 5.123 (130.12) 0.010 (0.25) 2.66 (67.6) 6 6.133 (155.78) 6.123 (155.52) 0.010 (0.25) 3.09 (78.5) The National Bureau of Standards Report BMS58, “Strength of Soft-Soldered Joints in Copper Tubing,” reporting on tests conducted with 3/4-inch tubing and fitting, says “When the clearance is greater than 0.010 inch (0.25 mm), there is difficulty in filling the joint properly.” 2. Depth of Solder Penetration drastically affects the breaking load of the joint. When there is too great a soldering clearance, there is no capillary flow to assure complete solder penetration. As shown in the chart below, the holding power of the 3/4-inch joint is directly proportional to the depth of solder penetration. For example: If you get only one-third penetration, you get approximately one-third the strength needed to assure complete satisfaction. Chart 2 – Type K 3/4" Tubing AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 55//1144//0022 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 44 SOLDER JOINT SPECIFICATION Copper Tube Fittings continued HOW TO BE SURE OF PROPER TOLERANCES It is apparent that all of the scientific apparatus used to test tube and fittings, according to the dimensions indicated in Chart 1, would be impractical to use on the job. It is therefore essential that you install tube and fittings manufactured by companies known to be dedicated to the highest quality control standards. Should you encounter a condition where there is difficulty in filling the joint properly, NIBCO will analyze the trouble without charge. Just send six inches of the tube, along with the fitting and our technicians will provide you with an authoritative report. Solder penetration of one-third the cup depth — breaking load, approximately 2,100 lb. (955 kg) Solder penetration of the entire cup depth — breaking load approximately 7,000 lb. (3175 kg) U.S. customary units in this document are the standard; the metric units are provided for reference only. The values stated in each system are not exact equivalents. AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 55//1144//0022 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 45 BRAZING INFORMATION For Estimating PurposesCopper Water Tube Size BrazingAFiller Required Torch Tip Acetylene Consumption Oxygen Pressure (Approx.) Acetylene Pressure (Approx.) (In Inches) Inches (mm) Drill Size No. C.F.H. (C.M.H.) PSI (kPa) PSI (kPa) 1/4 0.25B (6.4) 54 15.9 (0.5) 4 (27) 4 (27) 3/8 0.38B (9.7) 54 15.9 (0.5) 4 (27) 4 (27) 1/2 0.50 (12.7) 51 24.8 (0.7) 5 (34) 5 (34) 5/8 0.62 (15.7) 51 24.8 (0.7) 5 (34) 5 (34) 3/4 1.00 (25.0) 51 24.8 (0.7) 5 (34) 5 (34) 1 1.60 (41.0) 48 31.6 (0.9) 6 (41) 6 (41) 1 1/4 2.00 (51.0) 48 31.6 (0.9) 6 (41) 6 (41) 1 1/2 2.60 (66.0) 44 38.7 (1.1) 7 (48) 7 (48) 2 4.40 (112.0) 40 60.0 (1.7) 7 (48) 7 (48) 2 1/2 5.90 (150.0) 40 60.0 (1.7) 7 (48) 7 (48) 3 7.90 (200.0) 35 70.0 (2.0) 71/2 (52) 71/2 (52) 3 1/2 10.50 (207.0) 35 70.0 (2.0) 71/2 (52) 7 1/2 (52) 4 13.50 (343.0) 30 88.5 (2.5) 9 (62) 9 (62) 5 20.50 (521.0) 30 88.5 (2.5) 9 (62) 9 (62) 6 28.50 (724.0) 30 88.5 (2.5) 9 (62) 9 (62) AApproximate consumption when brazing one cup of the fitting. Actual consumption depends on workmanship. For filler sizes shown, one pound of filler alloy provides 1,068 inches (27.13 mm) of 1/16-inch wire or 475 inches (12,065 mm) of 3/32-inch wire. B1/16-inch (1.59 mm) diameter wire; all other is 3/32-inch (2.38 mm) diameter. SOLDER AND FLUX REQUIREMENTS Nom. Size Joint Solder Required, LB (kg) (In Inches) General Use Drainage Use 1/4 0.097 – 3/8 0.159 – 1/2 0.261 – 5/8 0.389 – 3/4 0.548 – 1 0.856 – 1 1/4 1.115 1.2 (0.5) 1 1/2 1.480 1.4 (0.6) 2 2.380 1.5 (0.7) 2 1/2 3.225 – 3 4.335 2.8 (1.3) 3 1/2 5.786 – 4 7.446 4.2 (1.9) 5 11.392 – 6 15.815 – 8 26.955 – Solder requirements in this table are based on estimate of weight of solder used to prepare 100 solder joints of sizes shown. Two (2) ounces (0.06 kg) of solder flux will be required for each pound (0.45 kg) of solder. U.S. customary units in this document are the standard; the metric units are provided for reference only. The values stated in each system are not exact equivalents. AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 33//2299//0044 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 46 Copper Tube Fittings continued RATED INTERNAL WORKING PRESSURES OF JOINTS MADE WITH FLARED FITTINGS AND COPPER WATER TUBE Nominal Size Joint (In Inches) Temperature, °F(°C) A Pressure, PSI (BAR)A 3/8, 1/2, 3/4, 1, 1 1/4, 1 1/2, 2 100 (38) 175 (12) A ASME B16.26 RATED INTERNAL WORKING PRESSURES OF POLYBUTYLENE TUBE AND COPPER BARBED INSERT FITTINGS Nominal Size Joint (In Inches) Temperature, °F (°C) Pressure, PSI (BAR) 3/8, 1/2, 3/4, 1 73 (23) 200 (14) 140 (60) 160 (11) 180 (82) 100 (7) 200 (93) 80 (5) RATED INTERNAL WORKING PRESSURES OF JOINTS MADE WITH COPPER WATER TUBE AND SOLDER TYPE FITTINGS, PSI (BAR) Maximum Gauge Working Pressure for Standard Water Tube Sizes [Note (1)] Saturated SteamWorking Temperature 1/8" though 1" 1 1/4" through 2" 2 1/2" through 4" 5" through 8" 10" to 12" LB (kg) Joining Material °F °C PSI BAR PSI BAR PSI BAR PSI BAR PSI BAR All Sizes Alloy Sn50 100 38 200 (14) 175 (12) 150 (10) 135 (9) 100 (6) 50-50 Tin-Lead solder 150 66 150 (10) 125 (9) 100 (7) 90 (6) 70 (5)15 [Notes (2), (3)]200 93 100 (7) 90 (6) 75 (5) 70 (5) 50 (3) 250 121 85 (6) 75 (5) 50 (3) 45 (3) 40 (3) Alloy Sb5 100 38 1090 (9)(75) 850 (8)(59) 705 (9)(49) 660 (8)(46) 340 (23) 95-5 Tin-Antimony solder 150 66 625(10)(43) 485(10)(34) 405(10)(28) 375(10)(26) 280 (19)15 [Note (4)]200 93 505(11)(35) 395(10)(27) 325(10)(32) 305(10)(21) 230 (16) 250 121 270 (19) 210 (15) 175 (12) 165 (11) 120 (8) Alloy E 100 38 710(10)(49) 555( 10)(38) 460(10)(32) 430(10)(30) 320 (22) 150 66 475(11)(33) 370(10)(26) 305(10)(21) 285(11)(20) 215 (15)15200 93 375 (26) 290 (20) 240(11)(17) 225(11)(16) 170 (12) 250 121 320 (22) 250 (17) 205 (14) 195 (13) 145 (9) Alloy HB 100 38 1035 (9)(71) 805 (8)(56) 670 (8)(46) 625 (9)(43) 340 (23) [Note (6)]150 66 710(10)(49) 555(10)(38) 460(10)(32) 430(10)(30) 320 (22)15 200 93 440(11)(30) 345(11)(24) 285(11)(20) 265(11)(18) 200 (14) 250 121 430(11)(30) 335(11)(23) 275(11)(19) 260(11)(18) 195 (13) Joining materials at or above 593°C Pressure-temperature ratings consistent with the materials and procedures employed. [Note (7)] GENERAL NOTE: For extremely low working temperatures in the 0°F to 200°F range, it is recommended that a joint material melting at or above 1000°F be employed [see Note (5)]. NOTES:(1) Standard water tube sizes per ASTM B 88 (2) ASTM B 32 Alloy Grade Sn50 (3) The Safe Drinking Water Act Amendment of 1986 prohibits the use of any solder having a lead content in excess of 0.2% in potable water systems. (4) ASTM B 32 Alloy Grade Sb5 (5) ASTM B 32 Alloy Grade E (6) ASTM B 32 Alloy Grade HB (7) These joining materials are defined as brazing alloys by the American Welding Society. (8) The solder joint exceeds the strength of Types K, L & M tube in drawn and annealed tempers. (9) The solder joint exceeds the strength of Types L & M tube in drawn temper and Type K tube in annealed temper. (10) The solder joint exceeds the strength of Type M tube in drawn temper and Types L & K in annealed temper. (11) The solder joint exceeds the strength of Type L tube in annealed temper. U.S. customary units in this document are the standard; the metric units are provided for reference only. The values stated in each system are not exact equivalents. RATED INTERNAL WORKING PRESSURE1 FOR COPPER FITTINGS, PSI (BAR) Water Temperature Range Nominal Water Tube Size -20° to 100°F 150°F 200°F 250°F 300°F 350°F 400°F (In Inches) (-29° to 38°C) (66°C) (95°C) (120°C) (149°C) (177°C) (204°C) 1/4 912 (62) 775 (53) 729 (50) 729 (50) 714 (49) 608 (42) 456 (31) 3/8 779 (54) 662 (46) 623 (43) 623 (43) 610 (42) 519 (36) 389 (27) 1/2 722 (50) 613 (42) 577 (40) 577 (40) 565 (39) 481 (33) 361 (25) 5/8 631 (43) 537 (37) 505 (35) 505 (35) 495 (34) 421 (29) 316 (21) 3/4 582 (40) 495 (34) 466 (32) 466 (32) 456 (31) 388 (27) 291 (20) 1 494 (34) 420 (29) 395 (27) 395 (27) 387 (26) 330 (23) 247 (17) 1 1/4 439 (30) 373 (26) 351 (24) 351 (24) 344 (23) 293 (20) 219 (15) 1 1/2 408 (28) 347 (24) 327 (23) 327 (23) 320 (22) 272 (19) 204 (14) 2 364 (25) 309 (21) 291 (20) 291 (20) 285 (20) 242 (17) 182 (13) 2 1/2 336 (23) 285 (20) 269 (19) 269 (19) 263 (18) 224 (15) 168 (12) 3 317 (22) 270 (19) 254 (17) 254 (17) 248 (17) 211 (15) 159 (11) 3 1/2 304 (21) 258 (18) 243 (17) 243 (17) 238 (16) 202 (14) 152 (10) 4 293 (20) 249 (17) 235 (16) 235 (16) 230 (16) 196 (13) 147 (10) 5 269 (19) 229 (16) 215 (15) 215 (15) 211 (15) 179 (12) 135 1(9) 6 251 (17) 213 (15) 201 (14) 201 (14) 196 (14) 167 (12) 125 1(8) 8 270 (19) 230 (16) 216 (15) 216 (15) 212 (15) 180 (12) 135 1(9) 1The fitting pressure rating applies to the largest opening of the fitting. AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 55//1144//0022 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 47 RATED INTERNAL WORKING PRESSURES OF CAST COPPER ALLOY FLANGES AND FLANGED FITTINGS Pressure (PSI) Nominal Size Joint Temperature (In Inches) °F (°C) A Class 125A, B Class 150B Class 150A, C 1/2, 3/4,1, 1 1/4, 0 – 150 (0 – 66) 105 (7) 210 (14) 225 (15) 1 1/2, 2, 2 1/2, 175 1(79) 100 (7) 205 (14) 220 (15) 3, 4, 5, 6, 8 200 1(93)195 (7) 195 (13) 210 (15) (also 10" for 225 (107)190 (6) 190 (13) 205 (14) Class 125) 250 (121)190 (6) 180 (12) 195 (13) 275 (135)185 (6) 175 (12) 190 (13) 300 (149)185 (6) 170 (12) 180 (12) 350 (177)175 (5) 150 (10) 165 (11) 406 (208)170 (5) 140 1(9) 150 (10) A MSS SP-106 B ASTM B584, UNS C83800 and UNS C84400 C ASTM B62, UNS C83600 and ASTM B584, UNS C83600 U.S. customary units in this document are the standard; the metric units are provided for reference only. The values stated in each system are not exact equivalents. AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 55//1144//0022 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 48 Copper Water Tube DIMENSIONAL DATA – SOLDER JOINT FITTING ENDS Solder Joint Fittings – Tolerances Solder Joint Fittings Solder Joint Fittings Copper Alloy – Pressure1, 2 Copper Alloy – Drainage3, 4 Male End (Fitting Connector) Female End (Solder Cup) Nominal Diameter Diameter Fitting End Length Solder Cup Length Fitting End Length Solder Cup Length Water Tube Min. Max. Min. Max. Min. Min. Min. Min. Size (In Inches) Inch (mm) Inch (mm) Inch (mm) Inch (mm) Inch (mm) Inch (mm) Inch (mm) Inch (mm) 1/8 0.248 (6.30) 0.251 (6.38) 0.252 (6.40) 0.256 (6.50) 0.31 (7.9) 0.25 (6.4) N/A N/A N/A N/A 1/4 0.373 (9.47) 0.376 (9.55) 0.377 (9.58) 0.381 (9.68) 0.38 (9.7) 0.31 (7.9) N/A N/A N/A N/A 3/8 0.497 (12.62) 0.501 (12.73) 0.502 (12.75) 0.506 (12.85) 0.44 (11.2) 0.38 (9.7) N/A N/A N/A N/A 1/2 0.622 (15.80) 0.626 (15.90) 0.627 (15.93) 0.631 (16.03) 0.56 (14.2) 0.50 (12.7) N/A N/A N/A N/A 5/8 0.747 (18.97) 0.751 (19.08) 0.752 (19.10) 0.756 (19.20) 0.69 (17.5) 0.62 (15.7) N/A N/A N/A N/A 3/4 0.872 (22.15) 0.876 (22.25) 0.877 (22.28) 0.881 (22.38) 0.81 (20.6) 0.75 (19.1) N/A N/A N/A N/A 1 1.122 (28.50) 1.127 (28.63) 1.128 (28.65) 1.132 (28.75) 0.97 (24.6) 0.91 (23.1) N/A N/A N/A N/A 1 1/4 1.372 (34.85) 1.377 (34.98) 1.378 (35.00) 1.382 (35.10) 1.03 (26.2) 0.97 (24.6) 0.56 (14.2) 0.50 (12.7) 1 1/2 1.621 (41.17) 1.627 (41.33) 1.628 (41.35) 1.633 (41.48) 1.16 (29.5) 1.09 (27.7) 0.62 (15.7) 0.56 (14.2) 2 2.121 (53.87) 2.127 (54.03) 2.128 (54.05) 2.133 (54.18) 1.41 (35.8) 1.34 (34.0) 0.69 (17.5) 0.62 (15.7) 2 1/2 2.621 (66.57) 2.627 (66.73) 2.628 (66.75) 2.633 (66.88) 1.53 (38.9) 1.47 (37.3) N/A N/A N/A N/A 3 3.121 (79.27) 3.127 (79.43) 3.128 (79.45) 3.133 (79.58) 1.72 (43.7) 1.66 (42.2) 0.81 (20.6) 0.75 (19.1) 3 1/2 3.621 (91.97) 3.627 (92.13) 3.628 (92.15) 3.633 (92.28) 1.97 (50.0) 1.91 (48.5) N/A N/A N/A N/A 4 4.121 (104.67) 4.127 (104.83) 4.128 (104.85) 4.133 (104.98) 2.22 (56.4) 2.16 (54.9) 1.06 (26.9) 1.00 (25.4) 5 5.121 (130.07) 5.127 (130.23) 5.128 (130.25) 5.133 (130.38) 2.72 (69.1) 2.66 (67.6) 1.31 (33.3) 1.25 (31.8) 6 6.121 (155.47) 6.127 (155.63) 6.128 (155.65) 3.133 (79.58) 3.22 (81.8) 3.09 (78.5) 1.62 (41.1) 1.50 (38.1) 8 8.119 (206.22) 8.127 (206.43) 8.128 (206.45) 8.133 (206.58) 4.09 (103.9) 3.97 (100.8) 2.12 (53.8) 2.00 (50.8) 10 10.119 (257.02) 10.127 (257.23) 10.128 (257.25) 10.133 (257.38) 4.12 (104.6) 4.00 (101.6) N/A N/A N/A N/A 12 12.119 (307.82) 12.127 (308.03) 12.128 (308.05) 12.133 (308.18) 4.62 (117.3) 4.50 (114.3) N/A N/A N/A N/A 1As shown Standard ASME B16.18 2As shown Standard ASME B16.22 3As shown Standard ASME B16.23 4As shown Standard ASME B16.29 The mechanics of making both the solder joint and the brazing joint are comparatively similar. Complete instructions on proper techniques of both of these joining methods are outlined in this catalog on pages 85-97. A very important consideration in Copper Piping is the selection of the proper bonding medium. As a general rule, the working temperature of the installation is a more important consideration than the working pressures. If the working temperature is not over 250°F (121°C), either 50-50%* or 95-5% solder can be used successfully. However, if the temperature exceeds 250°F (121°C), a low temperature brazing alloy should be used, with a melting temperature somewhat in excess of 1000°F (538°C). According to BMS report No. 58, joints made with tin or tin-alloy solders should not be subject continuously to temperatures above 250°F (121°C). A number of brazing alloys are available and a careful study should be made in every case to determine the proper alloy for the particular application. *The Safe Drinking Water Act Amendment of 1986 prohibits the use in potable water systems of any solder having a lead content in excess of 0.2%. U.S. customary units in this document are the standard; the metric units are provided for reference only. The values stated in each system are not exact equivalents. AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 55//1144//0022 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 49 DIMENSIONAL DATA – BRAZING FITTING ENDS Male End (Fitting Connector) Diameter Female End (Brazing Cup) Diameter Fitting End Solder Cup Length Length Nominal Min. Max. Min. Max. Min. Min. Water Tube Size (In Inches) Inch (mm) Inch (mm) Inch (mm) Inch (mm) Inch (mm) Inch (mm) 1/4 0.373 (9.47) 0.376 (9.55) 0.377 (9.58) 0.381 (9.68) 0.23 (5.8) 0.17 (4.3) 3/8 0.497 (12.62) 0.501 (12.73) 0.502 (12.75) 0.506 (12.85) 0.26 (6.6) 0.20 (5.1) 1/2 0.622 (15.80) 0.626 (15.90) 0.627 (15.93) 0.631 (16.03) 0.28 (7.1) 0.22 (5.6) 5/8 0.747 (18.97) 0.751 (19.08) 0.752 (19.10) 0.756 (19.20) N/A N/A N/A N/A 3/4 0.872 (22.15) 0.876 (22.25) 0.877 (22.28) 0.881 (22.38) 0.31 (7.9) 0.25 (6.4) 1 1.122 (28.50) 1.127 (28.63) 1.128 (28.65) 1.132 (28.75) 0.34 (8.6) 0.28 (7.1) 1 1/4 1.372 (34.85) 1.377 (34.98) 1.378 (35.00) 1.382 (35.10) 0.37 (9.4) 0.31 (7.9) 1 1/2 1.621 (41.17) 1.627 (41.33) 1.628 (41.35) 1.633 (41.48) 0.40 (10.2) 0.34 (8.6) 2 2.121 (53.87) 2.127 (54.03) 2.128 (54.05) 2.133 (54.18) 0.47 (11.9) 0.40 (10.2) 2 1/2 2.621 (66.57) 2.627 (66.73) 2.628 (66.75) 2.633 (66.88) 0.53 (13.5) 0.47 (11.9) 3 3.121 (79.27) 3.127 (79.43) 3.128 (79.45) 3.133 (79.58) 0.59 (15.0) 0.53 (13.5) 3 1/2 3.621 (91.97) 3.627 (92.13) 3.628 (92.15) 3.633 (92.28) 0.65 (16.5) 0.59 (15.0) 4 4.121 (104.67) 4.127 (104.83) 4.128 (104.85) 4.133 (104.98) 0.72 (18.3) 0.64 (16.3) 5 5.121 (130.07) 5.127 (130.23) 5.128 (130.25) 5.133 (130.38) 0.81 (20.6) 0.73 (18.5) 6 6.121 (155.47) 6.127 (155.63) 6.128 (155.65) 3.133 (79.58) 0.94 (23.9) 0.83 (21.1) 8 8.119 (206.22) 8.127 (206.43) 8.128 (206.45) 8.133 (206.58) 1.28 (32.5) 1.17 (29.7) 10 10.119 (257.02) 10.127 (257.23) 10.128 (257.25) 10.133 (257.38) N/A N/A N/A N/A 12 12.119 (307.82) 12.127 (308.03) 12.128 (308.05) 12.133 (308.18) N/A N/A N/A N/A 1 In accordance with MS SP-73 U.S. customary units in this document are the standard; the metric units are provided for reference only. The values stated in each system are not exact equivalents. AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 55//1144//0022 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 50 Copper Water Tube continued U.S. customary units in this document are the standard; the metric units are provided for reference only. The values stated in each system are not exact equivalents. DIMENSIONAL DATA – COPPER WATER TUBE – TYPE “K” TYPE “K” Hard Drawn: 20-ft. (6.1m) Straight Lengths Soft Annealed: 20-ft. (6.1m) Straight Lengths, or 40-ft. (12.2m) and 60-ft. (18.3m) Length Coils (to and including size 1 1/2) Usage: For underground service and general purpose plumbing and heating installations under severe conditions. Tolerances Hard Drawn Soft Annealed (Hard Drawn Only) Outside Tubing OD Nominal Wall Weight Bursting Safe Working Bursting Safe Working Nominal Diameter Thickness Per Foot PressureA PressureB PressureA PressureC Water Tube Min. Max. Size (In Inches) Inch (mm) Inch (mm) Inch (mm) Inch (mm) Lb (kg) psi (bars) psi (bars) psi (bars) psi (bars) 1/4 0.375 (9.53) 0.373 (9.47) 0.376 (9.55) 0.035 (0.89) 0.145 (0.07) N/A N/A 1612 (111) N/A N/A 913 (63) 3/8 0.500 (12.70) 0.497 (12.62) 0.501 (12.73) 0.049 (1.24) 0.269 (0.12) N/A N/A 1675 (115) N/A N/A 960 (66) 1/2 0.625 (15.88) 0.622 (15.80) 0.626 (15.90) 0.049 (1.24) 0.344 (0.16) 9840 (678) 1337 (92) 4535 (313) 758 (52) 5/8 0.750 (19.05) 0.747 (18.97) 0.751 (19.08) 0.049 (1.24) 0.418 (0.19) N/A N/A 1104 (76) N/A N/A 626 (43) 3/4 0.875 (22.23) 0.872 (22.15) 0.876 (22.25) 0.065 (1.65) 0.641 (0.29) 9300 (641) 1278 (88) 4200 (290) 724 (50) 1 1.125 (28.58) 1.122 (28.50) 1.127 (28.63) 0.065 (1.65) 0.839 (0.38) 7200 (496) 982 (68) 3415 (235) 557 (38) 1 1/4 1.375 (34.93) 1.372 (34.85) 1.377 (34.98) 0.065 (1.65) 1.040 (0.47) 5525 (381) 797 (55) 2800 (193) 452 (31) 1 1/2 1.625 (41.28) 1.621 (41.17) 1.627 (41.33) 0.072 (1.83) 1.360 (0.62) 5000 (345) 742 (51) 2600 (179) 420 (29) 2 2.125 (53.98) 2.121 (53.87) 2.127 (54.03) 0.083 (2.11) 2.060 (0.93) 3915 (270) 652 (45) 2235 (154) 370 (26) 2 1/2 2.625 (66.68) 2.621 (66.57) 2.627 (66.73) 0.095 (2.41) 2.930 (1.33) 3575 (246) 597 (41) N/A N/A 338 (23) 3 3.125 (79.38) 3.121 (79.27) 3.127 (79.43) 0.109 (2.77) 4.000 (1.81) 3450 (238) 578 (40) N/A N/A 328 (23) 3 1/2 3.625 (92.08) 3.621 (91.97) 3.627 (92.13) 0.120 (3.05) 5.120 (2.32) N/A N/A 549 (38) N/A N/A 311 (21) 4 4.125 (104.78) 4.121 (104.67) 4.127 (104.83) 0.134 (3.40) 6.510 (2.95) 3415 (235) 540 (37) N/A N/A 306 (21) 5 5.125 (130.18) 5.121 (130.07) 5.127 (130.23) 0.160 (4.06) 9.670 (4.39) 3585 (247) 517 (36) N/A N/A 293 (20) 6 6.125 (155.58) 6.121 (155.47) 6.127 (155.63) 0.192 (4.88) 13.900 (6.30) 3425 (236) 520 (36) N/A N/A 295 (20) 8 8.125 (206.38) 8.119 (206.22) 8.127 (206.43) 0.271 (6.88) 25.900 (11.75) 3635 (251) 553 (38) N/A N/A 314 (22) 10 10.125 (257.18) 10.119 (257.02) 10.127 (257.23) 0.338 (8.59) 40.300 (18.28) N/A N/A 553 (38) N/A N/A 314 (22) 12 12.125 (307.98) 12.119 (307.82) 12.127 (308.03) 0.405 (10.29) 57.800 (26.22) N/A N/A 555 (38) N/A N/A 314 (22) Note: Information and data contained in these charts, as taken from ASTM Specifications B 88. Rated internal pressure for copper water tube based on the strength of the tube alone and applicable to systems using suitable mechanical joints. ABased on actual laboratory test data provided by Copper Development Association, Inc. BBased upon 150°F (65.6°C) with an allowable stress of 9500 psi (668 kPa). CBased upon 150°F (65.6°C) with an allowable stress of 5100 psi (359 kPa). AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 55//1144//0022 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 51 U.S. customary units in this document are the standard; the metric units are provided for reference only. The values stated in each system are not exact equivalents. DIMENSIONAL DATA – COPPER WATER TUBE – TYPE “L” TYPE “L” Hard Drawn: 20-ft. (6.1m) Straight Lengths Soft Annealed: 20-ft. (6.1m) Straight Lengths, or 40-ft. (12.2m) and 60-ft. (18.3m) Length Coils (to and including size 1 1/2) Usage: For general purpose plumbing and heating conditions. Tolerances Hard Drawn Soft Annealed (Hard Drawn Only) Outside Tubing OD Nominal Wall Weight Bursting Safe Working Bursting Safe Working Nominal Diameter Thickness Per Foot PressureA PressureB PressureA PressureC Water Tube Min. Max. Size (In Inches) Inch (mm) Inch (mm) Inch (mm) Inch (mm) Lb (kg) psi (bars) psi (bars) psi (bars) psi (bars) 1/4 0.375 (9.53) 0.373 (9.47) 0.376 (9.55) 0.030 (0.76) 0.126 (0.06) N/A N/A 1367 (94) N/A N/A 775 (53) 3/8 0.500 (12.70) 0.497 (12.62) 0.501 (12.73) 0.035 (0.89) 0.198 (0.09) N/A N/A 1168 (81) N/A N/A 662 (46) 1/2 0.625 (15.88) 0.622 (15.80) 0.626 (15.90) 0.040 (1.02) 0.285 (0.13) 7765 (535) 1082 (75) 3885 (268) 613 (42) 5/8 0.750 (19.05) 0.747 (18.97) 0.751 (19.08) 0.042 (1.07) 0.362 (0.16) N/A N/A 947 (65) N/A N/A 537 (37) 3/4 0.875 (22.23) 0.872 (22.15) 0.876 (22.25) 0.045 (1.14) 0.455 (0.21) 5900 (407) 873 (60) 2935 (202) 495 (34) 1 1.125 (28.58) 1.122 (28.50) 1.127 (28.63) 0.050 (1.27) 0.655 (0.30) 5115 (353) 741 (51) 2650 (183) 420 (29) 1 1/4 1.375 (34.93) 1.372 (34.85) 1.377 (34.98) 0.055 (1.40) 0.884 (0.40) 4550 (314) 658 (45) 2400 (165) 373 (26) 1 1/2 1.625 (41.28) 1.621 (41.17) 1.627 (41.33) 0.060 (1.52) 1.140 (0.52) 4100 (283) 613 (42) 2200 (152) 347 (24) 2 2.125 (53.98) 2.121 (53.87) 2.127 (54.03) 0.070 (1.78) 1.750 (0.79) 3365 (232) 545 (38) 1910 (132) 309 (21) 2 1/2 2.625 (66.68) 2.621 (66.57) 2.627 (66.73) 0.080 (2.03) 2.480 (1.12) 3215 (222) 504 (35) N/A N/A 285 (20) 3 3.125 (79.38) 3.121 (79.27) 3.127 (79.43) 0.090 (2.29) 3.330 (1.51) 2865 (198) 476 (33) N/A N/A 270 (19) 3 1/2 3.625 (92.08) 3.621 (91.97) 3.627 (92.13) 0.100 (2.54) 4.290 (1.95) N/A N/A 455 (31) N/A N/A 258 (18) 4 4.125 (104.78) 4.121 (104.67) 4.127 (104.83) 0.110 (2.79) 5.380 (2.44) 2865 (198) 440 (30) N/A N/A 249 (17) 5 5.125 (130.18) 5.121 (130.07) 5.127 (130.23) 0.125 (3.18) 7.610 (3.45) 2985 (206) 404 (28) N/A N/A 229 (16) 6 6.125 (155.58) 6.121 (155.47) 6.127 (155.63) 0.140 (3.56) 10.200 (4.63) 2690 (185) 376 (26) N/A N/A 213 (15) 8 8.125 (206.38) 8.119 (206.22) 8.127 (206.43) 0.200 (5.08) 19.290 (8.75) 2650 (183) 406 (28) N/A N/A 230 (16) 10 10.125 (257.18) 10.119 (257.02) 10.127 (257.23) 0.250 (6.35) 30.100 (13.65) N/A N/A 407 (28) N/A N/A 231 (16) 12 12.125 (307.98) 12.119 (307.82) 12.127 (308.03) 0.280 (7.11) 40.400 (18.33) N/A N/A 380 (26) N/A N/A 215 (15) Note: Information and data contained in these charts, as taken from ASTM Specifications B 88. Rated internal pressure for copper water tube based on the strength of the tube alone and applicable to systems using suitable mechanical joints. ABased on actual laboratory test data provided by Copper Development Association, Inc. BBased upon 150°F (65.6°C) with an allowable stress of 9500 psi (668 kPa). CBased upon 150°F (65.6°C) with an allowable stress of 5100 psi (359 kPa). AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 55//1144//0022 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 52 U.S. customary units in this document are the standard; the metric units are provided for reference only. The values stated in each system are not exact equivalents. Copper Water Tube continued DIMENSIONAL DATA – COPPER WATER TUBE – TYPE “M” TYPE “M” Hard Drawn Only: 20-ft. (6.1m) Straight Lengths Usage: For general purpose plumbing, heating and drainage installations. Tolerances Hard Drawn (Hard Drawn Only) Outside Tubing OD Nominal Wall Weight Bursting Safe Working Nominal Diameter Thickness Per Foot PressureA PressureB Water Tube Min. Max. Size (In Inches) Inch (mm) Inch (mm) Inch (mm) Inch (mm) Lb (kg) psi (bars) psi (bars) 1/4 0.375 (9.53) 0.373 (9.47) 0.376 (9.55) N/A N/A N/A N/A N/A N/A N/A N/A 3/8 0.500 (12.70) 0.497 (12.62) 0.501 (12.73) 0.025 (0.64) 0.145 (0.07) N/A N/A 855 (59) 1/2 0.625 (15.88) 0.622 (15.80) 0.626 (15.90) 0.028 (0.71) 0.204 (0.09) 6135 (423) 741 (51) 5/8 0.750 (19.05) 0.747 (18.97) 0.751 (19.08) N/A N/A N/A N/A N/A N/A N/A N/A 3/4 0.875 (22.23) 0.872 (22.15) 0.876 (22.25) 0.032 (0.81) 0.328 (0.15) 4717 (325) 611 (42) 1 1.125 (28.58) 1.122 (28.50) 1.127 (28.63) 0.035 (0.89) 0.465 (0.21) 3865 (266) 506 (35) 1 1/4 1.375 (34.93) 1.372 (34.85) 1.377 (34.98) 0.042 (1.07) 0.682 (0.31) 3875 (267) 507 (35) 1 1/2 1.625 (41.28) 1.621 (41.17) 1.627 (41.33) 0.049 (1.24) 0.940 (0.43) 3550 (245) 497 (34) 2 2.125 (53.98) 2.121 (53.87) 2.127 (54.03) 0.058 (1.47) 1.460 (0.66) 2935 (202) 448 (31) 2 1/2 2.625 (66.68) 2.621 (66.57) 2.627 (66.73) 0.065 (1.65) 2.030 (0.92) 2800 (193) 411 (28) 3 3.125 (79.38) 3.121 (79.27) 3.127 (79.43) 0.072 (1.83) 2.680 (1.22) 2665 (184) 380 (26) 3 1/2 3.625 (92.08) 3.621 (91.97) 3.627 (92.13) 0.083 (2.11) 3.580 (1.62) N/A N/A 378 (26) 4 4.125 (104.78) 4.121 (104.67) 4.127 (104.83) 0.095 (2.41) 4.660 (2.11) 2215 (153) 377 (26) 5 5.125 (130.18) 5.121 (130.07) 5.127 (130.23) 0.109 (2.77) 6.660 (3.02) 2490 (172) 349 (24) 6 6.125 (155.58) 6.121 (155.47) 6.127 (155.63) 0.122 (3.10) 8.920 (4.05) 2000 (138) 328 (23) 8 8.125 (206.38) 8.119 (206.22) 8.127 (206.43) 0.170 (4.32) 16.500 (7.48) 2285 (158) 344 (24) 10 10.125 (257.18) 10.119 (257.02) 10.127 (257.23) 0.212 (5.38) 25.600 (11.61) N/A N/A 344 (24) 12 12.125 (307.98) 12.119 (307.82) 12.127 (308.03) 0.254 (6.45) 36.700 (16.65) N/A N/A 345 (24) Note: Information and data contained in these charts, as taken from ASTM Specifications B 88. Rated internal pressure for copper water tube based on the strength of the tube alone and applicable to systems using suitable mechanical joints. ABased on actual laboratory test data provided by Copper Development Association, Inc. BBased upon 150°F (65.6°C) with an allowable stress of 9500 psi (668 kPa). AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 55//1144//0022 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 53 U.S. customary units in this document are the standard; the metric units are provided for reference only. The values stated in each system are not exact equivalents. DIMENSIONAL DATA – COPPER WATER TUBE – TYPE “DWV” TYPE “DWV” Hard Drawn Only: 20-ft. (6.1m) Straight Lengths Usage: For drain, waste, vent and other non-pressure applications. Tolerances Hard Drawn (Hard Drawn Only) Outside Tubing OD Nominal Wall Weight Bursting Nominal Diameter Thickness Per Foot PressureA Water Tube Min. Max. Size (In Inches) Inch (mm) Inch (mm) Inch (mm) Inch (mm) Lb (kg) psi (bars) 1/4 0.375 (9.53) 0.373 (9.47) 0.376 (9.55) N/A N/A N/A N/A N/A N/A 3/8 0.500 (12.70) 0.497 (12.62) 0.501 (12.73) N/A N/A N/A N/A N/A N/A 1/2 0.625 (15.88) 0.622 (15.80) 0.626 (15.90) N/A N/A N/A N/A N/A N/A 5/8 0.750 (19.05) 0.747 (18.97) 0.751 (19.08) N/A N/A N/A N/A N/A N/A 3/4 0.875 (22.23) 0.872 (22.15) 0.876 (22.25) N/A N/A N/A N/A N/A N/A 1 1.125 (28.58) 1.122 (28.50) 1.127 (28.63) N/A N/A N/A N/A N/A N/A 1 1/4 1.375 (34.93) 1.372 (34.85) 1.377 (34.98) 0.040 (1.02) 0.650 (0.29) N/A N/A 1 1/2 1.625 (41.28) 1.621 (41.17) 1.627 (41.33) 0.042 (1.07) 0.809 (0.37) 440 (30) 2 2.125 (53.98) 2.121 (53.87) 2.127 (54.03) 0.042 (1.07) 1.070 (0.49) 326 (22) 2 1/2 2.625 (66.68) 2.621 (66.57) 2.627 (66.73) N/A N/A N/A N/A N/A N/A 3 3.125 (79.38) 3.121 (79.27) 3.127 (79.43) 0.045 (1.14) 1.690 (0.77) 239 (16) 3 1/2 3.625 (92.08) 3.621 (91.97) 3.627 (92.13) N/A N/A N/A N/A N/A N/A 4 4.125 (104.78) 4.121 (104.67) 4.127 (104.83) 0.058 (1.47) 2.870 (1.30) 225 (16) 5 5.125 (130.18) 5.121 (130.07) 5.127 (130.23) 0.072 (1.83) 4.430 (2.01) 227 (16) 6 6.125 (155.58) 6.121 (155.47) 6.127 (155.63) 0.083 (2.11) 6.100 (2.77) 223 (15) 8 8.125 (206.38) 8.119 (206.22) 8.127 (206.43) 0.109 N/A 10.600 (4.81) 219 (15) 10 10.125 (257.18) 10.119 (257.02) 10.127 (257.23) N/A N/A N/A N/A N/A N/A 12 12.125 (307.98) 12.119 (307.82) 12.127 (308.03) N/A N/A N/A N/A N/A N/A Note: Information and data contained in these charts, as taken from ASTM Specifications B 88. Rated internal pressure for copper water tube based on the strength of the tube alone and applicable to systems using suitable mechanical joints. ABased on actual laboratory test data provided by Copper Development Association, Inc. BBased upon 150°F (65.6°C) with an allowable stress of 9500 psi (668 kPa). CBased upon 150°F (65.6°C) with an allowable stress of 5100 psi (359 kPa). DWV Tube is for sanitary drainage applications. The tubing wall is thinner than Type “M” – making it both lighter and less expensive. Research indicates that DWV tube has a service life of approximately 100 years – considerably longer than any building in which it might be installed. The advantages of copper systems are augmented in DWV installations. Its light weight makes handling and transportation easier – only 0.34 lb. (0.15 kg) for a 20 ft. (6.1 m) length of size 3. Its thinner wall allows faster soldering. These advantages offer an economical option without sacrificing stability or longevity for both contractor and the home owner. Further information will be furnished on request from NIBCO’s Technical Services Department, at 1-888-446-4226 AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 55//1144//0022 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 54 Copper Water Tube continued Under normal conditions, the physical properties of copper tubes, when produced by responsible manufacturers are perfectly adapted for the conveyance of hot and cold water, steam, oil, gas, and air. Copper tubes will stand up under ordinary conditions, but the user is specifically cautioned against laying underground tube in cinderfill, especially if the ground is apt to be wet. Due to the sulphur compounds in the cinders, a condition of this kind may corrode the outside of the tubes. This may be overcome either by wrapping the tube with canvas and asphaltum or by surrounding the tube with a bed of clean sand mixed with lime, or with limestone or broken plaster. When conditions are doubtful, it is advisable to consult the Copper Development Association, or the tube manufacturer. Annealed copper tubes are generally recommended for underground use. 1/2" annealed copper tubes have been frozen as many as six times before finally bursting, eight times for 1" size, and eleven times for 2" size. Hard drawn copper tubes, however, burst during the first freezing the same as iron pipe. (Condensed from Copper Tube Handbook.) COMPARATIVE DATA – COPPER WATER TUBE AND IRON PIPES BTUs to Raise 100°F/38°C Nominal “A” “B” “C” “D” “E” “F” “G” “H” “I” Water New Pipe Inside Outside Weight Volume Water Pipe Heat Loss Flow Tube Size Diameter Diameter (In Inches) Inch (mm) Inch (mm) Lb (Kg)Gal/10ft. L/3.05m BTU kJ BTU kJ BTU kJ GPM LPM 3/8 Coper .430 (10.92) 0.500 (12.70) 0.198 (0.090) 0.0754 (0.2854) 62.89 (66.4) 18.61 (19.6) No Data No Data 1.873 (7.089) Iron .493 (12.52) 0.675 (17.15) 0.567 (0.257) 0.0992 (0.3755) 82.66 (87.2) 62.37 (65.8) No Data No Data 2.464 (9.326) 1/2 Coper .545 (13.84) 0.625 (15.88) 0.285 (0.129) 0.1212 (0.4587) 101.20 (106.8) 26.70 (28.2) 0.34 (0.36) 3.565 (13.494) Iron .622 (15.80) 0.840 (21.34) 0.850 (0.386) 0.1578 (0.5973) 131.60 (138.8) 93.50 (98.6) 5.94 (6.27) 4.585 (17.354) 3/4 Coper .785 (19.94) 0.875 (22.23) 0.455 (0.207) 0.2514 (0.9515) 209.60 (221.1) 42.67 (45.0) 0.41 (0.44) 9.599 (36.332) Iron .824 (20.93) 1.050 (26.67) 1.130 (0.513) 0.2770 (1.0484) 230.10 (242.8) 124.30 (131.1) 7.16 (7.55) 9.720 (36.790) 1 Coper 1.025 (26.04) 1.125 (28.58) 0.655 (0.297) 0.4287 (1.6226) 357.30 (377.0) 61.38 (64.8) 0.50 (0.53) 19.80 (74.94) Iron 1.049 (26.64) 1.315 (33.40) 1.678 (0.762) 0.4490 (1.6995) 374.30 (394.9) 184.58 (194.7) 8.62 (9.09) 18.53 (70.14) 1 1/4 Coper 1.265 (32.13) 1.375 (34.93) 0.884 (0.401) 0.6529 (2.4712) 544.30 (574.3) 82.91 (87.5) 0.62 (0.65) 35.05 (132.66) Iron 1.380 (35.05) 1.660 (42.16) 2.270 (1.031) 0.7770 (2.9409) 647.70 (683.4) 249.70 (263.4) 10.65 (11.24) 38.56 (145.95) 1 1/2 Coper 1.505 (38.23) 1.625 (41.28) 1.140 (0.518) 0.9241 (3.4977) 770.40 (812.8) 107.16 (113.1) 0.69 (0.73) 56.16 (212.57) Iron 1.610 (40.89) 1.900 (48.26) 2.720 (1.235) 1.0580 (4.0045) 881.60 (930.1) 298.10 (314.5) 11.97 (12.63) 58.20 (220.29) 2 Coper 1.985 (50.42) 2.125 (53.98) 1.750 (0.795) 1.6080 (6.0863) 1340.00 (1413.8) 164.50 (173.6) 0.84 (0.89) 119.10 (450.79) Iron 2.067 (52.50) 2.375 (60.33) 3.650 (1.657) 1.7430 (6.5973) 1453.00 (1533.0) 401.50 (423.6) 14.61 (15.41) 113.50 (429.60) 2 1/2 Coper 2.465 (62.61) 2.625 (66.68) 2.480 (1.126) 2.4790 (9.3830) 2066.00 (2179.7) 233.00 (245.8) 1.01 (1.07) 214.30 (811.13) Iron 2.469 (62.71) 2.875 (73.03) 5.790 (2.629) 2.4870 (9.4133) 2073.00 (2187.1) 636.90 (672.0) 17.42 (18.38) 182.50 (690.76) 3 Coper 2.945 (74.80) 3.125 (79.38) 3.330 (1.512) 3.5390 (13.3951) 2945.00 (3107.1) 313.20 (330.4) 1.13 (1.19) 347.40 (1314.91) Iron 3.068 (77.93) 3.5 (88.90) 7.58 (3.441) 3.8400 (14.5344) 3201.00 (3377.2) 832.70 (878.5) 20.63 (21.77) 326.00 (1233.91) 4 Coper 3.905 (99.19) 4.125 (104.78) 5.380 (2.443) 6.2220 (23.5503) 5186.00 (5471.5) 505.72 (533.6) 1.50 (1.58) 747.10 (2827.77) Iron 4.026 (102.26) 4.5 (114.30) 10.79 (4.899) 6.6130 (25.0302) 5513.00 (5816.5) 1186.90 (1252.2) 26.00 (27.43) 673.80 (2550.33) COLUMN A: The copper tube is Type L Standard, meeting the requirements of ASTM Specification B 88. The iron pipe is standard weight, schedule 40, bare pipe, except as to Column I where new galvanized pipe is referred to. COLUMN B: From manufacturers’ specifications. Slight variations can be noted between specifications of different manufacturers, but these figures are representative. COLUMN C: From manufacturers’ specifications with the same considerations as noted for Column B. COLUMN D: From manufacturers’ specifications. COLUMN E: Cubic contents of 10 linear feet/3.05 linear metres of tube and have been calculated from dimeters given in Column B, by the formula for the contents of a cylinder. COLUMN F: This column has been calculated from Column E and shows the number of BTUs (kilojoules) required to heat the water content only of 10 feet (3.05 metres) of the given tube and pipe 100°F (38°C). It requires 833.6 BTUs (879.5 kJ) to heat 1 gallon (3.875 litres) of water 100°F (38°C). COLUMN G: These figures are calculated from Column D and show the number of BTUs (kJ) required to raise the temperature of 10 feet (3.05 metres) of empty tube and pipe 100°F (38°C). Due to difference in the specific heat of the materials, it requires 9.4 BTUs (9.9 kJ) to raise 1 pound (0.454 kilograms) of copper 100°F (38°C) and 11.0 BTUs (11.6 kJ) to raise 1 pound (0.454 kilograms) of iron 100°F (38°C). COLUMN H: This column shows the heat emission from 10 feet (3.05 metres) of the given tube and pipe placed horizontally. The column in terms of BTUs lost per hour (kilojoules lost per hour) for each degree of difference in temperature between the pipe and the surrounding air. The figures for iron are taken from experimental data obtained at the Mellon Institute. Figures for copper have been calculated with reference to those for iron on the basis of the known ratio of heat emission between the two materials. COLUMN I: This column shows the number of gallons (litres) of water which will flow through 100 feet (30.48 metres) of the given tube and pipe with a pressure loss of 10 pounds per square inch (70 kilopascals). Flow is based on diameters in Column B according to Professor Dawson’s formulae for NEW galvanized iron pipe and NEW copper tube. Due to the corrosion of iron and its tendency to accumulate sediments and other foreign matter, Prof. Dawson suggests that 15% be deducted from the figures for iron pipe in order to arrive at a reasonable performance expectancy for such pipe in service. Because copper resists rust and is inherently more smooth, Professor Dawson suggests a deduction of only 5% from the figures given for copper tube. U.S. customary units in this document are the standard; the metric units are provided for reference only. The values stated in each system are not exact equivalents. RADII OF COILED EXPANSION LOOPS AND DEVELOPED LENGTHS OF EXPANSION OFFSETS Expected Expansion Nominal 1/2 1 1 1/2 2 2 1/2 3 3 1/2 4 TubeRLRLRLRLRLRLRLRL Size Inch (mm) Inch (mm) Inch (mm) Inch (mm) Inch (mm) Inch (mm) Inch (mm) Inch (mm) Inch (mm) 1/4 6 (152.4) 38 (965.2) 9 (228.6) 54 (1371.6) 11 (279.4) 66 (1676.4) 12 (304.8) 77 (1955.8) 14 (355.6) 3/8 7 (177.8) 44 (1117.6) 10 (254.0) 63 (1600.2) 12 (304.8) 77 (1955.8) 14 (355.6) 89 (2260.6) 16 (406.4) 1/2 8 (203.2) 50 (1270.0) 11 (279.4) 70 (1778.0) 14 (355.6) 89 (2260.6) 16 (406.4) 99 (2514.6) 18 (457.2) 3/4 9 (228.6) 59 (1498.6) 13 (330.2) 83 (2108.2) 16 (406.4) 101 (2565.4) 19 (482.6) 117 (2971.8) 21 (533.4) 1 11 (279.4) 67 (1701.8) 15 (381.0) 94 (2387.6) 18 (457.2) 115 (2921.0) 21 (533.4) 133 (3378.2) 24 (609.6) 1 1/2 13 (330.2) 80 (2032.0) 18 (457.2) 113 (2870.2) 22 (558.8) 138 (3505.2) 25 (635.0) 160 (4064.0) 29 (736.6) 2 15 (381.0) 91 (2311.4) 21 (533.4) 129 (3276.6) 25 (635.0) 158 (4013.2) 29 (736.6) 183 (4648.2) 33 (838.2) 2 1/2 16 (406.4) 102 (2590.8) 23 (584.2) 144 (3657.6) 28 (711.2) 176 (4470.4) 32 (812.8) 203 (5156.2) 36 (914.4) 3 18 (457.2) 111 (2819.4) 25 (635.0) 157 (3987.8) 30 (762.0) 191 (4851.4) 35 (889.0) 222 (5638.8) 40 (1016.0) 3 1/2 19 (482.6) 120 (3048.0) 27 (685.8) 169 (4292.6) 33 (838.2) 206 (5232.4) 38 (965.2) 239 (6070.6) 43 (1092.2) 4 20 (508.0) 128 (3251.2) 29 (736.6) 180 (4572.0) 35 (889.0) 220 (5588.0) 41 (1041.4) 255 (6477.0) 45 (1143.0) 5 23 (584.2) 142 (3606.8) 32 (812.8) 201 (5105.4) 39 (990.6) 245 (6223.0) 45 (1143.0) 284 (7213.6) 51 (1295.4) Inch (mm) Inch (mm) Inch (mm) Inch (mm) Inch (mm) Inch (mm) Inch (mm) 86 (2184.4) 15 (381.0) 94 (2387.6) 16 (406.4) 102 (2590.8) 17 (431.8) 109 (2768.6) 99 (2514.6) 17 (431.8) 109 (2768.6) 19 (482.6) 117 (2971.8) 20 (508.0) 126 (3200.4) 111 (2819.4) 19 (482.6) 122 (3098.8) 21 (533.4) 131 (3327.4) 22 (558.8) 140 (3556.0) 131 (3327.4) 23 (584.2) 143 (3632.2) 25 (635.0) 155 (3937.0) 26 (660.4) 166 (4216.4) 149 (3784.6) 26 (660.4) 163 (4140.2) 28 (711.2) 176 (4470.4) 30 (762.0) 188 (4775.2) 179 (4546.6) 31 (787.4) 196 (4978.4) 34 (863.6) 212 (5384.8) 36 (914.4) 226 (5740.4) 205 (5207.0) 36 (914.4) 224 (5689.6) 39 (990.6) 242 (6146.8) 41 (1041.4) 259 (6578.6) 227 (5765.8) 40 (1016.0) 249 (6324.6) 43 (1092.2) 269 (6832.6) 46 (1168.4) 288 (7315.2) 248 (6299.2) 43 (1092.2) 272 (6908.8) 47 (1193.8) 293 (7442.2) 50 (1270.0) 314 (7975.6) 267 (6781.8) 47 (1193.8) 293 (7442.2) 50 (1270.0) 316 (8026.4) 54 (1371.6) 338 (8585.2) 285 (7239.0) 50 (1270.0) 312 (7924.8) 54 (1371.6) 337 (8559.8) 57 (1447.8) 361 (9169.4) 318 (8077.2) 55 (1397.0) 348 (8839.2) 60 (1524.0) 376 (9550.4) 64 (1625.6) 402(10210.8) AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 55//1144//0022 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 55 In the majority of low-pressure heating systems employing copper tube and installed in small houses or private dwellings, provision for expansion and contraction is relatively simple. Mains, risers, and branches to radiators should be free or floating at one end of the line. Holes should be large enough to permit free movement of the tube, and care should be exercised so that pipe hangers and supports permit unrestricted movement and do not anchor the tube. Wrought copper tube hangers that are both practicable and neat in appearance are available. Unusually long runs of copper tubing should be provided with an expansion bend or loop. By bending soft temper copper tube, a simple form of expansion loop can be made. With the addition of combination flared-tube to solder joint fittings, as illustrated in Figure 1, these types of loops can be used when space or other limitations exist. The correct proportions of such expansion loop to meet various conditions are shown in the accompanying table. FIGURE 1 EXPANSION AND CONTRACTION U.S. customary units in this document are the standard; the metric units are provided for reference only. The values stated in each system are not exact equivalents. The above chart is calculated using 10ft (3.05m) of copper tubing as the reference point. You may use it as follows: 100ft (30.5m) of copper tube, with a 200°F (93.3°C) temperature change. Reference point .2256 inches for 10ft, (5.73mm for 3.05m), multipy by 10 for 100ft (30.5m), resulting in an answer of 2.256 inches (57.3mm) of expansion or contraction. NOTE: Calculations for expansion and contraction should be based on the average coefficient of expansion of copper which is 0.0000094 per °F (0.00001692 per °C) between 77°F and 212°F (25°C and 100°C). For example, the expansion for each 10ft (3.05m) of any size of tube heated from room temperature of 70°F (21.1°C) to 170°F (76.7°C), that is, 100°F (55.6°C) rise, is: Rise Coefficient 100°F 10ft 12 inches 0.000094 0.1128 in.xx x =(55.6°C) (3.05m) (1000mm) (0.00001692) (2.87mm) a. U-Bend c. Offset and Return b. Coiled Loop APPROXIMATE FRICTION LOSS ALLOWANCES FOR FITTINGS AND VALVES IN FEET OF STRAIGHT TUBE Wrought-Copper Fittings Cast Copper Alloy Fittings and Valves Nominal 90° 45° Tee Tee 90° 180° 90° 45° Tee Tee Comp. Globe Gate Tube Size Elbow Elbow Run Side Outlet Bend Bend Elbow Elbow Run Side Outlet Stop Valve Valve (In Inches) Feet (m) Feet (m) Feet (m) Feet (m) Feet (m) Feet (m) Feet (m) Feet (m) Feet (m) 3/8 0.5 (0.15) 0.5 (0.15) 0.5 (0.15) 1 (0.31) 0.5 (0.15) 0.5 (0.15) 1 (0.31) 0.5 (0.15) 0.5 (0.15) 1/2 0.5 (0.15) 0.5 (0.15) 0.5 (0.15) 1 (0.31) 0.5 (0.15) 1 (0.31) 1 (0.31) 0.5 (0.15) 0.5 (0.15) 5/8 0.5 (0.15) 0.5 (0.15) 0.5 (0.15) 2 (0.61) 1 (0.31) 1 (0.31) 2 (0.61) 1 (0.31) 0.5 (0.15) 3/4 1 (0.31) 0.5 (0.15) 0.5 (0.15) 2 (0.61) 1 (0.31) 2 (0.61) 2 (0.61) 1 (0.31) 0.5 (0.15) 1 1 (0.31) 1 (0.31) 0.5 (0.15) 3 (0.92) 2 (0.61) 2 (0.61) 4 (1.22) 2 (0.61) 0.5 (0.15) 1 1/4 2 (0.61) 1 (0.31) 0.5 (0.15) 4 (1.22) 2 (0.61) 3 (0.92) 5 (1.53) 2 (0.61) 1 (0.31) 1 1/2 2 (0.61) 2 (0.61) 1 (0.31) 5 (1.53) 2 (0.61) 4 (1.22) 8 (2.44) 3 (0.92) 1 (0.31) 2 2 (0.61) 2 (0.61) 1 (0.31) 7 (2.14) 3 (0.92) 8 (2.44) 11 (3.36) 5 (1.53) 2 (0.61) 2 1/2 2 (0.61) 3 (0.92) 2 (0.61) 9 (2.75) 4 (1.22) 16 (4.88) 14 (4.27) 8 (2.44) 2 (0.61) 3 3 (0.92) 4 (1.22) – – – – 5 (1.53) 20 (6.10) 18 (5.49) 11 (3.36) 2 (0.61) 3 1/2 4 (1.22) – – – – – – 7 (2.14) 24 (7.32) 24 (7.32) 14 (4.27) 2 (0.61) 4 – – – – – – – – 8 (2.44) 28 (8.54) 28 (8.54) 17 (5.19) 2 (0.61) 5 – – – – – – – – 10 (3.05) 37 (11.29) 41 (12.51) 22 (6.71) 2 (0.61) 6 – – – – – – – – 13 (3.97) 47 (14.34) 52 (15.86) 28 (8.54) 2 (0.61) Notes: This table is based on tests conducted at Harvard University (1948). If the type of fitting is not known – i.e., whether wrought copper or cast alloy – use cast copper alloy values for design. Feet (m)Feet (m) Feet (m) Feet (m) 2 (0.61) 9 (2.75) – – – – 2 (0.61) 13 (3.97) – – – – 3 (0.92) 17 (5.19) – – – – 3 (0.92) 21 (6.41) – – – – 5 (1.53) 30 (9.15) – – 1 (0.31) 7 (2.14) – – 53 (16.17) 1 (0.31) 9 (2.75) – – 66 (20.13) 2 (0.61) 12 (3.66) – – 90 (27.45) 2 (0.61) 16 (4.88) – – – – 2 (0.61) 20 (6.10) – – – – 2 (0.61) 31 (9.46) – – – – 2 (0.61) 37 (11.29) – – – – 2 (0.61) 48 (14.64) – – – – – – 61 (18.61) – – – – – – AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 55//1144//0022 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 56 SELECTION OF TUBE SIZES The smooth interior of copper tube, and the design of both solder joint and flared-tube-type fittings, which have no shoulders projecting into the flow of water, decrease friction loss. With the use of copper tube, no allowance is necessary for the accumulation of rust deposits in supply and service lines. Consequently, copper tube lines are usually figured one size smaller than iron pipe for the same service. This rule does not apply to lines from a well to a pump where the nominal diameters specified by the pump manufacturer must be adhered to strictly. Water passing through any pipe line encounters resistance by friction. The resistance is increased by bends and turns in the line, which should be taken into account in complex piping systems. For example, a one-inch 90° elbow will cause friction loss equivalent to that of one foot (0.305m) of straight one-inch tube. (See below for allowance to be made for fittings and valves in equivalent lengths of tube.) Friction loss in terms of head loss must be taken into consideration in calculating tube sizes to be used for various types of installations. For most average-size-house installations with water pressures 40 PSI (275.8kPa) and higher, 3/4" copper tube will be ample for main supply lines, and 1/2" copper tube can be used for risers and branches to all fixtures. The smaller 3/8" tube is adequate to supply branches, but with pressures at 40 PSI (275.8kPa) and higher, water hammer becomes a concern when the flow is suddenly stopped. Copper Water Tube continued U.S. customary units in this document are the standard; the metric units are provided for reference only. The values stated in each system are not exact equivalents. AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 55//1144//0022 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 57 COPPER WATER TUBE – INTERNAL WORKING PRESSURES* Service Temperature °F (°C) 100°F (37.8°C) 200°F (93.3°C) 300°F (148.9°C) 400°F (204.4°C) Nominal S = 6000psi (414 bars) S = 4800psi (331 bars)S=4700 psi (324 bars) S=3000 psi (207 bars) Tube Size (In Inches) Type K Type L Type M Type K Type L Type M Type K Type L Type K Type L 1/4 1210 (83.43) 1025 (70.67) – – 850 (58.61) 700 (48.27) – – 830 (57.23) 690 (47.58) 530 (36.54) 3/8 1275 (87.91) 890 (61.37) 625 (43.09) 930 (64.12) 630 (43.44) 460 (31.72) 910 (62.74) 610 (42.06) 590 (40.68) 1/2 1005 (69.29) 810 (55.85) 560 (38.61) 730 (50.33) 580 (39.99) 415 (28.61) 720 (49.64) 570 (39.30) 460 (31.72) 5/8 830 (57.23) 705 (48.61) – – 600 (41.37) 500 (34.48) – – 580 (39.99) 500 (34.48) 380 (26.20) 3/4 950 (65.50) 645 (44.47) 450 (31.03) 700 (48.27) 470 (32.41) 325 (22.41) 690 (47.58) 460 (31.72) 440 (30.34) 1 725 (49.99) 550 (37.92) 380 (26.20) 540 (37.23) 400 (27.58) 270 (18.62) 530 (36.54) 400 (27.58) 340 (23.44) 1 1/4 590 (40.68) 495 (34.13) 375 (25.86) 440 (30.34) 370 (25.51) 270 (18.62) 430 (29.65) 360 (24.82) 280 (19.31) 1 1/2 550 (37.92) 455 (31.37) 370 (25.51) 410 (28.27) 340 (23.44) 270 (18.62) 400 (27.58) 330 (22.75) 260 (17.93) 2 485 (33.44) 405 (27.92) 335 (23.10) 350 (24.13) 310 (21.37) 240 (16.55) 345 (23.79) 305 (21.03) 230 (15.86) 2 1/2 450 (31.03) 375 (25.86) 305 (21.03) 330 (22.75) 275 (18.96) 220 (15.17) 320 (22.06) 270 (18.62) 210 (14.48) 3 430 (29.65) 355 (24.48) 280 (19.31) 320 (22.06) 260 (17.93) 205 (14.13) 315 (21.72) 255 (17.58) 210 (14.48) 3 1/2 410 (28.27) 340 (23.44) 280 (19.31) 300 (20.69) 250 (17.24) 200 (13.79) 300 (20.69) 245 (16.89) 190 (13.10) 4 400 (27.58) 325 (22.41) 280 (19.31) 295 (20.34) 240 (16.55) 200 (13.79) 290 (20.00) 235 (16.20) 190 (13.10) 5 385 (26.55) 300 (20.69) 260 (17.93) 290 (20.00) 220 (15.17) 190 (13.10) 280 (19.31) 215 (14.82) 180 (12.41) 6 385 (26.55) 280 (19.31) 240 (16.55) 280 (19.31) 205 (14.13) 180 (12.41) 280 (19.31) 200 (13.79) 190 (13.10) 8 410 (28.27) 300 (20.69) 255 (17.58) 300 (20.69) 220 (15.17) 190 (13.10) 300 (20.69) 215 (14.82) 200 (13.79) 10 410 (28.27) 300 (20.69) 255 (17.58) 310 (21.37) 225 (15.51) 190 (13.10) 305 (21.03) 220 (15.17) 200 (13.79) 12 410 (28.27) 280 (19.31) 225 (15.51) 310 (21.37) 210 (14.48) 190 (13.10) 305 (21.03) 205 (14.13) 200 (13.79) *Rated internal pressures for Copper Water Tube based on the strength of the tube alone and applicable to systems using suitable mechanical joints. The values are based on the formula in the American Standard Code, Power Piping ANSI/ASME B31.1 1992. Formulas 450 (31.03) 400 (27.58) 370 (25.51) 330 (22.75) 300 (20.69) 260 (17.93) 230 (15.86) 220 (15.17) 190 (13.10) 180 (12.41) 170 (11.72) 160 (11.03) 150 (10.34) 140 (9.65) 130 (8.96) 140 (9.65) 150 (10.34) 140 (9.65) PDtm = + C2S + 0.8P or 2 S tmP = when C is OD - 0.8 tm tm Minimum tube wall thickness P Maximum rated internal working pressure D Outside diameter of tube S Allowable stress in material due to internal pressure at operating temperature C Allowance for threading, mechanical strength and/or corrosion U.S. customary units in this document are the standard; the metric units are provided for reference only. The values stated in each system are not exact equivalents. AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 55//1144//0022 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 58 1/4" TYPE “K” COPPER TUBE — WATER FLOW AND FRICTION LOSS PER 100 FEET Maximum O.D. = 0.3760 inches (9.550 mm) Nominal O.D. = 0.3750 inches (9.525 mm) Minimum O.D. = 0.3740 inches (9.499 mm) Nominal I.D. = 0.3050 inches (7.747 mm) Nominal Wall Thickness = 0.0350 inches (0.089 mm) Flow Area = 0.0731 sq. inches (47.14 sq. mm) Hazen Williams Formula C Factor = 150 FLOW, Q Pressure Loss Head Loss Velocity FLOW, Q Pressure Loss Head Loss Velocity (GPM) (psi/100 ft) (ft/100 ft) (ft./sec.) (cu. cm/sec.) (kPa/100 m) (m/100 m) (m/sec.) 0.50 3.77 8.81 2.20 32 0.85 8.81 0.67 1.00 13.62 31.77 4.39 63 3.08 31.77 1.34 1.50 28.86 67.27 6.59 95 6.53 67.27 2.01 2.00 49.17 114.54 8.78 126 11.12 114.54 2.68 2.50 74.33 173.08 10.98 158 16.81 173.08 3.35 3.00 104.18 242.51 13.17 189 23.57 242.51 4.02 3.50 138.60 322.54 15.37 221 31.35 322.54 4.68 4.00 177.49 412.92 17.57 252 40.15 412.92 5.35 4.50 220.75 513.46 19.76 284 49.94 513.46 6.02 5.00 268.32 623.96 21.96 315 60.70 623.96 6.69 1/4" TYPE “L” COPPER TUBE — WATER FLOW AND FRICTION LOSS PER 100 FEET Maximum O.D. = 0.3760 inches (9.550 mm) Nominal O.D. = 0.3750 inches (9.525 mm) Minimum O.D. = 0.3740 inches (9.499 mm) Nominal I.D. = 0.3150 inches (8.001 mm) Nominal Wall Thickness = 0.0300 inches (0.076 mm) Flow Area = 0.0779 sq. inches (50.28 sq. mm) Hazen Williams Formula C Factor = 150 FLOW, Q Pressure Loss Head Loss Velocity FLOW, Q Pressure Loss Head Loss Velocity (GPM) (psi/100 ft) (ft/100 ft) (ft./sec.) (cu. cm/sec.) (kPa/100 m) (m/100 m) (m/sec.) 0.50 3.22 7.53 2.06 32 0.73 7.53 0.63 1.00 11.64 27.16 4.12 63 2.63 27.16 1.25 1.50 24.67 57.50 6.18 95 5.58 57.50 1.88 2.00 42.02 97.90 8.23 126 9.51 97.90 2.51 2.50 63.53 147.94 10.29 158 14.37 147.94 3.14 3.00 89.05 207.28 12.35 189 20.14 207.28 3.76 3.50 118.47 275.69 14.41 221 26.80 275.69 4.39 4.00 151.71 352.94 16.47 252 34.32 352.94 5.02 4.50 188.68 438.87 18.53 284 42.68 438.87 5.65 5.00 229.34 533.32 20.58 315 51.88 533.32 6.27 3/8" TYPE “K” COPPER TUBE — WATER FLOW AND FRICTION LOSS PER 100 FEET Maximum O.D. = 0.5010 inches (12.725 mm) Nominal O.D. = 0.5000 inches (12.700 mm) Minimum O.D. = 0.4990 inches (12.674 mm) Nominal I.D. = 0.4020 inches (10.210 mm) Nominal Wall Thickness = 0.0490 inches (1.244 mm) Flow Area = 0.1269 sq. inches (81.89 sq. mm) Hazen Williams Formula C Factor = 150 FLOW, Q Pressure Loss Head Loss Velocity FLOW, Q Pressure Loss Head Loss Velocity (GPM) (psi/100 ft) (ft/100 ft) (ft./sec.) (cu. cm/sec.) (kPa/100 m) (m/100 m) (m/sec.) 1.00 3.55 8.29 2.53 63 0.80 8.29 0.77 1.50 7.53 17.55 3.79 95 1.70 17.55 1.16 2.00 12.83 29.89 5.06 126 2.90 29.89 1.54 2.50 19.39 45.16 6.32 158 4.39 45.16 1.93 3.00 27.18 63.28 7.58 189 6.15 63.28 2.31 3.50 36.16 84.16 8.85 221 8.18 84.16 2.70 4.00 46.31 107.74 10.11 252 10.48 107.74 3.08 4.50 57.60 133.97 11.37 284 13.03 133.97 3.47 5.00 70.01 162.80 12.64 315 15.84 162.80 3.85 5.50 83.52 194.19 13.90 347 18.89 194.19 4.24 6.00 98.13 228.11 15.17 379 22.20 228.11 4.62 6.50 113.81 264.51 16.43 410 25.74 264.51 5.01 7.00 130.55 303.38 17.69 442 29.53 303.38 5.39 7.50 148.34 344.68 18.96 473 33.56 344.68 5.78 8.00 167.18 388.40 20.22 505 37.82 388.40 6.16 8.50 187.04 434.49 21.49 536 42.31 434.49 6.55 9.00 207.93 482.96 22.75 568 47.03 482.96 6.93 9.50 229.83 533.76 24.01 599 51.99 533.76 7.32 10.00 252.73 586.89 25.28 631 57.17 586.89 7.70 U.S. customary units in this document are the standard; the metric units are provided for reference only. The values stated in each system are not exact equivalents. 3/8" TYPE “L” COPPER TUBE — WATER FLOW AND FRICTION LOSS PER 100 FEET Maximum O.D. = 0.5010 inches (12.725 mm) Nominal O.D. = 0.5000 inches (12.700 mm) Minimum O.D. = 0.4990 inches (12.675 mm) Nominal I.D. = 0.4500 inches (10.211 mm) Nominal Wall Thickness = 0.0350 inches (0.889 mm) Flow Area = 0.1590 sq. inches (102.61 sq. mm) Hazen Williams Formula C Factor = 150 FLOW, Q Pressure Loss Head Loss Velocity FLOW, Q Pressure Loss Head Loss Velocity (GPM) (psi/100 ft) (ft/100 ft) (ft./sec.) (cu. cm/sec.) (kPa/100 m) (m/100 m) (m/sec.) 1.00 2.56 5.97 2.21 63 0.58 5.97 0.67 1.50 5.43 12.65 3.31 95 1.23 12.65 1.01 2.00 9.24 21.54 4.42 126 2.09 21.54 1.35 2.50 13.98 32.54 5.52 158 3.16 32.54 1.68 3.00 19.59 45.60 6.63 189 4.43 45.60 2.02 3.50 26.06 60.65 7.73 221 5.90 60.65 2.36 4.00 33.37 77.64 8.84 252 7.55 77.64 2.69 4.50 41.51 96.54 9.94 284 9.39 96.54 3.03 5.00 50.45 117.32 11.05 315 11.41 117.32 3.37 5.50 60.19 139.94 12.15 347 13.62 139.94 3.70 6.00 70.72 164.38 13.26 379 16.00 164.38 4.04 6.50 82.01 190.62 14.36 410 18.55 190.62 4.38 7.00 94.08 218.63 15.46 442 21.28 218.63 4.71 7.50 106.90 248.40 16.57 473 24.18 248.40 5.05 8.00 120.48 279.90 17.67 505 27.25 279.90 5.39 8.50 134.79 313.12 18.78 536 30.49 313.12 5.72 9.00 149.84 348.04 19.88 568 33.90 348.04 6.06 9.50 165.62 384.65 20.99 599 37.47 384.65 6.40 10.00 182.13 422.94 22.09 631 41.20 422.94 6.73 3/8" TYPE “M” COPPER TUBE — WATER FLOW AND FRICTION LOSS PER 100 FEET Maximum O.D. = 0.5010 inches (12.725 mm) Nominal O.D. = 0.5000 inches (12.700 mm) Minimum O.D. = 0.4990 inches (12.675 mm) Nominal I.D. = 0.4020 inches (10.211 mm) Nominal Wall Thickness = 0.0250 inches (0.635 mm) Flow Area = 0.1269 sq. inches (81.89 sq. mm) Hazen Williams Formula C Factor = 150 FLOW, Q Pressure Loss Head Loss Velocity FLOW, Q Pressure Loss Head Loss Velocity (GPM) (psi/100 ft) (ft/100 ft) (ft./sec.) (cu. cm/sec.) (kPa/100 m) (m/100 m) (m/sec.) 1.00 2.05 4.79 2.02 63 0.46 4.79 0.61 1.50 4.35 10.14 3.03 95 0.98 10.14 0.92 2.00 7.41 17.26 4.03 126 1.68 17.26 1.23 2.50 11.20 26.09 5.04 158 2.53 26.09 1.54 3.00 15.70 36.55 6.05 189 3.55 36.55 1.84 3.50 20.89 48.61 7.06 221 4.73 48.61 2.15 4.00 26.75 62.23 8.07 252 6.05 62.23 2.46 4.50 33.27 77.39 9.08 284 7.53 77.39 2.77 5.00 40.44 94.04 10.09 315 9.15 94.04 3.07 5.50 48.25 112.17 11.09 347 10.91 112.17 3.38 6.00 56.68 131.76 12.10 379 12.82 131.76 3.69 6.50 65.74 152.79 13.11 410 14.87 152.79 4.00 7.00 75.41 175.25 14.12 442 17.06 175.25 4.30 7.50 85.69 199.10 15.13 473 19.38 199.10 4.61 8.00 96.57 224.35 16.14 505 21.84 224.35 4.92 8.50 108.04 250.98 17.15 536 24.44 250.98 5.23 9.00 120.11 278.97 18.16 568 27.17 278.97 5.53 9.50 132.76 308.32 19.16 599 30.03 308.32 5.84 10.00 145.99 339.01 20.17 631 33.02 339.01 6.15 AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 55//1144//0022 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 59 U.S. customary units in this document are the standard; the metric units are provided for reference only. The values stated in each system are not exact equivalents. AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 55//1144//0022 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 60 1/2" TYPE “K” COPPER TUBE — WATER FLOW AND FRICTION LOSS PER 100 FEET Maximum O.D. = 0.626 inches (15.900 mm) Nominal O.D. = 0.6250 inches (15.875 mm) Minimum O.D. = 0.624 inches (15.850 mm) Nominal I.D. = 0.527 inches (13.3858 mm) Nominal Wall Thickness = 0.049 inches (1.245 mm) Flow Area = 0.2181 sq. inches (140.73 sq. mm) Hazen Williams Formula C Factor = 150 FLOW, Q Pressure Loss Head Loss Velocity FLOW, Q Pressure Loss Head Loss Velocity (GPM) (psi/100 ft) (ft/100 ft) (ft./sec.) (cu. cm/sec.) (kPa/100 m) (m/100 m) (m/sec.) 1.00 0.95 2.22 1.47 63 0.22 2.22 0.45 1.50 2.02 4.70 2.21 95 0.46 4.70 0.67 2.00 3.44 8.00 2.94 126 0.78 8.00 0.90 2.50 5.19 12.10 3.68 158 1.18 12.10 1.12 3.00 7.28 16.95 4.41 189 1.65 16.95 1.34 3.50 9.69 22.54 5.15 221 2.19 22.54 1.57 4.00 12.40 28.86 5.88 252 2.81 28.86 1.79 4.50 15.43 35.88 6.62 284 3.49 35.88 2.02 5.00 18.75 43.61 7.35 315 4.24 43.61 2.24 5.50 22.37 52.01 8.09 347 5.06 52.01 2.47 6.00 26.28 61.10 8.83 379 5.95 61.10 2.69 6.50 30.48 70.85 9.56 410 6.90 70.85 2.91 7.00 34.97 81.26 10.30 442 7.91 81.26 3.14 7.50 39.73 92.32 11.03 473 8.99 92.32 3.36 8.00 44.78 104.03 11.77 505 10.13 104.03 3.59 8.50 50.10 116.38 12.50 536 11.33 116.38 3.81 9.00 55.69 129.36 13.24 568 12.60 129.36 4.03 9.50 61.56 142.97 13.97 599 13.93 142.97 4.26 10.00 67.69 157.20 14.71 631 15.31 157.20 4.48 10.50 74.10 172.05 15.44 662 16.76 172.05 4.71 11.00 80.76 187.51 16.18 694 18.27 187.51 4.93 11.50 87.69 203.58 16.91 725 19.84 203.58 5.16 12.00 94.88 220.26 17.65 757 21.46 220.26 5.38 12.50 102.34 237.54 18.39 789 23.15 237.54 5.60 13.00 110.05 255.41 19.12 820 24.89 255.41 5.83 13.50 118.01 273.89 19.86 852 26.70 273.89 6.05 14.00 126.23 292.95 20.59 883 28.56 292.95 6.28 1/2" TYPE “L” COPPER TUBE — WATER FLOW AND FRICTION LOSS PER 100 FEET Maximum O.D. = 0.626 inches (15.900 mm) Nominal O.D. = 0.6250 inches (15.875 mm) Minimum O.D. = 0.624 inches (15.850 mm) Nominal I.D. = 0.5450 inches (13.843 mm) Nominal Wall Thickness = 0.049 inches (1.245 mm) Flow Area = 0.2333 sq. inches (150.50 sq. mm) Hazen Williams Formula C Factor = 150 FLOW, Q Pressure Loss Head Loss Velocity FLOW, Q Pressure Loss Head Loss Velocity (GPM) (psi/100 ft) (ft/100 ft) (ft./sec.) (cu. cm/sec.) (kPa/100 m) (m/100 m) (m/sec.) 1.00 0.81 1.89 1.38 63 0.18 1.89 0.42 1.50 1.71 3.99 2.06 95 0.39 3.99 0.63 2.00 2.92 6.80 2.75 126 0.66 6.80 0.84 2.50 4.41 10.27 3.44 158 1.00 10.27 1.05 3.00 6.18 14.39 4.13 189 1.40 14.39 1.26 3.50 8.23 19.14 4.81 221 1.86 19.14 1.47 4.00 10.53 24.51 5.50 252 2.38 24.51 1.68 4.50 13.10 30.47 6.19 284 2.96 30.47 1.89 5.00 15.92 37.03 6.88 315 3.60 37.03 2.10 5.50 19.00 44.17 7.56 347 4.30 44.17 2.31 6.00 22.32 51.89 8.25 379 5.05 51.89 2.52 6.50 25.89 60.17 8.94 410 5.86 60.17 2.72 7.00 29.70 69.01 9.63 442 6.72 69.01 2.93 7.50 33.74 78.41 10.31 473 7.63 78.41 3.14 8.00 38.03 88.35 11.00 505 8.60 88.35 3.35 8.50 42.55 98.83 11.69 536 9.62 98.83 3.56 9.00 47.30 109.86 12.38 568 10.70 109.86 3.77 9.50 52.28 121.41 13.07 599 11.83 121.41 3.98 10.00 57.49 133.50 13.75 631 13.00 133.50 4.19 10.50 62.92 146.11 14.44 662 14.23 146.11 4.40 11.00 68.59 159.24 15.13 694 15.51 159.24 4.61 11.50 74.47 172.89 15.82 725 16.85 172.89 4.82 12.00 80.58 187.05 16.50 757 18.23 187.05 5.03 12.50 86.91 201.73 17.19 789 19.66 201.73 5.24 13.00 93.46 216.91 17.88 820 21.14 216.91 5.45 13.50 100.22 232.60 18.57 852 22.67 232.60 5.66 14.00 107.20 248.78 19.25 883 24.25 248.78 5.87 U.S. customary units in this document are the standard; the metric units are provided for reference only. The values stated in each system are not exact equivalents. AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 55//1144//0022 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 61 1/2" TYPE “M” COPPER TUBE — WATER FLOW AND FRICTION LOSS PER 100 FEET Maximum O.D. = 0.626 inches (15.900 mm) Nominal O.D. = 0.6250 inches (15.875 mm) Minimum O.D. = 0.624 inches (15.850 mm) Nominal I.D. = 0.5690 inches (14.4526 mm) Nominal Wall Thickness = 0.028 inches (0.711 mm) Flow Area = 0.2543 sq. inches (164.05 sq. mm) Hazen Williams Formula C Factor = 150 FLOW, Q Pressure Loss Head Loss Velocity FLOW, Q Pressure Loss Head Loss Velocity (GPM) (psi/100 ft) (ft/100 ft) (ft./sec.) (cu. cm/sec.) (kPa/100 m) (m/100 m) (m/sec.) 1.00 0.66 1.53 1.26 63 0.15 1.53 0.38 1.50 1.39 3.24 1.89 95 0.31 3.24 0.58 2.00 2.37 5.51 2.52 126 0.54 5.51 0.77 2.50 3.58 8.33 3.15 158 0.81 8.33 0.96 3.00 5.01 11.67 3.79 189 1.13 11.67 1.15 3.50 6.67 15.52 4.42 221 1.51 15.52 1.35 4.00 8.54 19.87 5.05 252 1.93 19.87 1.54 4.50 10.62 24.71 5.68 284 2.40 24.71 1.73 5.00 12.91 30.03 6.31 315 2.92 30.03 1.92 5.50 15.41 35.82 6.94 347 3.48 35.82 2.12 6.00 18.10 42.07 7.57 379 4.09 42.07 2.31 6.50 20.99 48.79 8.20 410 4.75 48.79 2.50 7.00 24.08 55.96 8.83 442 5.45 55.96 2.69 7.50 27.36 63.57 9.46 473 6.19 63.57 2.88 8.00 30.83 71.64 10.09 505 6.98 71.64 3.08 8.50 34.50 80.14 10.72 536 7.80 80.14 3.27 9.00 38.35 89.08 11.36 568 8.68 89.08 3.46 9.50 42.39 98.45 11.99 599 9.59 98.45 3.65 10.00 46.61 108.25 12.62 631 10.54 108.25 3.85 10.50 51.02 118.47 13.25 662 11.54 118.47 4.04 11.00 55.61 129.12 13.88 694 12.58 129.12 4.23 11.50 60.39 140.19 14.51 725 13.66 140.19 4.42 12.00 65.34 151.67 15.14 757 14.78 151.67 4.61 12.50 70.47 163.57 15.77 789 15.94 163.57 4.81 13.00 75.78 175.88 16.40 820 17.14 175.88 5.00 13.50 81.26 188.60 17.03 852 18.38 188.60 5.19 14.00 86.93 201.72 17.66 883 19.66 201.72 5.38 5/8" TYPE “K” COPPER TUBE — WATER FLOW AND FRICTION LOSS PER 100 FEET Maximum O.D. = 0.751 inches (19.075 mm) Nominal O.D. = 0.7500 inches (19.050 mm) Minimum O.D. = 0.749 inches (19.025 mm) Nominal I.D. = 0.6520 inches (16.5608 mm) Nominal Wall Thickness = 0.049 inches (1.245 mm) Flow Area = 0.3339 sq. inches (215.40 sq. mm) Hazen Williams Formula C Factor = 150 FLOW, Q Pressure Loss Head Loss Velocity FLOW, Q Pressure Loss Head Loss Velocity (GPM) (psi/100 ft) (ft/100 ft) (ft./sec.) (cu. cm/sec.) (kPa/100 m) (m/100 m) (m/sec.) 1.00 0.34 0.79 0.96 63 0.08 0.79 0.29 2.00 1.22 2.84 1.92 126 0.28 2.84 0.59 3.00 2.58 6.02 2.88 189 0.58 6.02 0.88 4.00 4.40 10.24 3.84 252 1.00 10.24 1.17 5.00 6.66 15.48 4.80 315 1.51 15.48 1.46 6.00 9.33 21.69 5.77 379 2.11 21.69 1.76 7.00 12.41 28.85 6.73 442 2.81 28.85 2.05 8.00 15.90 36.93 7.69 505 3.60 36.93 2.34 9.00 19.77 45.92 8.65 568 4.47 45.92 2.64 10.00 24.03 55.81 9.61 631 5.44 55.81 2.93 11.00 28.67 66.57 10.57 694 6.49 66.57 3.22 12.00 33.69 78.20 11.53 757 7.62 78.20 3.51 13.00 39.07 90.68 12.49 820 8.84 90.68 3.81 14.00 44.82 104.00 13.45 883 10.14 104.00 4.10 15.00 50.92 118.16 14.41 946 11.52 118.16 4.39 16.00 57.39 133.14 15.37 1009 12.98 133.14 4.69 17.00 64.21 148.95 16.34 1072 14.52 148.95 4.98 18.00 71.38 165.56 17.30 1136 16.15 165.56 5.27 19.00 78.89 182.98 18.26 1199 17.85 182.98 5.56 20.00 86.76 201.19 19.22 1262 19.63 201.19 5.86 21.00 94.96 220.19 20.18 1325 21.48 220.19 6.15 22.00 103.51 239.98 21.14 1388 23.41 239.98 6.44 U.S. customary units in this document are the standard; the metric units are provided for reference only. The values stated in each system are not exact equivalents. AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 55//1144//0022 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 62 5/8" TYPE “L” COPPER TUBE — WATER FLOW AND FRICTION LOSS PER 100 FEET Maximum O.D. = 0.751 inches (19.075 mm) Nominal O.D. = 0.7500 inches (19.050 mm) Minimum O.D. = 0.749 inches (19.025 mm) Nominal I.D. = 0.6660 inches (16.9164 mm) Nominal Wall Thickness = 0.042 inches (1.067 mm) Flow Area = 0.3484 sq. inches (224.75 sq. mm) Hazen Williams Formula C Factor = 150 FLOW, Q Pressure Loss Head Loss Velocity FLOW, Q Pressure Loss Head Loss Velocity (GPM) (psi/100 ft) (ft/100 ft) (ft./sec.) (cu. cm/sec.) (kPa/100 m) (m/100 m) (m/sec.) 1.00 0.30 0.71 0.92 63 0.07 0.71 0.28 2.00 1.10 2.56 1.84 126 0.25 2.56 0.56 3.00 2.33 5.43 2.76 189 0.53 5.43 0.84 4.00 3.97 9.24 3.68 252 0.90 9.24 1.12 5.00 6.00 13.96 4.60 315 1.36 13.96 1.40 6.00 8.41 19.56 5.53 379 1.90 19.56 1.68 7.00 11.20 26.02 6.45 442 2.53 26.02 1.96 8.00 14.34 33.31 7.37 505 3.24 33.31 2.25 9.00 17.83 41.41 8.29 568 4.03 41.41 2.53 10.00 21.67 50.33 9.21 631 4.90 50.33 2.81 11.00 25.86 60.03 10.13 694 5.85 60.03 3.09 12.00 30.38 70.52 11.05 757 6.87 70.52 3.37 13.00 35.23 81.77 11.97 820 7.97 81.77 3.65 14.00 40.41 93.79 12.89 883 9.14 93.79 3.93 15.00 45.92 106.56 13.81 946 10.39 106.56 4.21 16.00 51.75 120.07 14.74 1009 11.71 120.07 4.49 17.00 57.90 134.32 15.66 1072 13.10 134.32 4.77 18.00 64.37 149.30 16.58 1136 14.56 149.30 5.05 19.00 71.15 165.01 17.50 1199 16.09 165.01 5.33 20.00 78.24 181.43 18.42 1262 17.70 181.43 5.61 21.00 85.64 198.57 19.34 1325 19.37 198.57 5.89 22.00 93.34 216.42 20.26 1388 21.11 216.42 6.18 3/4" TYPE “K” COPPER TUBE — WATER FLOW AND FRICTION LOSS PER 100 FEET Maximum O.D. = 0.876 inches (22.250 mm) Nominal O.D. = 0.8750 inches (22.225 mm) Minimum O.D. = 0.874 inches (22.200 mm) Nominal I.D. = 0.7450 inches (18.923 mm) Nominal Wall Thickness = 0.065 inches (1.651 mm) Flow Area = 0.4359 sq. inches (281.24 sq. mm) Hazen Williams Formula C Factor = 150 FLOW, Q Pressure Loss Head Loss Velocity FLOW, Q Pressure Loss Head Loss Velocity (GPM) (psi/100 ft) (ft/100 ft) (ft./sec.) (cu. cm/sec.) (kPa/100 m) (m/100 m) (m/sec.) 2.00 0.64 1.49 1.47 126 0.14 1.49 0.45 4.00 2.30 5.35 2.94 252 0.52 5.35 0.90 6.00 4.88 11.34 4.42 379 1.10 11.34 1.35 8.00 8.31 19.30 5.89 505 1.88 19.30 1.79 10.00 12.56 29.17 7.36 631 2.84 29.17 2.24 12.00 17.61 40.87 8.83 757 3.98 40.87 2.69 14.00 23.42 54.36 10.30 883 5.30 54.36 3.14 16.00 30.00 69.59 11.78 1009 6.79 69.59 3.59 18.00 37.31 86.54 13.25 1136 8.44 86.54 4.04 20.00 45.35 105.16 14.72 1262 10.26 105.16 4.49 22.00 54.10 125.44 16.19 1388 12.24 125.44 4.94 24.00 63.56 147.34 17.66 1514 14.38 147.34 5.38 26.00 73.72 170.86 19.14 1640 16.68 170.86 5.83 28.00 84.56 195.97 20.61 1766 19.13 195.97 6.28 30.00 96.09 222.65 22.08 1893 21.74 222.65 6.73 U.S. customary units in this document are the standard; the metric units are provided for reference only. The values stated in each system are not exact equivalents. AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 55//1144//0022 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 63 3/4" TYPE “L” COPPER TUBE — WATER FLOW AND FRICTION LOSS PER 100 FEET Maximum O.D. = 0.876 inches (22.250 mm) Nominal O.D. = 0.8750 inches (22.225 mm) Minimum O.D. = 0.874 inches (22.200 mm) Nominal I.D. = 0.7850 inches (19.939 mm) Nominal Wall Thickness = 0.045 inches (1.143 mm) Flow Area = 0.4840 sq. inches (312.25 sq. mm) Hazen Williams Formula C Factor = 150 FLOW, Q Pressure Loss Head Loss Velocity FLOW, Q Pressure Loss Head Loss Velocity (GPM) (psi/100 ft) (ft/100 ft) (ft./sec.) (cu. cm/sec.) (kPa/100 m) (m/100 m) (m/sec.) 2.00 0.4944 1.1517 1.3258 126.17 0.1118 1.1517 0.4041 4.00 1.7846 4.1519 2.6516 252.35 0.4037 4.1519 0.8082 6.00 3.7815 8.7905 3.9774 378.52 0.8554 8.7905 1.2123 8.00 6.4425 14.9675 5.3032 504.69 1.4573 14.9675 1.6164 10.00 9.7393 22.6169 6.6290 630.87 2.2031 22.6169 2.0205 12.00 13.6513 31.6896 7.9548 757.04 3.0880 31.6896 2.4246 14.00 18.1618 42.1472 9.2806 883.21 4.1083 42.1472 2.8287 16.00 23.2573 53.9578 10.6064 1009.39 5.2610 53.9578 3.2328 18.00 28.9264 67.0944 11.9322 1135.56 6.5434 67.0944 3.6369 20.00 35.1590 81.5338 13.2580 1261.73 7.9532 81.5338 4.0411 22.00 41.9465 97.2555 14.5838 1387.91 9.4886 97.2555 4.4452 24.00 49.2811 114.2412 15.9096 1514.08 11.1477 114.2412 4.8493 26.00 57.1557 132.4747 17.2354 1640.25 12.9290 132.4747 5.2534 28.00 65.5641 151.9408 18.5613 1766.43 14.8311 151.9408 5.6575 30.00 74.5002 172.6261 19.8871 1892.60 16.8525 172.6261 6.0616 3/4" TYPE “M” COPPER TUBE — WATER FLOW AND FRICTION LOSS PER 100 FEET Maximum O.D. = 0.876 inches (22.250 mm) Nominal O.D. = 0.8750 inches (22.225 mm) Minimum O.D. = 0.874 inches (22.200 mm) Nominal I.D. = 0.8110 inches (20.5994 mm) Nominal Wall Thickness = 0.032 inches (0.813 mm) Flow Area = 0.5156 sq. inches (333.27 sq. mm) Hazen Williams Formula C Factor = 150 FLOW, Q Pressure Loss Head Loss Velocity FLOW, Q Pressure Loss Head Loss Velocity (GPM) (psi/100 ft) (ft/100 ft) (ft./sec.) (cu. cm/sec.) (kPa/100 m) (m/100 m) (m/sec.) 2.00 0.42 0.98 1.24 126 0.10 0.98 0.38 4.00 1.52 3.54 2.48 252 0.34 3.54 0.76 6.00 3.23 7.50 3.73 379 0.73 7.50 1.14 8.00 5.50 12.77 4.97 505 1.24 12.77 1.51 10.00 8.31 19.30 6.21 631 1.88 19.30 1.89 12.00 11.65 27.04 7.45 757 2.64 27.04 2.27 14.00 15.50 35.97 8.70 883 3.51 35.97 2.65 16.00 19.85 46.05 9.94 1009 4.49 46.05 3.03 18.00 24.69 57.26 11.18 1136 5.58 57.26 3.41 20.00 30.00 69.58 12.42 1262 6.79 69.58 3.79 22.00 35.80 83.00 13.66 1388 8.10 83.00 4.16 24.00 42.06 97.49 14.91 1514 9.51 97.49 4.54 26.00 48.78 113.05 16.15 1640 11.03 113.05 4.92 28.00 55.95 129.66 17.39 1766 12.66 129.66 5.30 30.00 63.58 147.32 18.63 1893 14.38 147.32 5.68 U.S. customary units in this document are the standard; the metric units are provided for reference only. The values stated in each system are not exact equivalents. AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 55//1144//0022 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 64 1" TYPE “K” COPPER TUBE — WATER FLOW AND FRICTION LOSS PER 100 FEET Maximum O.D. = 1.1265 inches (28.613 mm) Nominal O.D. = 1.1250 inches (28.575 mm) Minimum O.D. = 1.1235 inches (28.537 mm) Nominal I.D. = 0.9850 inches (25.273 mm) Nominal Wall Thickness = 0.0650 inches (1.651 mm) Flow Area = 0.7776 sq. inches (501.65 sq. mm) Hazen Williams Formula C Factor = 150 FLOW, Q Pressure Loss Head Loss Velocity FLOW, Q Pressure Loss Head Loss Velocity (GPM) (psi/100 ft) (ft/100 ft) (ft./sec.) (cu. cm/sec.) (kPa/100 m) (m/100 m) (m/sec.) 2.50 0.24 0.55 1.03 158 0.05 0.55 0.31 5.00 0.85 1.98 2.06 315 0.19 1.98 0.63 7.50 1.80 4.19 3.09 473 0.41 4.19 0.94 10.00 3.07 7.14 4.13 631 0.70 7.14 1.26 12.50 4.65 10.78 5.16 789 1.05 10.78 1.57 15.00 6.51 15.11 6.19 946 1.47 15.11 1.89 17.50 8.66 20.10 7.22 1104 1.96 20.10 2.20 20.00 11.09 25.73 8.25 1262 2.51 25.73 2.52 22.50 13.80 31.99 9.28 1419 3.12 31.99 2.83 25.00 16.77 38.88 10.32 1577 3.79 38.88 3.14 27.50 20.01 46.37 11.35 1735 4.53 46.37 3.46 30.00 23.51 54.47 12.38 1893 5.32 54.47 3.77 32.50 27.27 63.17 13.41 2050 6.17 63.17 4.09 35.00 31.28 72.45 14.44 2208 7.08 72.45 4.40 37.50 35.54 82.31 15.47 2366 8.04 82.31 4.72 40.00 40.05 92.75 16.50 2523 9.06 92.75 5.03 42.50 44.81 103.76 17.54 2681 10.14 103.76 5.34 45.00 49.81 115.33 18.57 2839 11.27 115.33 5.66 47.50 55.06 127.47 19.60 2997 12.46 127.47 5.97 50.00 60.55 140.15 20.63 3154 13.70 140.15 6.29 52.50 66.27 153.39 21.66 3312 14.99 153.39 6.60 55.00 72.24 167.18 22.69 3470 16.34 167.18 6.92 1" TYPE “L” COPPER TUBE — WATER FLOW AND FRICTION LOSS PER 100 FEET Maximum O.D. = 1.1265 inches (28.613 mm) Nominal O.D. = 1.1250 inches (28.575 mm) Minimum O.D. = 1.1235 inches (28.537 mm) Nominal I.D. = 1.0250 inches (26.035 mm) Nominal Wall Thickness = 0.0500 inches (1.270 mm) Flow Area = 0.8252 sq. inches (532.36 sq. mm) Hazen Williams Formula C Factor = 150 FLOW, Q Pressure Loss Head Loss Velocity FLOW, Q Pressure Loss Head Loss Velocity (GPM) (psi/100 ft) (ft/100 ft) (ft./sec.) (cu. cm/sec.) (kPa/100 m) (m/100 m) (m/sec.) 2.50 0.20 0.48 0.97 158 0.05 0.48 0.30 5.00 0.74 1.71 1.94 315 0.17 1.71 0.59 7.50 1.56 3.63 2.92 473 0.35 3.63 0.89 10.00 2.66 6.18 3.89 631 0.60 6.18 1.19 12.50 4.02 9.33 4.86 789 0.91 9.33 1.48 15.00 5.64 13.08 5.83 946 1.27 13.08 1.78 17.50 7.50 17.39 6.80 1104 1.70 17.39 2.07 20.00 9.60 22.27 7.78 1262 2.17 22.27 2.37 22.50 11.94 27.69 8.75 1419 2.70 27.69 2.67 25.00 14.52 33.65 9.72 1577 3.28 33.65 2.96 27.50 17.32 40.13 10.69 1735 3.92 40.13 3.26 30.00 20.35 47.14 11.66 1893 4.60 47.14 3.56 32.50 23.60 54.67 12.64 2050 5.34 54.67 3.85 35.00 27.07 62.70 13.61 2208 6.12 62.70 4.15 37.50 30.76 71.24 14.58 2366 6.96 71.24 4.44 40.00 34.66 80.27 15.55 2523 7.84 80.27 4.74 42.50 38.78 89.80 16.52 2681 8.77 89.80 5.04 45.00 43.11 99.81 17.50 2839 9.75 99.81 5.33 47.50 47.65 110.31 18.47 2997 10.78 110.31 5.63 50.00 52.40 121.29 19.44 3154 11.85 121.29 5.93 52.50 57.36 132.75 20.41 3312 12.97 132.75 6.22 55.00 62.52 144.68 21.38 3470 14.14 144.68 6.52 U.S. customary units in this document are the standard; the metric units are provided for reference only. The values stated in each system are not exact equivalents. AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 55//1144//0022 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 65 1" TYPE “M” COPPER TUBE — WATER FLOW AND FRICTION LOSS PER 100 FEET Maximum O.D. = 1.1265 inches (28.613 mm) Nominal O.D. = 1.1250 inches (28.575 mm) Minimum O.D. = 1.1235 inches (28.537 mm) Nominal I.D. = 1.0558 inches (26.797 mm) Nominal Wall Thickness = 0.0350 inches (0.889 mm) Flow Area = 0.8742 sq. inches (563.98 sq. mm) Hazen Williams Formula C Factor = 150 FLOW, Q Pressure Loss Head Loss Velocity FLOW, Q Pressure Loss Head Loss Velocity (GPM) (psi/100 ft) (ft/100 ft) (ft./sec.) (cu. cm/sec.) (kPa/100 m) (m/100 m) (m/sec.) 2.50 0.18 0.41 0.92 158 0.04 0.41 0.28 5.00 0.64 1.49 1.84 315 0.14 1.49 0.56 7.50 1.36 3.15 2.75 473 0.31 3.15 0.84 10.00 2.31 5.37 3.67 631 0.52 5.37 1.12 12.50 3.49 8.11 4.59 789 0.79 8.11 1.40 15.00 4.90 11.36 5.51 946 1.11 11.36 1.68 17.50 6.52 15.11 6.42 1104 1.47 15.11 1.96 20.00 8.34 19.35 7.34 1262 1.89 19.35 2.24 22.50 10.38 24.06 8.26 1419 2.35 24.06 2.52 25.00 12.61 29.24 9.18 1577 2.85 29.24 2.80 27.50 15.05 34.88 10.09 1735 3.40 34.88 3.08 30.00 17.68 40.97 11.01 1893 4.00 40.97 3.36 32.50 20.51 47.51 11.93 2050 4.64 47.51 3.64 35.00 23.52 54.49 12.85 2208 5.32 54.49 3.92 37.50 26.73 61.91 13.76 2366 6.05 61.91 4.19 40.00 30.12 69.76 14.68 2523 6.81 69.76 4.47 42.50 33.70 78.04 15.60 2681 7.62 78.04 4.75 45.00 37.47 86.74 16.52 2839 8.47 86.74 5.03 47.50 41.41 95.87 17.43 2997 9.37 95.87 5.31 50.00 45.54 105.41 18.35 3154 10.30 105.41 5.59 52.50 49.84 115.37 19.27 3312 11.28 115.37 5.87 55.00 54.33 125.74 20.19 3470 12.29 125.74 6.15 1 1/4" TYPE “K” COPPER TUBE — WATER FLOW AND FRICTION LOSS PER 100 FEET Maximum O.D. = 1.3765 inches (34.963 mm) Nominal O.D. = 1.3750 inches (34.925 mm) Minimum O.D. = 1.3735 inches (34.887 mm) Nominal I.D. = 1.2450 inches (31.623 mm) Nominal Wall Thickness = 0.0650 inches (1.651 mm) Flow Area = 1.2174 sq. inches (785.41 sq. mm) Hazen Williams Formula C Factor = 150 FLOW, Q Pressure Loss Head Loss Velocity FLOW, Q Pressure Loss Head Loss Velocity (GPM) (psi/100 ft) (ft/100 ft) (ft./sec.) (cu. cm/sec.) (kPa/100 m) (m/100 m) (m/sec.) 5.00 0.29 0.67 1.32 315 0.06 0.67 0.40 10.00 1.03 2.40 2.64 631 0.23 2.40 0.80 15.00 2.19 5.08 3.95 946 0.49 5.08 1.20 20.00 3.73 8.65 5.27 1262 0.84 8.65 1.61 25.00 5.64 13.06 6.59 1577 1.27 13.06 2.01 30.00 7.90 18.30 7.91 1893 1.79 18.30 2.41 35.00 10.51 24.34 9.22 2208 2.38 24.34 2.81 40.00 13.46 31.17 10.54 2523 3.04 31.17 3.21 45.00 16.74 38.75 11.86 2839 3.79 38.75 3.61 50.00 20.35 47.09 13.18 3154 4.60 47.09 4.02 55.00 24.27 56.18 14.49 3470 5.49 56.18 4.42 60.00 28.52 65.99 15.81 3785 6.45 65.99 4.82 65.00 33.07 76.52 17.13 4101 7.48 76.52 5.22 70.00 37.94 87.76 18.45 4416 8.58 87.76 5.62 75.00 43.11 99.71 19.77 4732 9.75 99.71 6.02 80.00 48.58 112.35 21.08 5047 10.99 112.35 6.43 U.S. customary units in this document are the standard; the metric units are provided for reference only. The values stated in each system are not exact equivalents. AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 55//1144//0022 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 66 1 1/4" TYPE “L” COPPER TUBE — WATER FLOW AND FRICTION LOSS PER 100 FEET Maximum O.D. = 1.3765 inches (34.963 mm) Nominal O.D. = 1.375 inches (34.925 mm) Minimum O.D. = 1.3735 inches (34.887 mm) Nominal I.D. = 1.265 inches (32.131 mm) Nominal Wall Thickness = 0.0550 inches (1.397 mm) Flow Area = 1.2568 sq. inches (810.85 sq. mm) Hazen Williams Formula C Factor = 150 FLOW, Q Pressure Loss Head Loss Velocity FLOW, Q Pressure Loss Head Loss Velocity (GPM) (psi/100 ft) (ft/100 ft) (ft./sec.) (cu. cm/sec.) (kPa/100 m) (m/100 m) (m/sec.) 5.00 0.26 0.62 1.28 315 0.06 0.62 0.39 10.00 0.96 2.22 2.55 631 0.22 2.22 0.78 15.00 2.02 4.70 3.83 946 0.46 4.70 1.17 20.00 3.45 8.00 5.11 1262 0.78 8.00 1.56 25.00 5.22 12.09 6.38 1577 1.18 12.09 1.95 30.00 7.31 16.94 7.66 1893 1.65 16.94 2.33 35.00 9.73 22.53 8.93 2208 2.20 22.53 2.72 40.00 12.45 28.84 10.21 2523 2.82 28.84 3.11 45.00 15.49 35.86 11.49 2839 3.50 35.86 3.50 50.00 18.83 43.58 12.76 3154 4.26 43.58 3.89 55.00 22.46 51.98 14.04 3470 5.08 51.98 4.28 60.00 26.39 61.06 15.32 3785 5.97 61.06 4.67 65.00 30.61 70.81 16.59 4101 6.92 70.81 5.06 70.00 35.11 81.21 17.87 4416 7.94 81.21 5.45 75.00 39.89 92.27 19.15 4732 9.02 92.27 5.84 80.00 44.96 103.97 20.42 5047 10.17 103.97 6.22 1 1/4" TYPE “M” COPPER TUBE — WATER FLOW AND FRICTION LOSS PER 100 FEET Maximum O.D. = 1.3765 inches (34.963 mm) Nominal O.D. = 1.3750 inches (34.925 mm) Minimum O.D. = 1.3735 inches (34.887 mm) Nominal I.D. = 1.2910 inches (32.7914 mm) Nominal Wall Thickness = 0.0420 inches (1.067 mm) Flow Area = 1.3090 sq. inches (844.52 sq. mm) Hazen Williams Formula C Factor = 150 FLOW, Q Pressure Loss Head Loss Velocity FLOW, Q Pressure Loss Head Loss Velocity (GPM) (psi/100 ft) (ft/100 ft) (ft./sec.) (cu. cm/sec.) (kPa/100 m) (m/100 m) (m/sec.) 5.00 0.24 0.56 1.23 315 0.05 0.56 0.37 10.00 0.87 2.01 2.45 631 0.20 2.01 0.75 15.00 1.83 4.26 3.68 946 0.41 4.26 1.12 20.00 3.12 7.25 4.90 1262 0.71 7.25 1.49 25.00 4.72 10.95 6.13 1577 1.07 10.95 1.87 30.00 6.62 15.34 7.35 1893 1.50 15.34 2.24 35.00 8.81 20.40 8.58 2208 1.99 20.40 2.61 40.00 11.28 26.12 9.80 2523 2.55 26.12 2.99 45.00 14.03 32.48 11.03 2839 3.17 32.48 3.36 50.00 17.05 39.47 12.25 3154 3.86 39.47 3.74 55.00 20.34 47.08 13.48 3470 4.60 47.08 4.11 60.00 23.90 55.31 14.71 3785 5.41 55.31 4.48 65.00 27.72 64.14 15.93 4101 6.27 64.14 4.86 70.00 31.80 73.56 17.16 4416 7.19 73.56 5.23 75.00 36.13 83.57 18.38 4732 8.17 83.57 5.60 80.00 40.72 94.17 19.61 5047 9.21 94.17 5.98 U.S. customary units in this document are the standard; the metric units are provided for reference only. The values stated in each system are not exact equivalents. AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 55//1144//0022 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 67 1 1/2" TYPE “K” COPPER TUBE — WATER FLOW AND FRICTION LOSS PER 100 FEET Maximum O.D. = 1.6270 inches (41.326 mm) Nominal O.D. = 1.6250 inches (41.275 mm) Minimum O.D. = 1.6230 inches (41.224 mm) Nominal I.D. = 1.4810 inches (38.227 mm) Nominal Wall Thickness = 0.0720 inches (1.829 mm) Flow Area = 1.7227 sq. inches (1111.39 sq. mm) Hazen Williams Formula C Factor = 150 FLOW, Q Pressure Loss Head Loss Velocity FLOW, Q Pressure Loss Head Loss Velocity (GPM) (psi/100 ft) (ft/100 ft) (ft./sec.) (cu. cm/sec.) (kPa/100 m) (m/100 m) (m/sec.) 5.00 0.12 0.29 0.93 315 0.03 0.29 0.28 10.00 0.44 1.03 1.86 631 0.10 1.03 0.57 15.00 0.94 2.18 2.79 946 0.21 2.18 0.85 20.00 1.60 3.72 3.72 1262 0.36 3.72 1.14 25.00 2.42 5.61 4.66 1577 0.55 5.61 1.42 30.00 3.39 7.87 5.59 1893 0.77 7.87 1.70 35.00 4.52 10.46 6.52 2208 1.02 10.46 1.99 40.00 5.78 13.39 7.45 2523 1.31 13.39 2.27 45.00 7.19 16.65 8.38 2839 1.63 16.65 2.55 50.00 8.74 20.24 9.31 3154 1.98 20.24 2.84 55.00 10.43 24.14 10.24 3470 2.36 24.14 3.12 60.00 12.26 28.36 11.17 3785 2.77 28.36 3.41 65.00 14.21 32.88 12.11 4101 3.22 32.88 3.69 70.00 16.30 37.72 13.04 4416 3.69 37.72 3.97 75.00 18.53 42.85 13.97 4732 4.19 42.85 4.26 80.00 20.88 48.28 14.90 5047 4.72 48.28 4.54 85.00 23.36 54.01 15.83 5362 5.28 54.01 4.83 90.00 25.97 60.04 16.76 5678 5.87 60.04 5.11 95.00 28.70 66.35 17.69 5993 6.49 66.35 5.39 100.00 31.56 72.96 18.62 6309 7.14 72.96 5.68 105.00 34.55 79.85 19.56 6624 7.82 79.85 5.96 110.00 37.66 87.03 20.49 6940 8.52 87.03 6.24 115.00 40.89 94.49 21.42 7255 9.25 94.49 6.53 1 1/2" TYPE “L” COPPER TUBE — WATER FLOW AND FRICTION LOSS PER 100 FEET Maximum O.D. = 1.6270 inches (41.326 mm) Nominal O.D. = 1.6250 inches (41.275 mm) Minimum O.D. = 1.6230 inches (41.224 mm) Nominal I.D. = 1.5050 inches (37.6174 mm) Nominal Wall Thickness = 0.0600 inches (1.524 mm) Flow Area = 1.7789 sq. inches (1147.71 sq. mm) Hazen Williams Formula C Factor = 150 FLOW, Q Pressure Loss Head Loss Velocity FLOW, Q Pressure Loss Head Loss Velocity (GPM) (psi/100 ft) (ft/100 ft) (ft./sec.) (cu. cm/sec.) (kPa/100 m) (m/100 m) (m/sec.) 5.00 0.11 0.26 0.90 315 0.03 0.26 0.27 10.00 0.41 0.95 1.80 631 0.09 0.95 0.55 15.00 0.87 2.02 2.71 946 0.20 2.02 0.82 20.00 1.48 3.44 3.61 1262 0.34 3.44 1.10 25.00 2.24 5.19 4.51 1577 0.51 5.19 1.37 30.00 3.14 7.27 5.41 1893 0.71 7.27 1.65 35.00 4.18 9.67 6.31 2208 0.94 9.67 1.92 40.00 5.35 12.39 7.21 2523 1.21 12.39 2.20 45.00 6.65 15.40 8.12 2839 1.50 15.40 2.47 50.00 8.09 18.72 9.02 3154 1.83 18.72 2.75 55.00 9.65 22.32 9.92 3470 2.18 22.32 3.02 60.00 11.33 26.22 10.82 3785 2.56 26.22 3.30 65.00 13.14 30.41 11.72 4101 2.97 30.41 3.57 70.00 15.08 34.88 12.62 4416 3.41 34.88 3.85 75.00 17.13 39.63 13.53 4732 3.88 39.63 4.12 80.00 19.31 44.65 14.43 5047 4.37 44.65 4.40 85.00 21.60 49.95 15.33 5362 4.89 49.95 4.67 90.00 24.01 55.52 16.23 5678 5.43 55.52 4.95 95.00 26.54 61.36 17.13 5993 6.00 61.36 5.22 100.00 29.19 67.47 18.03 6309 6.60 67.47 5.50 105.00 31.95 73.84 18.94 6624 7.23 73.84 5.77 110.00 34.82 80.48 19.84 6940 7.88 80.48 6.05 115.00 37.81 87.38 20.74 7255 8.55 87.38 6.32 U.S. customary units in this document are the standard; the metric units are provided for reference only. The values stated in each system are not exact equivalents. AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 55//1144//0022 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 68 1 1/2" TYPE “M” COPPER TUBE — WATER FLOW AND FRICTION LOSS PER 100 FEET Maximum O.D. = 1.6270 inches (41.326 mm) Nominal O.D. = 1.6250 inches (41.275 mm) Minimum O.D. = 1.6230 inches (41.224 mm) Nominal I.D. = 1.5270 inches (38.7858 mm) Nominal Wall Thickness = 0.0490 inches (1.2446 mm) Flow Area = 1.8313 sq. inches (1181.50 sq. mm) Hazen Williams Formula C Factor = 150 FLOW, Q Pressure Loss Head Loss Velocity FLOW, Q Pressure Loss Head Loss Velocity (GPM) (psi/100 ft) (ft/100 ft) (ft./sec.) (cu. cm/sec.) (kPa/100 m) (m/100 m) (m/sec.) 5.00 0.11 0.25 0.88 315 0.02 0.25 0.27 10.00 0.38 0.89 1.75 631 0.09 0.89 0.53 15.00 0.81 1.88 2.63 946 0.18 1.88 0.80 20.00 1.38 3.20 3.50 1262 0.31 3.20 1.07 25.00 2.09 4.84 4.38 1577 0.47 4.84 1.33 30.00 2.93 6.78 5.26 1893 0.66 6.78 1.60 35.00 3.89 9.02 6.13 2208 0.88 9.02 1.87 40.00 4.98 11.54 7.01 2523 1.13 11.54 2.14 45.00 6.20 14.35 7.88 2839 1.40 14.35 2.40 50.00 7.53 17.44 8.76 3154 1.70 17.44 2.67 55.00 8.99 20.80 9.64 3470 2.03 20.80 2.94 60.00 10.56 24.44 10.51 3785 2.39 24.44 3.20 65.00 12.25 28.34 11.39 4101 2.77 28.34 3.47 70.00 14.05 32.50 12.26 4416 3.18 32.50 3.74 75.00 15.96 36.92 13.14 4732 3.61 36.92 4.00 80.00 17.99 41.61 14.02 5047 4.07 41.61 4.27 85.00 20.13 46.55 14.89 5362 4.55 46.55 4.54 90.00 22.38 51.74 15.77 5678 5.06 51.74 4.81 95.00 24.73 57.18 16.64 5993 5.59 57.18 5.07 100.00 27.20 62.87 17.52 6309 6.15 62.87 5.34 105.00 29.77 68.81 18.40 6624 6.73 68.81 5.61 110.00 32.45 74.99 19.27 6940 7.34 74.99 5.87 115.00 35.23 81.42 20.15 7255 7.97 81.42 6.14 2" TYPE “K” COPPER TUBE — WATER FLOW AND FRICTION LOSS PER 100 FEET Maximum O.D. = 2.1270 inches (54.026 mm) Nominal O.D. = 2.1250 inches (53.975 mm) Minimum O.D. = 2.1230 inches (53.924 mm) Nominal I.D. = 1.9590 inches (49.7586 mm) Nominal Wall Thickness = 0.0830 inches (2.1082 mm) Flow Area = 3.0141 sq. inches (1944.58 sq. mm) Hazen Williams Formula C Factor = 150 FLOW, Q Pressure Loss Head Loss Velocity FLOW, Q Pressure Loss Head Loss Velocity (GPM) (psi/100 ft) (ft/100 ft) (ft./sec.) (cu. cm/sec.) (kPa/100 m) (m/100 m) (m/sec.) 10 0.11 0.26 1.06 631 0.03 0.26 0.32 20 0.41 0.95 2.13 1262 0.09 0.95 0.65 30 0.87 2.02 3.19 1893 0.20 2.02 0.97 40 1.48 3.43 4.26 2523 0.34 3.43 1.30 50 2.24 5.19 5.32 3154 0.51 5.19 1.62 60 3.14 7.27 6.39 3785 0.71 7.27 1.95 70 4.18 9.67 7.45 4416 0.95 9.67 2.27 80 5.35 12.38 8.52 5047 1.21 12.38 2.60 90 6.66 15.39 9.58 5678 1.51 15.39 2.92 100 8.09 18.71 10.64 6309 1.83 18.71 3.24 110 9.66 22.32 11.71 6940 2.18 22.32 3.57 120 11.34 26.21 12.77 7570 2.57 26.21 3.89 130 13.16 30.40 13.84 8201 2.98 30.40 4.22 140 15.09 34.86 14.90 8832 3.41 34.86 4.54 150 17.15 39.61 15.97 9463 3.88 39.61 4.87 160 19.33 44.63 17.03 10094 4.37 44.63 5.19 170 21.62 49.93 18.10 10725 4.89 49.93 5.52 180 24.04 55.50 19.16 11356 5.44 55.50 5.84 190 26.57 61.34 20.22 11986 6.01 61.34 6.16 200 29.22 67.44 21.29 12617 6.61 67.44 6.49 U.S. customary units in this document are the standard; the metric units are provided for reference only. The values stated in each system are not exact equivalents. AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 55//1144//0022 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 69 2" TYPE “L” COPPER TUBE — WATER FLOW AND FRICTION LOSS PER 100 FEET Maximum O.D. = 2.1270 inches (54.026 mm) Nominal O.D. = 2.1250 inches (53.975 mm) Minimum O.D. = 2.1230 inches (53.924 mm) Nominal I.D. = 1.9850 inches (50.419 mm) Nominal Wall Thickness = 0.0700 inches (1.778 mm) Flow Area = 3.0946 sq. inches (1996.54 sq. mm) Hazen Williams Formula C Factor = 150 FLOW, Q Pressure Loss Head Loss Velocity FLOW, Q Pressure Loss Head Loss Velocity (GPM) (psi/100 ft) (ft/100 ft) (ft./sec.) (cu. cm/sec.) (kPa/100 m) (m/100 m) (m/sec.) 10 0.11 0.25 1.04 631 0.02 0.25 0.32 20 0.39 0.89 2.07 1262 0.09 0.89 0.63 30 0.82 1.89 3.11 1893 0.18 1.89 0.95 40 1.39 3.22 4.15 2523 0.31 3.22 1.26 50 2.10 4.87 5.18 3154 0.48 4.87 1.58 60 2.95 6.82 6.22 3785 0.67 6.82 1.90 70 3.92 9.07 7.26 4416 0.89 9.07 2.21 80 5.02 11.61 8.29 5047 1.14 11.61 2.53 90 6.24 14.44 9.33 5678 1.41 14.44 2.84 100 7.59 17.55 10.37 6309 1.72 17.55 3.16 110 9.06 20.93 11.40 6940 2.05 20.93 3.48 120 10.64 24.58 12.44 7570 2.41 24.58 3.79 130 12.34 28.51 13.48 8201 2.79 28.51 4.11 140 14.15 32.70 14.51 8832 3.20 32.70 4.42 150 16.08 37.15 15.55 9463 3.64 37.15 4.74 160 18.13 41.86 16.59 10094 4.10 41.86 5.06 170 20.28 46.83 17.62 10725 4.59 46.83 5.37 180 22.54 52.05 18.66 11356 5.10 52.05 5.69 190 24.92 57.53 19.70 11986 5.64 57.53 6.00 200 27.40 63.25 20.73 12617 6.20 63.25 6.32 2" TYPE “M” COPPER TUBE — WATER FLOW AND FRICTION LOSS PER 100 FEET Maximum O.D. = 2.1270 inches (54.026 mm) Nominal O.D. = 2.1250 inches (53.975 mm) Minimum O.D. = 2.1230 inches (53.924 mm) Nominal I.D. = 2.0090 inches (51.0286 mm) Nominal Wall Thickness = 0.0580 inches (1.4732 mm) Flow Area = 3.1699 sq. inches (2045.11 sq. mm) Hazen Williams Formula C Factor = 150 FLOW, Q Pressure Loss Head Loss Velocity FLOW, Q Pressure Loss Head Loss Velocity (GPM) (psi/100 ft) (ft/100 ft) (ft./sec.) (cu. cm/sec.) (kPa/100 m) (m/100 m) (m/sec.) 10 0.10 0.23 1.01 631 0.02 0.23 0.31 20 0.36 0.84 2.02 1262 0.08 0.84 0.62 30 0.77 1.78 3.04 1893 0.17 1.78 0.93 40 1.31 3.04 4.05 2523 0.30 3.04 1.23 50 1.98 4.59 5.06 3154 0.45 4.59 1.54 60 2.78 6.43 6.07 3785 0.63 6.43 1.85 70 3.70 8.55 7.08 4416 0.84 8.55 2.16 80 4.74 10.95 8.10 5047 1.07 10.95 2.47 90 5.89 13.62 9.11 5678 1.33 13.62 2.78 100 7.16 16.55 10.12 6309 1.62 16.55 3.08 110 8.54 19.74 11.13 6940 1.93 19.74 3.39 120 10.03 23.19 12.15 7570 2.27 23.19 3.70 130 11.64 26.89 13.16 8201 2.63 26.89 4.01 140 13.35 30.84 14.17 8832 3.02 30.84 4.32 150 15.17 35.04 15.18 9463 3.43 35.04 4.63 160 17.10 39.48 16.19 10094 3.87 39.48 4.94 170 19.13 44.17 17.21 10725 4.33 44.17 5.24 180 21.26 49.09 18.22 11356 4.81 49.09 5.55 190 23.50 54.26 19.23 11986 5.32 54.26 5.86 200 25.84 59.66 20.24 12617 5.85 59.66 6.17 U.S. customary units in this document are the standard; the metric units are provided for reference only. The values stated in each system are not exact equivalents. AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 55//1144//0022 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 70 2 1/2" TYPE “K” COPPER TUBE — WATER FLOW AND FRICTION LOSS PER 100 FEET Maximum O.D. = 2.6270 inches (66.7258 mm) Nominal O.D. = 2.6250 inches (66.675 mm) Minimum O.D. = 2.6230 inches (66.6242 mm) Nominal I.D. = 2.4350 inches (61.849 mm) Nominal Wall Thickness = 0.0950 inches (2.413 mm) Flow Area = 4.6568 sq. inches (3004.380 sq. mm) Hazen Williams Formula C Factor = 150 FLOW, Q Pressure Loss Head Loss Velocity FLOW, Q Pressure Loss Head Loss Velocity (GPM) (psi/100 ft) (ft/100 ft) (ft./sec.) (cu. cm/sec.) (kPa/100 m) (m/100 m) (m/sec.) 20 0.14 0.33 1.38 1262 0.03 0.33 0.42 40 0.51 1.19 2.76 2523 0.12 1.19 0.84 60 1.09 2.52 4.13 3785 0.25 2.52 1.26 80 1.86 4.30 5.51 5047 0.42 4.30 1.68 100 2.81 6.49 6.89 6309 0.64 6.49 2.10 120 3.94 9.10 8.27 7570 0.89 9.10 2.52 140 5.24 12.10 9.65 8832 1.18 12.10 2.94 160 6.71 15.49 11.02 10094 1.52 15.49 3.36 180 8.34 19.26 12.40 11356 1.89 19.26 3.78 200 10.14 23.41 13.78 12617 2.29 23.41 4.20 220 12.10 27.92 15.16 13879 2.74 27.92 4.62 240 14.21 32.79 16.53 15141 3.21 32.79 5.04 260 16.48 38.03 17.91 16403 3.73 38.03 5.46 280 18.91 43.62 19.29 17664 4.28 43.62 5.88 300 21.48 49.55 20.67 18926 4.86 49.55 6.30 320 24.21 55.84 22.05 20188 5.48 55.84 6.72 2 1/2" TYPE “L” COPPER TUBE — WATER FLOW AND FRICTION LOSS PER 100 FEET Maximum O.D. = 2.6270 inches (66.7258 mm) Nominal O.D. = 2.6250 inches (66.675 mm) Minimum O.D. = 2.6230 inches (66.6242 mm) Nominal I.D. = 2.4650 inches (62.611 mm) Nominal Wall Thickness = 0.0800 inches (2.032 mm) Flow Area = 4.7723 sq. inches (3078.87 sq. mm) Hazen Williams Formula C Factor = 150 FLOW, Q Pressure Loss Head Loss Velocity FLOW, Q Pressure Loss Head Loss Velocity (GPM) (psi/100 ft) (ft/100 ft) (ft./sec.) (cu. cm/sec.) (kPa/100 m) (m/100 m) (m/sec.) 20 0.13 0.31 1.34 1262 0.03 0.31 0.41 40 0.48 1.12 2.69 2523 0.11 1.12 0.82 60 1.03 2.38 4.03 3785 0.23 2.38 1.23 80 1.75 4.05 5.38 5047 0.40 4.05 1.64 100 2.65 6.12 6.72 6309 0.60 6.12 2.05 120 3.71 8.57 8.07 7570 0.84 8.57 2.46 140 4.93 11.40 9.41 8832 1.12 11.40 2.87 160 6.32 14.59 10.76 10094 1.43 14.59 3.28 180 7.86 18.15 12.10 11356 1.78 18.15 3.69 200 9.55 22.05 13.45 12617 2.16 22.05 4.10 220 11.40 26.30 14.79 13879 2.58 26.30 4.51 240 13.39 30.90 16.13 15141 3.03 30.90 4.92 260 15.53 35.83 17.48 16403 3.51 35.83 5.33 280 17.81 41.09 18.82 17664 4.03 41.09 5.74 300 20.24 46.69 20.17 18926 4.58 46.69 6.15 320 22.81 52.61 21.51 20188 5.16 52.61 6.56 U.S. customary units in this document are the standard; the metric units are provided for reference only. The values stated in each system are not exact equivalents. AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 55//1144//0022 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 71 2 1/2" TYPE “M” COPPER TUBE — WATER FLOW AND FRICTION LOSS PER 100 FEET Maximum O.D. = 2.6270 inches (66.7258 mm) Nominal O.D. = 2.6250 inches (66.675 mm) Minimum O.D. = 2.6230 inches (66.6242 mm) Nominal I.D. = 2.4950 inches (63.373 mm) Nominal Wall Thickness = 0.0650 inches (1.651 mm) Flow Area = 4.8891 sq. inches (3154.27 sq. mm) Hazen Williams Formula C Factor = 150 FLOW, Q Pressure Loss Head Loss Velocity FLOW, Q Pressure Loss Head Loss Velocity (GPM) (psi/100 ft) (ft/100 ft) (ft./sec.) (cu. cm/sec.) (kPa/100 m) (m/100 m) (m/sec.) 20 0.13 0.29 1.31 1262 0.03 0.29 0.40 40 0.46 1.06 2.62 2523 0.10 1.06 0.80 60 0.97 2.24 3.94 3785 0.22 2.24 1.20 80 1.65 3.82 5.25 5047 0.37 3.82 1.60 100 2.50 5.77 6.56 6309 0.56 5.77 2.00 120 3.50 8.08 7.87 7570 0.79 8.08 2.40 140 4.65 10.75 9.19 8832 1.05 10.75 2.80 160 5.96 13.76 10.50 10094 1.35 13.76 3.20 180 7.41 17.11 11.81 11356 1.68 17.11 3.60 200 9.01 20.79 13.12 12617 2.04 20.79 4.00 220 10.75 24.80 14.44 13879 2.43 24.80 4.40 240 12.62 29.13 15.75 15141 2.86 29.13 4.80 260 14.64 33.78 17.06 16403 3.31 33.78 5.20 280 16.80 38.75 18.37 17664 3.80 38.75 5.60 300 19.09 44.02 19.69 18926 4.32 44.02 6.00 320 21.51 49.60 21.00 20188 4.87 49.60 6.40 3" TYPE “K” COPPER TUBE — WATER FLOW AND FRICTION LOSS PER 100 FEET Maximum O.D. = 3.1270 inches (79.4258 mm) Nominal O.D. = 3.1250 inches (79.375 mm) Minimum O.D. = 3.1230 inches (79.3242 mm) Nominal I.D. = 2.9070 inches (73.8378 mm) Nominal Wall Thickness = 0.1090 inches (2.7686 mm) Flow Area = 6.6371 sq. inches (4282.01 sq. mm) Hazen Williams Formula C Factor = 150 FLOW, Q Pressure Loss Head Loss Velocity FLOW, Q Pressure Loss Head Loss Velocity (GPM) (psi/100 ft) (ft/100 ft) (ft./sec.) (cu. cm/sec.) (kPa/100 m) (m/100 m) (m/sec.) 25 0.09 0.21 1.21 1577 0.02 0.21 0.37 50 0.33 0.76 2.42 3154 0.07 0.76 0.74 75 0.70 1.61 3.63 4732 0.16 1.61 1.11 100 1.19 2.74 4.83 6309 0.27 2.74 1.47 125 1.79 4.14 6.04 7886 0.41 4.14 1.84 150 2.51 5.80 7.25 9463 0.57 5.80 2.21 175 3.34 7.72 8.46 11040 0.76 7.72 2.58 200 4.28 9.88 9.67 12617 0.97 9.88 2.95 225 5.33 12.29 10.88 14195 1.20 12.29 3.32 250 6.47 14.94 12.08 15772 1.46 14.94 3.68 275 7.72 17.82 13.29 17349 1.75 17.82 4.05 300 9.07 20.93 14.50 18926 2.05 20.93 4.42 325 10.52 24.27 15.71 20503 2.38 24.27 4.79 350 12.07 27.83 16.92 22080 2.73 27.83 5.16 375 13.72 31.62 18.13 23658 3.10 31.62 5.53 400 15.46 35.63 19.34 25235 3.50 35.63 5.89 425 17.29 39.86 20.54 26812 3.91 39.86 6.26 U.S. customary units in this document are the standard; the metric units are provided for reference only. The values stated in each system are not exact equivalents. AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 55//1144//0022 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 72 3" TYPE “L” COPPER TUBE — WATER FLOW AND FRICTION LOSS PER 100 FEET Maximum O.D. = 3.1270 inches (79.4258 mm) Nominal O.D. = 3.1250 inches (79.375 mm) Minimum O.D. = 3.1230 inches (79.3242 mm) Nominal I.D. = 2.9450 inches (74.803 mm) Nominal Wall Thickness = 0.0900 inches (2.286 mm) Flow Area = 6.8118 sq. inches (4394.69 sq. mm) Hazen Williams Formula C Factor = 150 FLOW, Q Pressure Loss Head Loss Velocity FLOW, Q Pressure Loss Head Loss Velocity (GPM) (psi/100 ft) (ft/100 ft) (ft./sec.) (cu. cm/sec.) (kPa/100 m) (m/100 m) (m/sec.) 25 0.09 0.20 1.18 1577 0.02 0.20 0.36 50 0.31 0.71 2.35 3154 0.07 0.71 0.72 75 0.65 1.51 3.53 4732 0.15 1.51 1.08 100 1.11 2.57 4.71 6309 0.25 2.57 1.44 125 1.68 3.89 5.89 7886 0.38 3.89 1.79 150 2.36 5.45 7.06 9463 0.53 5.45 2.15 175 3.14 7.25 8.24 11040 0.71 7.25 2.51 200 4.02 9.28 9.42 12617 0.91 9.28 2.87 225 5.00 11.54 10.60 14195 1.13 11.54 3.23 250 6.08 14.02 11.77 15772 1.37 14.02 3.59 275 7.25 16.72 12.95 17349 1.64 16.72 3.95 300 8.52 19.65 14.13 18926 1.93 19.65 4.31 325 9.88 22.78 15.31 20503 2.23 22.78 4.67 350 11.33 26.13 16.48 22080 2.56 26.13 5.02 375 12.88 29.69 17.66 23658 2.91 29.69 5.38 400 14.51 33.45 18.84 25235 3.28 33.45 5.74 425 16.24 37.42 20.02 26812 3.67 37.42 6.10 3" TYPE “M” COPPER TUBE — WATER FLOW AND FRICTION LOSS PER 100 FEET Maximum O.D. = 3.1270 inches (79.4258 mm) Nominal O.D. = 3.1250 inches (79.375 mm) Minimum O.D. = 3.1230 inches (79.3242 mm) Nominal I.D. = 2.9810 inches (75.7174 mm) Nominal Wall Thickness = 0.0720 inches (1.8288 mm) Flow Area = 6.9793 sq. inches (4502.79 sq. mm) Hazen Williams Formula C Factor = 150 FLOW, Q Pressure Loss Head Loss Velocity FLOW, Q Pressure Loss Head Loss Velocity (GPM) (psi/100 ft) (ft/100 ft) (ft./sec.) (cu. cm/sec.) (kPa/100 m) (m/100 m) (m/sec.) 25 0.08 0.19 1.15 1577 0.02 0.19 0.35 50 0.29 0.67 2.30 3154 0.07 0.67 0.70 75 0.62 1.42 3.45 4732 0.14 1.42 1.05 100 1.05 2.43 4.60 6309 0.24 2.43 1.40 125 1.59 3.67 5.75 7886 0.36 3.67 1.75 150 2.22 5.14 6.90 9463 0.50 5.14 2.10 175 2.96 6.83 8.04 11040 0.67 6.83 2.45 200 3.79 8.75 9.19 12617 0.86 8.75 2.80 225 4.71 10.88 10.34 14195 1.07 10.88 3.15 250 5.73 13.22 11.49 15772 1.30 13.22 3.50 275 6.83 15.76 12.64 17349 1.55 15.76 3.85 300 8.03 18.52 13.79 18926 1.82 18.52 4.20 325 9.31 21.47 14.94 20503 2.11 21.47 4.55 350 10.68 24.63 16.09 22080 2.42 24.63 4.90 375 12.14 27.98 17.24 23658 2.75 27.98 5.25 400 13.68 31.53 18.39 25235 3.09 31.53 5.60 425 15.30 35.27 19.54 26812 3.46 35.27 5.95 U.S. customary units in this document are the standard; the metric units are provided for reference only. The values stated in each system are not exact equivalents. AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 55//1144//0022 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 73 3 1/2" TYPE “K” COPPER TUBE — WATER FLOW AND FRICTION LOSS PER 100 FEET Maximum O.D. = 3.6270 inches (92.1258 mm) Nominal O.D. = 3.6250 inches (92.075 mm) Minimum O.D. = 3.6230 inches (92.0242 mm) Nominal I.D. = 3.3850 inches (85.979 mm) Nominal Wall Thickness = 0.1200 inches (3.048 mm) Flow Area = 6.9993 sq. inches (5805.97 sq. mm) Hazen Williams Formula C Factor = 150 FLOW, Q Pressure Loss Head Loss Velocity FLOW, Q Pressure Loss Head Loss Velocity (GPM) (psi/100 ft) (ft/100 ft) (ft./sec.) (cu. cm/sec.) (kPa/100 m) (m/100 m) (m/sec.) 25 0.04 0.10 0.89 1577 0.01 0.10 0.27 50 0.16 0.36 1.78 3154 0.04 0.36 0.54 75 0.33 0.77 2.67 4732 0.08 0.77 0.81 100 0.57 1.31 3.57 6309 0.13 1.31 1.09 125 0.85 1.98 4.46 7886 0.19 1.98 1.36 150 1.20 2.77 5.35 9463 0.27 2.77 1.63 175 1.59 3.68 6.24 11040 0.36 3.68 1.90 200 2.04 4.71 7.13 12617 0.46 4.71 2.17 225 2.54 5.86 8.02 14195 0.57 5.86 2.44 250 3.09 7.12 8.91 15772 0.70 7.12 2.72 275 3.68 8.49 9.80 17349 0.83 8.49 2.99 300 4.33 9.98 10.70 18926 0.98 9.98 3.26 325 5.02 11.57 11.59 20503 1.13 11.57 3.53 350 5.76 13.27 12.48 22080 1.30 13.27 3.80 375 6.54 15.08 13.37 23658 1.48 15.08 4.07 400 7.37 16.99 14.26 25235 1.67 16.99 4.35 425 8.25 19.01 15.15 26812 1.87 19.01 4.62 450 9.17 21.12 16.04 28389 2.07 21.12 4.89 475 10.13 23.35 16.93 29966 2.29 23.35 5.16 500 11.14 25.67 17.83 31543 2.52 25.67 5.43 525 12.20 28.10 18.72 33121 2.76 28.10 5.70 550 13.29 30.62 19.61 34698 3.01 30.62 5.98 575 14.43 33.25 20.50 36275 3.26 33.25 6.25 600 15.62 35.97 21.39 37852 3.53 35.97 6.52 3 1/2" TYPE “L” COPPER TUBE — WATER FLOW AND FRICTION LOSS PER 100 FEET Maximum O.D. = 3.6270 inches (92.1258 mm) Nominal O.D. = 3.6250 inches (92.075 mm) Minimum O.D. = 3.6230 inches (92.0242 mm) Nominal I.D. = 3.4250 inches (86.995 mm) Nominal Wall Thickness = 0.1000 inches (2.540 mm) Flow Area = 9.2132 sq. inches (5944.00 sq. mm) Hazen Williams Formula C Factor = 150 FLOW, Q Pressure Loss Head Loss Velocity FLOW, Q Pressure Loss Head Loss Velocity (GPM) (psi/100 ft) (ft/100 ft) (ft./sec.) (cu. cm/sec.) (kPa/100 m) (m/100 m) (m/sec.) 25 0.04 0.09 0.87 1577 0.01 0.09 0.27 50 0.15 0.34 1.74 3154 0.03 0.34 0.53 75 0.31 0.73 2.61 4732 0.07 0.73 0.80 100 0.53 1.23 3.48 6309 0.12 1.23 1.06 125 0.81 1.87 4.35 7886 0.18 1.87 1.33 150 1.13 2.61 5.22 9463 0.26 2.61 1.59 175 1.51 3.48 6.09 11040 0.34 3.48 1.86 200 1.93 4.45 6.96 12617 0.44 4.45 2.12 225 2.40 5.53 7.84 14195 0.54 5.53 2.39 250 2.91 6.73 8.71 15772 0.66 6.73 2.65 275 3.48 8.02 9.58 17349 0.79 8.02 2.92 300 4.09 9.42 10.45 18926 0.92 9.42 3.18 325 4.74 10.93 11.32 20503 1.07 10.93 3.45 350 5.44 12.53 12.19 22080 1.23 12.53 3.71 375 6.18 14.24 13.06 23658 1.40 14.24 3.98 400 6.96 16.05 13.93 25235 1.57 16.05 4.25 425 7.79 17.95 14.80 26812 1.76 17.95 4.51 450 8.66 19.95 15.67 28389 1.96 19.95 4.78 475 9.57 22.05 16.54 29966 2.16 22.05 5.04 500 10.52 24.25 17.41 31543 2.38 24.25 5.31 525 11.52 26.54 18.28 33121 2.61 26.54 5.57 550 12.55 28.92 19.15 34698 2.84 28.92 5.84 575 13.63 31.40 20.02 36275 3.08 31.40 6.10 600 14.75 33.97 20.89 37852 3.34 33.97 6.37 U.S. customary units in this document are the standard; the metric units are provided for reference only. The values stated in each system are not exact equivalents. AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 55//1144//0022 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 74 3 1/2" TYPE “M” COPPER TUBE — WATER FLOW AND FRICTION LOSS PER 100 FEET Maximum O.D. = 3.6270 inches (92.1258 mm) Nominal O.D. = 3.6250 inches (92.075 mm) Minimum O.D. = 3.6230 inches (92.0242 mm) Nominal I.D. = 3.4590 inches (87.8586 mm) Nominal Wall Thickness = 0.0830 inches (2.1082 mm) Flow Area = 9.397 sq. inches (6062.59 sq. mm) Hazen Williams Formula C Factor = 150 FLOW, Q Pressure Loss Head Loss Velocity FLOW, Q Pressure Loss Head Loss Velocity (GPM) (psi/100 ft) (ft/100 ft) (ft./sec.) (cu. cm/sec.) (kPa/100 m) (m/100 m) (m/sec.) 25 0.04 0.09 0.85 1577 0.01 0.09 0.26 50 0.14 0.33 1.71 3154 0.03 0.33 0.52 75 0.30 0.69 2.56 4732 0.07 0.69 0.78 100 0.51 1.18 3.41 6309 0.12 1.18 1.04 125 0.77 1.78 4.27 7886 0.17 1.78 1.30 150 1.08 2.49 5.12 9463 0.24 2.49 1.56 175 1.44 3.31 5.97 11040 0.32 3.31 1.82 200 1.84 4.24 6.83 12617 0.42 4.24 2.08 225 2.29 5.27 7.68 14195 0.52 5.27 2.34 250 2.78 6.41 8.54 15772 0.63 6.41 2.60 275 3.31 7.65 9.39 17349 0.75 7.65 2.86 300 3.89 8.98 10.24 18926 0.88 8.98 3.12 325 4.52 10.41 11.10 20503 1.02 10.41 3.38 350 5.18 11.94 11.95 22080 1.17 11.94 3.64 375 5.89 13.57 12.80 23658 1.33 13.57 3.90 400 6.63 15.29 13.66 25235 1.50 15.29 4.16 425 7.42 17.11 14.51 26812 1.68 17.11 4.42 450 8.25 19.02 15.36 28389 1.87 19.02 4.68 475 9.12 21.02 16.22 29966 2.06 21.02 4.94 500 10.03 23.11 17.07 31543 2.27 23.11 5.20 525 10.98 25.29 17.92 33121 2.48 25.29 5.46 550 11.96 27.56 18.78 34698 2.71 27.56 5.72 575 12.99 29.93 19.63 36275 2.94 29.93 5.98 600 14.06 32.38 20.49 37852 3.18 32.38 6.24 4" TYPE “K” COPPER TUBE — WATER FLOW AND FRICTION LOSS PER 100 FEET Maximum O.D. = 4.1270 inches (104.8258 mm) Nominal O.D. = 4.1250 inches (104.775 mm) Minimum O.D. = 4.1230 inches (104.7242 mm) Nominal I.D. = 3.8570 inches (97.9678 mm) Nominal Wall Thickness = 0.1340 inches (3.4036 mm) Flow Area = 11.6839 sq. inches (7538.01 sq. mm) Hazen Williams Formula C Factor = 150 FLOW, Q Pressure Loss Head Loss Velocity FLOW, Q Pressure Loss Head Loss Velocity (GPM) (psi/100 ft) (ft/100 ft) (ft./sec.) (cu. cm/sec.) (kPa/100 m) (m/100 m) (m/sec.) 50 0.08 0.19 1.37 3154 0.02 0.19 0.42 100 0.30 0.69 2.75 6309 0.07 0.69 0.84 150 0.63 1.47 4.12 9463 0.14 1.47 1.26 200 1.08 2.50 5.49 12617 0.24 2.50 1.67 250 1.64 3.77 6.86 15772 0.37 3.77 2.09 300 2.29 5.29 8.24 18926 0.52 5.29 2.51 350 3.05 7.03 9.61 22080 0.69 7.03 2.93 400 3.91 9.00 10.98 25235 0.88 9.00 3.35 450 4.86 11.19 12.36 28389 1.10 11.19 3.77 500 5.90 13.60 13.73 31543 1.34 13.60 4.18 550 7.04 16.23 15.10 34698 1.59 16.23 4.60 600 8.27 19.06 16.48 37852 1.87 19.06 5.02 650 9.60 22.10 17.85 41006 2.17 22.10 5.44 700 11.01 25.35 19.22 44161 2.49 25.35 5.86 750 12.51 28.80 20.59 47315 2.83 28.80 6.28 800 14.10 32.45 21.97 50469 3.19 32.45 6.70 850 15.77 36.30 23.34 53624 3.57 36.30 7.11 900 17.53 40.35 24.71 56778 3.97 40.35 7.53 950 19.38 44.60 26.09 59932 4.38 44.60 7.95 1000 21.31 49.04 27.46 63087 4.82 49.04 8.37 U.S. customary units in this document are the standard; the metric units are provided for reference only. The values stated in each system are not exact equivalents. AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 55//1144//0022 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 75 4" TYPE “L” COPPER TUBE — WATER FLOW AND FRICTION LOSS PER 100 FEET Maximum O.D. = 4.1270 inches (104.8258 mm) Nominal O.D. = 4.1250 inches (104.775 mm) Minimum O.D. = 4.1230 inches (104.7242 mm) Nominal I.D. = 3.9050 inches (99.187 mm) Nominal Wall Thickness = 0.1100 inches (2.794 mm) Flow Area = 11.9766 sq. inches (7726.80 sq. mm) Hazen Williams Formula C Factor = 150 FLOW, Q Pressure Loss Head Loss Velocity FLOW, Q Pressure Loss Head Loss Velocity (GPM) (psi/100 ft) (ft/100 ft) (ft./sec.) (cu. cm/sec.) (kPa/100 m) (m/100 m) (m/sec.) 50 0.08 0.18 1.34 3154 0.02 0.18 0.41 100 0.28 0.65 2.68 6309 0.06 0.65 0.82 150 0.60 1.38 4.02 9463 0.14 1.38 1.22 200 1.02 2.35 5.36 12617 0.23 2.35 1.63 250 1.54 3.55 6.70 15772 0.35 3.55 2.04 300 2.16 4.98 8.04 18926 0.49 4.98 2.45 350 2.87 6.62 9.38 22080 0.65 6.62 2.86 400 3.68 8.48 10.72 25235 0.83 8.48 3.27 450 4.57 10.54 12.05 28389 1.03 10.54 3.67 500 5.56 12.81 13.39 31543 1.26 12.81 4.08 550 6.63 15.28 14.73 34698 1.50 15.28 4.49 600 7.79 17.95 16.07 37852 1.76 17.95 4.90 650 9.04 20.81 17.41 41006 2.04 20.81 5.31 700 10.37 23.87 18.75 44161 2.34 23.87 5.72 750 11.78 27.12 20.09 47315 2.66 27.12 6.12 800 13.27 30.56 21.43 50469 3.00 30.56 6.53 850 14.85 34.18 22.77 53624 3.36 34.18 6.94 900 16.51 38.00 24.11 56778 3.73 38.00 7.35 950 18.25 41.99 25.45 59932 4.13 41.99 7.76 1000 20.07 46.17 26.79 63087 4.54 46.17 8.17 4" TYPE “M” COPPER TUBE — WATER FLOW AND FRICTION LOSS PER 100 FEET Maximum O.D. = 4.1270 inches (104.8258 mm) Nominal O.D. = 4.1250 inches (104.775 mm) Minimum O.D. = 4.1230 inches (104.7242 mm) Nominal I.D. = 3.9350 inches (99.949 mm) Nominal Wall Thickness = 0.0950 inches (2.413 mm) Flow Area = 12.1613 sq. inches (7845.87 sq. mm) Hazen Williams Formula C Factor = 150 FLOW, Q Pressure Loss Head Loss Velocity FLOW, Q Pressure Loss Head Loss Velocity (GPM) (psi/100 ft) (ft/100 ft) (ft./sec.) (cu. cm/sec.) (kPa/100 m) (m/100 m) (m/sec.) 50 0.08 0.17 1.32 3154 0.02 0.17 0.40 100 0.27 0.63 2.64 6309 0.06 0.63 0.80 150 0.58 1.33 3.96 9463 0.13 1.33 1.21 200 0.98 2.27 5.28 12617 0.22 2.27 1.61 250 1.48 3.42 6.60 15772 0.34 3.42 2.01 300 2.08 4.80 7.91 18926 0.47 4.80 2.41 350 2.77 6.38 9.23 22080 0.63 6.38 2.81 400 3.54 8.17 10.55 25235 0.80 8.17 3.22 450 4.41 10.15 11.87 28389 1.00 10.15 3.62 500 5.36 12.34 13.19 31543 1.21 12.34 4.02 550 6.39 14.72 14.51 34698 1.45 14.72 4.42 600 7.51 17.29 15.83 37852 1.70 17.29 4.82 650 8.71 20.05 17.15 41006 1.97 20.05 5.23 700 9.99 23.00 18.47 44161 2.26 23.00 5.63 750 11.35 26.13 19.79 47315 2.57 26.13 6.03 800 12.79 29.44 21.11 50469 2.89 29.44 6.43 850 14.31 32.93 22.42 53624 3.24 32.93 6.83 900 15.91 36.61 23.74 56778 3.60 36.61 7.24 950 17.58 40.46 25.06 59932 3.98 40.46 7.64 1000 19.33 44.49 26.38 63087 4.37 44.49 8.04 U.S. customary units in this document are the standard; the metric units are provided for reference only. The values stated in each system are not exact equivalents. AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 55//1144//0022 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 76 5" TYPE “K” COPPER TUBE — WATER FLOW AND FRICTION LOSS PER 100 FEET Maximum O.D. = 5.1270 inches (130.2258 mm) Nominal O.D. = 5.1250 inches (130.175 mm) Minimum O.D. = 5.1230 inches (130.1242 mm) Nominal I.D. = 4.8050 inches (122.047 mm) Nominal Wall Thickness = 0.1600 inches (4.064 mm) Flow Area = 18.1333 sq. inches (11698.87 sq. mm) Hazen Williams Formula C Factor = 150 FLOW, Q Pressure Loss Head Loss Velocity FLOW, Q Pressure Loss Head Loss Velocity (GPM) (psi/100 ft) (ft/100 ft) (ft./sec.) (cu. cm/sec.) (kPa/100 m) (m/100 m) (m/sec.) 50 0.03 0.07 0.88 3154 0.01 0.07 0.27 100 0.10 0.24 1.77 6309 0.02 0.24 0.54 150 0.22 0.50 2.65 9463 0.05 0.50 0.81 200 0.37 0.86 3.54 12617 0.08 0.86 1.08 250 0.56 1.30 4.42 15772 0.13 1.30 1.35 300 0.79 1.81 5.31 18926 0.18 1.81 1.62 350 1.05 2.41 6.19 22080 0.24 2.41 1.89 400 1.34 3.09 7.08 25235 0.30 3.09 2.16 450 1.67 3.84 7.96 28389 0.38 3.84 2.43 500 2.03 4.67 8.85 31543 0.46 4.67 2.70 550 2.42 5.57 9.73 34698 0.55 5.57 2.97 600 2.84 6.54 10.62 37852 0.64 6.54 3.24 650 3.29 7.59 11.50 41006 0.75 7.59 3.51 700 3.78 8.70 12.39 44161 0.85 8.70 3.77 750 4.29 9.89 13.27 47315 0.97 9.89 4.04 800 4.84 11.14 14.15 50469 1.09 11.14 4.31 850 5.41 12.46 15.04 53624 1.22 12.46 4.58 900 6.02 13.85 15.92 56778 1.36 13.85 4.85 950 6.65 15.31 16.81 59932 1.50 15.31 5.12 1000 7.32 16.83 17.69 63087 1.65 16.83 5.39 1050 8.01 18.42 18.58 66241 1.81 18.42 5.66 1100 8.73 20.08 19.46 69395 1.97 20.08 5.93 1150 9.48 21.80 20.35 72550 2.14 21.80 6.20 5" TYPE “L” COPPER TUBE — WATER FLOW AND FRICTION LOSS PER 100 FEET Maximum O.D. = 5.1270 inches (130.2258 mm) Nominal O.D. = 5.1250 inches (130.175 mm) Minimum O.D. = 5.1230 inches (130.1242 mm) Nominal I.D. = 4.8750 inches (123.825 mm) Nominal Wall Thickness = 0.1250 inches (3.175 mm) Flow Area = 18.6655 sq. inches (12042.22 sq. mm) Hazen Williams Formula C Factor = 150 FLOW, Q Pressure Loss Head Loss Velocity FLOW, Q Pressure Loss Head Loss Velocity (GPM) (psi/100 ft) (ft/100 ft) (ft./sec.) (cu. cm/sec.) (kPa/100 m) (m/100 m) (m/sec.) 50 0.03 0.06 0.86 3154 0.01 0.06 0.26 100 0.10 0.22 1.72 6309 0.02 0.22 0.52 150 0.20 0.47 2.58 9463 0.05 0.47 0.79 200 0.35 0.80 3.44 12617 0.08 0.80 1.05 250 0.52 1.21 4.30 15772 0.12 1.21 1.31 300 0.73 1.69 5.16 18926 0.17 1.69 1.57 350 0.98 2.25 6.02 22080 0.22 2.25 1.83 400 1.25 2.88 6.88 25235 0.28 2.88 2.10 450 1.55 3.58 7.73 28389 0.35 3.58 2.36 500 1.89 4.35 8.59 31543 0.43 4.35 2.62 550 2.25 5.19 9.45 34698 0.51 5.19 2.88 600 2.65 6.10 10.31 37852 0.60 6.10 3.14 650 3.07 7.07 11.17 41006 0.69 7.07 3.41 700 3.52 8.11 12.03 44161 0.80 8.11 3.67 750 4.00 9.21 12.89 47315 0.91 9.21 3.93 800 4.51 10.38 13.75 50469 1.02 10.38 4.19 850 5.05 11.61 14.61 53624 1.14 11.61 4.45 900 5.61 12.91 15.47 56778 1.27 12.91 4.72 950 6.20 14.27 16.33 59932 1.40 14.27 4.98 1000 6.82 15.69 17.19 63087 1.54 15.69 5.24 1050 7.46 17.17 18.05 66241 1.69 17.17 5.50 1100 8.13 18.71 18.91 69395 1.84 18.71 5.76 1150 8.83 20.32 19.77 72550 2.00 20.32 6.02 U.S. customary units in this document are the standard; the metric units are provided for reference only. The values stated in each system are not exact equivalents. AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 55//1144//0022 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 77 5" TYPE “M” COPPER TUBE — WATER FLOW AND FRICTION LOSS PER 100 FEET Maximum O.D. = 5.1270 inches (130.2258 mm) Nominal O.D. = 5.1250 inches (130.175 mm) Minimum O.D. = 5.1230 inches (130.1242 mm) Nominal I.D. = 4.9070 inches (124.6378 mm) Nominal Wall Thickness = 0.1090 inches (2.7686 mm) Flow Area = 18.9113 sq. inches (12200.83 sq. mm) Hazen Williams Formula C Factor = 150 FLOW, Q Pressure Loss Head Loss Velocity FLOW, Q Pressure Loss Head Loss Velocity (GPM) (psi/100 ft) (ft/100 ft) (ft./sec.) (cu. cm/sec.) (kPa/100 m) (m/100 m) (m/sec.) 50 0.03 0.06 0.85 3154 0.01 0.06 0.26 100 0.09 0.21 1.70 6309 0.02 0.21 0.52 150 0.20 0.45 2.54 9463 0.04 0.45 0.78 200 0.34 0.77 3.39 12617 0.08 0.77 1.03 250 0.51 1.17 4.24 15772 0.11 1.17 1.29 300 0.71 1.64 5.09 18926 0.16 1.64 1.55 350 0.95 2.18 5.94 22080 0.21 2.18 1.81 400 1.21 2.79 6.79 25235 0.27 2.79 2.07 450 1.51 3.47 7.63 28389 0.34 3.47 2.33 500 1.83 4.22 8.48 31543 0.41 4.22 2.59 550 2.18 5.03 9.33 34698 0.49 5.03 2.84 600 2.56 5.91 10.18 37852 0.58 5.91 3.10 650 2.97 6.85 11.03 41006 0.67 6.85 3.36 700 3.41 7.86 11.88 44161 0.77 7.86 3.62 750 3.88 8.93 12.72 47315 0.88 8.93 3.88 800 4.37 10.06 13.57 50469 0.99 10.06 4.14 850 4.89 11.25 14.42 53624 1.11 11.25 4.40 900 5.43 12.51 15.27 56778 1.23 12.51 4.65 950 6.01 13.82 16.12 59932 1.36 13.82 4.91 1000 6.60 15.20 16.97 63087 1.49 15.20 5.17 1050 7.23 16.63 17.81 66241 1.64 16.63 5.43 1100 7.88 18.13 18.66 69395 1.78 18.13 5.69 1150 8.56 19.68 19.51 72550 1.94 19.68 5.95 6" TYPE “K” COPPER TUBE — WATER FLOW AND FRICTION LOSS PER 100 FEET Maximum O.D. = 6.1270 inches (155.6258 mm) Nominal O.D. = 6.1250 inches (155.575 mm) Minimum O.D. = 6.1230 inches (155.5242 mm) Nominal I.D. = 5.7410 inches (145.8214 mm) Nominal Wall Thickness = 0.1920 inches (4.8768 mm) Flow Area = 25.8860 sq. inches (16700.61 sq. mm) Hazen Williams Formula C Factor = 150 FLOW, Q Pressure Loss Head Loss Velocity FLOW, Q Pressure Loss Head Loss Velocity (GPM) (psi/100 ft) (ft/100 ft) (ft./sec.) (cu. cm/sec.) (kPa/100 m) (m/100 m) (m/sec.) 100 0.04 0.10 1.24 6309 0.01 0.10 0.38 200 0.16 0.36 2.48 12617 0.04 0.36 0.76 300 0.33 0.76 3.72 18926 0.07 0.76 1.13 400 0.56 1.30 4.96 25235 0.13 1.30 1.51 500 0.85 1.96 6.20 31543 0.19 1.96 1.89 600 1.19 2.75 7.44 37852 0.27 2.75 2.27 700 1.59 3.66 8.68 44161 0.36 3.66 2.64 800 2.04 4.69 9.92 50469 0.46 4.69 3.02 900 2.53 5.83 11.15 56778 0.57 5.83 3.40 1000 3.08 7.08 12.39 63087 0.70 7.08 3.78 1100 3.67 8.45 13.63 69395 0.83 8.45 4.16 1200 4.31 9.92 14.87 75704 0.98 9.92 4.53 1300 5.00 11.50 16.11 82013 1.13 11.50 4.91 1400 5.74 13.19 17.35 88321 1.30 13.19 5.29 1500 6.52 14.99 18.59 94630 1.47 14.99 5.67 1600 7.35 16.89 19.83 100939 1.66 16.89 6.04 1700 8.22 18.90 21.07 107247 1.86 18.90 6.42 1800 9.14 21.00 22.31 113556 2.07 21.00 6.80 U.S. customary units in this document are the standard; the metric units are provided for reference only. The values stated in each system are not exact equivalents. AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 55//1144//0022 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 78 6" TYPE “L” COPPER TUBE — WATER FLOW AND FRICTION LOSS PER 100 FEET Maximum O.D. = 6.1270 inches (155.6258 mm) Nominal O.D. = 6.1250 inches (155.575 mm) Minimum O.D. = 6.1230 inches (155.5242 mm) Nominal I.D. = 5.8450 inches (148.463 mm) Nominal Wall Thickness = 0.1400 inches (3.556 mm) Flow Area = 26.8324 sq. inches (17311.17 sq. mm) Hazen Williams Formula C Factor = 150 FLOW, Q Pressure Loss Head Loss Velocity FLOW, Q Pressure Loss Head Loss Velocity (GPM) (psi/100 ft) (ft/100 ft) (ft./sec.) (cu. cm/sec.) (kPa/100 m) (m/100 m) (m/sec.) 100 0.04 0.09 1.20 6309 0.01 0.09 0.36 200 0.14 0.33 2.39 12617 0.03 0.33 0.73 300 0.30 0.70 3.59 18926 0.07 0.70 1.09 400 0.52 1.19 4.78 25235 0.12 1.19 1.46 500 0.78 1.80 5.98 31543 0.18 1.80 1.82 600 1.09 2.52 7.17 37852 0.25 2.52 2.19 700 1.46 3.35 8.37 44161 0.33 3.35 2.55 800 1.87 4.29 9.57 50469 0.42 4.29 2.92 900 2.32 5.34 10.76 56778 0.52 5.34 3.28 1000 2.82 6.49 11.96 63087 0.64 6.49 3.64 1100 3.36 7.74 13.15 69395 0.76 7.74 4.01 1200 3.95 9.09 14.35 75704 0.89 9.09 4.37 1300 4.58 10.54 15.54 82013 1.04 10.54 4.74 1400 5.26 12.09 16.74 88321 1.19 12.09 5.10 1500 5.98 13.74 17.94 94630 1.35 13.74 5.47 1600 6.73 15.48 19.13 100939 1.52 15.48 5.83 1700 7.53 17.32 20.33 107247 1.70 17.32 6.20 1800 8.38 19.25 21.52 113556 1.89 19.25 6.56 6" TYPE “M” COPPER TUBE — WATER FLOW AND FRICTION LOSS PER 100 FEET Maximum O.D. = 6.1270 inches (155.6258 mm) Nominal O.D. = 6.1250 inches (155.575 mm) Minimum O.D. = 6.1230 inches (155.5242 mm) Nominal I.D. = 5.8810 inches (149.3774 mm) Nominal Wall Thickness = 0.1220 inches (3.0988 mm) Flow Area = 27.1639 sq. inches (17525.07 sq. mm) Hazen Williams Formula C Factor = 150 FLOW, Q Pressure Loss Head Loss Velocity FLOW, Q Pressure Loss Head Loss Velocity (GPM) (psi/100 ft) (ft/100 ft) (ft./sec.) (cu. cm/sec.) (kPa/100 m) (m/100 m) (m/sec.) 100 0.04 0.09 1.18 6309 0.01 0.09 0.36 200 0.14 0.32 2.36 12617 0.03 0.32 0.72 300 0.29 0.68 3.54 18926 0.07 0.68 1.08 400 0.50 1.16 4.72 25235 0.11 1.16 1.44 500 0.76 1.75 5.91 31543 0.17 1.75 1.80 600 1.06 2.45 7.09 37852 0.24 2.45 2.16 700 1.41 3.26 8.27 44161 0.32 3.26 2.52 800 1.81 4.17 9.45 50469 0.41 4.17 2.88 900 2.25 5.18 10.63 56778 0.51 5.18 3.24 1000 2.74 6.30 11.81 63087 0.62 6.30 3.60 1100 3.27 7.51 12.99 69395 0.74 7.51 3.96 1200 3.84 8.82 14.17 75704 0.87 8.82 4.32 1300 4.45 10.23 15.35 82013 1.01 10.23 4.68 1400 5.10 11.74 16.54 88321 1.15 11.74 5.04 1500 5.80 13.33 17.72 94630 1.31 13.33 5.40 1600 6.54 15.02 18.90 100939 1.48 15.02 5.76 1700 7.31 16.81 20.08 107247 1.65 16.81 6.12 1800 8.13 18.68 21.26 113556 1.84 18.68 6.48 U.S. customary units in this document are the standard; the metric units are provided for reference only. The values stated in each system are not exact equivalents. AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 55//1144//0022 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 79 8" TYPE “K” COPPER TUBE — WATER FLOW AND FRICTION LOSS PER 100 FEET Maximum O.D. = 8.1270 inches (206.4258 mm) Nominal O.D. = 8.1240 inches (206.3496 mm) Minimum O.D. = 8.1210 inches (206.2734 mm) Nominal I.D. = 7.5820 inches (192.5828 mm) Nominal Wall Thickness = 0.2710 inches (6.8834 mm) Flow Area = 45.1500 sq. inches (29128.95 sq. mm) Hazen Williams Formula C Factor = 150 FLOW, Q Pressure Loss Head Loss Velocity FLOW, Q Pressure Loss Head Loss Velocity (GPM) (psi/100 ft) (ft/100 ft) (ft./sec.) (cu. cm/sec.) (kPa/100 m) (m/100 m) (m/sec.) 200 0.04 0.09 1.42 12617 0.01 0.09 0.43 400 0.15 0.34 2.84 25235 0.03 0.34 0.87 600 0.31 0.71 4.26 37852 0.07 0.71 1.30 800 0.53 1.21 5.68 50469 0.12 1.21 1.73 1000 0.80 1.83 7.11 63087 0.18 1.83 2.17 1200 1.11 2.56 8.53 75704 0.25 2.56 2.60 1400 1.48 3.41 9.95 88321 0.34 3.41 3.03 1600 1.90 4.36 11.37 100939 0.43 4.36 3.47 1800 2.36 5.43 12.79 113556 0.53 5.43 3.90 2000 2.87 6.60 14.21 126173 0.65 6.60 4.33 2200 3.42 7.87 15.63 138791 0.77 7.87 4.76 2400 4.02 9.24 17.05 151408 0.91 9.24 5.20 2600 4.67 10.72 18.48 164025 1.06 10.72 5.63 2800 5.35 12.29 19.90 176643 1.21 12.29 6.06 3000 6.08 13.96 21.32 189260 1.38 13.96 6.50 3200 6.85 15.73 22.74 201877 1.55 15.73 6.93 3400 7.67 17.60 24.16 214495 1.73 17.60 7.36 3600 8.53 19.57 25.58 227112 1.93 19.57 7.80 3800 9.42 21.62 27.00 239729 2.13 21.62 8.23 4000 10.36 23.78 28.42 252347 2.34 23.78 8.66 8" TYPE “L” COPPER TUBE — WATER FLOW AND FRICTION LOSS PER 100 FEET Maximum O.D. = 8.1270 inches (206.4258 mm) Nominal O.D. = 8.1240 inches (206.3496 mm) Minimum O.D. = 8.1210 inches (206.2734 mm) Nominal I.D. = 7.7240 inches (196.1896 mm) Nominal Wall Thickness = 0.2000 inches (5.080 mm) Flow Area = 46.8570 sq. inches (30230.26 sq. mm) Hazen Williams Formula C Factor = 150 FLOW, Q Pressure Loss Head Loss Velocity FLOW, Q Pressure Loss Head Loss Velocity (GPM) (psi/100 ft) (ft/100 ft) (ft./sec.) (cu. cm/sec.) (kPa/100 m) (m/100 m) (m/sec.) 200 0.04 0.09 1.37 12617 0.01 0.09 0.42 400 0.13 0.31 2.74 25235 0.03 0.31 0.83 600 0.28 0.65 4.11 37852 0.06 0.65 1.25 800 0.48 1.11 5.48 50469 0.11 1.11 1.67 1000 0.73 1.67 6.85 63087 0.16 1.67 2.09 1200 1.02 2.34 8.22 75704 0.23 2.34 2.50 1400 1.35 3.12 9.59 88321 0.31 3.12 2.92 1600 1.73 3.99 10.96 100939 0.39 3.99 3.34 1800 2.16 4.96 12.32 113556 0.49 4.96 3.76 2000 2.62 6.03 13.69 126173 0.59 6.03 4.17 2200 3.13 7.19 15.06 138791 0.71 7.19 4.59 2400 3.68 8.44 16.43 151408 0.83 8.44 5.01 2600 4.26 9.79 17.80 164025 0.96 9.79 5.43 2800 4.89 11.23 19.17 176643 1.11 11.23 5.84 3000 5.56 12.76 20.54 189260 1.26 12.76 6.26 3200 6.26 14.38 21.91 201877 1.42 14.38 6.68 3400 7.01 16.08 23.28 214495 1.58 16.08 7.10 3600 7.79 17.88 24.65 227112 1.76 17.88 7.51 3800 8.61 19.76 26.02 239729 1.95 19.76 7.93 4000 9.47 21.72 27.39 252347 2.14 21.72 8.35 U.S. customary units in this document are the standard; the metric units are provided for reference only. The values stated in each system are not exact equivalents. AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 55//1144//0022 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 80 8" TYPE “M” COPPER TUBE — WATER FLOW AND FRICTION LOSS PER 100 FEET Maximum O.D. = 8.1270 inches (206.4258 mm) Nominal O.D. = 8.1240 inches (206.3496 mm) Minimum O.D. = 8.1210 inches (206.2734 mm) Nominal I.D. = 7.7840 inches (197.7136 mm) Nominal Wall Thickness = 0.1700 inches (4.3180 mm) Flow Area = 47.5878 sq. inches (30701.74 sq. mm) Hazen Williams Formula C Factor = 150 FLOW, Q Pressure Loss Head Loss Velocity FLOW, Q Pressure Loss Head Loss Velocity (GPM) (psi/100 ft) (ft/100 ft) (ft./sec.) (cu. cm/sec.) (kPa/100 m) (m/100 m) (m/sec.) 200 0.04 0.08 1.35 12617 0.01 0.08 0.41 400 0.13 0.30 2.70 25235 0.03 0.30 0.82 600 0.27 0.63 4.05 37852 0.06 0.63 1.23 800 0.46 1.07 5.39 50469 0.10 1.07 1.64 1000 0.70 1.61 6.74 63087 0.16 1.61 2.05 1200 0.98 2.26 8.09 75704 0.22 2.26 2.47 1400 1.30 3.00 9.44 88321 0.30 3.00 2.88 1600 1.67 3.84 10.79 100939 0.38 3.84 3.29 1800 2.08 4.78 12.14 113556 0.47 4.78 3.70 2000 2.53 5.80 13.48 126173 0.57 5.80 4.11 2200 3.01 6.92 14.83 138791 0.68 6.92 4.52 2400 3.54 8.13 16.18 151408 0.80 8.13 4.93 2600 4.11 9.43 17.53 164025 0.93 9.43 5.34 2800 4.71 10.81 18.88 176643 1.07 10.81 5.75 3000 5.35 12.29 20.23 189260 1.21 12.29 6.16 3200 6.03 13.85 21.57 201877 1.36 13.85 6.58 3400 6.75 15.49 22.92 214495 1.53 15.49 6.99 3600 7.50 17.22 24.27 227112 1.70 17.22 7.40 3800 8.29 19.03 25.62 239729 1.88 19.03 7.81 4000 9.12 20.92 26.97 252347 2.06 20.92 8.22 10" TYPE “K” COPPER TUBE — WATER FLOW AND FRICTION LOSS PER 100 FEET Maximum O.D. = 10.1270 inches (257.2258 mm) Nominal O.D. = 10.1230 inches (257.1242 mm) Minimum O.D. = 10.1190 inches (257.0226 mm) Nominal I.D. = 9.4470 inches (239.9538 mm) Nominal Wall Thickness = 0.3380 inches (8.5852 mm) Flow Area = 70.0935 sq. inches (45221.52 sq. mm) Hazen Williams Formula C Factor = 150 FLOW, Q Pressure Loss Head Loss Velocity FLOW, Q Pressure Loss Head Loss Velocity (GPM) (psi/100 ft) (ft/100 ft) (ft./sec.) (cu. cm/sec.) (kPa/100 m) (m/100 m) (m/sec.) 200 0.01 0.03 0.92 12617 0.00 0.03 0.28 400 0.05 0.12 1.83 25235 0.01 0.12 0.56 600 0.11 0.24 2.75 37852 0.02 0.24 0.84 800 0.18 0.42 3.66 50469 0.04 0.42 1.12 1000 0.27 0.63 4.58 63087 0.06 0.63 1.40 1200 0.38 0.88 5.49 75704 0.09 0.88 1.67 1400 0.51 1.17 6.41 88321 0.12 1.17 1.95 1600 0.65 1.50 7.32 100939 0.15 1.50 2.23 1800 0.81 1.86 8.24 113556 0.18 1.86 2.51 2000 0.98 2.26 9.15 126173 0.22 2.26 2.79 2200 1.17 2.70 10.07 138791 0.27 2.70 3.07 2400 1.38 3.17 10.99 151408 0.31 3.17 3.35 2600 1.60 3.68 11.90 164025 0.36 3.68 3.63 2800 1.84 4.22 12.82 176643 0.42 4.22 3.91 3000 2.09 4.79 13.73 189260 0.47 4.79 4.19 3200 2.35 5.40 14.65 201877 0.53 5.40 4.46 3400 2.63 6.04 15.56 214495 0.60 6.04 4.74 3600 2.92 6.71 16.48 227112 0.66 6.71 5.02 3800 3.23 7.42 17.39 239729 0.73 7.42 5.30 4000 3.55 8.16 18.31 252347 0.80 8.16 5.58 4200 3.89 8.93 19.22 264964 0.88 8.93 5.86 4400 4.24 9.73 20.14 277581 0.96 9.73 6.14 U.S. customary units in this document are the standard; the metric units are provided for reference only. The values stated in each system are not exact equivalents. AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 55//1144//0022 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 81 10" TYPE “L” COPPER TUBE — WATER FLOW AND FRICTION LOSS PER 100 FEET Maximum O.D. = 10.1270 inches (257.2258 mm) Nominal O.D. = 10.1230 inches (257.1242 mm) Minimum O.D. = 10.1190 inches (257.0226 mm) Nominal I.D. = 9.6230 inches (244.4242 mm) Nominal Wall Thickness = 0.2500 inches (6.3500 mm) Flow Area = 72.7295 sq. inches (46922.19 sq. mm) Hazen Williams Formula C Factor = 150 FLOW, Q Pressure Loss Head Loss Velocity FLOW, Q Pressure Loss Head Loss Velocity (GPM) (psi/100 ft) (ft/100 ft) (ft./sec.) (cu. cm/sec.) (kPa/100 m) (m/100 m) (m/sec.) 200 0.01 0.03 0.88 12617.33 0.00 0.03 0.27 400 0.05 0.11 1.76 25234.67 0.01 0.11 0.54 600 0.10 0.22 2.65 37852.00 0.02 0.22 0.81 800 0.16 0.38 3.53 50469.33 0.04 0.38 1.08 1000 0.25 0.57 4.41 63086.67 0.06 0.57 1.34 1200 0.35 0.80 5.29 75704.00 0.08 0.80 1.61 1400 0.46 1.07 6.18 88321.33 0.11 1.07 1.88 1600 0.60 1.37 7.06 100938.67 0.13 1.37 2.15 1800 0.74 1.70 7.94 113556.00 0.17 1.70 2.42 2000 0.90 2.07 8.82 126173.33 0.20 2.07 2.69 2200 1.07 2.47 9.70 138790.67 0.24 2.47 2.96 2400 1.26 2.90 10.59 151408.00 0.29 2.90 3.23 2600 1.46 3.36 11.47 164025.33 0.33 3.36 3.50 2800 1.68 3.85 12.35 176642.67 0.38 3.85 3.76 3000 1.91 4.38 13.23 189260.00 0.43 4.38 4.03 3200 2.15 4.93 14.12 201877.33 0.49 4.93 4.30 3400 2.40 5.52 15.00 214494.67 0.54 5.52 4.57 3600 2.67 6.13 15.88 227112.00 0.60 6.13 4.84 3800 2.95 6.78 16.76 239729.33 0.67 6.78 5.11 4000 3.25 7.45 17.65 252346.67 0.73 7.45 5.38 4200 3.56 8.16 18.53 264964.00 0.80 8.16 5.65 4400 3.88 8.89 19.41 277581.33 0.88 8.89 5.92 10" TYPE “M” COPPER TUBE — WATER FLOW AND FRICTION LOSS PER 100 FEET Maximum O.D. = 10.1270 inches (257.2258 mm) Nominal O.D. = 10.1230 inches (257.1242 mm) Minimum O.D. = 10.1190 inches (257.0226 mm) Nominal I.D. = 9.6990 inches (247.3546 mm) Nominal Wall Thickness = 0.2120 inches (5.3848 mm) Flow Area = 73.8829 sq. inches (47666.28 sq. mm) Hazen Williams Formula C Factor = 150 FLOW, Q Pressure Loss Head Loss Velocity FLOW, Q Pressure Loss Head Loss Velocity (GPM) (psi/100 ft) (ft/100 ft) (ft./sec.) (cu. cm/sec.) (kPa/100 m) (m/100 m) (m/sec.) 200 0.01 0.03 0.87 12617 0.00 0.03 0.26 400 0.04 0.10 1.74 25235 0.01 0.10 0.53 600 0.09 0.21 2.61 37852 0.02 0.21 0.79 800 0.16 0.37 3.47 50469 0.04 0.37 1.06 1000 0.24 0.55 4.34 63087 0.05 0.55 1.32 1200 0.34 0.77 5.21 75704 0.08 0.77 1.59 1400 0.45 1.03 6.08 88321 0.10 1.03 1.85 1600 0.57 1.32 6.95 100939 0.13 1.32 2.12 1800 0.71 1.64 7.82 113556 0.16 1.64 2.38 2000 0.87 1.99 8.68 126173 0.20 1.99 2.65 2200 1.03 2.37 9.55 138791 0.23 2.37 2.91 2400 1.21 2.79 10.42 151408 0.27 2.79 3.18 2600 1.41 3.23 11.29 164025 0.32 3.23 3.44 2800 1.62 3.71 12.16 176643 0.37 3.71 3.71 3000 1.84 4.21 13.03 189260 0.42 4.21 3.97 3200 2.07 4.75 13.90 201877 0.47 4.75 4.24 3400 2.31 5.31 14.76 214495 0.52 5.31 4.50 3600 2.57 5.90 15.63 227112 0.58 5.90 4.76 3800 2.84 6.53 16.50 239729 0.64 6.53 5.03 4000 3.13 7.17 17.37 252347 0.71 7.17 5.29 4200 3.42 7.85 18.24 264964 0.77 7.85 5.56 4400 3.73 8.56 19.11 277581 0.84 8.56 5.82 U.S. customary units in this document are the standard; the metric units are provided for reference only. The values stated in each system are not exact equivalents. AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 55//1144//0022 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 82 12" TYPE “K” COPPER TUBE — WATER FLOW AND FRICTION LOSS PER 100 FEET Maximum O.D. = 12.1270 inches (308.0258 mm) Nominal O.D. = 12.1230 inches (307.9242 mm) Minimum O.D. = 12.1190 inches (307.8226 mm) Nominal I.D. = 11.3130 inches (287.3502 mm) Nominal Wall Thickness = 0.4050 inches (10.2870 mm) Flow Area = 100.5184 sq. inches (64850.43 sq. mm) Hazen Williams Formula C Factor = 150 FLOW, Q Pressure Loss Head Loss Velocity FLOW, Q Pressure Loss Head Loss Velocity (GPM) (psi/100 ft) (ft/100 ft) (ft./sec.) (cu. cm/sec.) (kPa/100 m) (m/100 m) (m/sec.) 1000 0.11 0.26 3.19 63087 0.03 0.26 0.97 1200 0.16 0.37 3.83 75704 0.04 0.37 1.17 1400 0.21 0.49 4.47 88321 0.05 0.49 1.36 1600 0.27 0.62 5.11 100939 0.06 0.62 1.56 1800 0.34 0.77 5.75 113556 0.08 0.77 1.75 2000 0.41 0.94 6.38 126173 0.09 0.94 1.95 2200 0.49 1.12 7.02 138791 0.11 1.12 2.14 2400 0.57 1.32 7.66 151408 0.13 1.32 2.33 2600 0.67 1.53 8.30 164025 0.15 1.53 2.53 2800 0.76 1.75 8.94 176643 0.17 1.75 2.72 3000 0.87 1.99 9.58 189260 0.20 1.99 2.92 3200 0.98 2.25 10.21 201877 0.22 2.25 3.11 3400 1.09 2.51 10.85 214495 0.25 2.51 3.31 3600 1.22 2.79 11.49 227112 0.28 2.79 3.50 3800 1.34 3.09 12.13 239729 0.30 3.09 3.70 4000 1.48 3.39 12.77 252347 0.33 3.39 3.89 4200 1.62 3.71 13.41 264964 0.37 3.71 4.09 4400 1.76 4.05 14.04 277581 0.40 4.05 4.28 4600 1.92 4.39 14.68 290199 0.43 4.39 4.48 4800 2.07 4.75 15.32 302816 0.47 4.75 4.67 5000 2.24 5.13 15.96 315433 0.51 5.13 4.86 5200 2.40 5.51 16.60 328051 0.54 5.51 5.06 5400 2.58 5.91 17.24 340668 0.58 5.91 5.25 5600 2.76 6.32 17.87 353285 0.62 6.32 5.45 5800 2.94 6.75 18.51 365903 0.67 6.75 5.64 6000 3.13 7.18 19.15 378520 0.71 7.18 5.84 6200 3.33 7.63 19.79 391137 0.75 7.63 6.03 12" TYPE “L” COPPER TUBE — WATER FLOW AND FRICTION LOSS PER 100 FEET Maximum O.D. = 12.1270 inches (308.0258 mm) Nominal O.D. = 12.1230 inches (307.9242 mm) Minimum O.D. = 12.1190 inches (307.8226 mm) Nominal I.D. = 11.5630 inches (293.7002 mm) Nominal Wall Thickness = 0.2800 inches (7.1120 mm) Flow Area = 105.0101 sq. inches (67748.29 sq. mm) Hazen Williams Formula C Factor = 150 FLOW, Q Pressure Loss Head Loss Velocity FLOW, Q Pressure Loss Head Loss Velocity (GPM) (psi/100 ft) (ft/100 ft) (ft./sec.) (cu. cm/sec.) (kPa/100 m) (m/100 m) (m/sec.) 1000 0.10 0.23 3.06 63087 0.02 0.23 0.93 1200 0.14 0.33 3.67 75704 0.03 0.33 1.12 1400 0.19 0.44 4.28 88321 0.04 0.44 1.30 1600 0.24 0.56 4.89 100939 0.06 0.56 1.49 1800 0.30 0.70 5.50 113556 0.07 0.70 1.68 2000 0.37 0.85 6.11 126173 0.08 0.85 1.86 2200 0.44 1.01 6.72 138791 0.10 1.01 2.05 2400 0.52 1.19 7.33 151408 0.12 1.19 2.23 2600 0.60 1.37 7.94 164025 0.14 1.37 2.42 2800 0.69 1.58 8.55 176643 0.16 1.58 2.61 3000 0.78 1.79 9.17 189260 0.18 1.79 2.79 3200 0.88 2.02 9.78 201877 0.20 2.02 2.98 3400 0.98 2.26 10.39 214495 0.22 2.26 3.17 3600 1.09 2.51 11.00 227112 0.25 2.51 3.35 3800 1.21 2.77 11.61 239729 0.27 2.77 3.54 4000 1.33 3.05 12.22 252347 0.30 3.05 3.72 4200 1.46 3.34 12.83 264964 0.33 3.34 3.91 4400 1.59 3.64 13.44 277581 0.36 3.64 4.10 4600 1.72 3.95 14.05 290199 0.39 3.95 4.28 4800 1.86 4.27 14.67 302816 0.42 4.27 4.47 5000 2.01 4.61 15.28 315433 0.45 4.61 4.66 5200 2.16 4.96 15.89 328051 0.49 4.96 4.84 5400 2.32 5.31 16.50 340668 0.52 5.31 5.03 5600 2.48 5.68 17.11 353285 0.56 5.68 5.21 5800 2.65 6.07 17.72 365903 0.60 6.07 5.40 6000 2.82 6.46 18.33 378520 0.64 6.46 5.59 6200 2.99 6.86 18.94 391137 0.68 6.86 5.77 U.S. customary units in this document are the standard; the metric units are provided for reference only. The values stated in each system are not exact equivalents. AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 55//1144//0022 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 83 12" TYPE “M” COPPER TUBE — WATER FLOW AND FRICTION LOSS PER 100 FEET Maximum O.D. = 12.1270 inches (308.0258 mm) Nominal O.D. = 12.1230 inches (307.9242 mm) Minimum O.D. = 12.1190 inches (307.8226 mm) Nominal I.D. = 11.6150 inches (295.021 mm) Nominal Wall Thickness = 0.2540 inches (6.4516 mm) Flow Area = 105.9567 sq. inches (68359.01 sq. mm) Hazen Williams Formula C Factor = 150 FLOW, Q Pressure Loss Head Loss Velocity FLOW, Q Pressure Loss Head Loss Velocity (GPM) (psi/100 ft) (ft/100 ft) (ft./sec.) (cu. cm/sec.) (kPa/100 m) (m/100 m) (m/sec.) 1000 0.10 0.23 3.03 63087 0.02 0.23 0.92 1200 0.14 0.32 3.63 75704 0.03 0.32 1.11 1400 0.19 0.43 4.24 88321 0.04 0.43 1.29 1600 0.24 0.55 4.84 100939 0.05 0.55 1.48 1800 0.30 0.68 5.45 113556 0.07 0.68 1.66 2000 0.36 0.83 6.06 126173 0.08 0.83 1.85 2200 0.43 0.99 6.66 138791 0.10 0.99 2.03 2400 0.51 1.16 7.27 151408 0.11 1.16 2.22 2600 0.59 1.35 7.87 164025 0.13 1.35 2.40 2800 0.67 1.54 8.48 176643 0.15 1.54 2.58 3000 0.76 1.75 9.08 189260 0.17 1.75 2.77 3200 0.86 1.98 9.69 201877 0.19 1.98 2.95 3400 0.96 2.21 10.30 214495 0.22 2.21 3.14 3600 1.07 2.46 10.90 227112 0.24 2.46 3.32 3800 1.18 2.71 11.51 239729 0.27 2.71 3.51 4000 1.30 2.98 12.11 252347 0.29 2.98 3.69 4200 1.42 3.27 12.72 264964 0.32 3.27 3.88 4400 1.55 3.56 13.32 277581 0.35 3.56 4.06 4600 1.68 3.87 13.93 290199 0.38 3.87 4.25 4800 1.82 4.18 14.53 302816 0.41 4.18 4.43 5000 1.97 4.51 15.14 315433 0.44 4.51 4.61 5200 2.11 4.85 15.75 328051 0.48 4.85 4.80 5400 2.27 5.20 16.35 340668 0.51 5.20 4.98 5600 2.43 5.56 16.96 353285 0.55 5.56 5.17 5800 2.59 5.93 17.56 365903 0.59 5.93 5.35 6000 2.76 6.32 18.17 378520 0.62 6.32 5.54 6200 2.93 6.71 18.77 391137 0.66 6.71 5.72 U.S. customary units in this document are the standard; the metric units are provided for reference only. The values stated in each system are not exact equivalents. AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 55//1144//0022 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 84 Copper Water Tube continued COPPER TUBE – TYPES, STANDARDS, APPLICATIONS, TEMPERS AND LENGTHS Commercially Available Lengths Tube Type Color Code Standard Application Nominal or Standard Sizes Drawn Annealed Type K Green ASTM B 88 Domestic Water Service Distribution Straight Lengths:1/4-inch to 8-inch 20 ft. (6.1m) 20 ft. (6.1m) Fire Protection 10-inch 18 ft. (5.5m) 18 ft. (5.5m) Solar 12-inch 12 ft. (3.7m) 12 ft. (3.7m) Fuel/Fuel Oil Coils: 1/4-inch to 1-inch – 60 ft. (18.3m) HVAC – 100 ft. (30.5m) Snow Melting 1 1/4-inch & 11/2-inch – 60 ft. (18.3m) 2-inch – 40 ft. (12.2m) – 45 ft. (13.7m) Type L Blue ASTM B 88 Domestic Water Service Distribution Straight Lengths: 1/4-inch to 10-inch 20 ft. (6.1m) 20 ft. (6.1m) Fire Protection 12-inch 18 ft. (5.5m) 18 ft. (5.5m) Solar Fuel/Fuel Oil Natural Gas Coils: 1/4-inch to 1-inch – 60 ft. (18.3m) Liquified Petroleum (LP) Gas – 100 ft. (30.5m) HVAC 1 1/4-inch & 11/2-inch – 60 ft. (18.3m) Snow Melting 2-inch – 40 ft. (12.2m) – 45 ft. (13.7m) Type M Red ASTM B 88 Domestic Water Service Distribution Straight Lengths: 1/4-inch to 12-inch 20 ft. (6.1m) N/A Fire Protection Solar Fuel/Fuel Oil HVAC Snow Melting DWV Yellow ASTM B 306 Drain Straight Lengths: 1 1/4-inch to 8-inch 20 ft. (6.1m) N/A Waste Vent HVAC Solar ACR Blue ASTM B 280 Air Conditioning Straight Lengths: 1/4-inch to 41/8-inch 20 ft. (6.1m) 20 ft. (6.1m) 1 Refrigeration Natural Gas Coils: 1/8-inch to 15/8-inch – 50 ft. (15.3m) 1 Liquified Petroleum (LP) Gas OXY Type K ASTM B 819 Medical Gas Straight Lengths: 1/4-inch to 8-inch 20 ft. (6.1m) N/A MED Green OXY/MED OXY/ACR Type L ACR/MED Blue Type G Yellow ASTM B 837 Natural Gas Straight Lengths: 3/8-inch to 11/8-inch 12 ft. (3.7m) 12 ft. (3.7m) 1 Liquified Petroleum (LP) Gas 20 ft. (6.1m) 20 ft. (6.1m) 1 Coils:3/8-inch to 7/8-inch – 60 ft. (18.3m) 1 – 100 ft. (30.5m) 1 1Available as special order only. U.S. customary units in this document are the standard; the metric units are provided for reference only. The values stated in each system are not exact equivalents. The Fine Art of Soldering AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 55//1144//0022 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 85 1. Cut tube end square, ream, burr and size. When adjoining surfaces of copper and copper alloys meet under proper conditions of cleanliness and temperature, solder will make a perfect adhesion. The strength of joint is equal to or even greater than the strength of tube alone. Surface tension seals the joint. Capillary attraction draws solder into, around, and all about the joint. It’s easy to learn to make a perfect solder joint when you use NIBCO Fittings. WITH 95-5 SOLDER AND INTERMEDIATELY CORROSIVE FLUX 6. Remove excess solder with a small brush or wiping cloth while the solder is plastic. 2. Use sand cloth or steel wire brush to clean tube and cup to a bright metal finish. 3. Apply solder flux to outside of tube and inside of cup of fitting carefully so that surfaces to be joined are completely covered. Use flux sparingly. 4. Apply flame to the fitting to heat tube and solder cup of fitting until solder melts when placed at joint of tube and fitting. 5. Remove flame and feed solder into the joint at one or two points until a ring of solder appears at the end of the fitting. The correct amount of solder is approximately equal to 11/2 the diameter of the fitting… 3/4" (20mm) solder for 1/2" fitting, etc. 1. The tube should be cut to desired length with a square cut, preferably in a square-end sawing vise. The cutting wheel of the type specifically designed for cutting copper tube will also do a satisfactory job. The tube should be the exact length needed, so that the tube will enter the cup of the fitting all the way to the shoulder of the cup. Remove all slivers and burrs left from cutting the tube, by reaming and filing, both inside and outside. 2. To make a proper brazing joint, the clearance between the solder cup and the tube should be approximately 0.001" to 0.010" (0.0254mm to 0.254mm). Maintaining a good fit on parts to be brazed insures: Ease of Application — Excessively wide tolerances tend to break capillary force; and, as a result the alloy will either fail to flow throughout the joint or may flush out of the joint. Corrosion Resistance — There is also a direct relation between the corrosion resistance of a joint and the clearance between members. Economy — If brazing alloys are to be used economically, they, of necessity, must be applied in the joint proper and in minimum quantities, using merely enough alloy to fill the area between the members. 3. The surfaces to be joined must be clean and free from oil, grease and heavy oxides. The end of the tube need be cleaned only for a distance slightly more than it is to enter the cup. Special wire brushes designed to clean tube ends may be used, but they should be carefully used so that an excessive amount of metal will not be removed from the tube. Fine sand cloth or emery cloth may also be used with the same precautions. The cleaning should not be done with steel wool, because of the likelihood of leaving small slivers of the steel or oil in the joint. 4. The cup of the fitting should be cleaned by methods similar to those used for the tube end, and care should be observed in removing residues of the cleaning medium. Attempting to braze a contaminated or an improperly cleaned surface will result in an unsatisfactory joint. Brazing alloys will not flow over or bond to oxides; and oily or greasy surfaces tend to repel fluxes, leaving bare spots which will oxidize, resulting in voids and inclusions. 5. Flux should be applied to the tube and solder cup sparingly and in a fairly thin consistency. Avoid flux on areas not cleaned. Particularly avoid getting excess flux into the inside of the tube itself. Flux has three principal functions to perform: A. It prevents the oxidation of the metal surfaces during the heating operation by excluding oxygen. B. It absorbs and dissolves residual oxides that are on the surface and those oxides which may form during the heating operation. C. It assists in the flow of the alloy by presenting a clean nascent surface for the melted alloy to flow over. In addition, it is an excellent temperature indicator, especially if an indicating flux is used. 6. Immediately after fluxing, the parts to be brazed should be assembled. If fluxed parts are allowed to stand, the water in the flux will evaporate, and dried flux is liable to flake off, exposing the metal surfaces to oxidation from the heat. Assemble the joint by inserting the tube into the cup, hard against the stop. The assembly should be firmly supported so that it will remain in alignment during the brazing operation. AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 55//1144//0022 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 86 The Fine Art of Brazing Best results will be obtained by a skilled operator employing the step-by-step brazing technique that follows: AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 55//1144//0022 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 87 7. Brazing is started by applying heat to the parts to be joined. The preferred method is by the oxyacetylene flame. Propane and other gases are sometimes used on smaller sizes. A slightly reducing flame should be used, with a slight feather on the inner blue cone; the outer portion of the flame, pale green. Heat the tube first, beginning at about one inch from the edge of the fitting. Sweep the flames around the tube in short strokes up and down at right angles to the run of the tube. It is very important that the flame be in continuous motion and should not be allowed to remain on any one point to avoid burning through the tube. Generally, the flux may be used as a guide as to how long to heat the tube, continuing heating after the flux starts to bubble or work, and until the flux becomes quiet and transparent, like clear water. The flux will pass through four stages: A. At 212°F (100°C) the water boils off. B. At 600°F (315.6°C) the flux becomes white and slightly puffy and starts to work. C. At 800°F (426.7°C) it lays against the surface and has a milky appearance. D. At 1100°F (593.3°C) it is completely clear and active and has the appearance of water. 8. Now switch the flame to the fitting at the base of the cup. Heat uniformly, sweeping the flame from the fitting to the tube until the flux on the fitting becomes quiet. Avoid excessive heating of cast fittings. 9. When the flux appears liquid and transparent on both the tube and the fitting, start sweeping the flame back and forth along the axis of the joint to maintain heat on the parts to be joined, especially toward the base of the cup of the fitting. The flame must be kept moving to avoid burning the tube or the fitting. 10. Apply the brazing wire or rod at a point where the tube enters the socket of the fitting. The temperature of the joint should be hot enough to melt the brazing alloy. Keep the flame away from the rod or wire as it is fed into the joint. Keep both the fitting and the tube heated by moving the flame back and forth from one to the other as the alloy is drawn into the joint. When the proper temperature is reached, the alloy will flow readily into the space between the tube outer wall and the fitting socket, drawn in by the natural force of capillary attraction. When the joint is filled, a continuous fillet of brazing alloy will be visible completely around the joint. Stop feeding as soon as the joint is filled, using table on page 54 as a guide for the alloy consumption. NOTE: For tubing one inch and larger, it is difficult to bring the whole joint up to heat at one time. It frequently will be found desirable to use a double-tip torch to maintain the proper temperature over the larger area. A mild pre-heating of the whole fitting is recommended. The heating then can proceed as in steps 7, 8, 9, and 10. If difficulty is encountered in getting the whole joint up to heat at one time, then when the joint is nearly up to the desired temperature the alloy is concentrated in a limited area. At the brazing temperature the alloy is fed into the joint and the torch is then moved to an adjacent area and the operation carried on progressively all around the joint. HORIZONTAL JOINTS — When making horizontal joints, it is preferable to start applying the brazing alloy at the 5 o’clock position, then move around to the 7 o’clock position and then move up the sides to the top of the joint, making sure that the operations overlap. VERTICAL JOINTS — On vertical joints, it is immaterial where the start is made. If the opening of the cup is pointed down, care should be taken to avoid overheating the tube, as this may cause the alloy to run down the tube. If this condition is encountered, take the heat away and allow the alloy to set. Then reheat the solder cup of the fitting to draw up the alloy. After the brazing alloy has set, remove residual flux from the joint area as it is corrosive and presents an unclean appearance and condition. Hot water or steam and a soft cloth should be used. Wrot fittings may be chilled; however it is advisable to allow cast fittings to cool naturally to some extent before applying a swab. All flux must be removed before inspection and pressure testing. TROUBLE SPOTS If the alloy fails to flow or has a tendency to ball up, it indicates oxidation on the metal surfaces, or insufficient heat on the parts to be joined. If work starts to oxidize during heating, it indicates too little flux, or a flux of too thin consistency. If the brazing alloy refuses to enter the joint and tends to flow over the outside of either member of the joint, it indicates this member is overheated, or the other is underheated, or both. In both cases, operations should be stopped and the joints disassembled, recleaned and fluxed. AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 55//1144//0022 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 88 FITTING SYSTEM – INSERT/CRIMP TYPE* Making a Connection Polyethylene (PEX) Tubing *NIBCO recommends the use of copper crimp rings ONLY and a properly calibrated full circle crimping tool for joining PEX tubing and copper barbed fittings. 2. Slide copper crimp ring on tubing. 3. Insert ribbed fitting into tubing until tubing contacts the fitting shoulder (tube stop). Position the crimp ring on the tubing so that the edge of the ring is 1/8" to 1/4" (3 to 6mm) from the end of the tube. 4. Center the crimping tool jaws exactly over the ring while maintaining its position relative to the fitting. Crimp the ring by closing the handles together to the positive stop on the tool. Check the after-crimped diameter of each ring with the crimp gauge. If the small flats on the gauge do not fit over the crimped ring, the ring is under-crimped. Cut out any under-crimped rings and fittings and completely replace. DO NOT RE-CRIMP. 1. Using a tube cutter, cut tubing squarely and remove burrs. AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 55//1144//0022 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 89 FITTING SYSTEM – INSERT/CRIMP TYPE MADE BY NIBCO Making a Connection Polybutylene Tubing TOOLS AND RINGS • Use tools recommended by fitting and tubing manufacturers. All tools must make a full-circle crimp. • Check tool adjustment at least daily, and readjust as necessary. • Use crimp rings of copper as recommended by NIBCO INC. 2. Slide copper crimp ring on tubing. Only copper crimp rings should be used to ensure the highest quality connection. 3. Insert fitting into tubing, then position crimp ring squarely over barbs. Proper alignment is important for making the best connection. 4. Center the crimping tool jaws exactly over the ring, and bring the tool handles together until totally closed to the stop indicator. Check each crimp ring with the caliper gauge after completion. If the small flats on the gauge do not fit over the crimped ring, the ring is undercrimped. Cut out any undercrimped rings and fittings, and completely replace. 1. Using a tube cutter, cut tubing squarely and remove burrs. Frequently Asked Questions Q: What is the pressure rating of a given fitting? A: Fittings are rated per Table 1 of ASME B16.22. The system rated pressure shall be the lowest of the fitting, tube or joint. Q: When copper fails in a system, what is the problem? A: MOST COMMON: 1. Velocity – fluid is moving too fast. Recommendation: 2-3 fps (0.0508-0.0762 m/s) hot water 140°F, 5-8 fps (0.127- 0.2032 m/s) cold water. Refer to pages 68-93. 2. Turbulence – burrs left on the cut tubing causes a tumbling effect causing localized erosion and eventual failure. 3. Aggressive Waters – tend to cause pitting or green staining of fixtures. Aggressive, hard well waters that cause pitting typically are found to have total dissolved solids including suflates and chlorides, a pH in the range of 7.2 to 7.8, a high content of carbon dioxide gas and the pressence of dissolved oxygen gas. Soft acidic waters that cause green staining typically tend to be more corrosive. Low alkalinity, low mineralization, pH levels of 7 or lower should be avoided. LESS COMMON: 1. Flux Corrosion – using too much flux when making joints can potentially leave residue and cause isolated corrosion. Flux should be used sparingly and system adequately flushed. 2. Electrolysis – stray (D.C.) current; inadequate grounding for the piping. 3. Sand or other solid particulates – erosion/corrosion problems can occur. Lower velocities must be maintained if solids are present in flow media. 4. Galvanic Corrosion – destruction of a material by electrochemical interaction between the environment and the material. Q: Copper tubing wall thickness is designated “K,” “L” or “M.” What are the copper fittings applicable to? A: Copper fittings’ wall thickness is determined by standards (ASME B-16:22 and MSS-SP-104). These standards address minimum wall thickness (per size) for the full range of copper fittings and are not intended to match tubing wall thicknesses. Q: Can dissimilar metals (i.e., copper and iron) be joined together without use of dielectric insulators to prevent corrosion? A: In most situations dissimilar metals (copper/iron/steel) can be joined successfully without using dielectric insulators. Factors to consider: 1. The composition of the two metals. 2. The rate of liquid flow past the two metals. 3. Chemicals in the water which could enhance or destroy protective films. 4. The relative areas of the two metals - unless the surface area of the less noble (steel) material is less that 5% of the more noble (copper) material, the need for a dielectric separator is not needed. (Failures due to galvanic corrosion are very unusual and only occur under very strict conditions.) 5. Local code requirements. Q: What should the installer of copper unions know and do in order to assure a proper leak-free installation? A. The following should be done: 1. Make sure the ground-joint(mating area of unionís tail and thread pieces) are free of nicks and scratches. 2. Spray the ground-joint area with a food grade silicone spray or apply bees wax to enhance seating. 3. Make sure alignment of line does not put lateral stress on the ground-joint seal. 4. Make sure that excess solder (droplets) do not reach the ground-joint area. AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 55//1144//0022 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 90 Residential Copper Plumbing Products Limited Warranty What the warranty terms mean In this warranty “Manufacturer” refers to the company listed below which manufactured the Product and any person or company that assumes its obligations under this warranty. “Homeowner” means you as the owner of the residential building in the United States in which the Product has been installed and also means any succeeding owner during the original warranty term. “Product” means the copper water tube and/or copper or brass fittings manufactured by the Manufacturer for the residential building market in the United States. Each Manufacturer listed below separately and individually warrants only Products it has manufactured and does not warrant Products of any other company, whether or not listed below. Date the warranty begins The warranty begins on the date of the new home purchase, or in the case of home additions or renovations, on the date the installation is completed. The warranty is transferable to succeeding Homeowners for the remainder of the original warranty term, in which case the date the warranty begins shall continue without change. What is covered The Manufacturer warrants to the Homeowner for a period of 50 years from the date the warranty begins that its properly installed Product will be free of failure as a result of defects in material or workmanship in manufacturing the Product. What the manufacturer will do for you As long as (1) such a failure occurs within 50 years from the date the warranty begins and (2) the Homeowner promptly notifies the Manufacturer of the Product of that failure by contacting it through its 800 phone number listed below, the Manufacturer will correct that failure by repairing or replacing the Product within a reasonable time, without charge. This warranty is limited to the cost of repairing or replacing the Product, including installation. NIBCO TECHNICAL SERVICE 1-888-446-4226 What is not covered: Disclaimer of liability for consequential and other damages The Manufacturer does NOT warrant against failure: 1. of any product, parts, or systems that it has not manufactured; 2. if the Product is used for purposes other than residential plumbing applications; 3. caused by, contributed in whole or in part by, or resulting from, any of the following: (a) improper installation; (b) abuse, such as, without limitation, vandalism; (c) natural disasters, such as, without limitation, flooding, windstorm and lightning; (d) attachments or modifications to the Product that the Manufacturer did not authorize; (e) external causes, where external, physical or chemical qualities produce damage to the Product, such as, without limitation, aggressive water or an unsuitable or hostile environment; or (f) any other cause beyond the Manufacturer’s control. The Manufacturer shall NOT be liable under any circumstances for any other direct or any indirect, incidental or consequential damages of any kind. This is the only warranty This warranty is the only warranty for the Product provided by the Manufacturer, and is and shall be in lieu of any and all other warranties, express or implied, including but not limited to an implied warranty of merchantability, and of all other obligations or liabilities on the part of the Manufacturer. None of the Manufacturer’s employees, and no other person or business, is authorized to make any other warranty on the Manufacturer’s behalf covering the product. This warranty gives you specific legal rights, and you may also have other rights which vary from state to state. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 55//1144//0022 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 91 AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 55//1144//0022 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 92 Numerical Index Figure Number Page Figure Number Page Figure Number Page Figure Number Page Figure Number Page 100 Series Cast Heavy Flared 101............................... 23 104............................... 23 500 Series Cast Flared 500.............................. 24 503.............................. 23 504.............................. 23 507.............................. 23 507-3........................... 23 507-4........................... 23 511............................... 24 600 Series Wrot Pressure 600................................ 9 600-2........................... 15 600-DS........................ 10 600-RS ......................... 9 601.............................. 10 603................................ 6 603-2............................. 6 604................................ 7 604-2............................. 7 606.............................. 11 606-2........................... 11 607.............................. 12 607-2 ........................... 13 607-2-2........................ 13 607-2-2-LT.................... 13 607-2-I......................... 13 607-2-LT....................... 13 607-I ............................ 12 607-LT.......................... 12 611......................... 17-19 611-2............................ 19 616.............................. 16 617................................ 9 618................................ 8 618-3............................. 8 619 ............................... 8 620-L ............................ 8 621.............................. 21 623.............................. 16 624.............................. 16 633-W......................... 21 638.............................. 16 698.............................. 20 700 Series Cast Pressure 701.............................. 10 701-D........................... 10 702 ............................. 10 703................................ 6 703-2............................. 6 703-5 ............................ 6 703-5B .......................... 6 704................................ 7 704-2............................. 7 704-2-H......................... 8 704-F............................. 7 704-H............................ 7 705.............................. 16 705-D........................... 17 706-2........................... 12 707.............................. 12 707-2-4........................ 13 707-3 ........................... 14 707-3-5........................ 14 707-3-5-A .................... 14 707-3-6........................ 14 707-4 ........................... 14 707-4-6........................ 14 707-5 ........................... 14 707-5-A........................ 14 707-6 ........................... 15 708.............................. 15 710-3........................... 17 710-3-4........................ 17 711.............................. 19 711-5 ........................... 19 711-A........................... 19 712.............................. 20 712-5........................... 20 713 ............................. 20 714.............................. 20 717................................ 9 717-D............................. 9 718-3............................. 8 724-5-A ...................... 10 733.............................. 21 733-2........................... 21 733-3........................... 21 733-4........................... 21 735.............................. 11 736 ............................. 11 739.............................. 16 741............................... 15 748 ............................. 21 749 ............................. 21 750................................ 8 750-3............................. 8 750-4............................. 8 764.............................. 15 771.............................. 16 775.............................. 16 800 Series Cast DWV 801.............................. 34 801-2 ........................... 33 801-2-7 ........................ 31 801-T............................ 32 802.............................. 32 802-C........................... 32 802-F........................... 32 803.............................. 32 803-2........................... 32 804.............................. 32 804-2........................... 33 804-T........................... 33 805.............................. 31 805-N.......................... 31 806.............................. 35 806-2........................... 35 807.............................. 35 807-2........................... 35 807-3........................... 36 807-4........................... 36 807-9........................... 36 808.............................. 36 809.............................. 36 810.............................. 38 811.............................. 37 811-14.......................... 37 811-15.......................... 37 812.............................. 38 814.............................. 38 816.............................. 33 816-S........................... 33 818 A.S.A.................... 36 834.............................. 38 835.............................. 37 835-B........................... 37 836.............................. 38 837.............................. 36 851.............................. 34 851-C........................... 34 861-LH......................... 36 875-S........................... 40 878.............................. 40 879.............................. 40 880.............................. 39 881.............................. 39 884.............................. 39 885.............................. 39 890.............................. 39 891.............................. 39 892.............................. 39 892-3........................... 39 892-A........................... 39 900 Series Wrot DWV 901.............................. 34 901-2 ........................... 33 901-2-7 ........................ 31 901-2-F ........................ 33 901-7............................ 31 901-RP......................... 34 903.............................. 32 903-2........................... 32 903-7........................... 31 904.............................. 33 904-7........................... 31 905.............................. 31 906.............................. 35 906-2........................... 35 907.............................. 35 907-2........................... 35 907-LT.......................... 35 911.............................. 37 917-B........................... 37 951.............................. 34 960.............................. 36 Copper Insert Fittings for Polybutylene PB198 .......................... 29 PB600.......................... 29 PB600-FA .................... 29 PB607.......................... 29 PB607-FA..................... 29 PB611.......................... 29 Copper Insert Fittings for Polyethylene (PEX) PEX198.........................26 PEX600.........................26 PEX600.........................26 PEX600-2......................26 PEX600-FA...................26 PEX600-T......................26 PEX603.........................26 PEX604.........................26 PEX607.........................26 PEX607-FA...................26 PEX611.........................26 PEX707-3-5..................26 PEX841.........................27 PEX100.........................27 PEX6I6..........................27 AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 55//1144//0022 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 93 NOTES AHEAD OF THE FLOW ™ wwwwww..nniibbccoo..ccoomm RReevviissiioonn 55//1144//0022 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONAL SERVICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 94 NOTES NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH:1.888.446.4226 • FAX: 1.800.336.4226 • INTERNATIONAL OFFICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com It’s a new age of business, and a new way at NIBCO. From Elkhart, Indiana to Lodz, Poland, and points beyond, our company has integrated manufacturing, distribu- tion, and networked communica- tions to provide a seamless source of information and service, 24 hours a day, 7 days a week. But this integration hasn’t hap- pened overnight. It’s been part of a long-term strategic process that has pushed us to reconsid- er every aspect of our business. The result? We’re a vertically integrated manufacturer with the products and systems in place to deliver low cost and high quality. NIBCO’s products are manufactured under a Quality Management System conforming to the current revi- sion of ISO-9001 International Standards. We know the flow control industry is only going to get more demanding, and we are more than ready. We will continue to lead. That’s what NIBCO is all about. globally connecting you at all levels World Headquarters Elkhart, Indiana Metal Valves and Fittings Blytheville, Arkansas McAllen, Texas Nacogdoches, Texas South Glens Falls, New York Stuarts Draft, Virginia Plastic Pipe, Valves, and Fittings Greensboro, Georgia Goshen, Indiana Denmark, South Carolina Industrial Plastics Charlestown, Indiana International Lodz, Poland Reynosa, Mexico U.S. & International Distribution Centers Atlanta, Georgia Charlestown, Indiana Columbus, Ohio Lodz, Poland Los Angeles, California Global Offices Elkhart, Indiana Lodz, Poland Vilnilus, Lithuania MANUFACTURING DISTRIBUTION INTERNATIONAL Pipe Hangers & Support Systems Corona, California C-CF-0404 © 2004, NIBCO INC.Printed in USA NIBCO INC. WORLD HEADQUARTERS WEB: www.nibco.com 1516 MIDDLEBURY STREET ELKHART, IN 46516-4740 USA DOMESTIC CUSTOMER SERVICE PHONE: 800.234.0227 FAX: 800.234.0557 TECHNICAL SERVICE PHONE: 888.446.4226 FAX: 888.336.4226 INTERNATIONAL OFFICE PHONE: +1/574.295.3221 FAX: +1/574.295.3455 FITTINGS VALVES & ACTUATION CHEMTROL® TOLCO™ NIBCO®now offers complete support with its newest addition of TOLCO™brand piping solutions including: Pipe attachments • Structural attachments • Pipe rollers • Threaded products and accessories • Seismic components • Vibration isolation • Standard and specialty supports • TOL-Strut™channel and components. Pressure-rated bronze, iron and alloy-iron gate, globe and check valves • Pressure- rated bronze ball valves • Boiler specialty valves • Commercial and industrial butterfly valves • Circuit balancing valves • Carbon and stainless steel ball valves • ANSI flanged steel ball valves • Pneumatic and electric actuators and controls • Grooved ball and butterfly valves • High performance butterfly valves • UL/FM fire protection valves • MSS specification valves • Bronze specialty valves • Low- pressure gate, globe, check and ball valves • Frostproof sillcocks • Quarter--turn supply stops • PVC ball valves • CPVC CTS ball valves • Just Right®recirculating valves. Thermoplastic pipe, valves and fittings in PVC, Corzan®CPVC, polypropylene and PVDF Kynar®• Chem-Aire®thermoplastic compressed air piping systems • Pneumatic and electric actuation systems. Wrot and cast copper pressure fittings • Wrot and cast copper drainage fittings • Wrot copper PEXlink®fittings • Cast copper alloy flared fittings • Cast copper alloy flanges • ABS and PVC DWV fittings • Schedule 40 PVC pressure fittings • CPVC CTS fittings • CPVC CTS-to-metal transition fittings • Schedule 80 PVC and CPVC systems • CPVC metric piping systems. Corzan® is a registered trademark of Noveon, IP Holdings Corp. Kynar®is a registered trademark of ATOFINA Chemicals, Inc. eNIBCO A suite of services designed to make customers more efficient • More cost--effective • More informed • EDI—Electronic Data Interchange • VMI—Vendor Managed Inventory • NIBCO.com • NIBCOpartner.com • eNIBCO will continuously develop new products to deliver the competitive advantage. C-CF-0404 www.itwbuildex.com800-BUILDEX SSS39 082007 Part No.Wood UL UL Max Pipe Size, in.UL Test Load Min. Wood Thickness, in.FM FM Max Pipe Size FM Test Load Min. Wood Thickness, in. 8007957 GST 10 X CPVC 1-1/2 300 1.5 8020957 SWG 10 X CPVC 1-1/2 300 1.5 8008957 GST 20 X 2-1/2 850 1.5 X 4 1475 1.5 8068925 GST 20 SS X 2-1/2 850 1.5 8010957 GST 30 X 4 1500 1.5 X 4 1475 1.5 8009925 GST 25-380 X 4 1500 1.5 8022925 SWG 25-380 X 3-1/2 - 4*1500 1.5 8021957 SWG 20 X 2-1/2 - 3**1250 1.5 8073925 SWG 20 SS X 2-1/2 1250 1.5 8139957 SH GST 20 X 3 1050 1.5 X 4 1475 1.5 8141957 SH GST 30 X 4 1500 1.5 X 4 1475 1.5 Part No.Steel UL UL Max Pipe Size, in.UL Test Load Min. Steel Thickness, in.FM FM Max Pipe Size FM Test Load Min. Steel Thickness, in. 8038957 DSTR 1 X 4 1500 .035 X 4 1475 .1050 8037957 DSTR 1-1/2 X 4 1500 .035 X 4 1475 .1050 8039957 DSTR 516 X 4 1500 .037 X 4 1475 .1050 8045957 DST 516 X 4 1500 .188 X 4 1475 .1875 8046957 TEK 50 X 4 1500 .250 X 4 1475 .1875 8055957 SWDR 1 X 4 1500 .037 X 4 1475 .0600 8056957 SWDR 516 X 4 1500 .037 X 4 1475 .0600 8054957 SWDR 1-1/2 X 4 1500 .037 X 4 1475 .0600 8137957 SH DSTR 1 X 4 1500 .035 X 4 1475 .1050 8150922 XP 20 X 2-1/2 850 .027 X 4 1475 .1050 8153922 XP 35 X 3-1/2 1250 .043 X 4 1475 .1050 8294922 SXP 20Δ X 2 750 .027 X 4 1475 8295922 SXP 35 X 3-1/2 1250 .060 X 4 1475 8293957 SWXP 35 X 3-1/2 1250 .060 X 4 1475 Part No.Concrete UL UL Max Pipe Size, in.UL Test Load Min. PSI FM FM Max Pipe Size FM Test Load Material 8059957 CST 20 3000 X 4 1475 3000 PSI 8061957 SWC 20 3000 X 4 1475 3000 PSI 8150922 XP 20 X 2-1/2 850 Pre Pour Structural 3000 PSI 8150922 XP 20 X 2-1/2 850 Post Pour Range II LWC ≤ 35 PCF *SWG 25-380 Maximum pipe size in composite wood joist allowed by UL is 3-1/2”*SWG 25-380 Maximum pipe size in wood timber or joist allowed by UL is 4” **SWG 20 Maximum pipe size in composite wood joist allowed by UL is 2-1/2”**SWG 20 Maximum pipe size in wood timber or joist allowed by UL is 2-1/2” ΔSXP 20 Maximum allowable angle in 22 ga. steel is 45° UL and FM tests were performed in compliance with NFPA 13 Standards.Fastening requirement: 5 times weighth of water filled schedule 40 pipe 250 pounds. Approvals 2007! NEW!Takes the X-Press to the X-Treme! OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330 CUSTOMER SERVICE • 800.786.5266 www.tolco.com 62 www.tolco.com Revision 1/24/2007 Size Range — 3/8" thru 3/4" rod Function — For attachment to structural shapes requiring wider throat especially under roof with bar joist construction. This clamp may be used in the set screw down position only. Approvals — Conforms to Federal Specification WW-H-171E, Type 23 and Manufacturers Standardization Society SP-69, Type 19. Finish — Plain Note — Available in Electro-Galvanized finish. Order By — Figure number, rod size and finish Note — Do not over tighten set screw. Fig. 68 - Wide Throat Top Beam “C” Clamp w/Locknut Dimensions • Weights Rod Max. Rec. Approx. Size Load Lbs. Wt./100 3/8 400 34 1/2 500 50 5/8 600 53 3/4 800 86 OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330 CUSTOMER SERVICE • 800.786.5266 www.tolco.com 84 www.tolco.com Revision 5/24/2001 ™ ®a brand of www.tolco.com Revision 5/24/2001 Fig. 200 - “Trimline” Adjustable Band Hanger Size Range — 1/2" thru 8" pipe Material — Carbon Steel, Mil. Galvanized to G90 specifications Function — For fire sprinkler and other general piping purposes. Knurled swivel nut design permits hanger adjustment after installation. Features — • (1/2" thru 2") Flared edges ease installation for all pipe types and protect CPVC plastic pipe from abrasion. Captured design keeps adjusting nut from separating with hanger. Hanger is easily installed around pipe. • (21⁄2" thru 8" Spring tension on nut holds it securely in hanger before installation. Adjusting nut is easily removed. Approvals — Underwriters’ Laboratories listed (1/2" thru 8") in the USA (UL) and Canada (cUL) for steel and CPVC plastic pipe and Factory Mutual Engineering Approved (3/4" thru 8"). Conforms to Federal Specifications WW-H-171E, Type 10 and Manufacturers Standardization Society SP-69, Type 10. Maximum Temperature — 650°F Finish — Mil. Galvanized. For Stainless Steel materi- als, order TOLCO™ Fig. 200WON. Order By — Figure number and pipe size Dimensions • Weights Pipe Rod Size Max. Rec. Approx. Size Inch Metric A B Load Lbs. Length 1/2 3/8 8mm or 10mm 31⁄8 25⁄8 400 11 3/4 3/8 8mm or 10mm 31⁄8 21⁄2 400 11 1 3/8 8mm or 10mm 33⁄8 25⁄8 400 12 11⁄4 3/8 8mm or 10mm 33⁄4 27⁄8 400 13 11⁄2 3/8 8mm or 10mm 37⁄8 27⁄8 400 14 2 3/8 8mm or 10mm 41⁄2 3 400 15 21⁄2 3/8 10mm 55⁄8 41⁄8 600 27 3 3/8 10mm 57⁄8 4 600 29 31⁄2 3/8 10mm 73⁄8 51⁄4 600 34 4 3/8 10mm 73⁄8 5 1000 35 5 1/2 12mm 91⁄8 61⁄4 1250 66 6 1/2 12mm 101⁄8 63⁄4 1250 73 8 1/2 12mm 131⁄8 83⁄4 1250 136 Max. Rec. Load Wt. Per InchPipe Size Rod Size A B Adj. C D E lbs.kN lbs.kg 1/2 (15)3/8 113/16 (46.04)11/2 (38.10)211/16 (68.26)3 (76.20)300 (1.33).08 (.04) 3/4 (20)3/8 15/8 (41.28)13/16 (30.16)21/2 (63.50)215/16 (74.61)300 (1.33).08 (.04) 1 (25)3/8 19/16 (39.69)1 (25.40)29/16 (65.09)3 (76.20)300 (1.33).08 (.04) 11/4 (32)3/8 15/8 (41.28)15/16 (23.81)21/2 (63.50)33/16 (80.96)300 (1.33).09 (.04) 11/2 (40)3/8 111/16 (42.86)7/8 (22.23)29/16 (65.09)33/8 (85.73)300 (1.33).09 (.04) 2 (50)3/8 27/16 (61.91)13/8 (34.93)35/16 (84.14)43/8 (111.13)300 (1.33).11 (.05) 21/2 (65)3/8 213/16 (71.44)11/2 (38.10)37/8 (98.43)59/16 (141.29)525 (2.34).26 (.12) 3 (80)3/8 31/8 (79.38)19/16 (39.69)43/16 (106.36)53/4 (146.05)525 (2.34).28 (.13) 31/2 (90)1/2 31/2 (88.90)111/16 (42.86)49/16 (115.89)63/8 (161.93)525 (2.34).33 (.15) 4 (100)3/8 33/4 (95.25)111/16 (42.86)413/16 (122.24)615/16 (176.21)650 (2.89).33 (.15) 5 (125)1/2 41/8 (104.78)19/16 (39.69)53/16 (131.76)713/16 (198.44)1000 (4.45).56 (.25) 6 (150)1/2 45/8 (117.48)19/16 (39.69)511/16 (144.46)815/16 (227.01)1000 (4.45).65 (.29) Max. Rec. Load Wt. Per Inch Pipe Size Rod Size B Adj. C D E lbs.Kn lbs.kg 1/2 (15)3/8 17/8 (47.63)17/16 (36.51)23/4 (69.85)31/16 (77.79)300 (1.33).11 (.05) 3/4 (20)3/8 111/16 (42.86)11/8 (28.58)21/2 (63.50)31/16 (77.79)300 (1.33).13 (.06) 1 (25)3/8 15/8 (41.28)1 (25.40)21/2 (63.50)33/16 (80.96)300 (1.33).13 (.06) 11/4 (32)3/8 115/16 (49.21)11/16 (26.99)213/16 (71.44)39/16 (90.49)300 (1.33).15 (.07) 11/2 (40)3/8 21/8 (53.98)11/16 (26.99)31/8 (79.38)37/8 (98.43)300 (1.33).17 (.08) 2 (50)3/8 27/16 (61.91)11/8 (28.58)35/16 (84.14)43/8 (111.13)300 (1.33).18 (.08) 21/2 (65)3/8 31/16 (77.79)15/8 (41.28)315/16 (100.01)53/8 (136.53)525 (2.34).19 (.09) 3 (80)3/8 311/16 (93.66)17/8 (47.63)49/16 (115.89)65/16 (160.34)525 (2.34).23 (.10) 31/2 (90)3/8 33/4 (95.25)17/8 (47.63)45/8 (117.48)65/8 (168.28)525 (2.34).25 (.11) 4 (100)3/8 43/16 (106.36)17/8 (47.63)51/16 (128.59)75/16 (185.74)650 (2.89).30 (.14) 5 (125)1/2 45/8 (117.48)15/8 (41.28)55/8 (142.88)83/8 (212.73)1000 (4.45).50 (.23) 6 (150)1/2 55/8 (142.88)21/4 (57.15)61/2 (165.10)913/16 (249.24)1000 (4.45).58 (.26) 8 (200)1/2 613/16 (173.04)27/16 (61.91)715/16 (201.61)121/4 (311.15)1000 (4.45).90 (.41) Fig.152 & 154 COPPER TUBING SWIVEL RING FUNCTION:Designed for the suspension of non-insulated stationary copper tubing. The knurled insert allows for vertical adjustment after installation.The PVC coating on Fig.154 protects the tubing from contact with the metal surface of the hanger. APPROVALS:Complies with Federal Specification A-A-1192A (Type 10)and Manufacturers’Standardization Society ANSI/SP-69 and SP-58 (Type 10). MATERIAL:Low carbon steel ORDERING:Specify tube size and figure number. Unless otherwise specified,all dimensions on drawings and in charts are in inches and dimensions shown in parentheses are in millimeters. ADJUSTABLE SWIVEL RING HANGERS Fig. 154 COPPER COLOR EPOXY FINISH WITH PVC COATING Fig.152 COPPER COLOR EPOXY FINISH Note:If orderingFig.151F felt lined hangers for pipe sizes of 31/2"(90mm)or under,order the next largest size to allowfor the thickness of the felt lining. FUNCTION:Designed for the suspension of non-insulated stationary pipe lines. The PVC coating on Fig. 143 protects the pipe from contact with the metal surface of the hanger. Frequently used with Aluminum, Glass, Plastic, Brass or Copper pipe lines.This product is NOT compatible with CPVC pipe. APPROVALS:Underwriters’ Laboratories Listed in the U.S. (UL), Canada (CUL), and Factory Mutual Approved for sizes 3/4"(20mm)to 8"(200MM). Complies with Federal Specifications A-A-1192A (Type 10), and Manufacturers’ Standardization Society ANSI/SP-69 and SP-58 (Type 10). Fig.143 PVC COATED SWIVEL RING MATERIAL:Low carbon steel ORDERING:Specify pipe size and figure number. FINISH:Pre-galvanized with PVC Coating OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330 CUSTOMER SERVICE • 800.786.5266 www.tolco.com 72 www.tolco.com Max Rec. Load Lbs. Rod For Service Temps Approx. Size 650°F 750°F Wt./100 1/4 240 215 12 3/8 610 540 29 1/2 1130 1010 53 5/8 1810 1610 84 3/4 2710 2420 123 7/8 3770 3360 169 1 4960 4420 222 11⁄4 8000 7140 360 11⁄2 11630 10370 510 Revision 9/1/2006 Size Range — Secures 3/8" thru 7/8" hanger rod Material — Carbon Steel Function — Secures channel to hanger rod for vertical seismic bracing. Approvals — Underwriters Laboratories Listed in the USA (UL) and Canada (cUL). Included in our Seismic Restraints Catalog approved by the State of California Office of Statewide Health Planning and Development (OSHPD). For additional load, spacing and placement information relating to OSHPD projects, please refer to the TOLCO Seismic Restraint Systems Guidelines Finish — Electro Galvanized Note — Available in HDG finish or Stainless Steel materials. Order By — Figure number Fig. 98 - Rod Stiffener Fig. 99 - All Thread Rod Cut to Length Size Range — Secures 3/8" thru 7/8" rod in 1" increments Material — Carbon Steel Maximum Temperature — 750°F Finish — Plain Note — Available in Electro-Galvanized and HDG finish or Stainless Steel materials. Order By — Figure number, rod diameter, rod length and finish Fig. 100 - All Thread Rod Full Lengths Size Range — Secures 3/8" thru 7/8" rod in 10’ lengths Material — Carbon Steel Maximum Temperature — 750°F Finish — Plain Note — Available in Electro-Galvanized and HDG finish or Stainless Steel materials. Order By — Figure number, rod diameter and finish Dimensions Rod Max. Rec. Load Lbs. Size For Service Temps 650°F 750°F 3/8 610 540 1/2 1130 1010 5/8 1810 1610 3/4 2710 2420 7/8 3770 3360 Dimensions • Weights Component of State of California OSHPD Approved Seismic Restraints System