HomeMy WebLinkAboutF15-0024_Cut Sheets Calcs_1430777700.pdf CHATEAU d'OEX
3816 LUPINE DRIVE
VAIL, COLORADO 81657
HYDRAULIC CALCULATIONS
& PRODUCT SUBMITTALS
THIS SET OF FIRE SPRINKLER SHOP SPE IFICATIONS AND HYDRAULIC CALCULATIONS HAVE
BEEN REVIEWED AND FAO •• i 0 BE CCEPTABLE-N.LC.E.T.IV#102055 SR.ENGINEERING
A0
TECHNI •• i -FI' ^ ' •• • TI P ,NATIONAL INSTITUTE FOR CERTIFICATION IN
�GERING TECHNICIANS '-' 47/ �/
If
-4-44717 -r%SET DATE
PHOENIX AUTOMATIC SPRINKLER
7684 S. BRENTWOOD ST.
LITTLETON, CO 80128
720.922.9231 PHONE
CALCULATION SUMMARY
Project Name:CHATEAU d'OEX Project Location: 3816 LUPINE DRIVE
Drawing No. : City: VAIL, CO
Design Areas
Design Area Calc. Mode Occupancy Area of Total Water Pressure @ Min. Min. Min. Calculated Hose Margin To
Name (Model) Application Source Density Pressure Flow Heads Streams Source
up) (gpm) (psi) (gPm/tt2) (psi) (gpm) # (gpm) (Psi)
1 Demand (HW) DWELLING 1024 112.1 Req red 0.1 13.8 25.6 4 0 66
77
2 Demand (HW) DWELLING 900 106.6 Required 0.1 10.6 22.5 4 0 24.8
118.1
3 Demand (HW) DWELLING 900 99.6 Required 0.1 10.6 22.5 4 0 23.9
119.1
File:C:\dwg\Phoenix-Bersin\BerRes.dwg
Date 4/8/2015 Copyright©2002-2012 Tyco Fire Protection Products Page 1
HYDRAULIC CALCULATIONS
for
Job Information
Project Name:CHATEAU d'OEX
Contract No. : City: VAIL, CO
Project Location: 3816 LUPINE DRIVE Date: 12/30/1899
Contractor Information
Name of Contractor: PHOENIX
Address: 7684 SOUTH BRENTWOOD STREET City: LITTLETON, CO 80128
Phone Number: 303-523-2098 E-mail:
Name of Designer: DLT
Authority Having Jurisdiction: VAIL FIRE
Design
Remote Area Name 1
Remote Area Location BASEMENT GARAGE
Occupancy Classification DWELLING
Density(gpm/ft2) 0.1
Area of Application(ft2) 1024
Coverage per Sprinkler(ft2) 256
Number of Calculated Sprinklers 4
In-Rack Demand(gpm) 0
Special Heads
Hose Streams(gpm) 0
Total Water Required(incl. Hose Streams)(gpm) 112.1
Required Pressure at Source(psi) 77
Type of System Wet
Volume-Entire System (gal) 26.7 gal
Water Supply Information
Date March,2015
Location Near Site
Source W1
Notes
File:C:\dwg\Phoenix-Bersin\BerRes.dwg
Date 4/8/2015 Copyright©2002-2012 Tyco Fire Protection Products Page 2
Job:CHATEAU d'OEX
Hydraulic Analysis for : 1
Calculation Info
Calculation Mode Demand
Hydraulic Model Hazen-Williams
Fluid Name Water @ 60F (15.6C)
Fluid Weight, (Ib/ft3) N/A for Hazen-Williams calculation.
Fluid Dynamic Viscosity, (Ib•s/ft2) N/A for Hazen-Williams calculation.
Water Supply Parameters
Supply 1 : W1 Flow(gpm) Pressure(psi)
0 143
1985 136
Hoses
Inside Hose Flow/Standpipe Demand(gpm)
Outside Hose Flow(gpm)
Additional Outside Hose Flow(gpm)
Other(custom defined) Hose Flow(gpm)
Total Hose Flow(gpm)
Sprinklers
Ovehead Sprinkler Flow(gpm) 112.1
InRack Sprinkler Flow(gpm) 0
Other(custom defined)Sprinkler Flow(gpm) 0
Total Sprinkler Flow(gpm) 112.1
Other
Required Margin of Safety(psi) 0
W1 -Pressure(psi) 77
W1 -Flow(gpm) 112.1
Demand w/o System Pump(s) N/A
File:C:\dwg\Phoenix-Bersin\BerRes.dwg
Date 4/8/2015 Copyright©2002-2012 Tyco Fire Protection Products Page 3
Job:CHATEAU d'OEX
Hydraulic Analysis for : 1
f Supply f System Demand 1
15[ 11111---------
' 135.231
140
-11---. __----------_— � ______ --- S�
- -- -1
—
120_.. ----
110- ---- —
100_..-- ---- —
• 9 s _..--------- — _
0. D2 —r.- — -
i 80_ ; T--
N 70_ ------- —
G2 - — --• __
._
(7) 9 s ---- - —
i -
0 iiiiismo mo ==mm.......��������
0 60m0(B0®00100®100120013001400150016001700 1800 1900 2000 2100
Flow, gpm
File:C:\dwg\Phoenix-Bersin\BerRes.dwg
Date 4/8/2015 Copyright©2002-2012 Tyco Fire Protection Products Page 4
Job:CHATEAU d'OEX
Hydraulic Analysis for : 1
Graph Labels
Values
Label Description Flow (gpm) Pressure (psi)
S1 Supply point#1 -Static 0 143
S2 Supply point#2-Residual 1985 136
D1 Elevation Pressure 0 -1.1
D2 System Demand 112.1 77
Curve Intersections & Safety Margins
Intersection Safety Margin
Curve Name
Pressure (psi) Flow (gpm) Pressure (psi) @ Flow (gpm)
Supply 142.9 156.1 66 112.1
Open Heads
Required Calculated
Head Ref. Head Type Coverage K-Factor
Density Flow Pressure Density Flow Pressure
(ft2) (gpm/psi1/2) (gpm/ft2) (gpm) (psi) (gpm/ft2) (gpm) (psi)
101 Overhead 256 6.9 0.1 25.6 13.8 0.113 29 17.7
Sprinkler
102 Overhead 256 6.9 0.1 25.6 13.8 0.121 31 20.1
Sprinkler
103 Overhead 256 6.9 0.1 25.6 13.8 0.1 25.6 13.8
Sprinkler
104 Overhead 256 6.9 0.1 25.6 13.8 0.104 26.5 14.8
Sprinkler
File:C:\dwg\Phoenix-Bersin\BerRes.dwg
Date 4/8/2015 Copyright©2002-2012 Tyco Fire Protection Products Page 5
Job:CHATEAU d'OEX Hydraulic Calculations
PIPE INFORMATION
Node 1 Elev 1 K-Factor 1 Flow added (q) Nominal ID Fittings L C Factor total (Pt)
Node 2 Elev 2 K-Factor 2 Total flow (Q) Actual ID quantity x (name) = length F Pf per ft elev (Pe) NOTES
T frict (Pf)
(ft) (gpm/psi1/2) (gpm) (in) (ft) (ft) (psi) (psi)
Path No: 1
103 -1 6.9 25.6 1 lx(us.90)=3.82 0.5 150 13.8
077 -0.5 25.6 1.101 3.82 0.107 -0.2
4.32 0.5
077 -0.5 0 1 13 150 14
070 -0.5 25.6 1.055 0 0.1318 0
13 1.7
070 -0.5 26.5 1 1x(us.Tee-Br)=7.76 9.77 150 15.7
006 -0.5 52.1 1.055 7.76 0.492 0
17.53 8.6
006 -0.5 60 1.5 1x(coupling)=1.17 31.21 150 24.3
015-0 -2.54 112.1 1.527 2x(us.90)=9.34 10.5 0.3356 0.9
41.71 14
015-0 -2.54 0 1.5 0.78 0 39.3 Riser Manifold
015-I -3.32 112.1 0 0 4.0532 0.3 ***
0.78 3.2
015-I -3.32 0 1.5 1x(coupling)=1.17 1.92 150 42.8
016-0 -5.25 112.1 1.527 1.17 0.3356 0.8
3.09 1
016-0 -5.25 0 1.5 1.49 0 44.7 4000B DblChk
016-I -6.73 112.1 0 0 11.8813 0.6 ***
1.49 17.7
016-I -6.73 0 1.5 lx(coupling)=1.17 0.71 150 63.1
017-0 -7.45 112.1 1.527 1.17 0.3356 0.3
1.88 0.6
017-0 -7.45 0 2 0.63 0 64 RSV-1
017-I -8.07 112.1 0 0 3.696 0.3 ***
0.63 2.3
017-I -8.07 0 1.5 lx(coupling)=1.17 0.93 150 66.6
018 -9 112.1 1.527 1.17 0.3356 0.4
2.1 0.7
018 -9 0 2 3x(us.90)=17.44 123 150 67.8
W1 1.5 112.1 1.959 17.44 0.0997 -4.5
140.44 14
W1 77
Path No: 2
104 -1 6.9 26.5 1 lx(us.Tee-Br)=9.56 0.5 150 14.8
070 -0.5 26.5 1.101 9.56 0.1144 -0.2
10.06 1.2
070 15.7
File:C:\dwg\Phoenix-Bersin\BerRes.dwg
Date 4/8/2015 Copyright©2002-2012 Tyco Fire Protection Products Page 6
Job:CHATEAU d'OEX Hydraulic Calculations
PIPE INFORMATION
Path No: 3
101 -1 6.9 29 1 1x(us.90)=3.82 0.75 150 17.7
110 -0.25 29 1.101 3.82 0.135 -0.3
4.57 0.6
110 -0.25 0 1 lx(us.Tee-Br)=7.76 8.25 150 18
088 -0.25 29 1.055 7.76 0.1662 0
16.01 2.7
088 -0.25 0 1 1x(us.90)=2 0.25 120 20.6
087 -0.5 29 1.049 2 0.2584 0.1
2.25 0.6
087 -0.5 0 1.5 4.75 150 21.3
001 -0.5 29 1.527 0 0.0275 0
4.75 0.1
001 -0.5 31 1.5 lx(us.90)=4.67 22.71 150 21.5
006 -0.5 60 1.527 4.67 0.1054 0
27.37 2.9
006 24.3
Path No: 4
102 -1 6.9 31 1 lx(us.Tee-Br)=9.56 0.5 150 20.1
001 -0.5 31 1.101 9.56 0.1523 -0.2
10.06 1.5
001 21.5
* Pressures are balanced to a high degree of accuracy. Values may vary by 0.1 psi due to display rounding.
* Maximum Velocity of 19.64 ft/s occurs in the following pipe(s): (015-0-006), (016-0-015-I), (017-0-016-I), (018-017-I)
*** Device pressure loss (gain in the case of pumps) is calculated from the device's curve. If the device curve is printed with
this report, it will appear below. The length of the device as shown in the table above comes from the CAD drawing. The friction
loss per unit of length is calculated based upon the length and the curve-based loss/gain value. Internal ID and C Factor values
are irrelevant as the device is not represented as an addition to any pipe, but is an individual item whose loss/gain is based
solely on the curve data.
File:C:\dwg\Phoenix-Bersin\BerRes.dwg
Date 4/8/2015 Copyright©2002-2012 Tyco Fire Protection Products Page 7
Job:CHATEAU d'OEX Device Graphs
Pressure vs. Flow Function
Design Area: 1; Supply Ref.: W1; Supply Name:W1
160
150
140
130 1111111
120
110 ■■■■■■■
y
100 1111111
� 90
N 80
N
70
a
60
50
40
30
20
10 .■.■■■.
0 • •■
o o 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 00
M v1 O t- 00 0 0 V1 00
Flow,gpm
Pressure Loss Function
Design Area: 1; BFP Ref.: 157 (4000B DblChk, Size = 1.5); Inlet Node: 016-I; Outlet Node: 016-0
19.9
18.9 17.7 psi @ 112.1 gpm
17.9
16.9-
15.9- .0/
14.9
13.9
12.9
CA
— —
Q- 11.9
L 10.9"
7 "
Cl _) 9.9 —
L 8.9
CL
7.9
6.9" -
5.9
4.9
3.9-
2.9=
1.9=
0.9
o o 0 0 0
N 00 N
Flow,gpm
File:C:\dwg\Phoenix-Bersin\BerRes.dwg
Date 4/8/2015 Copyright©2002-2012 Tyco Fire Protection Products Page 8
Job :CHATEAU d'OEX Device Graphs
Pressure Loss Function
Design Area: 1; Valve Ref.: 156 (RSV-1, Size = 2); Inlet Node: 017-I; Outlet Node: 017-0
2.3 psi @ 112.1 gpm
2.36
1.86
y
a-
d
U) 1.36
y
G) -
L
0.86
0.36 •
o .n en 0 0 0 0 0 0 0 0 0 0 0 0 0 0
In 0 0 — Cl M 7 In
Flow,gpm
Pressure Loss Function
Design Area: 1; Valve Ref.: 158 (Riser Manifold, Size = 1.5); Inlet Node: 015-I; Outlet Node: 015-0
12.06 - — —
11.06
10.06
9.06
8.06
0_
7.06
-
tn 6.06
to
d _
a 5.06
4.06 3.2 psi @ 112.1 gpm
3.06 •
2.06)
1.06 —
0.06
Nn C r Cl
N
Flow,gpm
File:C:\dwg\Phoenix-Bersin\BerRes.dwg
Date 4/8/2015 Copyright©2002-2012 Tyco Fire Protection Products Page 9
HYDRAULIC CALCULATIONS
for
Job Information
Project Name:CHATEAU d'OEX
Contract No. : City: VAIL, CO
Project Location: 3816 LUPINE DRIVE Date: 12/30/1899
Contractor Information
Name of Contractor: PHOENIX
Address: 7684 SOUTH BRENTWOOD STREET City: LITTLETON, CO 80128
Phone Number: 303-523-2098 E-mail:
Name of Designer: DLT
Authority Having Jurisdiction: VAIL FIRE
Design
Remote Area Name 2
Remote Area Location LIVING HIGH CEILING
Occupancy Classification DWELLING
Density(gpm/ft2) 0.1
Area of Application(ft2) 900
Coverage per Sprinkler(ft2) 225
Number of Calculated Sprinklers 4
In-Rack Demand(gpm) 0
Special Heads
Hose Streams(gpm) 0
Total Water Required(incl. Hose Streams)(gpm) 106.6
Required Pressure at Source(psi) 118.1
Type of System Wet
Volume-Entire System (gal) 32.7 gal
Water Supply Information
Date March,2015
Location Near Site
Source W1
Notes
File:C:\dwg\Phoenix-Bersin\BerRes.dwg
Date 4/8/2015 Copyright©2002-2012 Tyco Fire Protection Products Page 10
Job:CHATEAU d'OEX
Hydraulic Analysis for : 2
Calculation Info
Calculation Mode Demand
Hydraulic Model Hazen-Williams
Fluid Name Water @ 60F (15.6C)
Fluid Weight, (Ib/ft3) N/A for Hazen-Williams calculation.
Fluid Dynamic Viscosity, (Ib•s/ft2) N/A for Hazen-Williams calculation.
Water Supply Parameters
Supply 1 : W1 Flow(gpm) Pressure(psi)
0 143
1985 136
Hoses
Inside Hose Flow/Standpipe Demand(gpm)
Outside Hose Flow(gpm)
Additional Outside Hose Flow(gpm)
Other(custom defined) Hose Flow(gpm)
Total Hose Flow(gpm)
Sprinklers
Ovehead Sprinkler Flow(gpm) 106.6
InRack Sprinkler Flow(gpm) 0
Other(custom defined)Sprinkler Flow(gpm) 0
Total Sprinkler Flow(gpm) 106.6
Other
Required Margin of Safety(psi) 0
W1 -Pressure(psi) 118.1
W1 -Flow(gpm) 106.6
Demand w/o System Pump(s) N/A
File:C:\dwg\Phoenix-Bersin\BerRes.dwg
Date 4/8/2015 Copyright©2002-2012 Tyco Fire Protection Products Page 11
Job:CHATEAU d'OEX
Hydraulic Analysis for : 2
f Supply f System Demand 1
15[ .---
-
140=II.....__---- — '-- ___ --- S�
135.231
13P --
D2 1-- — - —
120= 11-------
110- .------ —
100= ------- —
'y 90- ------ _ _ _ _
— --
i 80= ------- --
U) 70- -------- —
CL 60= -------- -- --
1 D1 -
----- _
- - -- -
0
0 60m0(B0®00100®100 2001300140015001600 1700 1800 1900 2000 2100
Flow, gpm
File:C:\dwg\Phoenix-Bersin\BerRes.dwg
Date 4/8/2015 Copyright©2002-2012 Tyco Fire Protection Products Page 12
Job:CHATEAU d'OEX
Hydraulic Analysis for : 2
Graph Labels
Values
Label Description Flow (gpm) Pressure (psi)
S1 Supply point#1 -Static 0 143
S2 Supply point#2-Residual 1985 136
D1 Elevation Pressure 0 3.4
D2 System Demand 106.6 118.1
Curve Intersections & Safety Margins
Intersection Safety Margin
Curve Name
Pressure (psi) Flow (gpm) Pressure (psi) @ Flow (gpm)
Supply 143 118.5 24.8 106.6
Open Heads
Required Calculated
Head Ref. Head Type Coverage K-Factor
Density Flow Pressure Density Flow Pressure
(ft2) (gpm/psi1/2) (gpm/ft2) (gpm) (psi) (gpm/ft2) (gpm) (psi)
201 Overhead 225 6.9 0.1 22.5 10.6 0.1 22.5 10.6
Sprinkler
202 Overhead 225 6.9 0.1 22.5 10.6 0.102 23 11.1
Sprinkler
203 Overhead 225 6.9 0.1 22.5 10.6 0.119 26.8 15.1
Sprinkler
204 Overhead 225 6.9 0.1 22.5 10.6 0.153 34.3 24.8
Sprinkler
File:C:\dwg\Phoenix-Bersin\BerRes.dwg
Date 4/8/2015 Copyright©2002-2012 Tyco Fire Protection Products Page 13
Job:CHATEAU d'OEX Hydraulic Calculations
PIPE INFORMATION
Node 1 Elev 1 K-Factor 1 Flow added (q) Nominal ID Fittings L C Factor total (Pt)
Node 2 Elev 2 K-Factor 2 Total flow (Q) Actual ID quantity x (name) = length F Pf per ft elev (Pe) NOTES
T frict (Pf)
(ft) (gpm/psi1/2) (gpm) (in) (ft) (ft) (psi) (psi)
Path No: 1
201 9 6.9 22.5 1 lx(us.90)=3.82 13 150 10.6
108 22 22.5 1.101 3.82 0.0843 -5.6
16.82 1.4
108 22 0 1 10 150 6.1
107 22 22.5 1.055 0 0.1038 0
10 1
107 22 23 1 12 150 7.1
106 22 45.5 1.055 0 0.3823 0
12 4.6
106 22 26.8 1 lx(us.Tee-Br)=7.76 6.69 150 11.7
105 22 72.3 1.055 7.76 0.9006 0
14.46 13
105 22 34.3 1.5 lx(us.90)=4.67 35.71 150 24.8
088 -0.25 106.6 1.527 2x(us.Tee-Br)=18.67 23.34 0.3056 9.6
59.05 18
088 -0.25 0 1 lx(us.90)=2 0.25 120 53
087 -0.5 106.6 1.049 2 2.8762 0.1
2.25 6.5
087 -0.5 0 1.5 lx(coupling)=1.17 58.67 150 59.6
015-0 -2.54 106.6 1.527 3x(us.90)=14 15.17 0.3056 0.9
73.84 22.6
015-0 -2.54 0 1.5 0.78 0 83.1 Riser Manifold
015-I -3.32 106.6 0 0 3.6918 0.3 ***
0.78 2.9
015-I -3.32 0 1.5 lx(coupling)=1.17 1.92 150 86.3
016-0 -5.25 106.6 1.527 1.17 0.3056 0.8
3.09 0.9
016-0 -5.25 0 1.5 1.49 0 88.1 4000B DblChk
016-I -6.73 106.6 0 0 11.3071 0.6 ***
1.49 16.8
016-I -6.73 0 1.5 lx(coupling)=1.17 0.71 150 105.6
017-0 -7.45 106.6 1.527 1.17 0.3056 0.3
1.88 0.6
017-0 -7.45 0 2 0.63 0 106.5 RSV-1
017-I -8.07 106.6 0 0 3.6536 0.3 ***
0.63 2.3
017-I -8.07 0 1.5 lx(coupling)=1.17 0.93 150 109.1
018 -9 106.6 1.527 1.17 0.3056 0.4
2.1 0.6
018 -9 0 2 3x(us.90)=17.44 123 150 110.2
W1 1.5 106.6 1.959 17.44 0.0908 -4.5
140.44 12.8
W1 118.1
Path No: 2
202 9 6.9 23 1 lx(us.Tee-Br)=9.56 13 150 11.1
107 22 23 1.101 9.56 0.0878 -5.6
22.56 2
107 7.1
File:C:\dwg\Phoenix-Bersin\BerRes.dwg
Date 4/8/2015 Copyright©2002-2012 Tyco Fire Protection Products Page 14
Job:CHATEAU d'OEX Hydraulic Calculations
PIPE INFORMATION
Node 1 Elev 1 K-Factor 1 Flow added (q) Nominal ID Fittings L C Factor total (Pt)
Node 2 Elev 2 K-Factor 2 Total flow (Q) Actual ID quantity x (name) = length F Pf per ft elev (Pe) NOTES
T frict (Pf)
(ft) (gpm/psi1/2) (gpm) (in) (ft) (ft) (psi) (psi)
Path No: 3
203 9 6.9 26.8 1 lx(us.Tee-Br)=9.56 13 150 15.1
106 22 26.8 1.101 9.56 0.1163 -5.6
22.56 2.6
106 11.7
Path No: 4
204 9 6.9 34.3 1 lx(us.90)=3.82 13 150 24.8
109 22 34.3 1.101 3.82 0.1845 -5.6
16.82 3.1
109 22 0 1 lx(us.Tee-Br)=7.76 4.65 150 21.9
105 22 34.3 1.055 7.76 0.2271 0
12.41 2.8
105 24.8
* Pressures are balanced to a high degree of accuracy. Values may vary by 0.1 psi due to display rounding.
* Maximum Velocity of 39.58 ft/s occurs in the following pipe(s): (087-088)
*** Device pressure loss (gain in the case of pumps) is calculated from the device's curve. If the device curve is printed with
this report, it will appear below. The length of the device as shown in the table above comes from the CAD drawing. The friction
loss per unit of length is calculated based upon the length and the curve-based loss/gain value. Internal ID and C Factor values
are irrelevant as the device is not represented as an addition to any pipe, but is an individual item whose loss/gain is based
solely on the curve data.
File:C:\dwg\Phoenix-Bersin\BerRes.dwg
Date 4/8/2015 Copyright©2002-2012 Tyco Fire Protection Products Page 15
Job:CHATEAU d'OEX Device Graphs
Pressure vs. Flow Function
Design Area: 2; Supply Ref.: W1; Supply Name:W1
160
150
140
130 1111111
120
110 ■■■■■■■
y
100 1111111
� 90
N 80
N
70
a
60
50
40
30
20
10 .■.■■■.
0 • •■
o o 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 00
M v1 O t- 00 0 0 V1 00
Flow,gpm
Pressure Loss Function
Design Area: 2; BFP Ref.: 157 (4000B DblChk, Size = 1.5); Inlet Node: 016-I; Outlet Node: 016-0
19.9
18.9-
16.8 psi @106.6gpm -
17.9-
16.9-
15.9-
14.9-
13.9-
CA
12.9- — —
Q- 11.9
10.9"
=
�) 9.9 —
UI
2 8.9
a
7.9"
6.9" -
5.9"
4.9.
3.9-
2.9=
1.9:
0.9:
o o 0 0 0
N O Cl
Flow,gpm
File:C:\dwg\Phoenix-Bersin\BerRes.dwg
Date 4/8/2015 Copyright©2002-2012 Tyco Fire Protection Products Page 16
Job :CHATEAU d'OEX Device Graphs
Pressure Loss Function
Design Area: 2; Valve Ref.: 156 (RSV-1, Size = 2); Inlet Node: 017-I; Outlet Node: 017-0
I
2.3 psi @ 106.6 gpm
2.36
•
1.86
y
a-
d
U) 1.36
y
G) -
L
0.86
0.36 •
•
0 0 0 0 0 0 0 0 0
0 - Cl M 7 In
Flow,gpm
Pressure Loss Function
Design Area: 2; Valve Ref.: 158 (Riser Manifold, Size = 1.5); Inlet Node: 015-I; Outlet Node: 015-0
12.06 - L
11.06
10.06
9.06
fA 8.06
-
0_
7.06
to 6.06
to
G) -
a 5.06
4.06 2.9 psi @ 106.6 gpm
3.06
2.06
1.06
0.06
N � n
Flow,gpm
File:C:\dwg\Phoenix-Bersin\BerRes.dwg
Date 4/8/2015 Copyright©2002-2012 Tyco Fire Protection Products Page 17
HYDRAULIC CALCULATIONS
for
Job Information
Project Name:CHATEAU d'OEX
Contract No. : City: VAIL, CO
Project Location: 3816 LUPINE DRIVE Date: 12/30/1899
Contractor Information
Name of Contractor: PHOENIX
Address: 7684 SOUTH BRENTWOOD STREET City: LITTLETON, CO 80128
Phone Number: 303-523-2098 E-mail:
Name of Designer: DLT
Authority Having Jurisdiction: VAIL FIRE
Design
Remote Area Name 3
Remote Area Location UPPER LEVEL BED RM
Occupancy Classification DWELLING
Density(gpm/ft2) 0.1
Area of Application(ft2) 900
Coverage per Sprinkler(ft2) 225
Number of Calculated Sprinklers 4
In-Rack Demand(gpm) 0
Special Heads
Hose Streams(gpm) 0
Total Water Required(incl. Hose Streams)(gpm) 99.6
Required Pressure at Source(psi) 119.1
Type of System Wet
Volume-Entire System (gal) 27 gal
Water Supply Information
Date March,2015
Location Near Site
Source W1
Notes
File:C:\dwg\Phoenix-Bersin\BerRes.dwg
Date 4/8/2015 Copyright©2002-2012 Tyco Fire Protection Products Page 18
Job:CHATEAU d'OEX
Hydraulic Analysis for : 3
Calculation Info
Calculation Mode Demand
Hydraulic Model Hazen-Williams
Fluid Name Water @ 60F (15.6C)
Fluid Weight, (Ib/ft3) N/A for Hazen-Williams calculation.
Fluid Dynamic Viscosity, (Ib•s/ft2) N/A for Hazen-Williams calculation.
Water Supply Parameters
Supply 1 : W1 Flow(gpm) Pressure(psi)
0 143
1985 136
Hoses
Inside Hose Flow/Standpipe Demand(gpm)
Outside Hose Flow(gpm)
Additional Outside Hose Flow(gpm)
Other(custom defined) Hose Flow(gpm)
Total Hose Flow(gpm)
Sprinklers
Ovehead Sprinkler Flow(gpm) 99.6
InRack Sprinkler Flow(gpm) 0
Other(custom defined)Sprinkler Flow(gpm) 0
Total Sprinkler Flow(gpm) 99.6
Other
Required Margin of Safety(psi) 0
W1 -Pressure(psi) 119.1
W1 -Flow(gpm) 99.6
Demand w/o System Pump(s) N/A
File:C:\dwg\Phoenix-Bersin\BerRes.dwg
Date 4/8/2015 Copyright©2002-2012 Tyco Fire Protection Products Page 19
Job:CHATEAU d'OEX
Hydraulic Analysis for : 3
f Supply f System Demand 1
15[ ----
-
140
-11---. __---- — '-- ___ --- S�
135.231
Z---1
13- D2- --- —
120=1- ----
110- ---- —
100_ ------- —
'y 90---------- _ _ _ _
— --
i= - r.-
80_ -------- --
U) 70_ -------- _
0_ 60:..--________
0_..--------- -- --
24,---- -
. .
_ . .
_ _
._ . .
0_,uIIIMME AMM ----------
0 60m0(B0®00100®100 2001300140015001600 1700 1800 1900 2000 2100
Flow, gpm
File:C:\dwg\Phoenix-Bersin\BerRes.dwg
Date 4/8/2015 Copyright©2002-2012 Tyco Fire Protection Products Page 20
Job:CHATEAU d'OEX
Hydraulic Analysis for : 3
Graph Labels
Values
Label Description Flow (gpm) Pressure (psi)
S1 Supply point#1 -Static 0 143
S2 Supply point#2-Residual 1985 136
D1 Elevation Pressure 0 8
D2 System Demand 99.6 119.1
Curve Intersections & Safety Margins
Intersection Safety Margin
Curve Name
Pressure (psi) Flow (gpm) Pressure (psi) @ Flow (gpm)
Supply 143 110.6 23.9 99.6
Open Heads
Required Calculated
Head Ref. Head Type Coverage K-Factor
Density Flow Pressure Density Flow Pressure
(ft2) (gpm/psi1/2) (gpm/ft2) (gpm) (psi) (gpm/ft2) (gpm) (psi)
301 Overhead 225 6.9 0.1 22.5 10.6 0.1 22.5 10.6
Sprinkler
302 Overhead 225 6.9 0.1 22.5 10.6 0.101 22.8 10.9
Sprinkler
303 Overhead 225 6.9 0.1 22.5 10.6 0.119 26.8 15.1
Sprinkler
304 Overhead 225 6.9 0.1 22.5 10.6 0.122 27.4 15.8
Sprinkler
File:C:\dwg\Phoenix-Bersin\BerRes.dwg
Date 4/8/2015 Copyright©2002-2012 Tyco Fire Protection Products Page 21
Job:CHATEAU d'OEX Hydraulic Calculations
PIPE INFORMATION
Node 1 Elev 1 K-Factor 1 Flow added (q) Nominal ID Fittings L C Factor total (Pt)
Node 2 Elev 2 K-Factor 2 Total flow (Q) Actual ID quantity x (name) = length F Pf per ft elev (Pe) NOTES
T frict (Pf)
(ft) (gpm/psi1/2) (gpm) (in) (ft) (ft) (psi) (psi)
Path No: 1
301 19 6.9 22.5 1 lx(us.90)=2.49 1 120 10.6
041 20 22.5 1.097 2.49 0.1297 -0.4
3.49 0.5
041 20 0 1 lx(us.90)=3.11 4.38 150 10.6
039 20 22.5 1.055 3.11 0.1038 0
7.48 0.8
039 20 22.8 1 1x(us.Tee-Br)=7.76 6.71 150 11.4
038 20 45.3 1.055 7.76 0.379 0
14.47 5.5
038 20 26.8 1.25 1x(us.90)=3.27 2.5 150 16.9
033 19.5 72.1 1.291 3.27 0.3357 0.2
5.77 1.9
033 19.5 27.4 1.25 3x(us.Tee-Br)=19.64 53.79 150 19.1
008 -0.5 99.6 1.291 2x(us.90)=6.55 26.19 0.61 8.7
79.98 48.8
008 -0.5 0 1.5 1x(coupling)=1.17 23.48 150 77
015-0 -2.54 99.6 1.527 2x(us.90)=9.34 10.5 0.2693 0.9
33.98 9.2
015-0 -2.54 0 1.5 0.78 0 87.1 Riser Manifold
015-I -3.32 99.6 0 0 3.2533 0.3 ***
0.78 2.5
015-I -3.32 0 1.5 lx(coupling)=1.17 1.92 150 90
016-0 -5.25 99.6 1.527 1.17 0.2693 0.8
3.09 0.8
016-0 -5.25 0 1.5 1.49 0 91.7 4000B DblChk
016-I -6.73 99.6 0 0 10.671 0.6 ***
1.49 15.9
016-I -6.73 0 1.5 1x(coupling)=1.17 0.71 150 108.3
017-0 -7.45 99.6 1.527 1.17 0.2693 0.3
1.88 0.5
017-0 -7.45 0 2 0.63 0 109.1 RSV-1
017-I -8.07 99.6 0 0 3.5965 0.3 ***
0.63 2.2
017-I -8.07 0 1.5 1x(coupling)=1.17 0.93 150 111.6
018 -9 99.6 1.527 1.17 0.2693 0.4
2.1 0.6
018 -9 0 2 3x(us.90)=17.44 123 150 112.6
W1 1.5 99.6 1.959 17.44 0.08 -4.5
140.44 11.2
W1 119.1
Path No: 2
302 19 6.9 22.8 1 lx(us.Tee-Br)=6.22 1 120 10.9
039 20 22.8 1.097 6.22 0.1327 -0.4
7.22 1
039 11.4
File:C:\dwg\Phoenix-Bersin\BerRes.dwg
Date 4/8/2015 Copyright©2002-2012 Tyco Fire Protection Products Page 22
Job:CHATEAU d'OEX Hydraulic Calculations
PIPE INFORMATION
Path No: 3
303 19 6.9 26.8 1 1x(us.90)=2.49 1 120 15.1
042 20 26.8 1.097 2.49 0.1798 -0.4
3.49 0.6
042 20 0 1 lx(us.Tee-Br)=7.76 3.29 150 15.3
038 20 26.8 1.055 7.76 0.1438 0
11.06 1.6
038 16.9
Path No: 4
304 19 6.9 27.4 1 lx(us.90)=2.49 0.5 120 15.8
036 19.5 27.4 1.097 2.49 0.1874 -0.2
2.99 0.6
036 19.5 0 1 1x(us.Tee-Br)=7.76 8.03 150 16.2
065 19.5 27.4 1.055 7.76 0.1499 0
15.8 2.4
065 19.5 0 1.25 1x(us.Tee-Br)=6.55 2.95 150 18.5
033 19.5 27.4 1.291 6.55 0.0561 0
9.5 0.5
033 19.1
* Pressures are balanced to a high degree of accuracy. Values may vary by 0.1 psi due to display rounding.
* Maximum Velocity of 24.4 ft/s occurs in the following pipe(s): (008-033)
*** Device pressure loss (gain in the case of pumps) is calculated from the device's curve. If the device curve is printed with
this report, it will appear below. The length of the device as shown in the table above comes from the CAD drawing. The friction
loss per unit of length is calculated based upon the length and the curve-based loss/gain value. Internal ID and C Factor values
are irrelevant as the device is not represented as an addition to any pipe, but is an individual item whose loss/gain is based
solely on the curve data.
File:C:\dwg\Phoenix-Bersin\BerRes.dwg
Date 4/8/2015 Copyright©2002-2012 Tyco Fire Protection Products Page 23
Job:CHATEAU d'OEX Device Graphs
Pressure vs. Flow Function
Design Area: 3; Supply Ref.: W1; Supply Name:W1
160
150
140
130 1111111
120
110 •■•■■■■
.y
100 1111111
� 90
80
N
70
O.
60
50
40
30
20
10 MENU..-
0 0 0 0 0 0 0 0
0 0 0 0 0 0 0
M v1 O l� 00 T O V1 0
Flow,gpm
Pressure Loss Function
Design Area: 3; BFP Ref.: 157 (4000B DblChk, Size = 1.5); Inlet Node: 016-I; Outlet Node: 016-0
19.9-
18.9_ /
17.9: 15.9 psi @ 99.6 gpml'
16.9-
15.9
—
14.9- ._--
13.9- — —
CA
12.9: — —
Q- 11.9-
0 10.9"
7 "
Ch 9.9_—
cn
L 8.9
CL
7.9"
6.9" -
5.9"
4.9=
3.9-
2.9:
1.9=
0.9=
0 0 0 0 0
N O Cl
Flow,gpm
File:C:\dwg\Phoenix-Bersin\BerRes.dwg
Date 4/8/2015 Copyright©2002-2012 Tyco Fire Protection Products Page 24
Job :CHATEAU d'OEX Device Graphs
Pressure Loss Function
Design Area: 3; Valve Ref.: 156 (RSV-1, Size = 2); Inlet Node: 017-I; Outlet Node: 017-0
2.2 psi @ 99.6 gpm
2.36
Y
1.86
y
a-
d
U) 1.36
y
G) -
L
0.86
0.36 •
0 0 0 0 0 0 0 0 0
0 - Cl M 7 In
Flow,gpm
Pressure Loss Function
Design Area: 3; Valve Ref.: 158 (Riser Manifold, Size = 1.5); Inlet Node: 015-I; Outlet Node: 015-0
12.06 - —
11.06
10.06
9.06
fA 8.06
-
0_
7.06
-
tn 6.06
to
G) -
a 5.06
4.06
2.5 psi @ 99.6 gpm
3.06
2.06
1.06
0.06
n
Flow,gpm
File:C:\dwg\Phoenix-Bersin\BerRes.dwg
Date 4/8/2015 Copyright©2002-2012 Tyco Fire Protection Products Page 25
WATER FLOW TEST REPORT
PROJECT NAME: BERSIN RES JOB#
HYDRANT# &LOCATION: Near Site DATE: 1/3/1900
TEST BY: PAS Day or Week: MARCH TIME OF DAY: Noon MIN. OF FLOW:
WATER SUPPLIED BY: Rangeview MW
PURPOSE OF TEST: FIRE FLOW
DATA
FLOW HYDRANT(S) Al A2 A3
SIZE OPENING: 2.5 0
COEFFICIENT: 0.9 0
PITOT READING: 140 0
GPM: 1985 0 0
TOTAL FLOW DURING TEST: 1985 GPM
STATIC READING: 153 PSI RESIDUAL: 146 PSI
RESULTS: AT 20 PSI RESIDUAL 9736 GPM AT 0 PSI 050 GPM
ESTIMATED CONSUMPTION: 1985 GAL.
REMARKS:
150 -
140
130
120
110
100
•y 90
a
m 80
y 70
m
a 60
50
40
30
20
10
0 ,
0 500 1000 1500 2000 2500 3000 3500 4000
Flow,gpm
VicoWorldwide
Fire Protection Contacts www.tyco-fire.com
Products
RAPID RESPONSE Series LFII Residential Sprinklers
4.9 K-factor Pendent
Wet Pipe and Dry Pipe Systems
General Escutcheon reduces the accuracy to
which the pipe drops to the sprinklers
Description must be cut.
The Series LFII Residential Sprinklers
The TYCO RAPID RESPONSE have been designed with heat sensi- . `___,.
Series LFII Residential Pendent tivity and water distribution charac- ir irr.
and Recessed Pendent Sprinklers teristics proven to help in the control
(TY2234) are decorative, fast of residential fires and to improve the
response, frangible bulb sprinklers chance for occupants to escape or be
designed for use in residential occu- evacuated.
pancies such as homes, apart- f
ments, dormitories, and hotels. When Dry Pipe System Application --
aesthetics and optimized flow charac- The Series LFII Residential Pendent
teristics are the major consideration, and Recessed Pendent Sprinklers
the Series LFII Residential Sprinklers offers a laboratory approved option S rinkler
(TY2234)should be the first choice. for designing dry pipe residential p
sprinkler systems, whereas, most
The Series LFII Residential Sprinklers
residential sprinklers are laboratory Identification
are intended for use in the following approved for wet systems only.
scenarios: Number (SIN)
Through extensive testing, it has been
• wet and dry pipe residential sprin- determined that the number of design TY2234
kler systems for one-and two-family sprinklers (hydraulic design area)for
dwellings and mobile homes per the Series LFII Residential Pendent
NFPA 13D and Recessed Pendent Sprinklers Technical
• wet and dry pipe residential sprin- (TY2234) need not be increased
kler systems for residential occu- over the number of design sprinklers Data
pancies up to and including four (hydraulic design area) as specified
stories in height per NFPA 13R for wet pipe sprinkler systems, as is Approvals
accustomed for density/area sprinkler UL Listed for use with wet pipe and
• wet and dry pipe sprinkler systems systems designed per NFPA 13. dry pipe systems
for the residential portions of any Consequently, the Series LFII C-UL Listed for use only with wet pipe
occupancy per NFPA 13 Residential Sprinklers offer the systems
The recessed version of the Series features of non-water filled pipe in NSF Certified to NSF/ANSI 61
LFII Residential Sprinklers is intended addition to not having to increase the
for use in areas with finished ceilings. number of design sprinklers(hydraulic For details on these approvals, refer
It employs a two-piece Style 20 design area)for systems designed to to the Design Criteria section.
Recessed Escutcheon.The Recessed NFPA 13, 13D, or 13R.
Escutcheon provides 1/4 inch(6,4 mm) Maximum Working Pressure
of recessed adjustment or up to 1/2 NOTICE 175 psi (12,1 bar)
inch (12,7 mm) of total adjustment Discharge Coefficient
from the flush ceiling position. The The Series LFII Residential Pendent and K—4.9 GPM/psi1/2 (70,6 LPM/bar1/2)
adjustment provided by the Recessed Recessed Pendent Sprinklers(TY2234)
described herein must be installed and Temperature Rating
maintained in compliance with this 155°F(68°C)or 175°F(79°C)
document and the applicable stan-
IMPORTANT dards of the National Fire Protection Finishes
Always refer to Technical Data Association, in addition to the stan- Natural Brass
Sheet TFP700 for the "INSTALLER dards of any authorities having jurisdic- Pure or Signal White
WARNING" that provides cautions tion. Failure to do so may impair the Chrome Plated
with respect to handling and instal- performance of these devices. Physical Characteristics
lation of sprinkler systems and The owner is responsible for main- Frame Brass
components. Improper handling and taining their fireprotection system and Button
Sealing Assembly Copper
Beryllium can permanentlydamage devices inprer operatin
condi- Nickel w/TEFLON
a sprinkler system or its components tion. Contact the installing contractor Bulb(3 mm) Glass
and cause the sprinkler to fail to or sprinkler manufacturer with Compression Screw Bronze
operate in a fire situation or cause it any questions. Deflector Bronze
to operate prematurely. Ejection Spring Stainless Steel
Page 1 of 6 FEBRUARY 2014 TFP400
TFP400
Page 2 of 6
7/16"(11,1 mm) ESCUTCHEON
1/2"
Components: NOMINAL NPT PLATE SEATING 2-7/8" DIA.
1 Frame MAKE-IN SURFACE (73,0 mm)
2 - Button
3 Sealing Assembly 1 _
4 Bulb
5 Compression 2 : 1
Screw 2-1/4"6 Deflector*
INLs �� �
if ((57,2 mm) wM �®
4 1 / Oil1-5/8" STYLE 20
41,3 mm)
WRENCH RECESSED
,
5 -- mFLATS
Temperature �
� ■ Of ESCUTCHEON
rating is
indicated on
Deflector.
CROSS SECTION PENDENT RECESSED PENDENT
FIGURE 1
RAPID RESPONSE SERIES LFII RESIDENTIAL
PENDENT AND RECESSED PENDENT SPRINKLERS(TY2234)
2-7/8" DIA.
es
(73,0 mm)
7/16±1/8" 1/2"(12,7 mm)
_
(11,1±3,2 mm) 2-1/4" DIA. 1/4" (6,4 mm)
WRENCH RECESS
FACE OF --n— (57,2 mm) ~ (END "A" USED
SPRINKLER MOUNTING FOR TY2234)
FITTING PLATE
FIGURE 3
1mW-TYPE 6
V/ � �Ua I SPRINKLER WRENCH
MOUNTING WRENCH
SURFACE IN 1/8" RECESS
(3,2 mm)
1-3/8" (34,9 mm)
CLOSURE TY2234
1-1/8" (28,6 mm)
FIGURE 2
STYLE 20 RECESSED ESCUTCHEON FOR USE WITH THE
RAPID RESPONSE SERIES LFII RESIDENTIAL PENDENT SPRINKLER
(TY2234) PUSH WRENCH
IN TO ENSURE
Operation Residential Sprinkler Design Guide ENGAGEMENT
N When conditions exist that are WITH SPRINKLER
The glass bulb contains a fluid that outside the scope of the provided WRENCHING AREA
expands when exposed to heat.When criteria, refer to the Residential FIGURE 4
the rated temperature is reached, the Sprinkler Design Guide TFP490 for W-TYPE 7 RECESSED
fluid expands sufficiently to shatter the the manufacturer's recommendations SPRINKLER WRENCH
glass bulb, allowing the sprinkler to that may be acceptable to the local
activate and flow water. authority having jurisdiction. Ceiling Types
S stem T es Smooth flat horizontal, or beamed, or
Y yp sloped, in accordance with the 2013
Design Per the UL Listing, wet pipe and dry Edition of NFPA 13D, 13R, or 13 as
pipe systems may be utilized. Per the applicable.
Criteria C-UL Listing, only wet pipe systems
may be utilized. Hydraulic Design
The TYCO RAPID RESPONSE Refer to Technical Data Sheet TFP485 (NFPA 13D and 13R)
Series LFII Residential Pendent for the use of residential sprinklers in For systems designed to NFPA
and Recessed Pendent Sprinklers residential drypipe systems. 13D or NFPA 13R, the minimum
(TY2234)are UL and C-UL Listed for p p y
installation in accordance with this required sprinkler flow rates are
section.
TFP4OO
Page 3 of 6
given in Tables A and B as a func- InstallationStep C. Tighten the sprinkler into the
tion of temperature rating and the sprinkler fitting using only the W-Type 7
maximum allowable coverage areas. The TYCO RAPID RESPONSE Recessed Sprinkler Wrench (Figure 4).
The sprinkler flow rate is the minimum Series LFII Residential Pendent With reference to Figure 1, apply the
required discharge from each of the and Recessed Pendent Sprinklers W-Type 7 Recessed Sprinkler Wrench
total number of"design sprinklers"as (TY2234) must be installed in accor to the sprinkler wrench flats.
specified in NFPA 13D or NFPA 13R.
The number of "design sprinklers" dance with this section: Step D. After the ceiling has been
specified in NFPA 13D and 13R for wet installed or the finish coat has been
pipe systems is to be applied when General Instructions applied, slide on the Style 20 Closure
designing dry pipe systems. Do not install any bulb type sprin- over the Series LFII Residential
kler if the bulb is cracked or there is a Sprinkler and push the Closure over the
Hydraulic Design loss of liquid from the bulb. With the Mounting Plate until its flange comes in
(NFPA 13) sprinkler held horizontally, a small air contact with the ceiling.
For systems designed to NFPA 13, bubble should be present. The diam-
the number of design sprinklers is eter of the air bubble is approximately
to be the four most hydraulically 1/16 inch (1,6 mm).
demanding sprinklers. The minimum A leak-tight 1/2 inch NPT sprinkler
required discharge from each of the joint should be obtained by applying
four sprinklers is to be the greater of
the following: a minimum-to-maximum torque of 7
to 14 ft.-lbs. (9,5 to 19,0 Nm). Higher
• The flow rates given in Tables A levels of torque can distort the sprin-
or B as a function of temperature kler Inlet with consequent leakage or
rating and the maximum allowable impairment of the sprinkler.
coverage area.
Do not attempt to compensate
• A minimum discharge of 0.1 gpm/ft2 for insufficient adjustment in an
over the "design area" comprised Escutcheon Plate by under- or over-
of the four most hydraulically tightening the sprinkler. Re-adjust the
demanding sprinklers for actual position of the sprinkler fitting to suit.
coverage areas protected by the
four sprinklers. Series LFII Residential Pendent
Sprinklers
The number of "design sprinklers" The Series LFII Residential Pendent
specified in NFPA 13 for wet pipe Sprinklers must be installed in accor-
systems is to be applied when dance with the following instructions.
designing dry pipe systems.
Step 1. Install pendent sprinklers in
Dry Pipe System Water Delivery the pendent position with the deflector
When using the Series LFII Residential parallel to the ceiling.
Sprinklers(TY2234) in dry pipe sprin- Step 2. With pipe thread sealant
klersystems, the time for water applied to the pipe threads, hand-
delivery must not exceed 15 seconds tighten the sprinkler into the sprinkler
for the most remote operating fitting.
sprinkler.
Step 3. Tighten the sprinkler into
Obstruction to Water Distribution the sprinkler fitting using only the
Sprinklers are to be located in accor- W-Type 6 Sprinkler Wrench (Figure
dance with the obstruction rules 3). With reference to Figure 1, apply
of NFPA 13D, 13R, and 13 as appli- the W-Type 6 Sprinkler Wrench to the
cable for residential sprinklers as wrench flats.
well as with the obstruction criteria Series LFII Residential Recessed
described within the Technical Data
Pendent Sprinklers
Sheet TFP490. The Series LFII Residential Recessed
Operational Sensitivity Pendent Sprinklers must be installed
Sprinklers are to be installed with a in accordance with the following
deflector-to-ceiling distance of 1-1/4 to instructions.
4 inches. Step A. Install recessed pendent
sprinklers in the pendent position with
Sprinkler Spacing the deflector parallel to the ceiling.
The minimum spacing between sprin- Step B. After installing the Style 20
klers is 8 feet (2,4 m). The maximum Mounting Plate over the sprinkler
spacing between sprinklers cannot threads and with pipe thread sealant
exceed the length of the coverage applied to the pipe threads, hand
area(Table A or B) being hydraulically tighten the sprinkler into the sprinkler
calculated(e.g., maximum 12 feet for a fitting.
12 ft. x 12 ft. coverage area, or 20 feet
for a 20 ft. x 20 ft. coverage area).
TFP400
Page 4 of 6
WET PIPE SYSTEM
Minimum Flow and Residual Pressure(b,C)
Max.
Coverage Ordinary Temp.Rating Intermediate Temp.Rating
Area(a) 155°F(68°C) 175°F(79°C) Minimum
Deflector to Installation Spacing
Ft.x Ft. Flow Pressure Flow Pressure Ceiling Type Ft.
(m x m) GPM PSI GPM PSI (m)
(L/min) (bar) (L/min) (bar)
12 x 12 13 7.0 13 7.0 Smooth
(3,7 x 3,7) (49,2) (0,48) (49,2) (0,48) Ceilings
1-1/4 14 x 14 13 7.0 13 7.0
(4,3 x 4,3) (49,2) (0,48) (49,2) (0,48) 4 inches Recessed
Beamed using Style 20
16 x 16 13 7.0 13 7.0 Ceilings per Escutcheon or 8
(4,9 x 4,9) (49,2) (0,48) (49,2) (0,48) NFPA 13D non-recessed (2,4)
18 x 18 17 12.0 17 12.0 or 13R pe13R or 13NFPAD
(5,5 x 5,5) (64,3) (0,83) (64,3) (0,83) 1-1/4 to 1-3/4
inches below
20 x 20 20 16.7 20 16.7 bottom of
(6,1 x 6,1) (75,7) (1,15) (75,7) (1,15) beam.
(a) For coverage area dimensions less than or between those indicated,use the minimum required flow for the next highest coverage
area for which hydraulic design criteria are stated.
(b) Requirement is based on minimum flow in GPM(LPM)from each sprinkler.The associated residual pressures are calculated using
the nominal K-factor.Refer to Hydraulic Design under the Design Criteria section.
(c) For NFPA 13 residential applications,the greater of 0.1 gpm/ft2 over the design area of the flow in accordance with the criteria in
this table must be used.
TABLE A
WET PIPE SYSTEM
SERIES LFII RESIDENTIAL PENDENT AND RECESSED PENDENT SPRINKLERS(TY2234)
NFPA 13D, 13R,AND 13 HYDRAULIC DESIGN CRITERIA
DRY PIPE SYSTEM
Maximum Minimum Flow and Residual Pressure(b,c)
Coverage Ordinary Temp.Rating Intermediate Temp.Rating
Area(a) 155°F(68°C) 175°F(79°C) Minimum
Ft.x Ft. Deflector to Installation Spacing
(m x m) Flow Pressure Flow Pressure Ceiling Type Ft.
GPM PSI GPM PSI (m)
(L/min) (bar) (L/min) (bar)
12 x 12 13 7.0 13 7.0 Smooth
(3,7 x 3,7) (49,2) (0,48) (49,2) (0,48) Ceilings
14 x 14 14 8.2 14 8.2 4 inches
(4,3 x 4,3) (53,0) (0,57) (53,0) (0,57) Recessed
using Sle
16 x 16 15 9.4 15 9.4 Beamed Escutcheon20 or 8
(4,9 x 4,9) (56,8) (0,65) (56,8) (0,65) Ceilings per non recessed (2,4)
NFPA 13D per NFPA 13D,
18 x 18 18 13.5 18 13.5 or 13R
13R,or 13
(5,5 x 5,5) (68,1) (0,93) (68,1) (0,93) 1-1/4 to 1-3/4
inches below
20 x 20 21 18.4 21 18.4 bottom of
(6,1 x 6,1) (79,5) (1,27) (79,5) (1,27) beam.
(a) For coverage area dimensions less than or between those indicated,use the minimum required flow for the next highest coverage
area for which hydraulic design criteria are stated.
(b) Requirement is based on minimum flow in GPM(LPM)from each sprinkler.The associated residual pressures are calculated using
the nominal K-factor.Refer to Hydraulic Design under the Design Criteria section.
(c) For NFPA 13 residential applications,the greater of 0.1 gpm/ft2 over the design area of the flow in accordance with the criteria in
this table must be used.
TABLE B
DRY PIPE SYSTEM
SERIES LFII RESIDENTIAL PENDENT AND RECESSED PENDENT SPRINKLERS(TY2234)
NFPA 13D, 13R,AND 13 HYDRAULIC DESIGN CRITERIA
TFP4OO
Page 5 of 6
Care and Automatic sprinkler systems are
recommended to be inspected,
Maintenance tested, and maintained by a qualified
Inspection Service in accordance with
The TYCO RAPID RESPONSE Series local requirements and/or national
LFII Residential Pendent and Recessed codes.
Pendent Sprinklers(TY2234) must be
maintained and serviced in accordance Limited
with this section:
Before closing a fire protection system Warranty
main control valve for maintenance
work on the fire protection system that For warranty terms and conditions,
it controls, permission to shut down visit www.tyco-fire.com.
the affected fire protection system
must be obtained from the proper Ordering
authorities and notify all personnel
who may be affected by this action. Procedure
Absence of the outer piece of an
escutcheon, which is used to cover Contact your local distributor for
a clearance hole, can delay sprinkler availability. When placing an order,
operation in a fire situation. indicate the full product name and Part
The owner must assure that the Number(P/N).
sprinklers are not used for hanging Sprinkler Assembly
any objects and that the sprinklers Specify: Series LFII (TY2234), K=4.9,
are only cleaned by means of gently Residential Pendent Sprinkler,
dusting with a feather duster; other- (specify)temperature rating, (specify)
wise, non-operation in the event of finish, P/N (specify):
a fire or inadvertent operation may
155°F(68°C)
result. Natural Brass P/N 51-201-1-155
Sprinklers which are found to be Pure White(RAL 9010)* P/N 51-201-3-155
leaking or exhibiting visible signs of Signal White(RAL 9003) P/N 51-201-4-155
chrome Plated P/N 51-201-9-155
corrosion must be replaced.
175°F(79°C)
Automatic sprinklers must never be Natural Brass P/N 51-201-1-175
painted, plated, coated, or other- Pure White(RAL 9010)* P/N 51-201-3-175
wise altered after leaving the factory. Signal White(RAL 9003) P/N 51-201-4-175
Modified sprinklers must be replaced. chrome Plated P/N 51-201-9-175
Sprinklers that have been exposed to *Eastern Hemisphere sales only
corrosive products of combustion, but Recessed Escutcheon
have not operated, should be replaced Specify: Style 20 Recessed
if they cannot be completely cleaned Escutcheon with (specify*)finish, P/N
by wiping the sprinkler with a cloth or (specify*)
by brushing it with a soft bristle brush.
Care must be exercised to avoid *Refer to Technical Data Sheet TFP770
damage to the sprinklers - before, Sprinkler Wrench
during, and after installation. Specify: W-Type 6 Sprinkler Wrench,
Sprinklers damaged by dropping, P/N 56-000-6-387
striking, wrench twist/slippage, or the Specify: W-Type 7 Sprinkler Wrench,
like, must be replaced. Also, replace P/N 56-850-4-001
any sprinkler that has a cracked bulb
or that has lost liquid from its bulb.
(Ref. Installation Section.)
The owner is responsible for the
inspection, testing, and mainte-
nance of their fire protection system
and devices in compliance with this
document, as well as with the appli-
cable standards of the National Fire
Protection Association (e.g., NFPA
25), in addition to the standards of any
authorities having jurisdiction. Contact
the installing contractor or sprinkler
manufacturer regarding any questions.
TFP400
Page 6 of 6
GLOBAL HEADQUARTERS 11400 Pennbrook Parkway,Lansdale,PA 19446 I Telephone+1-215-362-0700
Copyright©2014 Tyco Fire Products,LP. All rights reserved. t co
TEFLON is trademark of The DuPont Corporation. Fire Protection Products
ES-A-4000B
Series 4000B AME S
Reduced Pressure Zone Assemblies FIRE&WATERWORKS
Sizes: 1/2" —2" (15—50mm)
9 �.- --
r I pf,P ..
-
71%yy� te'_
;y. i .0 2" (50mm)4000B-HC
i .
a 1/2"(15mm)4000B
Features Series 4000B Reduced Pressure Zone Assemblies are designed to protect
• Single access cover and potable water supplies in accordance with national plumbing codes and wa-
modular check construction ter authority requirements. This series can be used in a variety of installa-
for ease of maintenance tions, including the prevention of health hazard cross connections in piping
• Top entry - all internals
systems or for containment at the service line entrance.
immediately accessible This series features two in-line, independent check valves, captured springs
• Captured springs for safe and replaceable check seats with an intermediate relief valve. Its compact
maintenance modular design facilitates easy maintenance and assembly access. Sizes
1/2"- 1" (15-25mm) shutoffs have tee handles.
• Internal relief valve for reduced
installation clearances
• Replaceable seats for
Specifications
economical repair p
• Bronze body construction for A Reduced Pressure Zone Assembly shall be installed at each potential
health hazard location to prevent backflow due to backsiphonage and/or
durability - '/2" to 2" (15-50mm) backpressure. The assembly shall consist of an internal pressure differential
• Ball valve test cocks - relief valve located in a zone between two positive seating check modules
screwdriver slotted -1/2" to 2" with captured springs and silicone seat discs. Seats and seat discs shall be
(15-50mm) replaceable in both check modules and the relief valve. There shall be no
• Large body passages provides threads or screws in the waterway exposed to line fluids. Service of all inter-
low pressure drop nal components shall be through a single access cover secured with stain-
• Compact, space saving design less steel bolts. The assembly shall also include two resilient seated isolation
• No special tools required for valves, four resilient seated test cocks and an air gap drain fitting. The as-
servicing sembly shall meet the requirements of: USC Manual 8th Editiont; ASSE Std.
1013; AWWA Std. C511; CSA B64.4. The assembly shall be an Ames Com-
pany Series 4000B.
Job Name Contractor
Job Location Approval
Engineer Contractor's P.O.No.
Approval Representative
Ames product specifications in U.S.customary units and metric are approximate and are provided for reference only.For precise measurements,please contact Ames Technical Service.Ames reserves the right
to change or modify product design,construction,specifications,or materials without prior notice and without incurring any obligation to make such changes and modifications on Ames products previously or
subsequently sold.
www.amesfirewater.com
Materials Pressure — Temperature
Bronze body construction, silicone rubber disc material in the Suitable for supply pressures up to 175psi (12.06 bar)
first and second check plus the relief valve. Replaceable poly- and water temperature to 180°F(75°C)continuous.
mer check seats for first and second checks. Removable stain-
less steel relief valve seat. Stainless steel cover bolts.
Standardly furnished with NPT body connections. For optional Available Models
bronze union inlet and outlet connections, specify prefix U Suffix:
(1/2" -2")(15-50mm). Series 4000B furnished with quarter turn, B - quarter-turn ball valves
full port, resilient seated, bronze ball valve shutoffs. LBV - less ball valves
Standards LH - locking handle ball valves(open position)
AWWA C511-92, USC Manual 8th Edition, IAPMO File No. 1563 SH - stainless steel ball valve handles
HC -21/" inlet/outlet fire hydrant fitting (2" valve)
Approvals S - bronze strainer
Prefix:
e), c-� ous
- union connections
c
us
1013 B64.4 3/4"-2"(20-50mm)
(LBV models only)
Approved by the Foundation for Cross-Connection Control
and Hydraulic Research at the University of Southern
California.
Approval models QT, U.
IMPORTANT Inquire with governing authorities for
local installation requirements.
Weights — Dimensions _ �� - T A
II!1IInt?LiJIff !!iI11i
•
< L >
M < A
Suffix HC - Fire Hydrant Fittings dimension "A" = 251/16 (637mm)
MODEL SIZE(DN) DIMENSIONS STRAINER DIMENSIONS WEIGHT
A B C D L M N
in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm lbs. kg.
4000B"" 1/2 15 10 250 45/8 117 3% 86 11/4 32 512 140 3 76 2 51 4.50 2.0
40008 M3** 3/4 20 10% 273 5 127 31/2 89 11/2 38 6% 171 35/6 84 25/6 59 5.75 2.6
40008 M2*" 1 25 16% 425 512 140 3 76 21/2 64 91/2 241 41 114 25/6 59 12.25 5.6
40006" 114 32 173/8 44 116 150 31/2 89 21/2 64 11% 289 51/8 130 31/8 79 14.62 6.6
40006" 11/2 40 171/2 454 6 150 312 89 21/2 64 111/8 283 _ 51/2 149 33/4 95 16.32 7.4
40006"" 2 50 213/8 543 7% 197 41/2 114 31/4 83 131/2 343 _ 63/6 157 41/2 124 30.00 13.6
Strainer sold separately
**Approved by the Foundation for Cross-Connection Control and Hydraulic Research at the University of Southern California.
2
Capacity
Performance as established by an independent testing laboratory.
*Typical maximum system flow rate(7.5 feet/sec.,2.3 meters/sec.)
kPa psi 1/4" (8mm) kPa psi 1" (25mm)
O 138 20 0 207 30
J 117 17 -I 172 25
N
a) 96 14 , 138 20
3 76 11
y y 103 15
d
a 35 8 a 69 10 - - -
OP 0 .25 .50 .75 1 1.17 gpm 34 5
0 .95 1.9 2.9 3.8 4.5 Ipm 0 0
0 5 10 20 30 40 50 60 70 80 gpm
Flow Rate oP 0 19 38 76 114 152 190 228 266 304 Ipm
7.5 15 fps
2.3 4.6 mps
Flow Rate
kPa psi %" (1Omm) kPa psi 11/4" (32mm)
w 138 20 y 172 25
p117 17 J 138 20
y 96 14 3 103 15
H 76 11 y 69 10
i 55 8 i
a 35 5 _ a 34 5 -
AP 0 .25 .50 .75 1 1.25 1.50 2.5 3.1 gpm 0 0
0 .95 1.9 2.9 3.8 4.8 5.7 9.5 11.8 Ipm AP 0 10 20 30 40 50 60 70 80 gpm
Flow Rate 0 38 76 114 152 190 228 266 304 Ipm
5 7.5 10 15 fps
1.5 2.3 3.0 4.6 mps
Flow Rate
kPa psi 1/2" (15mm) 11/2" (4Omm)
*
172 25 kPa psi *
U3 0 207 30
J138 20 o 172 25
= 103 15 L 138 20
h 69 10 _ y 103 15 -
,o 2 69 10
cr. 35 5 a 34 5
Ap 0 1 2.5 5 7.5 10 12.5 15 gpm 0 0
0 3.8 9.5 19 28.5 38 47.5 57 Ipm pp 0 10 20 30 40 50 60 70 80 90 100 110 120 gpm
5 7.5 15 fps 0 38 76 114 152 190 228 266 304 342 380 418 456 Ipm
1.5 2.3 4.6 mps 5 7.5 10 15 fps
Flow Rate 1.5 2.3 3.0 4.6 mps
Flow Rate
3/4" (2Omm) 2" (5Omm)
kPa psi * kPa psi *
207 30 207 30
y 165 24 2 172 25
o
124 18 J 138 20
t 83 12 I - ---------o
2 103 15 -�
fA /
U) 41 6 - y 69 10
` 34 5
13- 0 0 - 2 a
0 0
0 2 6 10 14 18 22 26 30 34 38 42 46 gpm APO 20 40 60 80 100 120 140 160 180 200 gpm
OP 0 7.6 23 38 53 68 84 99 114 129 144 160175 Ipm 0 76 152 228 304 380 456 532 608 684 760 Ipm
7.5 15 fps 5 7.5 10 15 fps
2.3 4.6 mps 1.5 2.3 3.0 4.6 mps
Flow Rate
Flow Rate
3
For additional information, visit our web site at: www.amesfirewater.com
A
A M E S ISO 9001
FIRE&WATERWORKS A Division of Watts Regulator Company www.amesfirewater.com CERTIFIED
1427 North Market Blvd. • Suite #9 • Sacramento, CA 95834 • Phone: 916-928-0123 • Fax: 916-928-9333
ES-A-4000B 0625 ©Ames Fire&Waterworks, 2007
tqco I Fire & Building
Products
rapid response
HOME FIRE SPRINKLER SYSTEM
Technical Services: Tel: (800)381-9312/Fax: (800)791-5500
Figure 513D (13D) and 513D/R (13D/R) Riser Manifolds
1, 1-1/2, and 2 Inch (DN25, DN40, and DN50)
For NFPA 13D/13R Residential Sprinkler Systems
General Technical
Description Data
The Riser Manifolds described in this Approvals ■:■ f
technical data sheet provide the nec- The Figure 513D (13D) and 513D/R
essary waterflow alarm, pressure (13D/R) Riser Manifolds with a cover
gauge,and drain equipment in a single tamper switch for the waterflow alarm
assembly for use in NFPA 13D or 13R switch are UL Listed, ULC Listed, and
residential sprinkler systems as fol- FM Approved. .
lows: The Figure 513D (13D) and 513D/R
NFPA 13D (13D/R) Riser Manifolds without a
Figure 513D (13D) cover tamper switch for the waterflow
1 Inch11 e 513D alarm switch are UL Listed and FM(DN2r
Female Thread x Female Thread
Approved. . _ ---
NFPA 13D/13R Maximum Working Pressure
175 psi (12,1 bar) line prior to performing the alarm test.
❑ Figure 513D/R (13D/R) Assembly The second option is to install an In-
1-1/2 Inch (DN40) The manifold body of the Figure 513 is spector's Test Connection down-
Male Thread x Female Thread ductile iron, whereas the manifold stream of the Waterflow Alarm Switch.
Male Thread x Male Thread body of the Figure 13 is cast iron. The (3) Never remove any piping compo-
Figure 513D/R (13D/R) two assemblies are completely inter- nent nor correct or modify any piping
2 Inch (DN50) changeable in function, application, deficiencies without first depressuriz-
Groove x Groove and end-to-end laying length. ing and draining the system.
Male Thread x Groove Finish Step 1. Install the manifold body with
The variety of sizes and end connec- Red painted. the flow arrow pointing in the down-
tions allow cost effective and easy stream position using threaded con-
transition to check valves, control Installation nections and/or listed mechanical
valves, and system piping. The Riser grooved connections, as applicable.
Manifolds may be installed in either the The Riser Manifolds may be installed Step 2. Connect the drain line, and
horizontal (flow switch on top)or verti- in either the horizontal (flow switch on then close the drain valve.
cal (flow going up). top) or vertical (flow going up). The
inlet of the Riser Manifold may be di- Step 3. Refer to Figure 4 for wiring
WARNING rectly connected to a shut-off control guidance. All wiring must be per-
The Riser Manifolds described herein valve. formed in accordance with the Author-
must be installed and maintained in ity Having Jurisdiction and/or the Na-
compliance with this document, as NOTES tional Electrical Code.
well as with the applicable standards (1) Where applicable pipe thread Step4. Place the system in service by
of the National Fire Protection Asso- pp y
sealant is to be applied sparingly. Use filling the system with water. When fill-
ciation, in addition to the standardsany other authorities having r/sdic-of of non-hardening pipe thread sealant ing the system, partially open the con-
tion. Failure to do so may impair the is recommended. trol valve to slowly fill the system. Fill-
performance of these devices. (2) Provisions for an alarm test flow ing the system slowly will help avoid
must be made. The alarm test flow is damaging the waterflow alarm switch.
The owner is responsible for maintain to be through an orifice having a flow After the system is fully pressurized,
ing their fire protection system and de- capacity equal to or smaller than the completely open the control valve.
vices in proper operating condition. smallest orifice sprinkler in the system.
The installing contractor or sprinkler One of two options can be considered. Step 5. Secure all supply valves
manufacturer should be contacted The first option is to temporarily install open.
with any questions. a test orifice in the outlet of the drain
Page 1 of 6 APRIL, 2006 TFP960
Page 2 of 6 TFP960
NO. DESCRIPTION QTY. P/N 1 1"Manifold Body, 3-1/2"Female x Female NPT... 1 N/A (88,9mm)2 WaterflowAlarm Switch:
VSR-SF modified with - L ,1/2"
Female x Femal
Paddle,UL/FM 1 971-096-01
VSR-SF modified with
Paddle and Cover Tamper
Switch,ULC/FM 1 976-519-01
3 200Pressure
rkPa
Water
'
Waterr Pree sss ure Gauge .. 1 2343
3 =1 2
NOTES: /
1. Approximate weight,7.5 lbs.(3,4 kg). Waterflow 1.1
2. ULC Listed Manifolds are equipped with4111
_
Cover Tamper Switches installed internal 9-3/4"
to the Waterfow Alarm Switches. (247,7 mm) MP
3. CH:Common Hardware laPPIMIIII
3-5/8" 2-7/8"
(92,1 mm) . 1 (73,0 mm)
lII;ILLi! f
3/4"NPT
Drain Valve 4-1/2"
(Normally Closed) (114,3 mm)
10"
(254,0 mm)
FIGURE 1
1 INCH(DN25)RISER MANIFOLD ASSEMBLY AND DIMENSIONS
NO. DESCRIPTION QTY. P/N f , in,
1 1-1/2"Manifold Body, 3-1/2"Male x Female NPT 1 N/A (88,9 mm) 7 lMale x Male NPT 1 N/A ,�MPS u I _
2 WaterflowAlarm Switch: ` d
VSR-SF modified with
Paddle,UUFM 1 971-096-00
VSR-SF modified with
Paddle and Cover Tamper
Switch,ULC/FM 1 976-519-02
3 300 psi/2000 kPa
Water Pressure Gauge .. 1 2341 3 / 2
NOTES: Waterfow 1.1 1
1. Approximate weight,8.7 lbs.(3,9 kg). .
4111 =
2. ULC Listed Manifolds are equipped with
Cover Tamper Switches installed internal 11-3/8" iHiIiiiiii
to the Waterfow Alarm Switches. (288,9 mm)
3. CH:Common Hardware .
4-1/2"
it I
5-3/8" (114,3 mm)
(136,5 mm) _
huLl!. 1"
NPT
Drain Valve IFS 2-1/8"
(Normally Closed) (54,0 mm)
10"(254,0 mm)
Male x Female NPT
Manifold
11-1/8"(282,6 mm)
Male x Male NPT
Manifold
FIGURE 2
1-1/2 INCH(DN40)RISER MANIFOLD ASSEMBLY AND DIMENSIONS
TFP960 Page 3 of 6
NO. DESCRIPTION QTY. P/N _: ,_r
1 2"Manifold Body, 3-1/2"
Groove x Groove 1 N/A (88,9 mm)
Male NPT x Groove 1 N/A
2 Waterflow Alarm Switch: —� .CD --
VSC with Paddle,
UL/FM 1 976-357-01
VSC with Paddle and
Cover Tamper Switch,
ULC/FM 1 976-520-01
3 kPa — 3
/ 2
Water Press
ure Gauge .. 1 2341 I=1 Optionally
Grooved or
NOTES: 1 Waterflow Male NPT
1. Approximate weight,11.0 lbs.(5,0 kg).
\ Supply End
I
Connection
2. ULC Listed Manifolds are equipped with
Cover Tamper Switches installed internal 12"
to the Waterflow Alarm Switches. (304,8 mm)
II
3. CH:Common Hardware }
4-1/2"
5-7/16" W (114,3 mm)
(138,1 mm)
III 11011 U 1"
NPT
FIGURE 3, Drain Valve 2-1/4"
(Normally Closed) (57,2 mm)
2 INCH(DN50)RISER MANIFOLD ASSEMBLY
AND DIMENSIONS 13"(330,2 mm)
Groove x Groove,
Male NPT x Groove
result in operation of the associated recorded for the system when it was
Care and
alarms. Consequently, notification first installed.
must be given to the owner and the fire
Maintenance department, central station, or other Alarm Test Procedure With A Test
signal station to which the alarms are Orifice (See Installation Note 2)
The following inspection procedure connected, and notification must be
must be performed as indicated, in ad- given to the building occupants. Step 1. Temporarily install a test ori-
dition to any specific requirements of fice in the drain line outlet.
the NFPA, and any impairment must Before closing a fire protection system
be immediately corrected. control valve for inspection or mainte- Step 2. Fully open the drain valve.
nance work on the fire protection sys- Make certain that drainage water will
The owner is responsible for the in- tern that it controls,permission to shut not cause any damage or injury.
spection, testing, and maintenance of down the effected fire protection sys- Step 3.Verify operation of the associ-
their fire protection system and de- tern must first be obtained from the
vices in compliance with this docu- proper authorities and all personnel ated alarms.
ment, as well as with the applicable who may be affected by this action Step 3. Close the drain valve.
standards of the National Fire Protec- must be notified.
tion Association (e.g., NFPA 25), in Step 4. Remove the test orifice from
addition to the standards of any After placing a fire protection system the drain line outlet.
authority having jurisdiction. The in- in service, notify the proper authorities
stalling contractor or product manufac and advise those responsible for moni- Alarm Test Procedure With An
turer should be contacted relative to toring proprietary and/or central sta- Inspector's Test Connection (See
any questions. tion alarms. Installation Note 2)
It is recommended that automatic Flow Test Procedure Step 1.Fully open the Inspector's Test
sprinkler systems be inspected, Connection Valve. Make certain that
tested, and maintained by a qualified Step 1. Fully open the drain valve. drainage water will not cause any dam-
Inspection Service in accordance with Make certain that drainage water will age or injury.
local requirements and/or national not cause any damage or injury.
codes. Step 2.Verify operation of the associ
Step 2. Verify that the residual (flow- ated alarms.
NOTES ing) pressure indicated by the pres- Step 3. Close the Inspector's Test
No attempt is to be made to repair any sure gauge is no less that originally Connection Valve.
Riser Manifold component in the field. recorded for the system when it was
Only the pressure gauge or waterflow first installed.
alarm switch can be replaced. If any Step 3. Close the drain valve.
other problems are encountered the
entire riser manifold must be replaced. Step 4.Verify that the static(not flow
ing) pressure indicated by the pres-
The flow and alarm test procedure will sure gauge is no less that originally
Page 4 of 6 TFP960
SWITCH TERMINAL CONNECTIONS
UNINSULATED CLAMPING SEVERED
LOOPED SECTION CAUTION: PLATE STRIPPED
SINGLE An uninsulated section of a TERMINAL ENDS
CONDUCTOR single conductor is not � SEPARATE
permitted to be looped around CONDUCTORS
CLAMPING , the terminal and serve as two % °1fr
PLATE separate connections.The
TERMINAL wire must be severed to serve ', INCOMING
Nkomo as two separate connections,
41r-o- thereby providing supervision
of the connection in the event
that the wire becomes
dislodged from the terminal.
OUTGOING
IMPROPER CONNECTION METHOD PROPER CONNECTION METHOD
WATERFLOW SWITCH TYPICAL ELECTRICA CONNECTIONS
CONTACTS SPDT(Form C) END OF LINE
40 LOCAL RESISTOR
CONTACT RATING .... 5A @ 125 VAC SIGNAL
2.5A @ 30 VDC DEVICE
NC
NO NC yo_er
NO• �G NC M
1 I COM
COM CONTROL
POWER PANEL
NO FLOW NON-SUPERVISED STYLE B/CLASS B
CONDITION CIRCUIT SUPERVISED CIRCUIT
(SEE NOTE)
NOTE:
For supervised circuits,see"Switch Terminal Connections"above.The Waterflow Alarm
Switch has two switches,one can be used to operate a central station,proprietary or remove
signaling unit,while the other contact is used to operate a local audible or visual annunciator.
COVER TAMPER SWITCH(ULC ASSEMBLIES ONLY)
CONTACTS SPDT(Form C)
CONTACT RATING .... 3A @ 250 VAC
5A @ 125 VAC
1mA@5VDCmin.
NO I\ • NC
COM
CONTACTS SHOWN
WITH COVER IN PLACE
FIGURE 4
WIRING GUIDANCE
TFP960 Page 5 of 6
Limited Ordering
Warranty Information
Products manufactured by Tyco Fire& Riser Manifold:
Building Products (TFBP) are war- Specify;Size(specify),Figure(specify
ranted solely to the original Buyer for 513D or 513D/R, (specify connection
ten (10)years against defects in mate- type inlet x outlet) Riser Manifold
rial and workmanship when paid for (specify-without or with)a cover tarn-
and properly installed and maintained per switch for the waterflow alarm
under normal use and service. This switch, P/N (specify).
warranty will expire ten (10) years
from date of shipment by TFBP. No NOTES
warranty is given for products or corn- Orders for Figure 513D or513D/R may
ponents manufactured by companies be filled with a Figure 13D or 13D/R,
not affiliated by ownership with TFBP respectively. The two assemblies are
or for products and components which completely interchangeable in func-
have been subject to misuse,improper tion, application, and end-to-end lay-
installation, corrosion, or which have ing length.
not been installed, maintained, modi-
If a ULC Listing is required, the Riser
fied or repaired in accordance with ap- Manifold must be ordered with a cover
plicable Standards of the National Fire tamper switch for the waterflow alarm
Protection Association, and/or the switch.
standards of any other Authorities
Having Jurisdiction. Materials found
by TFBP to be defective shall be either UL/ULC/FM Assemblies
repaired or replaced, at TFBP's sole With Cover Tamper Switch
option. TFBP neither assumes, nor 1 Inch(DN25)
authorizes any person to assume for it, FT x FT P/N 4085
any other obligation in connection with 1-1/2 Inch(DN40)
MT x FT P/N 4088
the sale of products or parts of prod- 1-1/2 Inch(DN40)
ucts.TFBP shall not be responsible for MT x MT P/N 4089
sprinkler system design errors or inac- 2 Inch(DN50)
curate or incomplete information sup- G x G P/N 4093
plied byBuyerBuyer's re re- 2 Inch(DN5o)
or y repre- x G P/N 4094
sentatives.
In no event shall TFBP be liable, in UL/FM Assemblies
contract, tort, strict liability or under Without Cover Tamper Switch
other legal theory, for incidental, 1 Inch(DN25)
any g y FT x FT P/N 4047
indirect,special or consequential dam- 1-1/2 Inch(DN40)
ages, including but not limited to labor MT x FT P/N 4057
charges, regardless of whether TFBP 1-1/2 Inch(DN40)
was informed about the possibility of MT x MT P/N 4058
such damages, and in no event shall 2 Inch(GN50)
g G x G P/N 4059
TFBP's liability exceed an amount 2 Inch(DN50)
equal to the sales price. MT x G P/N 4064
The foregoing warranty is made in lieu
of any and all other warranties. ex- Replacement Parts:
press or implied, including warranties Specify: (description)for use with Fig-
of merchantability and fitness for a par- ure 513D, 513D/R, 13D, or 13D/R
ticular purpose. Riser Manifold, P/N (Ref. Figure 1, 2
This limited warranty sets forth the ex or 2, as applicable).
clusive remedy for claims based on
failure of or defect in products, materi-
als or components, whether the claim
is made in contract, tort, strict liability
or any other legal theory.
This warranty will apply to the full ex-
tent permitted by law.The invalidity, in
whole or part, of any portion of this
warranty will not affect the remainder.
Page 6 of 6 TFP960
TYCO FIRE&BUILDING PRODUCTS,451 North Cannon Avenue,Lansdale, Pennsylvania 19446
tLfCfl I Flow Tyco Fire
Control Products
BlazeMaster °
FIRE SPRINKLER PIPE & FITTINGS SUBMITTAL SHEET
TYCO FIRE PRODUCTS
451 North Cannon Avenue
Lansdale, Pennsylvania 19446
www.tyco-fire.corn
TECHNICAL SERVICES
TEL: (800) 381-9312 • Fax: (800) 791-5500
E-MAIL: techserv@tycofp.com
-1 (
i;t
No. 19-1.5
TD915
Ad.
4-1.1.20
9/2001
sO)
Introduction
Tyco Fire Products (TFP) BlazeMaster°CPVC pipe and the same time, they provide superior heat resistance and
fittings are designed exclusively for use in wet pipe strength as compared to traditional CPVC and PVC piping
automatic fire sprinkler systems.They are made from a materials used in the plumbing trade. Various adapters are
specially developed thermoplastic compound composed of available to connect CPVC pipe to metallic piping.All female
post chlorinated polyvinyl chloride (CPVC) resin and state of pipe thread adapters have brass inserts for durability.
the art additives. TFP BlazeMaster®CPVC products are Grooved adapters connect directly to grooved end valves
easier to install than traditional steel pipe systems, and at and metallic pipe, with flexible grooved end couplings.
Technical Data
Sizes: 3/4"-3" Manufacture Source: U.S.A.
Maximum Working Pressure: 175 psi Material:
Approvals: UL, FM, CUL, NSF, Dade County, LPCB, Pipe: ASTM F442, SDR 13.5
MEA, and the City of Los Angeles Fittings: ASTM F438 (Sch. 40) and
Note: See current TFP BlazeMaster Installation Instructions and ASTM F439 (Sch. 80)
Technical Manual,for exact listing/approval information Color: Orange
Pipe
Nom.Pipe Size Avg.O.D. Inches Avg. I.D. Inches Wt.Lbs./Ft. Wt.H2O filled Pipe Lbs./Ft. Ft. of Pipe per Lift Wt.per Lift Lbs.
3/4" 1.050 0.874 0.17 0.43 7875 1413
1" 1.315 1.101 0.26 0.67 5040 1320
11/4" 1.660 1.394 0.42 1.07 2835 1191
11/2" 1.900 1.598 0.55 1.40 2205 1136
2" 2.375 2.003 0.86 2.20 1260 1063
21/2" 2.875 2.423 1.26 3.22 1215 1531
3" 3.500 2.952 1.87 4.79 720 1344
Fittings
T/O
IN T/O 7ip
T/O �
45° Elbow _ �* Reducing _ 90° Elbow =
�� 90° Elbow -® T/OZ vo
-111li -III
Part No. Size Sch. T/O Wt. Part T/O Wt. Part No. Size Sch. T/O Wt.
Size Sch.
80050 3/4" 40 3/8" 0.08 lb. No. 1 2 lb. 80025 3/4" 40 9/16" 0.09 lb.
80051 1" 40 3/8" 0.11 lb. 80032 1" x3/4" 40 11/16" 13/,6" 0.16 80026 1" 40 3/4" 0.14 lb.
80052 11/4" 40 3/4" 0.20 lb. 80027 11/4" 40 '/e" 0.21 lb.
80053 1'/2" 80 7/16" 0.31 lb. 80028 11/2" 80 11/16" 0.40 lb.
_80054 2" 80 3/4" 0.56 lb. 80029 2" 80 11/4" 0.79 lb.
80055 21/2" 80 3/4" 0.89 lb. 80030 21/2" 80 11/2" 1.14 lb.
80056 3" 80 1" 1.19 lb. 80031 3" 80 113/16" 1.82 lb.
1
I
T/O -T/O I L
,____
Tee _._._._.__. T'O Reducing �p�_ Cross _._/._. I . _
Cross
n
I
T/O
T/O T/O � -T/O _ �
T/O' MU. T/O'
T/O I l T/O
Part No. Size Sch. T/O Wt. Part T/O Wt. Part No. Size Sch. T/O Wt.
80000 3/4" 40 5/8" 0.11 lb. No. Size Sch. 1 2 lb. 80009 3/4" 40 9/16" 0.13 lb.
80001 1" 40 3/4" 0.19 lb. 80015 1"x3/4" 40 11/16" 11/16" 0.28 80010 1" 40 15/16" 0.23 lb.
80002 11/4" 40 7/8" 0.26 lb. 80011 11/4" 40 15/16" 0.34 lb.
80003 11/2" 80 1" 0.51 lb. 80012 11/2" 80 11/16" 0.67 lb.
80004 2" 80 13/8" 0.90 lb. 80013 2" 80 13/8" 1.00 lb.
80005 21/2" 80 19/16" 1.59 lb. 80014 21/2" 80 19/16" 1.91 lb.
80006 3" 80 111/16" 2.41 lb. 80008 3" 80 113/16" 2.89 lb.
CFRTIFIF
"CONIPPNY
-1-TIO T/O -1 -T/O
7
Coupling _._._._._._._._._. Cap _A.r_ Reducer _._.__._._._._._.
Bushing = `
Part No._ Size Sch._T/O Wt.
Part No. Size Sch. T/O Wt. Part No. Size Sch. T/O Wt. - 80200 1" x 3/4" 40 7/16" 0.04 lb.
80075 3/4" 40 1/8" 0.07 lb. 80100 3/4" 40 5/16" 0.04 lb. 80201 11/4"x3/4" 40 7/16" 0.11 lb.
80076 1" 40 1/8" 0.11 lb. 80101 1" 40 3/8" 0.06 lb. 80202 11/4"x 1" 40 5/16" 0.12 lb.
80077 11/4" 40 3/16" 0.12 lb. 80102 11/4" 40 1/2" 0.10 lb. 80203 11/2" x3/4" 80 5/8" 0.16 lb.
80078 11/2" 80 3/16" 0.25 lb. 80103 11/2" 80 5/8" 0.20 lb. 80204 112"x 1" 80 1/2" 0.14 lb.
80079 2" 80 3/16" 0.38 lb. 80104 2" 80 5/8" 0.31 lb. 80205 11/2" x 11/4" 80 3/8" 0.17 lb.
80080 21/2" 80 3/16" 0.67 lb. 80105 21/2" 80 7/8" 0.58 lb. 80206 2" x 3/4" 80 3/4" 0.27 lb.
80081 3" 80 3/16" 0.91 lb. 80106 3" 80 1" 0.88 lb. 80207 2" x 1" 80 11/16" 0.26 lb.
80208 2" x 11/4" 80 9/16" 0.24 lb.
T/O 80209 2" x 11/2" 80 7/16" 0.19 lb.
Grooved MI
80215 2'/2"x 1" 80 115/16" 0.42 Ib.
Coupling 0.D. 80214 21/2" x 11/4" 80 13/4" 0.45 Ib.
Adapter 80213 21/20 x 11/2" 80 15/8" 0.46 lb.
80211 21/2"x 2" 80 19/16" 0.29 lb.
Part No. Size Sch. T/O Wt. Pipe OD 80210 3" x 2" 80 2 3/16" 0.72 lb.
80160 11/4" x 11/4" Grooved 40 2 5/16" 0.78 lb. 11/4" (1.660") 80212 3" x 21/2" 80 115/16" 0.47 lb.
80161 11/2" x 11/2" Grooved 80 2 5/16" 0.95 lb. 11/2" (1.900")
80162 2" x 2" Grooved 80 2 5/16" 1.42 lb. 2" (2.375")
80163 21/2" x 21/2" Grooved 80 2 5/16" 2.28 lb. 2'/2" (2.875") '
J.
80164 3" x 3" Grooved 80 21/4" 3.00 lb. 3" (3.500") Reducing ` '-. -.-.-
80168 3" x 76.1mm Grooved 80 21/4" 2.72 lb. 76.1mm (3.000") Tee _L
T/0' T/0'
in T/O Part T/O Wt.
No.80132 Size Sch. 1 2 3 lb.
Female 3/4"x x 1
3/4" " 40 3/4" 3/4" 5/8" 0.14
liTtill
Adapter .� 80133 1"x3/4"x3/4" - -
40 /2"_ "/,6" 3/4" 0.14
80134 1" x 3/4"x 1" 40 5/8" 3/4" 3/4" 0.17
Part No. Size Sch. T/O Wt. 80260 1" x 1" x 3/4" 40 3/40 3/40 11/16" 0.16
80142 3/4"x 3/4" NPT 40 5/8" 0.41 lb. 80135 11/4" x 1"x3/4" 40 7/16" 3/4" 15/16" 0.21
80145 1"x 1" NPT 40 3/4" 0.63 lb. 80136 _ 1'/4"x 1"x 1" 40 11/16" 3/4" 15/16" 0.22
80146 11/4"x 11/4" NPT 40 7/8" 1.03 lb. 80137 _ 11/4"x 1"x 11/4" _ 40 13/,6" 5/160_ 3/16" 0.26
80147 11/2"x 11/2" NPT 80 1" 1.42 lb. 80261 11/4"x 11/4"x 3/4" 40 5/8" 5/8" 7/8" 0.23
80148 2"x 2" NPT 80 13/8" 2.66 lb. 80262 11/4" x 11/4" x 1" 403/4" 3/4" /8" 0.26
80138 1'/4" X 11/4" X 11/2" 80 1" 1" 1" 0.43
T/0 80140 11/2" x 11/4" x 3/4" 80 '/2" 5/8" 1" 0.36
'4.••_ 80141 11/2" x 11/4" x 1" 80 1/2" 5/8" 11/8" 0.38
Male 80263 11/2"x 11/2"x3/4" 809/,6" 9/16"_ 1- " 0.36
Adapter . ...,, 80264 11/2" x 11/2"x 1" 809/,6" 9/16" 1- " 0.38
80275 11/2"x 11/2"x 11/4" 80 7/8" 7/8" 1" 0.45
Part No. Size Sch. T/O Wt. 80265 2" x 2" x 3/4" 80 3/4" 3/4" 13/8" 0.61
80157 3/4" x 3/4" NPT 40 15/16" 0.33 lb. 80266 2" x 2"x 1" 80 7/8" 7/8" 13/8" 0.66
80158 1" x 1" NPT 40 13/8" 0.56 lb. 80274 2"x 2" x 11/4" 80 1" 1" 13/8" 0.74
80267 2"x 2"x 11/2" 80 11/8" 11/8" 13/8" 0.78
T/O 80271 21/2" x 21/2"x 1" 80 111/16" 1 11/16"" 19/16" 1.43
80272 21/2"x 21/2"x 11/4" 80 111/16" 111/16" 19/16" 1.46
Reducing J 80273 21/2" x 21/2"x 11/2" 80 111/16" 111/16" 19/16" 1.48
Coupling 80276 21/2"x 21/2"x 2" 80 111/16" 111/16" 19/16" 1.50
80270 3"x 3" x 11/2" 80 13/4" 13/4" 113/16" 2.28
Part No. Size Sch. T/O Wt. 80268 3"x 3"x 2" 80 13/4" 13/4" 13/4" 2.25
80220 1" x3/4" 40 1/8" 0.08 lb. 80269 3"x 3"x 21/2" 80 13/4" 13/4" 115/16" 2.44
4
iso
8""2
CERTIFIED COMPANY
T/O T/O
Sprinkler Head Adapter _ �' Sprinkler HeadAdapter _ri with Brass Threaded Insert
IT
with Brass Threaded Insert
Part No. Size Sch. T/O Wt. Part No. Size Sch. T/O Wt.
80175E 3/4" x 1/2" NPT 80 7/16" 0.20 Ib. 80175W 3/4" x1/2" NPT 40 7/16" 0.19 Ib.
80176E 1" x 1/2" NPT 80 716" 0.22 Ib. 80176W 1" x1/2" NPT 40 7/16" 0.18 Ib.
80177WL 3/4" x1/2" NPT 40 9/16" 0.16 Ib.
80179 1 x3/4" NPT 40 3/4" 0.43 Ib.
—T/O' J jL._
T/O ^4 j
Back-to-Back Cross -.--.--.-. .-i_. .-.--.--.-
Sprinkler Head Adapter
-11574011111 with Brass Threaded Insert
(Spigot) ----- —T/O'
with Brass Threaded Insert
T/O I T/O:
Part No. Size Sch. T/O Wt. Part T/O Wt.
80177L 3/4" x1/2" NPT 40 1/2" 0.16 Ib. No. Size Sch. 1 2 Ib.
80178 1" x'/2" NPT 40 1/2" 0.20 Ib. 80462 1"x 1"x'/2" NPT x'/2" NPT 40 5/8" 1'/3" 0.46
80463 1"x 1"x'/2" NPT x'/2" NPT 40 5/8" 15/16" 0.47
T/O'
Sprinkler Head Adapter
o
90 Elbow T/o= Back-to-Back Tee T/
with Brass Threaded Insert with Brass Threaded Insert .
�i`���
T/O 2 T/O
Part T/O Wt. Part Size Sch. T/O Wt.
No. Size Sch. 1 2 Ib. No. 1 2 lb.
80199 3/4" x 1/2" NPT 40 5/8" 15/16" 0.20 80459 1" x 1/2" NPT x1/2" NPT 40 11h6" 15/16" 0.48
80189 1" x 1/2" NPT 40 13/16" 13/16" 0.26 80460 1" x1/2" NPT x1/2" NPT 40 11h6" 11/8" 0.46
Part T/O Wt.
No. Size Sch. 1 2 3 lb.
80250 3/4"x 3/4"x 1/2" NPT 40 5/8" 5/8" 1" 0.22
80251 1"x 1"x'/2" NPT 40 11/168 11/16" 13/16" 0.29
80249 1"x 1" x 1" NPT 40 15/16" 15/16" 1'/16" 0.73
Sprinkler Head Adapter J T/O" 80256 11/4" x 1"x 1/2" NPT 40 3/46" 9/16" 11/8" 0.30
Tee ------- ------� 80252 11/4"x 11/4"x 1/2" NPT 40 3/46" 7/16" 11/8" 0.31
with Brass Threaded Insert • —' • 80257 11/2"x 11/4"x 1/2" NPT 80 9/16" 5/8" l'/16" 0.43
T/0'-1—I T/02 80254 11/2"x 11/2"x 1/2" NPT 80 9/16" 9/16" 1'/16" 0.46
80258 2"x 11/2"x 1/2" NPT 80 1/2" 5/8" 15/8" 0.56
80253 2"x 2"x 1/2" NPT 80 1/2" 1/2" 15/8" 0.62
Limited Warranty
Products manufactured by Tyco Fire Products are warranted solely to the original Buyer for ten(10)years against defects in
material and workmanship when paid for and properly installed and maintained under normal use and service. This warranty will
expire ten(10)years from date of shipment by Tyco Fire Products. No warranty is given for products or components manufactured
by companies not affiliated by ownership with Tyco Fire Products or for products and components which have been subject to
misuse,improper installation,corrosion,or which have not been installed,maintained,modified or repaired in accordance with
applicable Standards of the National Fire Protection Association(NFPA),and/or the standards of any other Authorities Having
Jurisdiction. Materials found by Tyco Fire Products to be defective shall be either repaired or replaced,at Tyco Fire Products sole
option. Tyco Fire Products neither assumes,nor authorizes any person to assume for it,any other obligation in connection with the
sale of products or parts of products. Tyco Fire Products shall not be responsible for sprinkler system design errors or inaccurate or
incomplete information supplied by Buyer or Buyer's representatives.
IN NO EVENT SHALL TYCO FIRE PRODUCTS BE LIABLE,IN CONTRACT,TORT,STRICT LIABILITY OR UNDER ANY OTHER LEGAL
THEORY,FOR INCIDENTAL,INDIRECT,SPECIAL OR CONSEQUENTIAL DAMAGES,INCLUDING BUT NOT LIMITED TO LABOR
CHARGES,REGARDLESS OF WHETHER TYCO FIRE PRODUCTS WAS INFORMED ABOUT THE POSSIBILITY OF SUCH DAMAGES,
AND IN NO EVENT SHALL TYCO FIRE PRODUCT'S LIABILITY EXCEED AN AMOUNT EQUAL TO THE SALES PRICE.
THE FOREGOING WARRANTY IS MADE IN LIEU OF ANY AND ALL OTHER WARRANTIES EXPRESS OR IMPLIED,INCLUDING
WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.
�[ICO/Flow Control IP Tyco Fire
roducts
.y
hi ] - �_ j.,� _�� for
WET FireFR / iYR• I 4 I
• 1
• • . Time Tested. . . 15 years and millions of gallons installed
if ' i
•,. '. V
. -- . I ,•
FireFighte"TM iv
1ne ahler ' i Freeze Protection Fluid
Fred*praiccilan fJln�a
'5 r 1loy,pro F�•{I• ....NtFM•TOVIC.
5o F U Glycerine solutions for CPVC
wet fire sprinkler systems
FireFighterTM nr i
Freeze Protection Fluid
Propylene Glycol solutions for
Fire Fighter-PGmost wet fire sprinkler systems
Fr4eic Pr t tdon F+wld
`-1 F IIu� pr Fscl■pn,rloIM•TiaXIe,
z, r4 il.• Easy to Use
�iEsykL SiFiEM�r>FI •OO NST plLlfrE
�111�14 wer rir.�+o�a•t7�o. • •
in- -- J -•.- Available in 5 gallon containers, 55
gallon drums, totes or tank trucks.
~ "'= • Ready to use or concentrates
^_ � :—=-- I • Custom blends available
-6• -•.7Aall
J
� ,�, Easy to Maintain
,_' =
Instruments necessary 1IJ
to test the fluids and
maintain the protection
Hydrometer
The Noble Company RefractometerNa it--:-----------------
800-878- 5788 4 --
r
www.noblecompany.com ••
FireFighter is a trademark of The Noble Company. Digital Refractometer
PRODUCT DESCRIPTION FDA References
FireFighter GL and FireFighter PG are non-toxic*' anti- GRAS:FireFighter GL and FireFighter PG are consid-
freezes designed specifically for fire protection systems. ered"Generally Regarded as Safe"(GRAS)by the Fed-
These products are used in place of water and other wa- eral Food and Drug Administration.
ter-like fluids in sprinkler systems where freezing may
either cause damage or interfere with the functioning of
systems or equipment,and/or toxicity to humans or ani- Typical Physical Properties of "Ready-to-Use"
mals is a concern. FireFighter GL and FireFighter PG
"Ready-to-Use"
FireFighter GL FireFighter PG
FireFighter GL
Color: Orange Red
FireFighter GL is a Glycerine based material which is
compatible with all approved types of pipe,including Density @ 77°F: 1.137 1.026
BlazeMaster®CPVC sprinkler pipe and fittings. (grams/ml)
Active Ingredient:USP or CP Glycerine Viscosity @ 77°F: 7.05 6.15
Other ingredients:Water (Centipoise)
Viscosity Reduction Agent
Dye pH: 7.0 8.0-9.6
Boiling Point @
Atmospheric Pressure:
FireFighter PG (760 mm) 212°F 222°F
FireFighter PG is a Propylene Glycol based material Minimum Flow
which is compatible with all approved types of sprinkler Temperature: -15°F -15°F
systems,with the exception of CPVC.
Minimum Burst
Active Ingredient:Propylene Glycol Temperature: -50°F -50°F
Other Ingredients:Water (Hard Freeze)
Viscosity Reduction Agent
Inhibitor Flash Point 350°F 214°F
Dye Fire Point 400°F 220°F
Concentrate
(Pensky-Martens
Closed Cup)
Flammability
FireFighter GL and FireFighter PG are not flammable Other FireFighter Antifreeze Products
since they have no measurable flash point;however,both
products can flash or burn if the water content is evapo- • FireFighter GL Concentrate
rated off.No harmful fumes are produced. • FireFighter PG Concentrate(New Formula)
• GL and PG Custom Blends
For specifications on these products please contact us.
Toxicological,Environmental and Health
Information *FireFighter is a Trademark of The Noble Company
*BlazeMaster is a Registered Trademark of Noveon
FireFighter GL and FireFighter PG are virtually harmless *'Non-Toxic is used to describe extremely low chronic and acute toxic-
to animals or plants;however,the disposal of these mate- ity.No maximum safe intake for humans has been established.The
product is considered GRAS by The Food and Drug Administration.
rials should be in conformance with national,state and
local health codes.
Sizes
FireFighter GL and FireFighter PG are available in:
• 1 gallon plastic bottles (6 per case, PG Ready- RECOMMENDED CONCENTRATIONS
to-Use only)
• 5 gallon pails
• 30 gallon drums
• 55 gallon drums
• 275 or 330 gallon totes FireFighter GL Ready-to-Use
• 5000 gallon tank truck
Specific Gravity Freeze Point Burst Point
@ 77°F
System Requirements and Limitations 1.141 -15°F -50°F
All fire protection sprinkler systems that use Fire- 1.116 5°F -45°F
Fighter GL and FireFighter PG should conform to 1.102 0°F -40°F
local, state and NFPA requirements. The use of an-
tifreeze within these systems should also conform 1.096 10°F -35°F
to NFPA requirements.
Use of antifreeze solutions should also be in confor-
mance with any state or local health codes. Please FireFighter PG Ready-to-Use
contact your local health authorities if you have any
questions concerning the codes in your area.
Specific Gravity Freeze Point Burst Point
@ 77°F
Maintenance 1.033 0°F -50°F
Chemicals which compose FireFighter GL and Fire-
1.028 to°F -20°F
Fighter PG can break down over time. NFPA 25 re- 1.024 +15°F 0°F
quires that the freezing point of the system should
be tested at least once a year. Periodic testing of 1.020 +20°F +10°F
systems is critical to maintaining the proper con-
centration and freeze point of the fluid. Leaks,
pressure surges and temperature changes to the
system can cause antifreeze to flow out of the sys-
tem or water to flow into the system changing the FireFighter GL Concentrate
freeze temperature.
GL Concentrate Freeze Point Specific Gravity
@60°F
Testing
To test the freeze protection level of FireFighter GL 40% +5°F 1.100
or FireFighter PG the correct instrument must be
used. 50% -15°F 1.133
For testing FireFighter GL we have two instruments. 60% 22°F 1.151
A lab grade hydrometer or a digital refractometer.
70% -40°F 1.165
For testing FireFighter PG we have three instru-
ments for test. A lab grade hydrometer, an analog
refractometer or a digital refractometer.
When testing indicates that the solution has weak-
ened, empty the system and replace with fresh
FireFighter GL or FireFighter PG, according to the
installation instructions.
For further information concerning correct testing
procedures and test instruments, contact our tech-
nical services department and ask for"How to
Choose the Correct Antifreeze Loop Tester':
RECOMMENDED CONCENTRATIONS
FireFighter PG Concentrate
(New Formula)
The Noble Company
FF PG Freeze Point Specific Gravity
Concentrate @ 60°F P.O. Box 350
60r -60°F 1.045 Grand Haven, MI 49417-0350
50% -26°F 1.041 www.noblecompany.com
40% -6°F 1.034 Phone: (231) 799-8000
30% +9°F 1.027 (800) 878-5788
Fax: (231) 799-8850
Fast Fax: (800) 272-1519
ACCESSORIES
• Lab Grade Hydrometer
• Analog Refractometer
• Digital Refractometer AFSA
i�+r#i**n Firm.
94pr1Nkl.r A iomcIjt
AVAILABILITY
M E B E
FireFighter GL and Firefighter PG are
available throughout the U.S. throughaino-ku, w
•
wholesale distributors. Please contact The
Noble Company for your local representa-
tive and wholesaler.
TECHNICAL SUPPORT I
MEM6ER
Specifications, installation design, instal-
lation techniques and unique applications
will be reviewed upon request. Address
inquiries ATTN: FireFighter Technical
Support, Email: www.noblecompany.com
or phone us at: 800-878-5788
Field services are available through fac-
tory representatives and Noble Company
staff. Contact The Noble Company for
local representatives.
Additional product information and MSDS
are available immediately through our
website at www.noblecompany.com or
our Fast Fax service at 1-800-272-1519.
These are available 24 hours a day, 7
©2004 Form#FFPIG 1004
days a week. Supercedes 0604
WILKINS Model WXTP
a zuRN,,, company Water Thermal Expansion Tank
SPECIFICATION SUBMITTAL SHEE-'
- APPLICATION
Air
Designed for installation on potable water lines between the
backflow preventer or pressure reducing valve and the water
heater to protect against water thermal expansion. When
ii, system pressure increases,water enters the tank's bladder
which expands into the pre-charged air chamber, keeping
system pressure below the relief valve setting.
imr
STANDARDS COMPLIANCE
FEATURES • IAPMO®Listed NSF
Sizes (liters): ❑ 8 ❑ 18 ❑ 32 ❑ 50V • NSF®Listed `®
❑ 75V ❑ 120V ❑ 165V ❑ 320V Certified to
ANSI/NSF 67
(V=vertical,free-standing)
Maximum working water pressure 150 PSI MATERIALS
End connections Threaded NPT
ANSI B1.20.1 Outer shell High Grade Steel
Precharge(adjustable) 40 PSI Coatings Epoxy finish(outer shell)
Connection Brass (sizes: 8 thru 32)
5 year warranty Stainless Steel (sizes: 50V thru 320V)
Bladder Butyl Rubber(FDA approved)
LIc
ACCESSORIES �A
U BR4 - water pressure reducing valve 1 °
❑ TP1100A - temperature&pressure relief valve
❑ P1000A - pressure relief valve
❑ 975XL - reduced pressure backflow preventer
IU
B B
NOTE: Model WXTP tanks are certified to NSF Standard
61 cold, but are suitable for temperatures up to 200°F.
c - 0
HAJ
WXTP 50V-320V WXTP 8-32
DIMENSIONS&WEIGHTS(do not include pkg.)
TANK SPECIFICATIONS
MAXIMUM TOTAL FACTORY DIMENSIONS
MODEL WEIGHT
WORKING VOLUME ACCEPTANCE PRECHARGE DIAMETER HEIGHT SYSTEM
NUMBER PRESSURE GALLON VOLUME (PSI) CONNECTION
S in. mm in. mm lbs. kg
WXTP-8 150 PSIG 2.1 0.84 40 8 1/2 216 11 1/2 292 3/4" MNPT 7 3.2
WXTP-18 150 PSIG 4.5 1.8 40 10 254 15 381 3/4" MNPT 10 4.5
WXTP-32 150 PSIG 8.5 3.4 40 12 1/2 318 19 3/16 487 3/4" MNPT 15 6.8
WXTP-50V 150 PSIG 14 5.6 40 16 406 21 11/16 551 1" FNPT 32 14.5
WXTP-75V 150 PSIG 20 8.0 40 16 406 28 13/16 732 1" FNPT 39 17.7
WXTP-120V 150 PSIG 32 12.8 40 21 533 27 13/16 706 1" FNPT 60 27.2
WXTP-165V 150 PSIG 44 17.6 40 21 533 36 3/16 919 1 1/4" FNPT 72 32.7
WXTP-320V 150 PSIG 85 34.0 40 26 660 44 7/16 1129 1 1/4" FNPT 140 63.4
NOTE: RELIEF VALVE MUST BE SET AT 150 PSIG MAXIMUM
DOCUMENT#: REVISION:
WXT-WXTP 4/05
Page 1 of 2
SIZING CHART
Supply WATER HEATER CAPACITY (U.S. gal)
Pressure(psig) 20 30 40 50 60 80 100 120 150 175 200
40 8 8 8 8 8 18 18 18 32 32 32 _
50 8 8 8 8 8 18 18 18 32 32 32
55 8 8 8 8 8 18 18 18 32 32 32
60 8 8 8 8 18 18 18 18 32 32 32 _
70 8 8 8 8 18 18 18 18 32 32 32
80 8 8 8 8 18 18 18 32 32 32 32
90 8 8 8 18 18 18 32 32 32 50V 50V
100 8 8 18 18 18 32 32 32 50V 50V 50V
110 8 I 1818 18 1 32 32 32 1 50V 50V 75V 75V
120 18 18 I 32 32 32 50V 50V 50V 120V 120V 120V
Supply WATER HEATER CAPACITY (U.S. gal)
Pressure(psig) 240 260 280 300 350 400 450 500 600 800 1000
40 50V 50V 50V 50V 50V 75V 75V 75V 120V 120V 165V
50 50V 50V 50V 50V 50V 75V 75V 75V 120V 120V 165V
55 50V 50V 50V 50V 50V 75V 75V 75V 120V 120V 165V
60 50V 50V 50V 50V 50V 75V 75V 75V 120V 120V 165V
70 50V 50V 50V 50V 50V 75V 75V 75V 120V 120V 165V
80 50V 50V 50V 50V 75V 75V 75V 120V 120V 165V 165V
90 50V 50V 50V I 75V 75V 75V 120V 120V 120V 165V 320V
100 75V 75V 75V 75V1 120V 120V 120V 165V 165V 320V 320V
110 120V 120V 120V 120V 120V 165V 165V 320V 320V 320V 1 X
120 165V 165V 165V 320V 320V 320V 320V 320V X X X
(Based upon 100° F temperature rise(40° F to 140° F) X=multiple tanks required(contact your WILKINS Rep)
TYPICAL INSTALLATION
Local codes shall govern installation requirements. Unless otherwise specified, the assembly shall be mounted on the cold
water supply and at least 18"from the cold water inlet to the heater. Note: If incoming water pressure is above 40 psi, the
precharge pressure of the expansion tank should be adjusted to equal the incoming water pressure, not to exceed 80 psi.
- - TAP VALVE
Hui _ILII_ _/IIS
IL)QI
HOSE BIBB
-^ HOT WATER TSP VALVE
uiNiMielt III*T HOSE
II / HEATER B
-
MODEL STEAL MODEL BRA 1 Tr
e&IIIINIM11111 ISI illiH.HEATER
WATER PRESSURE MODEL 975XL
REDUCING VALVE...K�l�� IIIII MODEL BRA lim'' . /Il�fn'. p 311 I�II% M DEL BR VA VEE Ipp
OD
I' MODEL WXTP RAIN I MF •111111111
1D IDIRECTION OF FLow
III. ` DIRECTION OF FLOW �11r •. II/ RAM
MODEL WXTP INSTALLATION MODEL WXTP INSTALLATION "V'SERIES
SPECIFICATIONS
The Water Thermal Expansion Tank shall be IAPMO® and NSF® Listed. The outer shell shall be high grade steel
with exterior coating. The bladder shall be FDA approved butyl rubber and prevent water from contact with shell
interior. The assembly shall incorporate a shrader valve for adjustable air precharge and a lead free bronze system
connection. The Water Thermal Expansion Tank shall be a WILKINS Model WXTP.
Page 2 of 2
WILKINS a Zurn Company, 1747 Commerce Way, Paso Robles, CA 93446 Phone:805/238-7100 Fax:805/238-5766
IN CANADA:ZURN INDUSTRIES LIMITED,3544 Nashua Dr., Mississauga,Ontario L4V 1L2 Phone:905/405-8272 Fax:905/405-1292
Product Support Help Line: 1-877-BACKFLOW (1-877-222-5356) • Website: http://www.zurn.com
(2,01 -roLcor www.tolco.com
abrand ofNlBCO Revision 5/24/2001
Fig. 23 - Hanger for CPVC Plastic Pipe
Double Fastener Strap Type p
Size Range— 3/4" thru 2" CPVC pipe .. _
Material — Carbon Steel, Pre-Galvanized
Function — Intended to perform as a hanger/restrainer to support / •
only CPVC piping used in automatic fire sprinkler systems. Can be +
installed on the top or on the bottom of a beam. The Fig. 23 can also ti
be installed on the side of a beam. The Fig. 23 can also function as
a restrainer to prevent the upward movement of the sprinkler head 9,............1 I
during activation.
Approvals— Underwriters' Laboratories Listed in the USA (UL) and k.
Canada (cUL) to support fire sprinkler piping. Meets and exceeds I
the requirements of NFPA 13, 13R and 13D. ' B
Features — Fig. 23 incorporates features which protect the pipe and
ease installation. The flared edge design* protects the CPVC pipe N....T.
from any rough surface. It also incorporates snap restrainers allow-
ing easier and faster installation. Easily attaches to the building C B A
structure using the two UL Listed hex head self threading screws**
furnished with the product. It is recommended that rechargeable
electric drills fitted with a hex socket attachment be used as installa-
tion tools. No impact tools (such as a hammer) or impact fasteners
(such as drive screws or nails) are allowed. Damage has been
known to result from installations using impact type tools.
No pre-drilling of a pilot hole in wood is required.
Finish — Pre-Galvanized
Order By— Figure number and pipe size
* Patent Pending
** Hardened hex head self threading screw is furnished with the
product and is the minimum fastener size acceptable.
Dimensions •Weights
CPVC Max. Hanger Fastener Hex Approx.
Pipe Size A B C Spacing (Ft.) Head Size Wt./100
3/4 31/8 19/16 13/16 51/2 5/16 9
1 33/8 111/18 13/,6 6 5/16 9
11/4 43/16 23/32 13/16 61/2 5/16 11
11/2 47/,6 27/32 13/,6 7 5/16 12
2 47/8 27/16 13/16 8 5/16 15
Cffi ce/Manufacturing Faci I i ty•1375 Sampson Ave.•Cbrcna,CA 92879•Fh: 909.737.5599•Fax 909.737.0330
Customer Service•800.786.5266 39
www.tolco.com
® TDLCO www.tolco.com
a brand ofNlBCO Revision 5/24/2001
Fig. 24 - Hanger for CPVC Plastic Pipe
Double Fastener Strap Type Side Mount
Size Range— 3/4" thru 2" CPVC pipe C
Material — Carbon Steel, Pre-Galvanized ,
Function — Intended to perform as a hanger/restrainer to support only • .
CPVC piping used in automatic fire sprinkler systems. Can be installed
on the top or on the bottom of a beam. The Fig. 24 can also function [
7
as a restrainer to prevent the upward movement of the sprinkler head !
during activation.
Approvals — Underwriters' Laboratories Listed in the USA (UL) and i
Canada (cUL) to support fire sprinkler piping. Meets and exceeds the
requirements of NFPA 13, 13R and 13D.
Features— Fig. 24 incorporates features which protect the pipe and
ease installation. The flared edge design* protects the CPVC pipe from
any rough surface. Easily attaches to the building structure using the two
UL Listed hex head self threading screws** furnished with the product. It ti
is recommended that rechargeable electric drills fitted with a hex socket
attachment be used as installation tools. No impact tools (such as a hammer) B
or impact fasteners (such as drive screws or nails) are allowed. Damage has
been known to result from installations using impact type tools. No pre-drilling
of a pilot hole in wood is required. B A
Finish — Pre-Galvanized
..0,0:,,,„,...,--'..
Order By— Figure number and pipe size
* Patent Pending
** Hardened hex head self threading screw is furnished with the
product and is the minimum fastener size acceptable.
Dimensions •Weights
CPVC Max. Hanger Fastener Hex Approx.
Pipe Size A B C Spacing (Ft.) Head Size Wt./100
3/4 25/16 15/32 13/16 51/2 5/16 9
1 25/8 15/,6 13/16 6 5/16 9
11/4 3 11/2 13/16 61/2 5/16 11
11/2 31/4 15/8 13/16 7 5/16 12
2 311/16
127/32 13/16 8 5/16 15
Main Office/Manufacturing Facility•1375 Said Ave.•Corona,Ca,92879•Fh: 909.737.5599•Fax 909.737.0330
40 Customer Servi ce•800.786.5266
www.totco.com
0TOLCO www.tolco.com
a brand of NIBCO' Revision 4/27/2006
Fig. 28
u uL u5 LISTED
"Stand-Off" Hanger & Restrainer for CPVC Plastic Pipe
Size Range—3A" through 2"
Material — Carbon Steel, Pre-Galvanized
Function — Designed to be used as a hanger and restrainer for CPVC piping where
the "stand-off' design will ease installation by eliminating the need for wood blocking. `
Features:
• Flared edge design protects CPVC pipe from any rough or abrasive surfaces.
A
• Unique twist and lock design holds pipe firmly in place and allows retrofit type B
of installation.
• The "Stand-Off' design eliminates the need for wood block extension. C ,
• Can be installed on horizontal or vertical piping regardless of mounting .• .1
surface orientation.
• Attaches easily to wood structure with two hex head self-threading screws
furnished with product.
Nit"
• Installs easily using rechargeable electrical driver with 5/16" extension socket
eliminating impact tool damage to pipe.
• Attaches easily to steel, minimum 18 gauge with (2) 1/4" x 1" tek type self drilling
tapping screws. C410.. St°
• U.L. Listed as a hanger and a restrainer for fire sprinkler piping.
Approvals — Underwriters' Laboratory Listed in the USA (UL) and Canada (cUL) to
support automatic fire sprinkler systems. May be installed into wood using fasteners ,
supplied with product, or into minimum 18 gauge steel using (2) 1/4" x 1" tek type screws.
Meets and exceeds the requirements of NFPA 13, 13R and 13D. Fig. 28 satisfies the UL14 411111141111"-4111141111k
vertical restraint requirement where needed. UL Listed as a hanger and vertical restraint
when installed on 3/8" composite wood material. Use two Fig. 27B Speed Nuts when
used as a hanger and restraint. Use one Fig. 27B Speed Nut on the upper installed 1 N
screw when used as a hanger only. I 1
Order by— Figure number and pipe size.
US AND INTERNATIONAL PATENT APPLICATION IN PROCESS.
F1)I E 3
4
(1J REQUIRED FIG.27E
HIGH SIDE (2J REQUIRED
OF HANGER
.1 I .11 1
A •
. .II Ii .4*r
Dimensions •Weights
HANGER APPLICATION HANGER 8 RESTRAINT Pipe Approx.
APPLICATION Size A B C Wt.
FGI
■I■•I 3/4 31/32 2 31 .180
A — 1 35/6 23/6 31/2 .210
114 35/s 23/a 31/2 .225
lrl.71- i'_ 1Y2 4 2Y2 3� 310
FI326 ° " 2 41 211A6 3% .340
IIII FvaF
,r
-■ ■■
IA
.AEf
JJ
CFR GE/MANUFACTURING FAG UTY•1375 SQMF92N AE•OZFCINP,CA 92879•Fl-t 951.737.5599•FAX 951.737.0330
38 CLJSTCM ER SERA CE•800.786.5266
www.tolco.com
® TDLCO' www.tolco.com
a brand ofNlBC❑ Revision 5/24/2001
Fig. 22C - Combination
Hanger & Restrainer Application
Size Range — 3/4" thru 2" CPVC pipe
Material — Carbon Steel, Pre-Galvanized 518"
Function — Designed to support a CPVC pipe away
'—''N )11 .-•->.
from the corner of a beam. This position allows for easy
installation of drops or risers without adding additional "• 3 518"
wood blocks.
c
Approvals — Underwriters' Laboratories Listed in the USA
(UL) and Canada (cUL) for use as a combination hanger and ...,-
TRUSS Hi=AOE
R
restrainer. 1 OR
Finish — Pre-Galvanized — TRUSS JET
Note—Approved UL Listed fastener into wood is furnished {TSP}
with the product. A fastener into light gauge metal may be
ordered separately. Minimum acceptable#10 x 1" hardened 4. x'3 518„
self threading screw with 5/16" hex washer head.
Order By— Fig. 22C application is composed of two r >• 1 "
standard Fig. 22 models—order two singles for each hanger )1.;-1)..414.,. _.,,I,
and restrainer application required.
eihil\
1111P.-
1■15J8"
I
� >1 518-
L
.Q.,%;../' 0
.Ado..0..... -....,
qk ) ,1
Is„..
OM
Mtlilil
Main Office/Manufacturing Facility•1375 Said Ave.•Corona,Ca,92879•Fh: 909.737.5599•Fax 909.737.0330
38 Customer Servi ce•800.786.5266
www.totco.com
6341.6345 SES FIRE DEPT. INLET CONN. FLUSH TYPE) CROKER
SINGLE INLET
An inlet connection with 250 G.P.M. minimum inlet capacity
to supplement the fire protection water supply. Provides 41kli abie
unobstructed water supply. Flush round design enhances
r' • appearance and provides unobstructed passage. .
•
•k .•r STANDARD EQUIPMENT: Cast Brass round plate with double � - }
female adapter; plug and chain; branding as selected. _.
•'l SPECIFY THREAD AND BRANDING. v '
BRANDING: "Standpipe", "Auto Spkr."
44
FINISH: Cast Brass
Figure No. 6341 Figure No. 6342
OPTIONAL FINISH: PB-Polished Brass
PC-Polished Chrome
Round Plate
Figure No. Size
6341 2 1/2 X 2 1/2
6342 3 X 2 1/2
6343 3 X 3
RESIDENTIAL FIRE DEPT. CONNECTION
An inlet connection to supplement the water supply to a
,fes residential sprinkler system.
1. ' i STANDARD EQUIPMENT: 1 1/2" cast brass round plate
assembly with integral pin lug swivel inlet. Hose thread inlet
_ :i N. , swivel, 1 1/2" NPT female outlet on back of plate. Cast brass
plug and brass chain. Overall outside Diameter 4 3/8".
SPECIFY THREAD AND BRANDING.
U/L LISTED.
• BRANDING: "Auto Spkr."
a
FINISH: Cast Brass
Figure No. 6345
OPTIONAL FINISH: PB-Polished Brass
PC-Polished Chrome
Page 6-12
NIBCO° www.nibco.com
AHEAD OF THE FLO W1' Revised 08/01/03
200 lb. WWP Bronze Check Valves Dezincification
Fire Protection Valve • Horizontal Swing • Rubber Disc Resistant
200 PSI/13.8 Bar Non-Shock Cold Water
•
•
. r {
CONFORMS TO MSS SP-80 �Y
MATERIAL LIST
PART SPECIFICATION KT-403-W
1. Bonnet Bronze ASTM B 62 Threaded
or B 584 Alloy C84400
2. Body Bronze ASTM B 62
or B 584 Alloy C84400
3. Hinge Pin Bronze ASTM B 140 Alloy C31400
or B 134 Alloy C23000
4. Disc Hanger Bronze ASTM B 62
5. Hanger Nut Bronze ASTM B 97 Alloy C65500
or Brass ASTM B 16
6. Disc Holder Bronze ASTM B 62
7. Seat Disc Buna-N(W) o
TFE
sA 0
8. Seat Disc Nut Brass ASTM B 16
0
or B 97 Alloy C65500 4 �q
9. Hinge Pin Plug Bronze ASTM B 140 Alloy C32000 0 o�No�
(Not Shown)
*10. Seat Disc Washer Stainless Steel 0 ..nON% , �.,
*Sizes 3/4",1",11/4"and 11/2"only. a I'IIIIIIIIII�� �-' • 111111112'/2'and 3"size only. w �r�°'-
m IIIIIIIIIII��'11111iiIII�
hllllu
UVa 6.-veal ohmooala
A
DIMENSIONS-WEIGHTS-QUANTITIES KT-403-W
Dimensions NPT x NPT
Size A B Weight Box Master.
In. mm. In. mm. In. mm. Lbs. Kg. Qty. Ctn.Qty.
1/2 15 2.44 62 1.69 43 .58 .26 10 50
3/4 20 2.94 75 1.88 48 .92 .42 10 50
1 25 3.56 90 2.31 59 1.55 .70 5 30
11/4 32 4.19 106 2.69 68 2.32 1.05 5 20
11/2 40 4.50 114 2.94 75 3.00 1.36 2 10
2 50 5.25 133 3.81 97 4.87 2.21 2 10
21/2 65 8.00 203 5.06 129 11.48 5.22 1 5
3 80 9.25 235 6.25 159 17.53 7.97 1 4
Sizes 2W and 3"supplied as T-433-Y with TFE seat disc.
NIBCO check valves may be installed in both horizontal and vertical
lines with upward flow or in any intermediate position.
WARNING-Valve must be installed downstream of receiver tank if
used in line with reciprocating air compressor.
NIBCO INC.WORLD HEADQUARTERS•1516 MIDDLEBURY ST.•ELKHART,IN 46516-4740•USA•PH:1.800.234.0227
14 TECH SERVICES PH:1.888.446.4226•FAX:1.800.234.0557•INTERNATIONAL OFFICE PH:+1.574.295.3221 •FAX:+1.574.295.3455
www.nibco.com
WHEELOCK
P1 SERIES MT AND MT STROBE
® The Symbol of Protection MULTITONE ELECTRONIC SIGNALS
Wheelock's MT and MT Strobe Series Multitone Electronic Signals offer a choice of eight(8)nationally and internationally
recognized alerting sounds: Horn,Bell,March Time Horn,Code-3 Tone,Code-3 Horn,Slow Whoop,Siren or Hi/Lo Tone.
Wheelock's Code-3 horn and tone patterns are engineered to comply with NFPA/ANSI Temporal Pattern specifications
without requiring additional coding means. With MT and MT Strobe Signals, one alarm appliance meets most of your
signaling needs. Wheelock's MT and MT Strobe Signals are UL Listed, FM, CSFM and NYMEA Approved.
Features
• One alarm appliance with (8) eight selective signals to
provide superior sound penetration for various ambient
and wall conditions with two field selectable sound output ` (?L
levels. F _
• Code-3 Horn and Tone meet NFPA/ANSI/ISO temporal I
pattern for standard emergency evacuation signaling. tsiI 1 ill
• Audible and strobe can operate from a single signaling D
circuit. I`
• Designed to meetorexceed NFPA/ANSI Standards and Liummi, E
ADA Accessibility Guidelines. 110 VAC model does not
meet ADA requirements.
• Low current draw with low temperature compensation to
reduce power consumption and wiring costs.
• Low cost installation via standard electrical boxes.
Attractive flush or surface mounting options available. MT-24-1575W-FR SHOWN
I
MT-121575W-FR MT 12/24 MT-24-1575W-FR* MT4-115-WH-VFR
(Strobe/Horn) (Horn) (Strobe/Horn) Indoor (Strobe/Horn)
Model Stock No. 1610921 Stock No. 1610914 Stock No. 1610915 Stock No. 1610216
Mounting Options** Mounting Options** Mounting Options** Mounting Options**
D,E,F,L,M,O,P,R D,E,F,L,M,O,P,R D,E,F,L,M,O,P,R D,E,J,K,N,O,R
dBA and Current Ratings
Average Current Ratings(Amps) dBA Reverberant Ratings dBA Anechoic Ratings
Per UL 464
Tone @ 24VDC @ 12VDC @ 24VDC @ 12VDC @ 12 and 24VDC
HI STD HI STD HI STD HI STD HI STD
Horn 0.038 0.024 0.095 0.019 92 87 90 77 99 93
Bell 0.019 0.012 0.030 0.010 86 80 85 69 92 87
March Time Horn 0.038 0.024 0.095 0.019 89 84 89 74 99 93
Code-3 Horn 0.038 0.024 0.095 0.019 88 83 88 73 99 93
Code-3 Tone 0.027 0.016 0.057 0.014 85 80 84 70 95 90
Slow Whoop 0.047 0.025 0.095 0.024 90 89 89 75 99 94
Siren 0.034 0.022 0.078 0.019 89 84 89 75 98 93
Hi/Lo 0.020 0.013 0.042 0.011 86 81 86 71 93 88
• For outdoor installation use MTWP-2475W-FR with IOB-R backbox.
** See next page for mounting options.
Potter Electric Signal Company•2081 Craig Road,St.Louis,MO,63146-4161 •Phone:800-325-3936/Canada 888-882-1833•www.pottersignal.com
PRINTED IN USA MKT.#8850002-REV H PAGE 1 OF 2
2/03
le WHEELOCK
POTTERSERIES MT AND MT STROBE
The Symbol of Protection MULTITONE ELECTRONIC SIGNALS
MOUNTING ACCESSORIES
(D)4"SQUARE,FLUSH(BO) (E)4"SQUARE,DEEP,FLUSH(BO) (F)DOUBLE-GANG,FLUSH(BO)
0 0 O p p p 0 0
®o ort'
Oe0 (, 0
MAXIMUM NUMBER OF,____CONDUCTORS MAXIMUM NUMBER OF CONDUCTORS MAXIMUM NUMBER OF CONDUCTORS
AWG.#18 AWG.#16 AWG.#14 AWG.#12 AWG.#18 AWG.#16 AWG.#14 AWG.#12 AWG.#18 AWG.#16 AWG.#14 AWG.#12
4 4 4 4 8 8 8 4 4 4 4 4
(J)BB BACKBOX (K)WBB WEATHER RESISTANT BACKBOX (L)ISP SURFACE ADAPTER
(Order Code:2830) (Order Code:2959) (Order Code:5306)
Standard steel backbox with knockouts for Sturdy die-cast housing,threaded conduit hole Indoor use.
interior surface mounting,concealed conduit and knockout for outdoor applications.It is
mounting or semi-flush applications. It is painted to match the signal.
painted to match the signal.
4 I e v
—ean
= LLIl_l `rrIIL}
l—
\
1-02,017 'A14'
n ,29/32 �i.- iO „Yma i l O V r
080O II{I
•a/
lir loc..
1 VeOMa. M.- I- �•-va-
MAXIMUM NUMBER OF CONDUCTORS MAXIMUM NUMBER OF CONDUCTORS MAXIMUM NUMBER OF CONDUCTORS
AWG.#18 AWG.#16 AWG.#14 AWG.#12 AWG.#18 AWG.#16 AWG.#14 AWG.#12 AWG.#18 AWG.#16 AWG.#14 AWG.#12
4 4 4 4 4 4 4 4 8 8 8 4
(0)RP-R RETROFIT PLATE (R)SFP SEMI-FLUSH PLATE (M)10B BACKBOX
(Order Code:5042) (Order Code:2957) (Order Code:5046)
Stamped aluminum surface wall plate which For surface mounting MT products.
mounts behind the basic unit and serves to
cover recessed backboxes in semi-flush
mounting applications.It is painted to match '-0n
I -1-
1- —'-'--1' r'n—. II 1 o 1 7[—"" the signal.
dal
=VS AM lir
7-.7
" �� +_
I ) .I , .
epe
+ + I ouo
7
- UM +o 0=+ I
MAXIMUM NUMBER OF CONDUCTORS
DWG, 48850002-1 AWG.#18 AWG.#16 AWG.#14 AWG.#12
8 8 8 4
MOUNTING NOTES
CAUTION:The mounting options figures show the maximum number of field wires(conductors)that can enter the backbox used with each mounting option.If these limits are
exceeded,there may be insufficient space in the backbox to accommodate the field wires and stresses from the wires could damage the product.
Although the limits shown for each mounting option comply with the National Electrical code(NEC),Wheelock recommends use of the largest backbox option and the use of
approved stranded field wires whenever possible,to provide additional wiring room for easy installation and minimum stress on the product from wiring.
CAUTION:Check that the installed product will have sufficient clearance and wiring room prior to installing backboxes and conduit,especially if sheathed multiconductor cable
or 3/4"conduit fittings are used.
1. Mounting hardware for each mounting option is supplied.
2. Conduit entrances to the backbox should be selected to provide sufficient wiring clearance for the installed product.When extension rings are required,conduit should enter
through the backbox,not the extension ring.Use Steel City#53151(1-1/2"deep)or#53171(2-1/8"deep)extension rings(as noted in the mounting options)or equivalent
with the same cut-out area.
3. When terminating field wires,do not use more lead length than required.Excess lead length could result in insufficient wiring space for the appliance.
4. Use care and proper techniques to position the field wires in the backbox so that they use minimum space and produce minimum stress on the product.This is especially
important for stiff,heavy gauge wires and wires with thick insulation or sheathing.
5. Do not pass additional wires(used for other than the appliance)through the backbox.Such additional wires could result in insufficient wiring space for the appliance.
PRINTED IN USA MKT.#8850002-REV H PAGE 2 OF 2
2/03
122
ASHCROFT® Fire Protection, Sprinkler
Service Gauge Type 1005P, XUL
ASME B 40.1 Grade B
(±3-2-3%of span)
▪ Underwriters Laboratory listed and Ashcroft@ fire protection sprinkler
Factory Mutual approved gauges are Underwriters Laboratory
•Corrosion-resistant ABScase listed and Factory Mutual approved /,'' 120 150�Ig0'1/�
for fire protection sprinkler service. /%\:
▪ Heat-resistant polycarbonate The case material on Type 1005P, '90 210 ,\\
push-in window XUL gauges is ABS.The 0 300 psi =.60 240..-'...1• Patented PowerFlexTM movement pressure range is used on"wet" 270
ATEP
with polyester segment systems where water is available to -30 :Ea 300
the sprinkler heads.The 0-80 retard \ ���� �
▪True ZeroTM indication, a unique to 250 psi pressure range is used on °As"`°�,o j
safety feature dry systems where the lines are q93 =
filled with air pressure until system
activation.
The patented PowerFlexi move-
ment with polyester segment is
designed to provide unequalled True Zero indication, a standard
shock and vibration resistance feature on these gauges, reduces
resulting in superior performance the potential risk of installing a dam-
and extended gauge life. aged gauge on your equipment.
GAUGE SPECIFICATIONS GAUGE OPTIONS
Type no.: 1005P,XUL Operating Customized dials
Accuracy: ASME B 40.1 Grade B temperature: —40°F to 150°F Other UL listed ranges on application
(±3-2-3%of span) Connection: 'i NPT lower
Size: 3/" Ranges: 0-300 psi(water)
Case: ABS(Polycarbonate blend) 0-80 retard to 250 psi(air)
Ring: None UL 393 Listed,UL of Canada
Listed and FM approved.
Window: Polycarbonate,push-in Equivalent(single or dual
Dial: Black figures on white back- scale)metric scales are
ground available NOTES
Pointer: Black,aluminum @LISTED
Bourdon tube: "C"shaped bronze
Movement: Patented PowerFlex
with polyester segment 4>
Socket: Brass LOOK FOR THESE AGENCY
MARKS ON OUR PRODUCTS
Restrictor: None
TO ORDER THIS TYPE 1005P,XUL GAUGE:
Select: 35 W 1005 P H 02L XUL 300#
1. Dial Size:3'/E" 1
2. Patented PowerFlexfm Movement
3. Case Type Number:1005
4. Case Type Material:ABS
5. Socket Material:Brass
6. Connection Size/Location:'/NPT lower
7. UL listed,FM approved
8. Range:300 psi
Consult factory for guidance in product selection ...„ii
Phone(203)385-0217,Fax(203)385-0602 or DRESSER
visit our web site at www.ashcroft.com Instruments
CENTRAL H d . Cab . 11 -9 4
Close
Sprinkler
Head a ine
r
Central Sprinkler Company
451 North Cannon Avenue, Lansdale, Pennsylvania 19446
Product Technical 3 , 6 & 12
Description Data Head
Central Sprinkler Head Cabinets Model: Sprinkler Head Cabinet Sprinkle r
are constructed of a metal enclosure Style: 3, 6 or 12 head
with a hinged cover designed to
HeadStandard Finish: Red enamel
provide on-site storage of an
emergency supply of sprinkler heads Mfgr. Source: Non-domestic
and a sprinkler head wrench. Capacity: 3 sprinkler heads C a b i n e t
NFPA 13 requires a representative 6 sprinkler heads
number of each type of sprinkler 12 sprinkler heads
head used in a sprinkler system to be Dimensions:
stored in a cabinet on-site to allow for
immediate removal and replacement 3 head-5"high x 7'/z"long x 2'/z"deep
of sprinklers which may have 6 head-5"high x 14"long x 3'/a"deep
operated or become damaged. 12 head-5"high x143/4" long x 5"deep
Central Sprinkler Head Cabinets Weight: 3 head - 1.5 lbs.
are manufactured of heavy gauge 6 head -2.3 lbs.
steel with knock-outs to 12 head -4 lbs.
accommodate either 1/2" or 3/" N.P.T.
threaded sprinkler heads and are
painted an attractive red enamel.
They are available in three (3), six (6)
or twelve (12) head capacity.
No. 28-6.0
Close
I nstal I at i on Care & • aderi ng
Maintenance wig I of ormat i on
Central's Sprinkler Head Cabinet is The Cabinet, wrench, and stock of When placing an order, indicate the
designed with two%s'diameter holes spare sprinklers should be inspected full product name. Please specify the
for wall mounting or direct attachment at least quarterly. The following items quantity, model, style, capacity, and
to the system riser with a strap-type should be checked: size.
hanger. The Cabinet should be Sprinklers, wrenches, and hard-
installed at or near the system control 1. The Cabinet should be readily ware for hanging are not supplied
valve and must be stocked with an accessible, and not exposed to with the Cabinet. They must be
adequate supply of spare sprinklers a corrosive atmosphere or ordered separately.
and a sprinkler wrench. temperatures in excess of
The stock of spare sprinklers 100°F/38°C. Availability and Service: Central
should include sprinklers of each type sprinklers, accessories, and other
and temperature rating as are 2. The stock of spare sprinklers products are available throughout the
installed in the sprinkler system, in should include an adequate U.S. and Canada, and internationally
the following quantities: number of each type and through a network of Central
temperature rating. Sprinkler distribution centers. You
Sprinklers Spare Sprinklers may write directly to Central Sprinkler
In System Required 3. The stock of sprinklers must be Company, or call (215) 362-0700 for
in good condition. the distributor nearest you.
under 300 6
300-1000 12 4. A sprinkler wrench of the Guarantee: Central Sprinkler
over 1000 24 appropriate type must be Company will repair and/or replace
included in the Cabinet. any products found to be defective in
The Cabinets are designed to material or workmanship within a
accept both %"and %" N.P.T. period of one year from date of
threaded sprinklers. For%" N.P.T. shipment. Please refer to the current
sprinklers, leave the removable Price List for further details of the
knockout in the hole. For%" N.P.T. warranty.
sprinklers, insert a screwdriver blade
from the front top of the shelf and Conversion Table:
under the near bottom part of the 1 inch = 25.400 mm
knockout annular ring. Press the 1 foot = 0.3048 M
screwdriver handle down to remove 1 pound = 0.4536 kg
the knockout ring. The hole, with the
knockout ring removed, will accept a Conversions are approximate.
%" N.P.T. sprinkler.
CENTRAL
Central Sprinkler Company
451 North Cannon Avenue, Lansdale, PA 19446
©1994 Central Sprinkler Company Phone(215)362-0700
Printed in U.S.A. FAX (215)362-5385 Hd.Cab.2
CENTRAL Sign 1 -9 5
Close
Signs THF CO��R«
AUTOMATIC
4TIC SPRIM iE S
r i
t
For sprinkler systems & devices ;:r ' ' o.LL
.1 • :I� ati'ti��•
r MIN DT Mil
143.HO1µ{IQ TIL! LR711 PLII K +iT ILT .1U1
Anln • a.i.. _.1-14:,•,.• n.a.• . .
•IL a a
Manufactured by: Central Sprinkler Company ••
451 North Cannon Avenue, Lansdale, Pennsylvania 19446
P
Main prn
Product sprinkler sprinkler control
11
Desc• ion Open sprinkler drain Identification
Test valve
Triangular main drain Signs
Water motor
Central's Identification Signs are Water motor line
designed to provide information to the
end user about the sprinkler system Techni cal
and it's components. They are
available with a variety of wording Data
to meet the signing
requirements of NFPA 13.
The five basic types of signs are as Model: Sign
follows: Style: Flat, rectangular
Type A- Control Valve Sign Standard Finish: porcelain or mylar
Type B - Multi-purpose Text Signs Size: Type A- 9" x 7"
Type C - Cold Weather Sign Type B - 6" x 2"
Type D - Fire Alarm Sign Type C- 73/a" x 1'/a"
Type E - Hydraulic Calculation Sign Type D -9" x 7"
The Signs are constructed of 18 Type E - 5" x 7"
gauge steel or aluminum with a Weight: Type A-4.5 oz.
porcelain enamel or printed mylar Type B - 0.5 oz.
facing respectively. The signs have Type C-2.0 oz.
corner holes or slots for easy attach-
ment in the field. Type D -4.0 oz.
Sign Type B is available with the Type E - 1.5 oz.
following text options:
Air control Installation
Air control valve
Air line
Alarm test
Alarm line
Antifreeze system The Identification Signs are pro-
Auxiliary drain vided with 1/8" diameter or larger holes
Control (or slots) in the corners for easy
Control valve attachment using standard hardware
Drain chain, wire, plastic lock ties, or light
Drain valve gauge metal strap (not included).
Entire system
From city main
In this building
In this section
Inspectors test
Main control
No. 28-9.0
Close
Sign -Type A Sign -Type D k Q"Cer i ng
• •
THIS VALVE CONTROLS
SUPPLY AUTOMATIC SPRI NIQERS SPRINKLERa4I reformat i on
TO
' FIRE - ALARM rill
• • When placing an order, indicate
MUST OPEN AT ALL WHEN BELL RINGS
BE TIMES the full product name. Please
TO BE HANDLED ONLY BY AUTHORIZED PERSON OR CALL specify the quantity and type.
BY EMPLOYEE CARING FOR SPRINKLER SYSTEM
IN CASE OF FIRE FIRE DEFT OR POLICE Hardware for hanging is not
DO NOT SHUT VALVE UNTIL FIRE IS ENTIRELY OUTil
supplied with the Sign. It must be
WHEN VALVE IS SHUT FOR EMERGENCY-REPAIRS-OR FIRE- ordered separately.
NOTIFY:
.r Availability and Service:
REQUEST DIRECTIONS--RESTORE PROTECTION QUICKLY Central sprinklers, accessories,
and other products are available
The blank spaces on this sign may throughout the U.S. and Canada,
be utilized to provide message and internationally through a
flexibility. Simply add combinations of Sign -Type E network of Central Sprinkler
sign Type B and Type C as desired. • HYDRAULIC-SYSTEM • distribution centers. You may
This Building is Protected by a write directly to Central Sprinkler
Sign -Type B Hydraulically Designed Automatic Company, or call (215) 362-0700
Sprinkler System
• • for the distributor nearest you.
AUXILIARY DRAIN Location Guarantee: Central Sprinkler
No. of Sprinklers Company will repair and/or
• • replace any products found to be
Basis of Design defective in material or
1.DENSITY GPM/SQ.FT. workmanship within a period of
Sign -Type C 2 DESIGNED AREA OF DISCHARGE SQ.FT. one year from date of shipment.
System Demand Please refer to the current Price
FRONT List for further details of the
• • 1.WATER FLOW RATE GPM
VALVE 2.RESIDUAL PRESSURE AT THE PSI warranty.
VALVE MUST BE OPENED IN CASE OF FIRE BASE OF THE RISER
SHUT ALSO DURING SUMMER MONTHS SHUT Conversion Table:
• • 1 inch = 25.400 mm
BACK 1 foot = 0.3048 M
• 1 pound = 0.4536 kg
AND MUST BE KEPT OP EN EXCEPT DURING WINTER MONTHS, `conversions are approximate.
WHEN VALVE IS TO BE CLOSED AND PIPES DRAINED.
CENTRAL
_,..„
Central Sprinkler Company
451 N. Cannon Avenue, Lansdale, PA 19446
©1995 Central Sprinkler Company Phone (215)362-0700
Printed in U.S.A. FAX (215) 362-5385 Signs.1
1LE - ,
DthGNGP4 . ' P
5151 Bannock k5t .
Denver, CO 8021 :
303 -291401
31. 3 - 383 - 5023 F
firesprjnkler@afssco . com
A FIkE SPRINKLER
DESIGN COMPANY