F15-0024_FP1_1436883720.pdf
What is this? Reviewed for compliance. System should be in copper not cpvc per calcs and cut sheets. Vaughan 0355 Vail Fire & Emergency Services 07/14/15 Vail Fire & Emergency Services 07/14/15 CHATEAU d'OEX3816 LUPINE DRIVEVAIL, COLORADO 81657HYDRAULIC CALCULATIONS& PRODUCT SUBMITTALSTIDS SET OF FIRE SPRINKLER~IO...Q.BEEN REVIEWED AND F TE I FPHOENIX AUTOMATIC SPRINKLER7684 S. BRENTWOOD ST.LITTLETON, CO 80128720.922.9231 PHONEVail Fire & Emergency Services 07/14/15 Vail Fire & Emergency Services 07/14/15 Project Name : CHATEAU d'OEX Drawing No. :Project Location: 3816 LUPINE DRIVE City: VAIL, COCALCULATION SUMMARY Design Areas Design Area Name Min. Density Area of Application Occupancy Calculated Heads Min. Pressure Hose Streams Total Water Pressure @ Source Margin To Source (gpm/ft²) (ft²) # (psi) (gpm) (gpm) (psi) (psi) Min. Flow (gpm) Calc. Mode (Model) 1 DWELLING 512 53 Required86.2 0.1 25.6 2 0 56.8 13.8 Demand (HW) 2 DWELLING 450 45.5 Required90.1 0.1 22.5 2 0 52.9 10.6 Demand (HW) 3 DWELLING 450 45.3 Required92.9 0.1 22.5 2 0 50.1 10.6 Demand (HW) Date 5/11/2015 Page 1 Copyright © 2002-2012 Tyco Fire Protection Products File: C:\Users\Dorgan.AMS\appdata\local\temp\BerRes2_1_1_0161.sv$ Vail Fire & Emergency Services 07/14/15 Design Remote Area Name Remote Area Location Occupancy Classification Density (gpm/ft²) Area of Application (ft²) Coverage per Sprinkler (ft²) Number of Calculated Sprinklers In-Rack Demand (gpm) Special Heads Hose Streams (gpm) Total Water Required (incl. Hose Streams) (gpm) Required Pressure at Source (psi) Type of System Volume - Entire System (gal) 1 BASEMENT GARAGE DWELLING 0.1 512 256 2 0 0 53 86.2 Wet 9 gal Water Supply Information Date Location Source HYDRAULIC CALCULATIONS for March, 2015 Near Site W1 Project Name : CHATEAU d'OEX Contract No. : Project Location: 3816 LUPINE DRIVE City: VAIL, CODate: 12/30/1899 Name of Contractor: PHOENIX Address: 7684 SOUTH BRENTWOOD STREET Phone Number: 303-523-2098 Name of Designer: DLT Authority Having Jurisdiction: VAIL FIRECity: LITTLETON, CO 80128 E-mail: Job Information Contractor Information Notes Date 5/11/2015 Page 2 Copyright © 2002-2012 Tyco Fire Protection Products File: C:\Users\Dorgan.AMS\appdata\local\temp\BerRes2_1_1_0161.sv$ Vail Fire & Emergency Services 07/14/15 Job : CHATEAU d'OEX Diagram for Design Area : 1 (Optimized Hydraulic Simplified) Node Labels: Pipe Labels: Off Off Date 5/11/2015 Page 3 Copyright © 2002-2012 Tyco Fire Protection Products File: C:\Users\Dorgan.AMS\appdata\local\temp\BerRes2_1_1_0161.sv$ Vail Fire & Emergency Services 07/14/15 Job : CHATEAU d'OEX Hydraulic Analysis for : 1 Water Supply Parameters Calculation Info Calculation Mode Hydraulic Model Fluid Name Fluid Weight, (lb/ft³) Fluid Dynamic Viscosity, (lb·s/ft²) Demand Hazen-Williams Water @ 60F (15.6C) N/A for Hazen-Williams calculation. N/A for Hazen-Williams calculation. Supply 1 : W1 Flow (gpm) Pressure (psi) 0 143 1985 136 Inside Hose Flow / Standpipe Demand (gpm) Outside Hose Flow (gpm) Additional Outside Hose Flow (gpm) Other (custom defined) Hose Flow (gpm) Total Hose Flow (gpm) Hoses Ovehead Sprinkler Flow (gpm) InRack Sprinkler Flow (gpm) Other (custom defined) Sprinkler Flow (gpm) Total Sprinkler Flow (gpm) 53 0 0 53 Required Margin of Safety (psi) W1 - Pressure (psi) W1 - Flow (gpm) Demand w/o System Pump(s) 0 86.2 53 N/A Sprinklers Other Date 5/11/2015 Page 4 Copyright © 2002-2012 Tyco Fire Protection Products File: C:\Users\Dorgan.AMS\appdata\local\temp\BerRes2_1_1_0161.sv$ Vail Fire & Emergency Services 07/14/15 Job : CHATEAU d'OEX Hydraulic Analysis for : 1 Supply System Demand Flow, gpm Pressure, psi 150 140 130 120 110 100 90 80 70 60 50 40 30 20 10 0 S1 S2 135.231 D1 D2 0 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 Date 5/11/2015 Page 5 Copyright © 2002-2012 Tyco Fire Protection Products File: C:\Users\Dorgan.AMS\appdata\local\temp\BerRes2_1_1_0161.sv$ Vail Fire & Emergency Services 07/14/15 Job : CHATEAU d'OEX Hydraulic Analysis for : 1Pressure (psi) Label Graph Labels Flow (gpm) Values Description 0 S1 143 Supply point #1 - Static 1985 S2 136 Supply point #2 - Residual 0 D1 3.3 Elevation Pressure 53 D2 86.2 System Demand Pressure (psi) Curve Name Curve Intersections & Safety Margins Flow (gpm) Safety Margin Intersection Pressure (psi) @ Flow (gpm) 70.2 Supply 143 56.8 53 Open Heads Head Ref. Density Density K-Factor Pressure Flow Pressure (gpm/ft²) (gpm/ft²) (gpm/psi½) (psi) (gpm) (psi) Flow (gpm) Coverage (ft²) Required Calculated Head Type 101 6.9 0.1 25.6 13.8 0.1 13.8 25.6 256 Overhead Sprinkler 102 6.9 0.1 25.6 13.8 0.107 15.7 27.4 256 Overhead Sprinkler Date 5/11/2015 Page 6 Copyright © 2002-2012 Tyco Fire Protection Products File: C:\Users\Dorgan.AMS\appdata\local\temp\BerRes2_1_1_0161.sv$ Vail Fire & Emergency Services 07/14/15 Job : CHATEAU d'OEX Node Data Hydraulic Calculations / Fluid Delivery Time Analysis Node# Elev ft Type Hgroup K-Fact. Open/Closed gpm/psi½ Discharge Overdischarge gpm gpm Coverage Density ft² gpm/ft² Tot. Pres. Elev. Pres. psi psi Req. Pres. Req. Discharge psi gpm 001 -0.5 Node NODE 16.7 -3.5 015-I -3.32 Node NODE 23.8 -2.2 015-O -2.54 Node NODE 23.4 -2.6 016-I -6.73 Node NODE 40.5 -0.8 016-O -5.25 Node NODE 24.9 -1.4 017-I -8.07 Node NODE 43.2 -0.2 017-O -7.45 Node NODE 41 -0.5 020 -9.5 Node NODE 45.2 0.4 090 -0.5 Node NODE 16.6 -3.5 091 -0.25 Node NODE 16 -3.6 101 -1 Overhead Sprinkler HEAD 6.9 Open 25.6 0 256 0.1 13.8 -3.2 13.8 25.6 102 -1 Overhead Sprinkler HEAD 6.9 Open 27.4 1.8 256 0.107 15.7 -3.2 13.8 25.6 111 -0.25 Node NODE 13.9 -3.6 W1 -8.5 Supply SUPPLY -53 86.2 0 Date 5/11/2015 Page 7 Copyright © 2002-2012 Tyco Fire Protection Products File: C:\Users\Dorgan.AMS\appdata\local\temp\BerRes2_1_1_0161.sv$ Vail Fire & Emergency Services 07/14/15 Hydraulic Calculations Job : CHATEAU d'OEX PIPE INFORMATION Node 1 Node 2 Elev 1 Elev 2 (ft) K-Factor 1 K-Factor 2 (gpm/psi½) Flow added (q) Total flow (Q) (gpm) Nominal ID Actual ID (in) Fittings quantity x (name) = length (ft) L F T (ft) C Factor Pf per ft (psi) total (Pt) elev (Pe) frict (Pf) (psi) NOTES 1 Path No: 101 111 -1 -0.25 6.9 25.6 25.6 1 1.101 1x(us.90)=3.82 0.75 3.82 4.57 150 0.107 13.8 -0.3 0.5 111 091 -0.25 -0.25 0 25.6 1 1.055 1x(us.Tee-Br)=7.76 8.25 7.76 16.01 150 0.1318 13.9 0 2.1 091 090 -0.25 -0.5 0 25.6 1 1.049 1x(us.90)=2 0.25 2 2.25 120 0.2048 16 0.1 0.5 090 001 -0.5 -0.5 0 25.6 1.5 1.527 4.75 0 4.75 150 0.0218 16.6 0 0.1 001 015-O -0.5 -2.54 27.4 53 1.5 1.527 1x(coupling)=1.17 3x(us.90)=14 53.91 15.17 69.08 150 0.0836 16.7 0.9 5.8 015-O 015-I -2.54 -3.32 0 53 1.5 0 0.78 0 0.78 0 0.0677 23.4 0.3 0.1 Riser Manifold *** 015-I 016-O -3.32 -5.25 0 53 1.5 1.527 1x(coupling)=1.17 1.92 1.17 3.09 150 0.0836 23.8 0.8 0.3 016-O 016-I -5.25 -6.73 0 53 1.5 0 1.49 0 1.49 0 10.0685 24.9 0.6 15 Ames4000B *** 016-I 017-O -6.73 -7.45 0 53 1.5 1.527 1x(coupling)=1.17 0.71 1.17 1.88 150 0.0836 40.5 0.3 0.2 017-O 017-I -7.45 -8.07 0 53 2 0 0.63 0 0.63 0 3.2236 41 0.3 2 RSV-1 *** 017-I 020 -8.07 -9.5 0 53 1.5 1.527 1x(coupling)=1.17 2x(us.90)=9.34 5.11 10.5 15.62 150 0.0836 43.2 0.6 1.3 020 W1 -9.5 -8.5 0 53 1 0.995 3x(us.90)=7 54.5 7 61.5 150 0.6733 45.2 -0.4 41.4 W1 86.2 2 Path No: 102 001 -1 -0.5 6.9 27.4 27.4 1 1.101 1x(us.Tee-Br)=9.56 0.5 9.56 10.06 150 0.121 15.7 -0.2 1.2 001 16.7 Date 5/11/2015 Page 8 Copyright © 2002-2012 Tyco Fire Protection Products File: C:\Users\Dorgan.AMS\appdata\local\temp\BerRes2_1_1_0161.sv$ Vail Fire & Emergency Services 07/14/15 Hydraulic Calculations Job : CHATEAU d'OEX PIPE INFORMATION Node 1 Node 2 Elev 1 Elev 2 (ft) K-Factor 1 K-Factor 2 (gpm/psi½) Flow added (q) Total flow (Q) (gpm) Nominal ID Actual ID (in) Fittings quantity x (name) = length (ft) L F T (ft) C Factor Pf per ft (psi) total (Pt) elev (Pe) frict (Pf) (psi) NOTES * Pressures are balanced to a high degree of accuracy. Values may vary by 0.1 psi due to display rounding. *** Device pressure loss (gain in the case of pumps) is calculated from the device’s curve. If the device curve is printed with this report, it will appear below. The length of the device as shown in the table above comes from the CAD drawing. The friction loss per unit of length is calculated based upon the length and the curve-based loss/gain value. Internal ID and C Factor values are irrelevant as the device is not represented as an addition to any pipe, but is an individual item whose loss/gain is based solely on the curve data. * Maximum Velocity of 21.85 ft/s occurs in the following pipe(s): (W1-020) Date 5/11/2015 Page 9 Copyright © 2002-2012 Tyco Fire Protection Products File: C:\Users\Dorgan.AMS\appdata\local\temp\BerRes2_1_1_0161.sv$ Vail Fire & Emergency Services 07/14/15 Device Graphs Job : CHATEAU d'OEX Pressure vs. Flow Function Design Area: 1; Supply Ref.: W1; Supply Name:W1 Flow, gpm 0300 500 600 700 800 900 1000 1500 1985 Pressure, psi160 150 140 130 120 110 100 90 80 70 60 50 40 30 20 10 0 Pressure Loss Function Design Area: 1; BFP Ref.: 160 (Ames4000B, Size = 1.5); Inlet Node: 016-I; Outlet Node: 016-O Flow, gpm 0 10 20 30 40 50 60 70 80 90 100 110 120 Pressure, psi 20.23 19.23 18.23 17.23 16.23 15.23 14.23 13.23 12.23 11.23 10.23 9.23 8.23 7.23 6.23 5.23 4.23 3.23 2.23 1.23 0.23 15 psi @ 53 gpm Date 5/11/2015 Page 10 Copyright © 2002-2012 Tyco Fire Protection Products File: C:\Users\Dorgan.AMS\appdata\local\temp\BerRes2_1_1_0161.sv$ Vail Fire & Emergency Services 07/14/15 Device Graphs Job : CHATEAU d'OEX Pressure Loss Function Design Area: 1; Valve Ref.: 159 (RSV-1, Size = 2); Inlet Node: 017-I; Outlet Node: 017-O Flow, gpm 05 7 10 20 30 40 50 60 70 90 100 110 120 130 140 150 175 200 225 250Pressure, psi3.46 2.96 2.46 1.96 1.46 0.96 0.46 2 psi @ 53 gpm Pressure Loss Function Design Area: 1; Valve Ref.: 161 (Riser Manifold, Size = 1.5); Inlet Node: 015-I; Outlet Node: 015-O Flow, gpm 0 500 1000 Pressure, psi 0.6 0.1 0.1 psi @ 53 gpm Date 5/11/2015 Page 11 Copyright © 2002-2012 Tyco Fire Protection Products File: C:\Users\Dorgan.AMS\appdata\local\temp\BerRes2_1_1_0161.sv$ Vail Fire & Emergency Services 07/14/15 Design Remote Area Name Remote Area Location Occupancy Classification Density (gpm/ft²) Area of Application (ft²) Coverage per Sprinkler (ft²) Number of Calculated Sprinklers In-Rack Demand (gpm) Special Heads Hose Streams (gpm) Total Water Required (incl. Hose Streams) (gpm) Required Pressure at Source (psi) Type of System Volume - Entire System (gal) 2 LIVING HIGH CEILING DWELLING 0.1 450 225 2 0 0 45.5 90.1 Wet 14.5 gal Water Supply Information Date Location Source HYDRAULIC CALCULATIONS for March, 2015 Near Site W1 Project Name : CHATEAU d'OEX Contract No. : Project Location: 3816 LUPINE DRIVE City: VAIL, CODate: 12/30/1899 Name of Contractor: PHOENIX Address: 7684 SOUTH BRENTWOOD STREET Phone Number: 303-523-2098 Name of Designer: DLT Authority Having Jurisdiction: VAIL FIRECity: LITTLETON, CO 80128 E-mail: Job Information Contractor Information Notes Date 5/11/2015 Page 12 Copyright © 2002-2012 Tyco Fire Protection Products File: C:\Users\Dorgan.AMS\appdata\local\temp\BerRes2_1_1_0161.sv$ Vail Fire & Emergency Services 07/14/15 Job : CHATEAU d'OEX Diagram for Design Area : 2 (Optimized Hydraulic Simplified) Node Labels: Pipe Labels: Off Off Date 5/11/2015 Page 13 Copyright © 2002-2012 Tyco Fire Protection Products File: C:\Users\Dorgan.AMS\appdata\local\temp\BerRes2_1_1_0161.sv$ Vail Fire & Emergency Services 07/14/15 Job : CHATEAU d'OEX Hydraulic Analysis for : 2 Water Supply Parameters Calculation Info Calculation Mode Hydraulic Model Fluid Name Fluid Weight, (lb/ft³) Fluid Dynamic Viscosity, (lb·s/ft²) Demand Hazen-Williams Water @ 60F (15.6C) N/A for Hazen-Williams calculation. N/A for Hazen-Williams calculation. Supply 1 : W1 Flow (gpm) Pressure (psi) 0 143 1985 136 Inside Hose Flow / Standpipe Demand (gpm) Outside Hose Flow (gpm) Additional Outside Hose Flow (gpm) Other (custom defined) Hose Flow (gpm) Total Hose Flow (gpm) Hoses Ovehead Sprinkler Flow (gpm) InRack Sprinkler Flow (gpm) Other (custom defined) Sprinkler Flow (gpm) Total Sprinkler Flow (gpm) 45.5 0 0 45.5 Required Margin of Safety (psi) W1 - Pressure (psi) W1 - Flow (gpm) Demand w/o System Pump(s) 0 90.1 45.5 N/A Sprinklers Other Date 5/11/2015 Page 14 Copyright © 2002-2012 Tyco Fire Protection Products File: C:\Users\Dorgan.AMS\appdata\local\temp\BerRes2_1_1_0161.sv$ Vail Fire & Emergency Services 07/14/15 Job : CHATEAU d'OEX Hydraulic Analysis for : 2 Supply System Demand Flow, gpm Pressure, psi 150 140 130 120 110 100 90 80 70 60 50 40 30 20 10 0 S1 S2 135.231 D1 D2 0 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 Date 5/11/2015 Page 15 Copyright © 2002-2012 Tyco Fire Protection Products File: C:\Users\Dorgan.AMS\appdata\local\temp\BerRes2_1_1_0161.sv$ Vail Fire & Emergency Services 07/14/15 Job : CHATEAU d'OEX Hydraulic Analysis for : 2Pressure (psi) Label Graph Labels Flow (gpm) Values Description 0 S1 143 Supply point #1 - Static 1985 S2 136 Supply point #2 - Residual 0 D1 7.6 Elevation Pressure 45.5 D2 90.1 System Demand Pressure (psi) Curve Name Curve Intersections & Safety Margins Flow (gpm) Safety Margin Intersection Pressure (psi) @ Flow (gpm) 59.5 Supply 143 52.9 45.5 Open Heads Head Ref. Density Density K-Factor Pressure Flow Pressure (gpm/ft²) (gpm/ft²) (gpm/psi½) (psi) (gpm) (psi) Flow (gpm) Coverage (ft²) Required Calculated Head Type 201 6.9 0.1 22.5 10.6 0.1 10.6 22.5 225 Overhead Sprinkler 202 6.9 0.1 22.5 10.6 0.102 11.1 23 225 Overhead Sprinkler Date 5/11/2015 Page 16 Copyright © 2002-2012 Tyco Fire Protection Products File: C:\Users\Dorgan.AMS\appdata\local\temp\BerRes2_1_1_0161.sv$ Vail Fire & Emergency Services 07/14/15 Job : CHATEAU d'OEX Node Data Hydraulic Calculations / Fluid Delivery Time Analysis Node# Elev ft Type Hgroup K-Fact. Open/Closed gpm/psi½ Discharge Overdischarge gpm gpm Coverage Density ft² gpm/ft² Tot. Pres. Elev. Pres. psi psi Req. Pres. Req. Discharge psi gpm 015-I -3.32 Node NODE 38.3 -2.2 015-O -2.54 Node NODE 37.9 -2.6 016-I -6.73 Node NODE 55 -0.8 016-O -5.25 Node NODE 39.3 -1.4 017-I -8.07 Node NODE 57.7 -0.2 017-O -7.45 Node NODE 55.4 -0.5 020 -9.5 Node NODE 59.3 0.4 090 -0.5 Node NODE 32.4 -3.5 091 -0.25 Node NODE 30.9 -3.6 106 22 Node NODE 17.6 -13.2 108 22 Node NODE 7.5 -13.2 109 22 Node NODE 6.4 -13.2 201 9 Overhead Sprinkler HEAD 6.9 Open 22.5 0 225 0.1 10.6 -7.6 10.6 22.5 202 9 Overhead Sprinkler HEAD 6.9 Open 23 0.5 225 0.102 11.1 -7.6 10.6 22.5 W1 -8.5 Supply SUPPLY -45.5 90.1 0 Date 5/11/2015 Page 17 Copyright © 2002-2012 Tyco Fire Protection Products File: C:\Users\Dorgan.AMS\appdata\local\temp\BerRes2_1_1_0161.sv$ Vail Fire & Emergency Services 07/14/15 Hydraulic Calculations Job : CHATEAU d'OEX PIPE INFORMATION Node 1 Node 2 Elev 1 Elev 2 (ft) K-Factor 1 K-Factor 2 (gpm/psi½) Flow added (q) Total flow (Q) (gpm) Nominal ID Actual ID (in) Fittings quantity x (name) = length (ft) L F T (ft) C Factor Pf per ft (psi) total (Pt) elev (Pe) frict (Pf) (psi) NOTES 1 Path No: 201 109 9 22 6.9 22.5 22.5 1 1.101 1x(us.90)=3.82 13 3.82 16.82 150 0.0843 10.6 -5.6 1.4 109 108 22 22 0 22.5 1 1.055 10 0 10 150 0.1038 6.4 0 1 108 106 22 22 23 45.5 1 1.055 1x(us.Tee-Br)=7.76 18.69 7.76 26.46 150 0.3823 7.5 0 10.1 106 091 22 -0.25 0 45.5 1.5 1.527 1x(us.90)=4.67 2x(us.Tee-Br)=18.67 35.71 23.34 59.05 150 0.0631 17.6 9.6 3.7 091 090 -0.25 -0.5 0 45.5 1 1.049 1x(us.90)=2 0.25 2 2.25 120 0.5942 30.9 0.1 1.3 090 015-O -0.5 -2.54 0 45.5 1.5 1.527 1x(coupling)=1.17 3x(us.90)=14 58.67 15.17 73.84 150 0.0631 32.4 0.9 4.7 015-O 015-I -2.54 -3.32 0 45.5 1.5 0 0.78 0 0.78 0 0.0582 37.9 0.3 0.0 Riser Manifold *** 015-I 016-O -3.32 -5.25 0 45.5 1.5 1.527 1x(coupling)=1.17 1.92 1.17 3.09 150 0.0631 38.3 0.8 0.2 016-O 016-I -5.25 -6.73 0 45.5 1.5 0 1.49 0 1.49 0 10.0869 39.3 0.6 15 Ames4000B *** 016-I 017-O -6.73 -7.45 0 45.5 1.5 1.527 1x(coupling)=1.17 0.71 1.17 1.88 150 0.0631 55 0.3 0.1 017-O 017-I -7.45 -8.07 0 45.5 2 0 0.63 0 0.63 0 3.1639 55.4 0.3 2 RSV-1 *** 017-I 020 -8.07 -9.5 0 45.5 1.5 1.527 1x(coupling)=1.17 2x(us.90)=9.34 5.11 10.5 15.62 150 0.0631 57.7 0.6 1 020 W1 -9.5 -8.5 0 45.5 1 0.995 3x(us.90)=7 54.5 7 61.5 150 0.5084 59.3 -0.4 31.3 W1 90.1 2 Path No: 202 108 9 22 6.9 23 23 1 1.101 1x(us.Tee-Br)=9.56 13 9.56 22.56 150 0.0878 11.1 -5.6 2 108 7.5 Date 5/11/2015 Page 18 Copyright © 2002-2012 Tyco Fire Protection Products File: C:\Users\Dorgan.AMS\appdata\local\temp\BerRes2_1_1_0161.sv$ Vail Fire & Emergency Services 07/14/15 Hydraulic Calculations Job : CHATEAU d'OEX PIPE INFORMATION Node 1 Node 2 Elev 1 Elev 2 (ft) K-Factor 1 K-Factor 2 (gpm/psi½) Flow added (q) Total flow (Q) (gpm) Nominal ID Actual ID (in) Fittings quantity x (name) = length (ft) L F T (ft) C Factor Pf per ft (psi) total (Pt) elev (Pe) frict (Pf) (psi) NOTES * Pressures are balanced to a high degree of accuracy. Values may vary by 0.1 psi due to display rounding. *** Device pressure loss (gain in the case of pumps) is calculated from the device’s curve. If the device curve is printed with this report, it will appear below. The length of the device as shown in the table above comes from the CAD drawing. The friction loss per unit of length is calculated based upon the length and the curve-based loss/gain value. Internal ID and C Factor values are irrelevant as the device is not represented as an addition to any pipe, but is an individual item whose loss/gain is based solely on the curve data. * Maximum Velocity of 18.77 ft/s occurs in the following pipe(s): (W1-020) Date 5/11/2015 Page 19 Copyright © 2002-2012 Tyco Fire Protection Products File: C:\Users\Dorgan.AMS\appdata\local\temp\BerRes2_1_1_0161.sv$ Vail Fire & Emergency Services 07/14/15 Device Graphs Job : CHATEAU d'OEX Pressure vs. Flow Function Design Area: 2; Supply Ref.: W1; Supply Name:W1 Flow, gpm 0300 500 600 700 800 900 1000 1500 1985 Pressure, psi160 150 140 130 120 110 100 90 80 70 60 50 40 30 20 10 0 Pressure Loss Function Design Area: 2; BFP Ref.: 160 (Ames4000B, Size = 1.5); Inlet Node: 016-I; Outlet Node: 016-O Flow, gpm 0 10 20 30 40 50 60 70 80 90 100 110 120 Pressure, psi 20.23 19.23 18.23 17.23 16.23 15.23 14.23 13.23 12.23 11.23 10.23 9.23 8.23 7.23 6.23 5.23 4.23 3.23 2.23 1.23 0.23 15 psi @ 45.5 gpm Date 5/11/2015 Page 20 Copyright © 2002-2012 Tyco Fire Protection Products File: C:\Users\Dorgan.AMS\appdata\local\temp\BerRes2_1_1_0161.sv$ Vail Fire & Emergency Services 07/14/15 Device Graphs Job : CHATEAU d'OEX Pressure Loss Function Design Area: 2; Valve Ref.: 159 (RSV-1, Size = 2); Inlet Node: 017-I; Outlet Node: 017-O Flow, gpm 05 7 10 20 30 40 50 60 70 90 100 110 120 130 140 150 175 200 225 250Pressure, psi3.46 2.96 2.46 1.96 1.46 0.96 0.46 2 psi @ 45.5 gpm Pressure Loss Function Design Area: 2; Valve Ref.: 161 (Riser Manifold, Size = 1.5); Inlet Node: 015-I; Outlet Node: 015-O Flow, gpm 0 500 1000 Pressure, psi 0.6 0.1 0.0 psi @ 45.5 gpm Date 5/11/2015 Page 21 Copyright © 2002-2012 Tyco Fire Protection Products File: C:\Users\Dorgan.AMS\appdata\local\temp\BerRes2_1_1_0161.sv$ Vail Fire & Emergency Services 07/14/15 Design Remote Area Name Remote Area Location Occupancy Classification Density (gpm/ft²) Area of Application (ft²) Coverage per Sprinkler (ft²) Number of Calculated Sprinklers In-Rack Demand (gpm) Special Heads Hose Streams (gpm) Total Water Required (incl. Hose Streams) (gpm) Required Pressure at Source (psi) Type of System Volume - Entire System (gal) 3 UPPER LEVEL BED RM DWELLING 0.1 450 225 2 0 0 45.3 92.9 Wet 9.6 gal Water Supply Information Date Location Source HYDRAULIC CALCULATIONS for March, 2015 Near Site W1 Project Name : CHATEAU d'OEX Contract No. : Project Location: 3816 LUPINE DRIVE City: VAIL, CODate: 12/30/1899 Name of Contractor: PHOENIX Address: 7684 SOUTH BRENTWOOD STREET Phone Number: 303-523-2098 Name of Designer: DLT Authority Having Jurisdiction: VAIL FIRECity: LITTLETON, CO 80128 E-mail: Job Information Contractor Information Notes Date 5/11/2015 Page 22 Copyright © 2002-2012 Tyco Fire Protection Products File: C:\Users\Dorgan.AMS\appdata\local\temp\BerRes2_1_1_0161.sv$ Vail Fire & Emergency Services 07/14/15 Job : CHATEAU d'OEX Diagram for Design Area : 3 (Optimized Hydraulic Simplified) Node Labels: Pipe Labels: Off Off Date 5/11/2015 Page 23 Copyright © 2002-2012 Tyco Fire Protection Products File: C:\Users\Dorgan.AMS\appdata\local\temp\BerRes2_1_1_0161.sv$ Vail Fire & Emergency Services 07/14/15 Job : CHATEAU d'OEX Hydraulic Analysis for : 3 Water Supply Parameters Calculation Info Calculation Mode Hydraulic Model Fluid Name Fluid Weight, (lb/ft³) Fluid Dynamic Viscosity, (lb·s/ft²) Demand Hazen-Williams Water @ 60F (15.6C) N/A for Hazen-Williams calculation. N/A for Hazen-Williams calculation. Supply 1 : W1 Flow (gpm) Pressure (psi) 0 143 1985 136 Inside Hose Flow / Standpipe Demand (gpm) Outside Hose Flow (gpm) Additional Outside Hose Flow (gpm) Other (custom defined) Hose Flow (gpm) Total Hose Flow (gpm) Hoses Ovehead Sprinkler Flow (gpm) InRack Sprinkler Flow (gpm) Other (custom defined) Sprinkler Flow (gpm) Total Sprinkler Flow (gpm) 45.3 0 0 45.3 Required Margin of Safety (psi) W1 - Pressure (psi) W1 - Flow (gpm) Demand w/o System Pump(s) 0 92.9 45.3 N/A Sprinklers Other Date 5/11/2015 Page 24 Copyright © 2002-2012 Tyco Fire Protection Products File: C:\Users\Dorgan.AMS\appdata\local\temp\BerRes2_1_1_0161.sv$ Vail Fire & Emergency Services 07/14/15 Job : CHATEAU d'OEX Hydraulic Analysis for : 3 Supply System Demand Flow, gpm Pressure, psi 150 140 130 120 110 100 90 80 70 60 50 40 30 20 10 0 S1 S2 135.231 D1 D2 0 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 Date 5/11/2015 Page 25 Copyright © 2002-2012 Tyco Fire Protection Products File: C:\Users\Dorgan.AMS\appdata\local\temp\BerRes2_1_1_0161.sv$ Vail Fire & Emergency Services 07/14/15 Job : CHATEAU d'OEX Hydraulic Analysis for : 3Pressure (psi) Label Graph Labels Flow (gpm) Values Description 0 S1 143 Supply point #1 - Static 1985 S2 136 Supply point #2 - Residual 0 D1 11.9 Elevation Pressure 45.3 D2 92.9 System Demand Pressure (psi) Curve Name Curve Intersections & Safety Margins Flow (gpm) Safety Margin Intersection Pressure (psi) @ Flow (gpm) 58.8 Supply 143 50.1 45.3 Open Heads Head Ref. Density Density K-Factor Pressure Flow Pressure (gpm/ft²) (gpm/ft²) (gpm/psi½) (psi) (gpm) (psi) Flow (gpm) Coverage (ft²) Required Calculated Head Type 301 6.9 0.1 22.5 10.6 0.1 10.6 22.5 225 Overhead Sprinkler 302 6.9 0.1 22.5 10.6 0.101 10.9 22.8 225 Overhead Sprinkler Date 5/11/2015 Page 26 Copyright © 2002-2012 Tyco Fire Protection Products File: C:\Users\Dorgan.AMS\appdata\local\temp\BerRes2_1_1_0161.sv$ Vail Fire & Emergency Services 07/14/15 Job : CHATEAU d'OEX Node Data Hydraulic Calculations / Fluid Delivery Time Analysis Node# Elev ft Type Hgroup K-Fact. Open/Closed gpm/psi½ Discharge Overdischarge gpm gpm Coverage Density ft² gpm/ft² Tot. Pres. Elev. Pres. psi psi Req. Pres. Req. Discharge psi gpm 301 19 Overhead Sprinkler HEAD 6.9 Open 22.5 0 225 0.1 10.6 -11.9 10.6 22.5 302 19 Overhead Sprinkler HEAD 6.9 Open 22.8 0.3 225 0.101 10.9 -11.9 10.6 22.5 068 20 Node NODE 10.7 -12.3 066 20 Node NODE 11.4 -12.3 065 20 Node NODE 16.9 -12.3 008 -0.5 Node NODE 38 -3.5 015-O -2.54 Node NODE 41 -2.6 015-I -3.32 Node NODE 41.3 -2.2 016-O -5.25 Node NODE 42.4 -1.4 016-I -6.73 Node NODE 58 -0.8 017-O -7.45 Node NODE 58.5 -0.5 017-I -8.07 Node NODE 60.7 -0.2 020 -9.5 Node NODE 62.3 0.4 W1 -8.5 Supply SUPPLY -45.3 92.9 0 Date 5/11/2015 Page 27 Copyright © 2002-2012 Tyco Fire Protection Products File: C:\Users\Dorgan.AMS\appdata\local\temp\BerRes2_1_1_0161.sv$ Vail Fire & Emergency Services 07/14/15 Hydraulic Calculations Job : CHATEAU d'OEX PIPE INFORMATION Node 1 Node 2 Elev 1 Elev 2 (ft) K-Factor 1 K-Factor 2 (gpm/psi½) Flow added (q) Total flow (Q) (gpm) Nominal ID Actual ID (in) Fittings quantity x (name) = length (ft) L F T (ft) C Factor Pf per ft (psi) total (Pt) elev (Pe) frict (Pf) (psi) NOTES 1 Path No: 301 068 19 20 6.9 22.5 22.5 1 1.097 1x(us.90)=2.49 1 2.49 3.49 120 0.1297 10.6 -0.4 0.5 068 066 20 20 0 22.5 1 1.055 1x(us.90)=3.11 4.38 3.11 7.48 150 0.1038 10.7 0 0.8 066 065 20 20 22.8 45.3 1 1.055 1x(us.Tee-Br)=7.76 6.71 7.76 14.47 150 0.379 11.4 0 5.5 065 008 20 -0.5 0 45.3 1.25 1.291 3x(us.Tee-Br)=19.64 3x(us.90)=9.82 56.29 29.47 85.76 150 0.1418 16.9 8.9 12.2 008 015-O -0.5 -2.54 0 45.3 1.5 1.527 1x(coupling)=1.17 2x(us.90)=9.34 23.48 10.5 33.98 150 0.0626 38 0.9 2.1 015-O 015-I -2.54 -3.32 0 45.3 1.5 0 0.78 0 0.78 0 0.0579 41 0.3 0.0 Riser Manifold *** 015-I 016-O -3.32 -5.25 0 45.3 1.5 1.527 1x(coupling)=1.17 1.92 1.17 3.09 150 0.0626 41.3 0.8 0.2 016-O 016-I -5.25 -6.73 0 45.3 1.5 0 1.49 0 1.49 0 10.0874 42.4 0.6 15 Ames4000B *** 016-I 017-O -6.73 -7.45 0 45.3 1.5 1.527 1x(coupling)=1.17 0.71 1.17 1.88 150 0.0626 58 0.3 0.1 017-O 017-I -7.45 -8.07 0 45.3 2 0 0.63 0 0.63 0 3.1622 58.5 0.3 2 RSV-1 *** 017-I 020 -8.07 -9.5 0 45.3 1.5 1.527 1x(coupling)=1.17 2x(us.90)=9.34 5.11 10.5 15.62 150 0.0626 60.7 0.6 1 020 W1 -9.5 -8.5 0 45.3 1 0.995 3x(us.90)=7 54.5 7 61.5 150 0.504 62.3 -0.4 31 W1 92.9 2 Path No: 302 066 19 20 6.9 22.8 22.8 1 1.097 1x(us.Tee-Br)=6.22 1 6.22 7.22 120 0.1327 10.9 -0.4 1 066 11.4 Date 5/11/2015 Page 28 Copyright © 2002-2012 Tyco Fire Protection Products File: C:\Users\Dorgan.AMS\appdata\local\temp\BerRes2_1_1_0161.sv$ Vail Fire & Emergency Services 07/14/15 Hydraulic Calculations Job : CHATEAU d'OEX PIPE INFORMATION Node 1 Node 2 Elev 1 Elev 2 (ft) K-Factor 1 K-Factor 2 (gpm/psi½) Flow added (q) Total flow (Q) (gpm) Nominal ID Actual ID (in) Fittings quantity x (name) = length (ft) L F T (ft) C Factor Pf per ft (psi) total (Pt) elev (Pe) frict (Pf) (psi) NOTES * Pressures are balanced to a high degree of accuracy. Values may vary by 0.1 psi due to display rounding. *** Device pressure loss (gain in the case of pumps) is calculated from the device’s curve. If the device curve is printed with this report, it will appear below. The length of the device as shown in the table above comes from the CAD drawing. The friction loss per unit of length is calculated based upon the length and the curve-based loss/gain value. Internal ID and C Factor values are irrelevant as the device is not represented as an addition to any pipe, but is an individual item whose loss/gain is based solely on the curve data. * Maximum Velocity of 18.69 ft/s occurs in the following pipe(s): (W1-020) Date 5/11/2015 Page 29 Copyright © 2002-2012 Tyco Fire Protection Products File: C:\Users\Dorgan.AMS\appdata\local\temp\BerRes2_1_1_0161.sv$ Vail Fire & Emergency Services 07/14/15 Device Graphs Job : CHATEAU d'OEX Pressure vs. Flow Function Design Area: 3; Supply Ref.: W1; Supply Name:W1 Flow, gpm 0300 500 600 700 800 900 1000 1500 1985 Pressure, psi160 150 140 130 120 110 100 90 80 70 60 50 40 30 20 10 0 Pressure Loss Function Design Area: 3; BFP Ref.: 160 (Ames4000B, Size = 1.5); Inlet Node: 016-I; Outlet Node: 016-O Flow, gpm 0 10 20 30 40 50 60 70 80 90 100 110 120 Pressure, psi 20.23 19.23 18.23 17.23 16.23 15.23 14.23 13.23 12.23 11.23 10.23 9.23 8.23 7.23 6.23 5.23 4.23 3.23 2.23 1.23 0.23 15 psi @ 45.3 gpm Date 5/11/2015 Page 30 Copyright © 2002-2012 Tyco Fire Protection Products File: C:\Users\Dorgan.AMS\appdata\local\temp\BerRes2_1_1_0161.sv$ Vail Fire & Emergency Services 07/14/15 Device Graphs Job : CHATEAU d'OEX Pressure Loss Function Design Area: 3; Valve Ref.: 159 (RSV-1, Size = 2); Inlet Node: 017-I; Outlet Node: 017-O Flow, gpm 05 7 10 20 30 40 50 60 70 90 100 110 120 130 140 150 175 200 225 250Pressure, psi3.46 2.96 2.46 1.96 1.46 0.96 0.46 2 psi @ 45.3 gpm Pressure Loss Function Design Area: 3; Valve Ref.: 161 (Riser Manifold, Size = 1.5); Inlet Node: 015-I; Outlet Node: 015-O Flow, gpm 0 500 1000 Pressure, psi 0.6 0.1 0.0 psi @ 45.3 gpm Date 5/11/2015 Page 31 Copyright © 2002-2012 Tyco Fire Protection Products File: C:\Users\Dorgan.AMS\appdata\local\temp\BerRes2_1_1_0161.sv$ Vail Fire & Emergency Services 07/14/15 WATER FLOW TEST REPORT PROJECT NAME: JOB # HYDRANT # & LOCATION: DATE: 1/3/1900 TEST BY: Day or Week: MARCH TIME OF DAY: Noon MIN. OF FLOW: WATER SUPPLIED BY: Rangeview MW PURPOSE OF TEST: DATA FLOW HYDRANT(S) A1 A2 A3 SIZE OPENING: 2.5 0 COEFFICIENT: 0.9 0 PITOT READING: 140 0 GPM: 1985 0 0 TOTAL FLOW DURING TEST: 1985 GPM STATIC READING: 153 PSI RESIDUAL: 146 PSI RESULTS: AT 20 PSI RESIDUAL 9736 GPM AT 0 PSI 10501 GPM ESTIMATED CONSUMPTION: 1985 GAL. REMARKS: BERSIN RES PAS Near Site FIRE FLOW 1985 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 0 500 1000 1500 2000 2500 3000 3500 4000 Pressure, psigFlow, gpmVail Fire & Emergency Services 07/14/15 RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Pendent Wet Pipe and Dry Pipe Systems Page 1 of 6 FEBRUARY 2014 TFP400 Worldwide Contacts www.tyco-fire.com IMPORTANT Always refer to Technical Data Sheet TFP700 for the “INSTALLER WARNING” that provides cautions with respect to handling and instal-lation of sprinkler systems and components. Improper handling and installation can permanently damage a sprinkler system or its components and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. General Description The TYCO RAPID RESPONSE Series LFII Residential Pendent and Recessed Pendent Sprinklers (TY2234) are decorative, fast response, frangible bulb sprinklers designed for use in residential occu-pancies such as homes, apart-ments, dormitories, and hotels. When aesthetics and optimized flow charac-teristics are the major consideration, the Series LFII Residential Sprinklers (TY2234) should be the first choice. The Series LFII Residential Sprinklers are intended for use in the following scenarios: • wet and dry pipe residential sprin-kler systems for one- and two-family dwellings and mobile homes per NFPA 13D • wet and dry pipe residential sprin-kler systems for residential occu-pancies up to and including four stories in height per NFPA 13R • wet and dry pipe sprinkler systems for the residential portions of any occupancy per NFPA 13 The recessed version of the Series LFII Residential Sprinklers is intended for use in areas with finished ceilings. It employs a two-piece Style 20 Recessed Escutcheon. The Recessed Escutcheon provides 1/4 inch (6,4 mm) of recessed adjustment or up to 1/2 inch (12,7 mm) of total adjustment from the flush ceiling position. The adjustment provided by the Recessed Escutcheon reduces the accuracy to which the pipe drops to the sprinklers must be cut. The Series LFII Residential Sprinklers have been designed with heat sensi-tivity and water distribution charac-teristics proven to help in the control of residential fires and to improve the chance for occupants to escape or be evacuated. Dry Pipe System Application The Series LFII Residential Pendent and Recessed Pendent Sprinklers offers a laboratory approved option for designing dry pipe residential sprinkler systems, whereas, most residential sprinklers are laboratory approved for wet systems only. Through extensive testing, it has been determined that the number of design sprinklers (hydraulic design area) for the Series LFII Residential Pendent and Recessed Pendent Sprinklers (TY2234) need not be increased over the number of design sprinklers (hydraulic design area) as specified for wet pipe sprinkler systems, as is accustomed for density/area sprinkler systems designed per NFPA 13. Consequently, the Series LFII Residential Sprinklers offer the features of non-water filled pipe in addition to not having to increase the number of design sprinklers (hydraulic design area) for systems designed to NFPA 13, 13D, or 13R. NOTICE The Series LFII Residential Pendent and Recessed Pendent Sprinklers (TY2234) described herein must be installed and maintained in compliance with this document and the applicable stan-dards of the National Fire Protection Association, in addition to the stan-dards of any authorities having jurisdic-tion. Failure to do so may impair the performance of these devices. The owner is responsible for main-taining their fire protection system and devices in proper operating condi-tion. Contact the installing contractor or sprinkler manufacturer with any questions. Sprinkler Identification Number (SIN) TY2234 Technical Data Approvals UL Listed for use with wet pipe and dry pipe systems C-UL Listed for use only with wet pipe systems NSF Certified to NSF/ANSI 61 For details on these approvals, refer to the Design Criteria section. Maximum Working Pressure 175 psi (12,1 bar) Discharge Coefficient K = 4.9 GPM/psi1/2 (70,6 LPM/bar1/2)Temperature Rating 155°F (68°C) or 175°F (79°C) Finishes Natural Brass Pure or Signal White Chrome Plated Physical Characteristics Frame.............................Brass Button............................Copper Sealing Assembly . . . . . . . . . . . . . . . . Beryllium Nickel w/TEFLON Bulb (3 mm) ........................ Glass Compression Screw . . . . . . . . . . . . . . . . Bronze Deflector..........................Bronze Ejection Spring...............Stainless Steel Vail Fire & Emergency Services 07/14/15 TFP400 Page 2 of 6 Operation The glass bulb contains a fluid that expands when exposed to heat. When the rated temperature is reached, the fluid expands sufficiently to shatter the glass bulb, allowing the sprinkler to activate and flow water. Design Criteria The TYCO RAPID RESPONSE Series LFII Residential Pendent and Recessed Pendent Sprinklers (TY2234) are UL and C-UL Listed for installation in accordance with this section. Residential Sprinkler Design Guide When conditions exist that are outside the scope of the provided criteria, refer to the Residential Sprinkler Design Guide TFP490 for the manufacturer’s recommendations that may be acceptable to the local authority having jurisdiction. System Types Per the UL Listing, wet pipe and dry pipe systems may be utilized. Per the C-UL Listing, only wet pipe systems may be utilized. Refer to Technical Data Sheet TFP485 for the use of residential sprinklers in residential dry pipe systems. Ceiling Types Smooth flat horizontal, or beamed, or sloped, in accordance with the 2013 Edition of NFPA 13D, 13R, or 13 as applicable. Hydraulic Design (NFPA 13D and 13R) For systems designed to NFPA 13D or NFPA 13R, the minimum re quired sprinkler flow rates are SURFACE ESCUTCHEON PLATE SEATING 1-5/8" (41,3 mm) - 2 Button Temperature rating is indicated on Deector. DeectorCompression Screw Bulb Sealing Assembly - 6 *- 4 5 - 3 - * * 64 5 1 3 2 Components: Frame 1 - 1/2" NPT 7/16" (11,1 mm) MAKE-IN NOMINAL ESCUTCHEON STYLE 20 RECESSED WRENCH (57,2 mm) 2-1/4" FLATS (73,0 mm)2-7/8" DIA. CROSS SECTION PENDENT RECESSED PENDENT TY2234 2-7/8" DIA. (73,0 mm) (57,2 mm) 2-1/4" DIA. MOUNTING SPRINKLER CLOSURE SURFACE FITTING FACE OF (11,1±3,2 mm) 7/16±1/8" MOUNTING PLATE 1-3/8" (34,9 mm) 1-1/8" (28,6 mm) (3,2 mm) 1/8" 1/2" (12,7 mm) 1/4" (6,4 mm) WRENCH RECESS (END "A" USED FOR TY2234) RECESS WRENCH WITH SPRINKLER ENGAGEMENT IN TO ENSURE WRENCHING AREA PUSH WRENCH FIGURE 1 RAPID RESPONSE SERIES LFII RESIDENTIAL PENDENT AND RECESSED PENDENT SPRINKLERS (TY2234) FIGURE 3 W-TYPE 6 SPRINKLER WRENCH FIGURE 4 W-TYPE 7 RECESSED SPRINKLER WRENCH FIGURE 2 STYLE 20 RECESSED ESCUTCHEON FOR USE WITH THE RAPID RESPONSE SERIES LFII RESIDENTIAL PENDENT SPRINKLER (TY2234) Vail Fire & Emergency Services 07/14/15 TFP400 Page 3 of 6 given in Tables A and B as a func-tion of temperature rating and the maximum allowable coverage areas. The sprinkler flow rate is the minimum required discharge from each of the total number of “design sprinklers” as specified in NFPA 13D or NFPA 13R. The number of “design sprinklers” specified in NFPA 13D and 13R for wet pipe systems is to be applied when designing dry pipe systems. Hydraulic Design (NFPA 13) For systems designed to NFPA 13, the number of design sprinklers is to be the four most hydraulically demanding sprinklers. The minimum required discharge from each of the four sprinklers is to be the greater of the following: • The flow rates given in Tables A or B as a function of temperature rating and the maximum allowable coverage area. • A minimum discharge of 0.1 gpm/ft2 over the “design area” comprised of the four most hydraulically demanding sprinklers for actual coverage areas protected by the four sprinklers. The number of “design sprinklers” specified in NFPA 13 for wet pipe systems is to be applied when designing dry pipe systems. Dry Pipe System Water Delivery When using the Series LFII Residential Sprinklers (TY2234) in dry pipe sprin-kler systems, the time for water delivery must not exceed 15 seconds for the most remote operating sprinkler. Obstruction to Water Distribution Sprinklers are to be located in accor-dance with the obstruction rules of NFPA 13D, 13R, and 13 as appli-cable for residential sprinklers as well as with the obstruction criteria described within the Technical Data Sheet TFP490. Operational Sensitivity Sprinklers are to be installed with a deflector-to-ceiling distance of 1-1/4 to 4 inches. Sprinkler Spacing The minimum spacing between sprin-klers is 8 feet (2,4 m). The maximum spacing between sprinklers cannot exceed the length of the coverage area (Table A or B) being hydraulically calculated (e.g., maximum 12 feet for a 12 ft. x 12 ft. coverage area, or 20 feet for a 20 ft. x 20 ft. coverage area). Installation The TYCO RAPID RESPONSE Series LFII Residential Pendent and Recessed Pendent Sprinklers (TY2234) must be installed in accor-dance with this section: General Instructions Do not install any bulb type sprin-kler if the bulb is cracked or there is a loss of liquid from the bulb. With the sprinkler held horizontally, a small air bubble should be present. The diam-eter of the air bubble is approximately 1/16 inch (1,6 mm). A leak-tight 1/2 inch NPT sprinkler joint should be obtained by applying a minimum-to-maximum torque of 7 to 14 ft.-lbs. (9,5 to 19,0 Nm). Higher levels of torque can distort the sprin-kler Inlet with consequent leakage or impairment of the sprinkler. Do not attempt to compensate for insufficient adjustment in an Escutcheon Plate by under- or over-tightening the sprinkler. Re-adjust the position of the sprinkler fitting to suit. Series LFII Residential Pendent Sprinklers The Series LFII Residential Pendent Sprinklers must be installed in accor-dance with the following instructions. Step 1. Install pendent sprinklers in the pendent position with the deflector parallel to the ceiling. Step 2. With pipe thread sealant applied to the pipe threads, hand-tighten the sprinkler into the sprinkler fitting. Step 3. Tighten the sprinkler into the sprinkler fitting using only the W-Type 6 Sprinkler Wrench (Figure 3). With reference to Figure 1, apply the W-Type 6 Sprinkler Wrench to the wrench flats. Series LFII Residential Recessed Pendent Sprinklers The Series LFII Residential Recessed Pendent Sprinklers must be installed in accordance with the following instructions. Step A. Install recessed pendent sprinklers in the pendent position with the deflector parallel to the ceiling. Step B. After installing the Style 20 Mounting Plate over the sprinkler threads and with pipe thread sealant applied to the pipe threads, hand-tighten the sprinkler into the sprinkler fitting. Step C. Tighten the sprinkler into the sprinkler fitting using only the W-Type 7 Recessed Sprinkler Wrench (Figure 4). With reference to Figure 1, apply the W-Type 7 Recessed Sprinkler Wrench to the sprinkler wrench flats. Step D. After the ceiling has been installed or the finish coat has been applied, slide on the Style 20 Closure over the Series LFII Residential Sprinkler and push the Closure over the Mounting Plate until its flange comes in contact with the ceiling. Vail Fire & Emergency Services 07/14/15 TFP400 Page 4 of 6 Maximum Coverage Area (a) Ft. x Ft. (m x m) DRY PIPE SYSTEM Minimum Flow and Residual Pressure (b, c) Ordinary Temp. Rating 155°F (68°C) Intermediate Temp. Rating 175°F (79°C) Deflector to Ceiling Installation Type Minimum Spacing Ft. (m) Flow GPM (L/min) Pressure PSI (bar) Flow GPM (L/min) Pressure PSI (bar) 12 x 12 (3,7 x 3,7) 13 (49,2) 7.0 (0,48) 13 (49,2) 7.0 (0,48) Smooth Ceilings 1-1/4 to 4 inches Beamed Ceilings per NFPA 13D or 13R 1-1/4 to 1-3/4 inches below bottom of beam. Recessed using Style 20 Escutcheon or non-recessed per NFPA 13D, 13R, or 13 8 (2,4) 14 x 14 (4,3 x 4,3) 14 (53,0) 8.2 (0,57) 14 (53,0) 8.2 (0,57) 16 x 16 (4,9 x 4,9) 15 (56,8) 9.4 (0,65) 15 (56,8) 9.4 (0,65) 18 x 18 (5,5 x 5,5) 18 (68,1) 13.5 (0,93) 18 (68,1) 13.5 (0,93) 20 x 20 (6,1 x 6,1) 21 (79,5) 18.4 (1,27) 21 (79,5) 18.4 (1,27) (a) For coverage area dimensions less than or between those indicated, use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. (b) Requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are calculated using the nominal K-factor. Refer to Hydraulic Design under the Design Criteria section. (c) For NFPA 13 residential applications, the greater of 0.1 gpm/ft2 over the design area of the flow in accordance with the criteria in this table must be used. Max. Coverage Area (a) Ft. x Ft. (m x m) WET PIPE SYSTEM Minimum Flow and Residual Pressure (b, c) Ordinary Temp. Rating 155°F (68°C) Intermediate Temp. Rating 175°F (79°C) Deflector to Ceiling Installation Type Minimum Spacing Ft. (m) Flow GPM (L/min) Pressure PSI (bar) Flow GPM (L/min) Pressure PSI (bar) 12 x 12 (3,7 x 3,7) 13 (49,2) 7.0 (0,48) 13 (49,2) 7.0 (0,48) Smooth Ceilings 1-1/4 to 4 inches Beamed Ceilings per NFPA 13D or 13R 1-1/4 to 1-3/4 inches below bottom of beam. Recessed using Style 20 Escutcheon or non-recessed per NFPA 13D, 13R, or 13 8 (2,4) 14 x 14 (4,3 x 4,3) 13 (49,2) 7.0 (0,48) 13 (49,2) 7.0 (0,48) 16 x 16 (4,9 x 4,9) 13 (49,2) 7.0 (0,48) 13 (49,2) 7.0 (0,48) 18 x 18 (5,5 x 5,5) 17 (64,3) 12.0 (0,83) 17 (64,3) 12.0 (0,83) 20 x 20 (6,1 x 6,1) 20 (75,7) 16.7 (1,15) 20 (75,7) 16.7 (1,15) (a) For coverage area dimensions less than or between those indicated, use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. (b) Requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are calculated using the nominal K-factor. Refer to Hydraulic Design under the Design Criteria section. (c) For NFPA 13 residential applications, the greater of 0.1 gpm/ft2 over the design area of the flow in accordance with the criteria in this table must be used. TABLE A WET PIPE SYSTEM SERIES LFII RESIDENTIAL PENDENT AND RECESSED PENDENT SPRINKLERS (TY2234) NFPA 13D, 13R, AND 13 HYDRAULIC DESIGN CRITERIA TABLE B DRY PIPE SYSTEM SERIES LFII RESIDENTIAL PENDENT AND RECESSED PENDENT SPRINKLERS (TY2234) NFPA 13D, 13R, AND 13 HYDRAULIC DESIGN CRITERIA Vail Fire & Emergency Services 07/14/15 TFP400 Page 5 of 6 Care and Maintenance The TYCO RAPID RESPONSE Series LFII Residential Pendent and Recessed Pendent Sprinklers (TY2234) must be maintained and serviced in accordance with this section: Before closing a fire protection system main control valve for maintenance work on the fire protection system that it controls, permission to shut down the affected fire protection system must be obtained from the proper authorities and notify all personnel who may be affected by this action. Absence of the outer piece of an escutcheon, which is used to cover a clearance hole, can delay sprinkler operation in a fire situation. The owner must assure that the sprinklers are not used for hanging any objects and that the sprinklers are only cleaned by means of gently dusting with a feather duster; other-wise, non-operation in the event of a fire or inadvertent operation may result. Sprinklers which are found to be leaking or exhibiting visible signs of corrosion must be replaced. Automatic sprinklers must never be painted, plated, coated, or other-wise altered after leaving the factory. Modified sprinklers must be replaced. Sprinklers that have been exposed to corrosive products of combustion, but have not operated, should be replaced if they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush. Care must be exercised to avoid damage to the sprinklers - before, during, and after installation. Sprinklers damaged by dropping, striking, wrench twist/slippage, or the like, must be replaced. Also, replace any sprinkler that has a cracked bulb or that has lost liquid from its bulb. (Ref. Installation Section.) The owner is responsible for the inspection, testing, and mainte-nance of their fire protection system and devices in compliance with this document, as well as with the appli-cable standards of the National Fire Protection Association (e.g., NFPA 25), in addition to the standards of any authorities having jurisdiction. Contact the installing contractor or sprinkler manufacturer regarding any questions. Automatic sprinkler systems are recommended to be inspected, tested, and maintained by a qualified Inspection Service in accordance with local requirements and/or national codes. Limited Warranty For warranty terms and conditions, visit www.tyco-fire.com. Ordering Procedure Contact your local distributor for availability. When placing an order, indicate the full product name and Part Number (P/N). Sprinkler Assembly Specify: Series LFII (TY2234), K = 4.9, Residential Pendent Sprinkler, (specify) temperature rating, (specify) finish, P/N (specify): 155°F (68°C) Natural Brass..............P/N 51-201-1-155 Pure White (RAL 9010)* ...... P/N 51-201-3-155 Signal White (RAL 9003) ..... P/N 51-201-4-155 Chrome Plated............. P/N 51-201-9-155 175°F (79°C) Natural Brass..............P/N 51-201-1-175 Pure White (RAL 9010)* ......P/N 51-201-3-175 Signal White (RAL 9003) .....P/N 51-201-4-175 Chrome Plated.............P/N 51-201-9-175 *Eastern Hemisphere sales only Recessed Escutcheon Specify: Style 20 Recessed Escutcheon with (specify*) finish, P/N (specify*) *Refer to Technical Data Sheet TFP770 Sprinkler Wrench Specify: W-Type 6 Sprinkler Wrench, P/N 56-000-6-387 Specify: W-Type 7 Sprinkler Wrench, P/N 56-850-4-001 Vail Fire & Emergency Services 07/14/15 GLOBAL HEADQUARTERS | 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700 TFP400 Page 6 of 6 Copyright © 2014 Tyco Fire Products, LP. All rights reserved. TEFLON is trademark of The DuPont Corporation. Vail Fire & Emergency Services 07/14/15 Series 4000B Reduced Pressure Zone Assemblies are designed to protect potable water supplies in accordance with national plumbing codes and wa-ter authority requirements. This series can be used in a variety of installa-tions, including the prevention of health hazard cross connections in piping systems or for containment at the service line entrance.This series features two in-line, independent check valves, captured springs and replaceable check seats with an intermediate relief valve. Its compact modular design facilitates easy maintenance and assembly access. Sizes 1⁄2"- 1" (15-25mm) shutoffs have tee handles.Specifications A Reduced Pressure Zone Assembly shall be installed at each potentialhealth hazard location to prevent backflow due to backsiphonage and/or backpressure. The assembly shall consist of an internal pressure differentialrelief valve located in a zone between two positive seating check modules with captured springs and silicone seat discs. Seats and seat discs shall be replaceable in both check modules and the relief valve. There shall be no threads or screws in the waterway exposed to line fluids. Service of all inter-nal components shall be through a single access cover secured with stain-less steel bolts. The assembly shall also include two resilient seated isolation valves, four resilient seated test cocks and an air gap drain fitting. The as-sembly shall meet the requirements of: USC Manual 8th Edition†; ASSE Std. 1013; AWWA Std. C511; CSA B64.4. The assembly shall be an Ames Com-pany Series 4000B. ES-A-4000B 2" (50mm) 4000B-HC Series 4000B Reduced Pressure Zone Assemblies Sizes: 1⁄2" – 2" (15 – 50mm) Job Name ________________________________________________Contractor ______________________________________________ Job Location ______________________________________________Approval________________________________________________ Engineer__________________________________________________Contractor’s P.O. No. ______________________________________ Approval__________________________________________________Representative __________________________________________ Ames product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements, please contact Ames Technical Service.Ames reserves the right to change or modify product design, construction, specifications, or materials without prior notice and without incurring any obligation to make such changes and modifications on Ames products previously or subsequently sold. www.amesfirewater.com Features • Single access cover and modular check construction for ease of maintenance • Top entry - all internals immediately accessible • Captured springs for safe maintenance • Internal relief valve for reduced installation clearances • Replaceable seats for economical repair • Bronze body construction for durability - 1⁄2" to 2" (15-50mm) • Ball valve test cocks -screwdriver slotted -1⁄2" to 2" (15-50mm) • Large body passages provides low pressure drop • Compact, space saving design • No special tools required for servicing 1/2" (15mm) 4000B Vail Fire & Emergency Services 07/14/15 2 Pressure — Temperature Suitable for supply pressures up to 175psi (12.06 bar) and water temperature to 180°F (75°C) continuous. Available Models Suffix: B - quarter-turn ball valves LBV - less ball valves LH - locking handle ball valves (open position) SH - stainless steel ball valve handles HC - 21⁄2" inlet/outlet fire hydrant fitting (2" valve) S - bronze strainer Prefix: U -union connections MODEL SIZE (DN) DIMENSIONS STRAINER DIMENSIONS WEIGHT ABCDLMN in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm lbs. kg. 4000B** 1⁄2 15 10 250 45⁄8 117 33⁄8 86 11⁄4 32 51⁄2 140 3 76 2 51 4.50 2.0 4000B M3** 3⁄4 20 103⁄4 273 5 127 31⁄2 89 11⁄2 38 63⁄4 171 35⁄16 84 25⁄16 59 5.75 2.6 4000B M2** 1 25 163⁄4 425 51⁄2 140 3 76 21⁄2 64 91⁄2 241 41⁄2 114 25⁄16 59 12.25 5.6 4000B** 11⁄4 32 173⁄8 44 116 150 31⁄2 89 21⁄2 64 113⁄8 289 51⁄8 130 31⁄8 79 14.62 6.6 4000B** 11⁄2 40 177⁄8 454 6 150 31⁄2 89 21⁄2 64 111⁄8 283 57⁄8 149 33⁄4 95 16.32 7.4 4000B** 2 50 213⁄8 543 73⁄4 197 41⁄2 114 31⁄4 83 131⁄2 343 63⁄16 157 47⁄8 124 30.00 13.6 **Approved by the Foundation for Cross-Connection Control and Hydraulic Research at the University of Southern California. Suffix HC - Fire Hydrant Fittings dimension "A" = 251⁄16 (637mm) M C B N L Weights — Dimensions IMPORTANT: Inquire with governing authorities for local installation requirements. Strainer sold separately Materials Bronze body construction, silicone rubber disc material in the first and second check plus the relief valve. Replaceable poly-mer check seats for first and second checks. Removable stain-less steel relief valve seat. Stainless steel cover bolts. Standardly furnished with NPT body connections. For optional bronze union inlet and outlet connections, specify prefix U (1⁄2" - 2")(15-50mm). Series 4000B furnished with quarter turn, full port, resilient seated, bronze ball valve shutoffs. Standards AWWA C511-92, USC Manual 8th Edition, IAPMO File No. 1563 Approvals Approved by the Foundation for Cross-Connection Control and Hydraulic Research at the University of Southern California. Approval models QT, U. 1013 B64.4 3⁄4" - 2" (20-50mm) (LBV models only) DA Vail Fire & Emergency Services 07/14/15 3 Capacity Performance as established by an independent testing laboratory. *Typical maximum system flow rate (7.5 feet/sec., 2.3 meters/sec.) 1⁄4" (8mm)kPa psi 138 20 117 17 96 14 76 11 55 8 35 5 0 .25 .50 .75 1 1.17 gpm 0 .95 1.9 2.9 3.8 4.5 lpm 3⁄8" (10mm) 0 .25 .50 .75 1 1.25 1.50 2.5 3.1 gpm 0 .95 1.9 2.9 3.8 4.8 5.7 9.5 11.8 lpm 1⁄2" (15mm) 3⁄4" (20mm) 1" (25mm) 11⁄4" (32mm) 11⁄2" (40mm) 2" (50mm) kPa psi 138 20 117 17 96 14 76 11 55 8 35 5 kPa psi 172 25 138 20 103 15 69 10 35 5 0 1 2.5 5 7.5 10 12.5 15 gpm 0 3.8 9.5 19 28.5 38 47.5 57 lpm 5 7.5 15 fps 1.52.3 4.6 mps ΔP ΔP ΔP kPa psi 207 30 165 24 124 18 83 12 41 6 00 0261 01 41 82 226303 43 84246gpm0 7.6 23 38 53 68 84 99 114 129 144 160 175 lpm 7.5 15 fps 2.3 4.6 mps ΔP kPa psi 207 30 172 25 138 20 103 15 69 10 34 5000 5 10 20 30 40 50 60 70 80 gpm 0 19 38 76 114 152 190 228 266 304 lpm 7.5 15 fps 2.3 4.6 mps kPa psi 172 25 138 20 103 15 69 10 34 500 01 020 3040 5060 70 80gpm0 38 76 114 152 190 228 266 304 lpm 5 7.5 10 15 fps 1.5 2.3 3.0 4.6 mps ΔP ΔP kPa psi 207 30 172 25 138 20 103 1569 10 34 5 00ΔP 01 020304 05060708090100110 120 gpm0 38 76 114 152 190228 266304 342 380 418 456 lpm 5 7.5 10 15 fps 1.5 2.3 3.0 4.6 mps kPa psi 207 30 172 25 138 20 103 15 69 10 34 5 00 ΔP0 20 40 60 80 100 120 140 160 180 200 gpm 0 76 152 228 304 380 456 532 608 684 760 lpm 5 7.5 10 15 fps 1.5 2.3 3.0 4.6 mps * * ** * * Flow Rate Flow Rate Flow Rate Flow Rate Flow Rate Flow RateFlow Rate Flow Rate Pressure LossPressure LossPressure LossPressure Loss Pressure LossPressure LossPressure LossPressure Loss Vail Fire & Emergency Services 07/14/15 ES-A-4000B 0625 ©Ames Fire & Waterworks, 2007 A Division of Watts Regulator Company www.amesfirewater.com 1427 North Market Blvd. • Suite #9 • Sacramento, CA 95834 • Phone: 916-928-0123 • Fax: 916-928-9333 For additional information, visit our web site at: www.amesfirewater.com Vail Fire & Emergency Services 07/14/15 General Description The Riser Manifolds described in this technical data sheet provide the nec-essary waterflow alarm, pressure gauge,anddrainequipmentin asingle assembly for use in NFPA 13D or 13R residential sprinkler systems as fol- lows: NFPA 13D · Figure 513D (13D) 1 Inch (DN25) Female Thread x Female Thread NFPA 13D/13R · Figure 513D/R (13D/R) 1-1/2 Inch (DN40) Male Thread x Female Thread Male Thread x Male Thread · Figure 513D/R (13D/R) 2 Inch (DN50) Groove x Groove Male Thread x Groove The variety of sizes and end connec-tions allow cost effective and easy transition to check valves, control valves, and system piping. The Riser Manifoldsmaybeinstalledineitherthe horizontal (flow switch on top) or verti-cal (flow going up). WARNING The Riser Manifolds described herein must be installed and maintained in compliance with this document, as well as with the applicable standards of the National Fire Protection Asso-ciation, in addition to the standards of any other authorities having jurisdic- tion. Failure to do so may impair the performance of these devices. The owner is responsible for maintain-ing their fire protection system and de-vices in proper operating condition. The installing contractor or sprinkler manufacturer should be contacted with any questions. Technical Data Approvals The Figure 513D (13D) and 513D/R (13D/R) Riser Manifolds with a cover tamper switch for the waterflow alarm switch are UL Listed, ULC Listed, and FM Approved. The Figure 513D (13D) and 513D/R (13D/R) Riser Manifolds without a cover tamper switch for the waterflowalarm switch are UL Listed and FMApproved.Maximum Working Pressure 175 psi (12,1 bar) Assembly The manifold body of the Figure 513 is ductile iron, whereas the manifold body of the Figure 13 is cast iron. The two assemblies are completely inter-changeable in function, application, and end-to-end laying length. Finish Red painted. Installation The Riser Manifolds may be installed in either the horizontal (flow switch on top) or vertical (flow going up). The inlet of the Riser Manifold may be di-rectly connected to a shut-off control valve.NOTES (1) Where applicable pipe thread sealant is to be applied sparingly. Use ofanon-hardeningpipethreadsealant is recommended. (2) Provisions for an alarm test flow must be made. The alarm test flow isto be through an orifice having a flow capacity equal to or smaller than the smallestorificesprinklerinthesystem.One of two options can be considered. The first option is to temporarily install a test orifice in the outlet of the drain line prior to performing the alarm test. The second option is to install an In-spector’s Test Connection down-stream of the Waterflow Alarm Switch. (3) Never remove any piping compo-nent nor correct or modify any piping deficiencies without first depressuriz-ing and draining the system. Step 1. Install the manifold body with the flow arrow pointing in the down-stream position using threaded con-nections and/or listed mechanical grooved connections, as applicable. Step 2. Connect the drain line, and then close the drain valve.Step 3. Refer to Figure 4 for wiring guidance. All wiring must be per-formed in accordance with the Author-ity Having Jurisdiction and/or the Na-tional Electrical Code.Step 4. Place the system in service by filling the system with water. When fill-ing the system, partially open the con-trol valve to slowly fill the system. Fill-ing the system slowly will help avoid damaging the waterflow alarm switch.After the system is fully pressurized, completely open the control valve.Step 5. Secure all supply valves open.Figure 513D (13D) and 513D/R (13D/R) Riser Manifolds 1, 1-1/2, and 2 Inch (DN25, DN40, and DN50) For NFPA 13D/13R Residential Sprinkler Systems Page 1 of 6 TFP960 APRIL, 2006 Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 Vail Fire & Emergency Services 07/14/15 Page 2 of 6 TFP960 FIGURE 1 1 INCH (DN25) RISER MANIFOLD ASSEMBLY AND DIMENSIONS 4-1/2" to the Waterflow Alarm Switches. Cover Tamper Switches installed internal ULC Listed Manifolds are equipped with (114,3 mm) 10" (254,0 mm) Approximate weight, 7.5 lbs. (3,4 kg). 1. 2. NOTES: 3/4" NPT (92,1 mm) 3-5/8" 1 (73,0 mm) 2-7/8" 9-3/4" (247,7 mm) Waterflow 3 2 CH: Common Hardware 3. (88,9 mm) 3-1/2" Paddle and Cover Tamper VSR-SF modified with QTY. DESCRIPTION Female x Female NPT 1" Manifold Body, Water Pressure Gauge 200 psi/1400 kPa VSR-SF modified with Waterflow Alarm Switch: 1 3 2 NO. . . 1 . . . 1 N/A 2343 P/N Paddle, UL/FM . . . . . . . . 1 971-096-01 Switch, ULC/FM 1 976-519-01 . . . . . . . . (Normally Closed) Drain Valve FIGURE 2 1-1/2 INCH (DN40) RISER MANIFOLD ASSEMBLY AND DIMENSIONS (136,5 mm) 5-3/8" (288,9 mm) 11-3/8" Male x Male NPT Manifold 11-1/8" (282,6 mm) (54,0 mm) Male x Female NPT Manifold 10" (254,0 mm) NPT 2-1/8" 1" (114,3 mm) 4-1/2" Waterflow 3 2to the Waterflow Alarm Switches. Cover Tamper Switches installed internal ULC Listed Manifolds are equipped with Approximate weight, 8.7 lbs. (3,9 kg). 1. 2. NOTES: CH: Common Hardware 3. (88,9 mm) 3-1/2" QTY. DESCRIPTION 1-1/2" Manifold Body, Male x Female NPT Water Pressure Gauge 300 psi/2000 kPa 3 2 1 NO. . . 1 . . . . . 1 2341 N/A P/N Switch, ULC/FM . . . . . . . . 1 976-519-02 . . . . . . . . . Waterflow Alarm Switch: VSR-SF modified with VSR-SF modified with Paddle and Cover Tamper Paddle, UL/FM 971-096-00 1 1 (Normally Closed) Drain Valve Male x Male NPT . . . . . . . 1 N/A Vail Fire & Emergency Services 07/14/15 Care and Maintenance The following inspection procedure must be performed as indicated, in ad-dition to any specific requirements of the NFPA, and any impairment must be immediately corrected. The owner is responsible for the in- spection, testing, and maintenance of their fire protection system and de-vices in compliance with this docu-ment, as well as with the applicable standards of the National Fire Protec-tion Association (e.g., NFPA 25), in addition to the standards of any authority having jurisdiction. The in- stallingcontractor orproductmanufac-turer should be contacted relative to any questions. It is recommended that automatic sprinkler systems be inspected, tested, and maintained by a qualified Inspection Service in accordance with local requirements and/or national codes. NOTES No attempt is to be made to repair any Riser Manifold component in the field. Only the pressure gauge or waterflow alarm switch can be replaced. If any other problems are encountered the entire riser manifold must be replaced. The flow and alarm test procedure will result in operation of the associated alarms. Consequently, notification must be given to the owner and the fire department, central station, or other signal station to which the alarms are connected, and notification must be given to the building occupants. Before closing a fire protection system control valve for inspection or mainte-nance work on the fire protection sys-tem that it controls, permission to shut down the effected fire protection sys-tem must first be obtained from the proper authorities and all personnel who may be affected by this action must be notified. After placing a fire protection system in service, notify the proper authorities andadvisethoseresponsibleformoni-toring proprietary and/or central sta-tion alarms. Flow Test Procedure Step 1. Fully open the drain valve. Make certain that drainage water will not cause any damage or injury. Step 2. Verify that the residual (flow-ing) pressure indicated by the pres-sure gauge is no less that originally recorded for the system when it was first installed. Step 3. Close the drain valve. Step 4. Verify that the static (not flow-ing) pressure indicated by the pres-sure gauge is no less that originally recorded for the system when it was first installed. Alarm Test Procedure With A Test Orifice (See Installation Note 2) Step 1. Temporarily install a test ori-fice in the drain line outlet. Step 2. Fully open the drain valve. Make certain that drainage water will not cause any damage or injury. Step 3. Verify operation of the associ-ated alarms.Step 3. Close the drain valve. Step 4. Remove the test orifice from the drain line outlet. Alarm Test Procedure With An Inspector’s Test Connection (See Installation Note 2) Step 1. Fully open the Inspector’s Test Connection Valve. Make certain that drainagewaterwillnotcauseanydam-age or injury. Step 2. Verify operation of the associ-ated alarms. Step 3. Close the Inspector’s Test Connection Valve. TFP960 Page 3 of 6 FIGURE 3, 2 INCH (DN50) RISER MANIFOLD ASSEMBLY AND DIMENSIONS Optionally Supply EndGrooved or Male NPT (57,2 mm) (114,3 mm) 2-1/4" 2. ULC Listed Manifolds are equipped with Cover Tamper Switches installed internal to the Waterflow Alarm Switches. . . . . . . . 1 N/A Groove x Groove Male NPT x Groove 300 psi/2000 kPa Water Pressure Gauge Approximate weight, 11.0 lbs. (5,0 kg). NOTES: 1. 3 2 5-7/16" (138,1 mm) 1" NPT 4-1/2" . . 1 2341 (304,8 mm) 12" N/A 1 . . . . . Waterflow DESCRIPTION 2" Manifold Body, 1 NO. P/N QTY. 3 2 CH: Common Hardware 3. ULC/FM . . . . . . . . . . . . . . 1 976-520-01 . . . . . . . . . . . . . . . WaterflowAlarm Switch: VSC with Paddle, VSC with Paddle and Cover Tamper Switch, UL/FM 976-357-01 1 13" (330,2 mm) Male NPT x Groove Groove x Groove, Connection (88,9 mm) 3-1/2" 1 (Normally Closed) Drain Valve Vail Fire & Emergency Services 07/14/15 Page 4 of 6 TFP960 FIGURE 4 WIRING GUIDANCE INCOMING OUTGOING SINGLE CONDUCTOR TERMINAL PLATE LOOPED SECTION UNINSULATED CLAMPING CONDUCTORS SEPARATE STRIPPED ENDS SWITCH TERMINAL CONNECTIONS CLAMPING TERMINAL PLATE IMPROPER CONNECTION METHOD PROPER CONNECTION METHOD SEVERED CAUTION: An uninsulated section of a single conductor is not permitted to be looped around the terminal and serve as two separate connections. The wire must be severed to serve as two separate connections, thereby providing supervision of the connection in the event that the wire becomes dislodged from the terminal. WATERFLOW SWITCH TYPICAL ELECTRICA CONNECTIONS COM NC NO NO FLOW CONTACTS SPDT (Form C) 5A @ 125 VAC CONTACT RATING 2.5A @ 30 VDC . . . . . . . . . . . . . . COM NO NC POWER SIGNAL LOCAL DEVICE NON-SUPERVISED CIRCUIT CONDITION END OF LINE RESISTOR COM SUPERVISED CIRCUIT STYLE B/CLASS B CONTROL NO NC PANEL signaling unit, while the other contact is used to operate a local audible or visual annunciator. Switch has two switches, one can be used to operate a central station, proprietary or remove For supervised circuits, see "Switch Terminal Connections" above. The Waterflow Alarm NOTE: (SEE NOTE) COVER TAMPER SWITCH (ULC ASSEMBLIES ONLY) CONTACTS SHOWN WITH COVER IN PLACE COM . . . . . . . . . . . . . . CONTACT RATING NO CONTACTS 3A @ 250 VAC 5A @ 125 VAC NC SPDT (Form C) 1mA @ 5 VDC min. Vail Fire & Emergency Services 07/14/15 Limited Warranty Products manufactured by Tyco Fire & Building Products (TFBP) are war-ranted solely to the original Buyer for ten (10) years against defects in mate-rial and workmanship when paid for and properly installed and maintained under normal use and service. This warranty will expire ten (10) years from date of shipment by TFBP. No warranty is given for products or com-ponents manufactured by companies not affiliated by ownership with TFBP or for products and components which havebeensubject tomisuse,improper installation, corrosion, or which have not been installed, maintained, modi- fied or repaired in accordance with ap-plicable Standards of the National Fire Protection Association, and/or the standards of any other Authorities Having Jurisdiction. Materials found by TFBP to be defective shall be either repaired or replaced, at TFBP’s sole option. TFBP neither assumes, nor authorizes anypersontoassumeforit, any other obligation in connection with the sale of products or parts of prod-ucts. TFBP shall not beresponsiblefor sprinkler system design errors or inac- curate or incomplete information sup- plied by Buyer or Buyer’s repre-sentatives. In no event shall TFBP be liable, in contract, tort, strict liability or under any other legal theory, for incidental, indirect,specialorconsequentialdam-ages, including but not limited to labor charges, regardless of whether TFBP was informed about the possibility of such damages, and in no event shall TFBP’s liability exceed an amount equal to the sales price. The foregoing warranty is made in lieu of any and all other warranties, ex- press or implied, including warranties ofmerchantabilityandfitnessforapar- ticular purpose. This limited warranty sets forth the ex-clusive remedy for claims based on failure of or defect in products, materi-als or components, whether the claim is made in contract, tort, strict liability or any other legal theory. This warranty will apply to the full ex-tent permitted by law. The invalidity, in whole or part, of any portion of this warranty will not affect the remainder. Ordering Information Riser Manifold: Specify; Size (specify), Figure (specify 513D or 513D/R, (specify connection type inlet x outlet) Riser Manifold (specify - without or with) a cover tam-per switch for the waterflow alarm switch, P/N (specify). NOTES Orders forFigure513Dor513D/Rmay be filled with a Figure 13D or 13D/R, respectively. The two assemblies are completely interchangeable in func-tion, application, and end-to-end lay-ing length. If a ULC Listing is required, the Riser Manifold must be ordered with a cover tamper switch for the waterflow alarm switch.UL/ULC/FM Assemblies With Cover Tamper Switch 1 Inch (DN25) FT x FT. . . . . . . . . . . . . . . P/N 4085 1-1/2 Inch (DN40) MT x FT . . . . . . . . . . . . . . P/N 4088 1-1/2 Inch (DN40) MT x MT . . . . . . . . . . . . . . P/N 4089 2 Inch (DN50) G x G . . . . . . . . . . . . . . . . P/N 4093 2 Inch (DN50) MT x G . . . . . . . . . . . . . . . P/N 4094 UL/FM Assemblies Without Cover Tamper Switch 1 Inch (DN25) FT x FT. . . . . . . . . . . . . . . P/N 4047 1-1/2 Inch (DN40) MT x FT . . . . . . . . . . . . . . P/N 4057 1-1/2 Inch (DN40) MT x MT . . . . . . . . . . . . . . P/N 4058 2 Inch (DN50) G x G . . . . . . . . . . . . . . . . P/N 4059 2 Inch (DN50) MT x G . . . . . . . . . . . . . . . P/N 4064 Replacement Parts: Specify: (description) for use with Fig-ure 513D, 513D/R, 13D, or 13D/R Riser Manifold, P/N (Ref. Figure 1, 2 or 2, as applicable). TFP960 Page 5 of 6 Vail Fire & Emergency Services 07/14/15 Page 6 of 6 TFP960 TYCO FIRE & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446 Vail Fire & Emergency Services 07/14/15 FIRESPRINKLERPIPE& F ITTINGSSUBMITTAL SHEET No. 19–1.5 TD915 4–1.1.20 9/2001 TYCOFIREPRODUCTS 451 North Cannon Avenue Lansdale, Pennsylvania 19446 www.tyco-fire.com TECHNICAL SERVICES TEL: (800) 381-9312 • FAX: (800) 791-5500 E-MAIL : techserv@tycofp.com Vail Fire & Emergency Services 07/14/15 Part No. Size Sch. T/O Wt. 80000 3/4"40 5/8" 0.11 lb. 80001 1" 40 3/4" 0.19 lb. 80002 11/4"40 7/8" 0.26 lb. 80003 11/2" 80 1" 0.51 lb. 80004 2" 80 13/8" 0.90 lb. 80005 21/2"8 019/16" 1.59 lb. 80006 3" 80 111/16" 2.41 lb. Tee Part No. Size Sch. T/O Wt. 80025 3/4"40 9/16" 0.09 lb. 80026 1" 40 3/4" 0.14 lb. 80027 11/4"40 7/8" 0.21 lb. 80028 11/2"8 011/16" 0.40 lb. 80029 2" 80 11/4" 0.79 lb. 80030 21/2"8 011 /2" 1.14 lb.80031 3" 80 113/16" 1.82 lb. 90°Elbow Reducing 90°Elbow Cross Reducing Cross Part Size Sch. T/O Wt. No. 1 2 lb. 80015 1" x 3/4"40 11/16" 11/16" 0.28 Part No. Size Sch. T/O Wt. 80009 3/4"40 9/16" 0.13 lb. 80010 1" 40 15/16" 0.23 lb. 80011 11/4"40 15/16" 0.34 lb. 80012 11/2"8 011 /16" 0.67 lb.80013 2" 80 13/8" 1.00 lb. 80014 21/2"8 019/16" 1.91 lb. 80008 3" 80 113/16" 2.89 lb. Part No. Size Sch. T/O Wt. 80050 3/4"40 3/8" 0.08 lb. 80051 1" 40 3/8" 0.11 lb. 80052 11/4"40 3/4" 0.20 lb. 80053 11/2"80 7/16" 0.31 lb. 80054 2" 80 3/4" 0.56 lb. 80055 21/2"80 3/4" 0.89 lb. 80056 3" 80 1" 1.19 lb. 45°Elbow Fittings Nom.Pipe Size Avg. O.D. Inches Avg. I.D. Inches Wt. Lbs./Ft. Wt. H2O filled Pipe Lbs./Ft. Ft. of Pipe per Lift Wt. per Lift Lbs. 3/4" 1.050 0.874 0.17 0.43 7875 1413 1" 1.315 1.101 0.26 0.67 5040 1320 11/4" 1.660 1.394 0.42 1.07 2835 1191 11/2" 1.900 1.598 0.55 1.40 2205 1136 2" 2.375 2.003 0.86 2.20 1260 1063 2 1/2" 2.875 2.423 1.26 3.22 1215 1531 3" 3.500 2.952 1.87 4.79 720 1344 Introduction 2 2 1 1 T/OT/OT/O T/OPart Size Sch. T/O Wt. No. 1 2 lb. 80032 1" x 3/4"40 11/16" 13/16" 0.16 Pipe Technical Data Tyco Fire Products (TFP) BlazeMaster® CPVC pipe and fittings are designed exclusively for use in wet pipe automatic fire sprinkler systems. They are made from a specially developed thermoplastic compound composed of post chlorinated polyvinyl chloride (CPVC) resin and state of the art additives. TFPBlazeMaster® CPVC products are easier to install than traditional steel pipe systems, and at the same time, they provide superior heat resistance and strength as compared to traditional CPVC and PVC piping materials used in the plumbing trade. Various adapters are available to connect CPVC pipe to metallic piping. All female pipe thread adapters have brass inserts for durability. Grooved adapters connect directly to grooved end valves and metallic pipe, with flexible grooved end couplings. Sizes: 3/4"– 3" Maximum Working Pressure: 175 psi Approvals: UL, FM, CUL, NSF, Dade County, LPCB, MEA, and the City of Los Angeles Note: See current TFPBlazeMaster Installation Instructions and Technical Manual, for exact listing/approval information Manufacture Source: U.S.A. Material: Pipe: ASTM F442, SDR 13.5 Fittings: ASTM F438 (Sch. 40) and ASTM F439 (Sch. 80) Color: Orange Vail Fire & Emergency Services 07/14/15 Part No. Size Sch. T/O Wt. Pipe OD 80160 11/4" x 1 1 /4" Grooved 40 2 5/16" 0.78 lb. 1 1 /4" (1.660")80161 11/2" x 1 1 /2" Grooved 80 2 5 /16" 0.95 lb. 11/2" (1.900")80162 2" x 2" Grooved 80 2 5/16" 1.42 lb. 2" (2.375") 80163 21/2" x 2 1 /2" Grooved 80 2 5 /16" 2.28 lb. 21/2" (2.875")80164 3" x 3" Grooved 80 21/4" 3.00 lb. 3" (3.500") 80168 3" x 76.1mm Grooved 80 21/4" 2.72 lb. 76.1mm (3.000") Grooved Coupling Adapter Part No. Size Sch. T/O Wt. 80142 3/4" x 3/4" NPT 40 5/8" 0.41 lb. 80145 1" x 1" NPT 40 3/4" 0.63 lb. 80146 11/4" x 11/4" NPT 40 7/8" 1.03 lb. 80147 11/2" x 11/2" NPT 80 1" 1.42 lb. 80148 2" x 2" NPT 80 13/8" 2.66 lb. Female Adapter Part No. Size Sch. T/O Wt. 80157 3/4" x 3/4" NPT 40 15/16" 0.33 lb. 80158 1" x 1" NPT 40 13/8" 0.56 lb. Male Adapter Reducer Bushing Part No. Size Sch. T/O Wt. 80200 1" x 3/4"40 7/16" 0.04 lb. 80201 11/4" x 3 /4"40 7/16" 0.11 lb.80202 11/4" x 1" 40 5/16" 0.12 lb. 80203 11/2" x 3 /4"805/8" 0.16 lb. 80204 11/2" x 1" 80 1/2" 0.14 lb. 80205 11/2" x 1 1 /4"803/8" 0.17 lb. 80206 2" x 3/4"80 3/4" 0.27 lb. 80207 2" x 1" 80 11/16" 0.26 lb. 80208 2" x 11/4"80 9/16" 0.24 lb. 80209 2" x 11/2"80 7/16" 0.19 lb. 80215 21/2" x 1" 80 1 15 /16" 0.42 lb.80214 21/2" x 11/4"8013 /4" 0.45 lb.80213 21/2" x 11/2"8015 /8" 0.46 lb.80211 21/2" x 2" 80 19/16" 0.29 lb. 80210 3" x 2" 80 2 3/16" 0.72 lb. 80212 3" x 21/2"80115/16" 0.47 lb. Reducing Tee Part Size Sch. T/O Wt. No. 1 2 3 lb. 80132 3/4" x 3/4" x 1" 40 3/4" 3/4" 5/8" 0.14 80133 1" x 3/4" x 3/4"4 01/2" 11/16" 3/4" 0.14 80134 1" x 3/4" x 1" 40 5/8" 3/4" 3/4" 0.17 80260 1" x 1" x 3/4"4 03/4" 3/4" 11/16" 0.1680135 11/4" x 1" x 3/4"4 07/16" 3/4" 15/16" 0.21 80136 11/4" x 1" x 1" 40 11/16" 3/4" 15/16" 0.22 80137 11/4" x 1" x 11/4"40 13/16" 15/16" 13/16" 0.26 80261 11/4" x 11/4" x 3/4"40 5/8" 5/8" 7/8" 0.23 80262 11/4" x 11/4" x 1" 40 3/4" 3/4" 7/8" 0.26 80138 11/4" x 11/4" x 11/2" 80 1" 1" 1" 0.43 80140 11/2" x 1 1 /4" x 3 /4"80 1/2"5/8" 1" 0.36 80141 11/2" x 11/4" x 1" 80 1/2" 5/8"11/8" 0.38 80263 11/2" x 11/2" x 3/4"80 9/16" 9/16" 1" 0.36 80264 11/2" x 1 1 /2" x 1" 809/16" 9/16" 1" 0.38 80275 11/2" x 11/2" x 11/4"80 7/8" 7/8" 1" 0.45 80265 2" x 2" x 3/4"8 03/4" 3/4"13/8" 0.61 80266 2" x 2" x 1" 80 7/8" 7/8"13/8" 0.66 80274 2" x 2" x 11/4"8 0 1 "1" 13/8" 0.74 80267 2" x 2" x 11/2"8 0 11/8"11 /8"13 /8" 0.78 80271 21/2" x 21/2" x 1" 80 111/16"111/16"" 1 9 /16" 1.4380272 21/2" x 21/2" x 11/4"80 111/16"111/16"19/16" 1.46 80273 21/2" x 2 1 /2" x 1 1 /2"80 111/16"111 /16"19/16" 1.4880276 21/2" x 21/2" x 2" 80 111/16"111/16"19/16" 1.50 80270 3" x 3" x 11/2"8 0 13 /4"13 /4"113/16" 2.2880268 3" x 3" x 2" 80 13/4"13/4"13/4" 2.25 80269 3" x 3" x 21/2"8 0 13/4"13 /4"115 /16" 2.44Part No. Size Sch. T/O Wt. 80220 1" x 3/4"40 1/8" 0.08 lb. Reducing Coupling Part No. Size Sch. T/O Wt. 80075 3/4"40 1/8" 0.07 lb. 80076 1" 40 1/8" 0.11 lb. 80077 11/4"40 3/16" 0.12 lb. 80078 11/2"80 3/16" 0.25 lb. 80079 2" 80 3/16" 0.38 lb. 80080 21/2"80 3/16" 0.67 lb. 80081 3" 80 3/16" 0.91 lb. Part No. Size Sch. T/O Wt. 80100 3/4"40 5/16" 0.04 lb. 80101 1" 40 3/8" 0.06 lb. 80102 11/4"40 1/2" 0.10 lb. 80103 1 1/2"805/8" 0.20 lb. 80104 2" 80 5/8" 0.31 lb. 80105 21/2"80 7/8" 0.58 lb. 80106 3" 80 1" 0.88 lb. Cap Coupling 3 T/O2 1 T/OT/OT/O T/O Pipe O.D. T/O Vail Fire & Emergency Services 07/14/15 Sprinkler Head Adapter Tee with Brass Threaded Insert Part Size Sch. T/O Wt. No. 1 2 3 lb. 80250 3/4" x 3 /4" x 1 /2" NPT 405/8" 5/8" 1" 0.22 80251 1" x 1" x 1/2" NPT 40 11/16" 11/16" 13/16" 0.29 80249 1" x 1" x 1" NPT 40 15/16" 15/16"17 /16" 0.7380256 11/4" x 1" x 1/2" NPT 40 7/16" 9/16"11 /8" 0.3080252 11/4" x 11/4" x 1/2" NPT 40 7/16" 7/16"11 /8" 0.3180257 11/2" x 11/4" x 1/2" NPT 80 9/16" 5/8"17 /16" 0.4380254 11/2" x 11/2" x 1/2" NPT 80 9/16" 9/16"1 7/16" 0.4680258 2" x 11/2" x 1/2" NPT 80 1/2" 5/8"15 /8" 0.5680253 2" x 2" x 1/2" NPT 80 1/2" 1/2"15 /8" 0.62Part Size Sch. T/O Wt. No. 1 2 lb. 80199 3/4" x 1/2" NPT 40 5/8" 15/16" 0.20 80189 1" x 1/2" NPT 40 13/16"13 /16" 0.26Sprinkler Head Adapter 90°Elbow with Brass Threaded Insert Part Size Sch. T/O Wt. No. 1 2 lb. 80459 1" x 1/2" NPTx 1 /2" NPT 4011/16"15/16" 0.48 80460 1" x 1/2" NPTx 1 /2" NPT 4011/16"11/8" 0.46 Back-to-Back Tee with Brass Threaded Insert Sprinkler Head Adapter with Brass Threaded Insert Sprinkler Head Adapter with Brass Threaded Insert Sprinkler Head Adapter (Spigot) with Brass Threaded Insert Back-to-Back Cross with Brass Threaded Insert Part Size Sch. T/O Wt. No. 1 2 lb. 80462 1" x 1" x 1/2" NPTx 1 /2" NPT 405/8"11/8" 0.46 80463 1" x 1" x 1/2" NPTx 1 /2" NPT 405/8"15/16" 0.47 Part No. Size Sch. T/O Wt. 80177L 3/4" x 1 /2" NPT 401/2" 0.16 lb. 80178 1" x 1/2" NPT 40 1/2" 0.20 lb. Part No. Size Sch. T/O Wt. 80175W 3/4" x 1 /2" NPT 407/16" 0.19 lb. 80176W 1" x 1/2" NPT 40 7/16" 0.18 lb. Part No. Size Sch. T/O Wt. 80175E 3/4" x 1 /2" NPT 807/16" 0.20 lb. 80176E 1" x 1/2" NPT 80 7/16" 0.22 lb. 80177WL 3/4" x 1/2" NPT 40 9/16" 0.16 lb. 80179 1 x 3/4" NPT 40 3/4" 0.43 lb. T/O T/O T/O 2 2 1 T/OT/OT/O 1 2 T/OT/O3 T/O2 1 T/OT/OLimited Warranty Products manufactured by Tyco Fire Products are warranted solely to the original Buyer for ten (10) years against defects in material and workmanship when paid for and properly installed and maintained under normal use and service. This warranty will expire ten (10) years from date of shipment by Tyco Fire Products. No warranty is given for products or components manufactured by companies not affiliated by ownership with Tyco Fire Products or for products and components which have been subject to misuse, improper installation, corrosion, or which have not been installed, maintained, modified or repaired in accordance with applicable Standards of the National Fire Protection Association (NFPA), and/or the standards of any other Authorities Having Jurisdiction. Materials found by Tyco Fire Products to be defective shall be either repaired or replaced, at Tyco Fire Products sole option. Tyco Fire Products neither assumes, nor authorizes any person to assume for it, any other obligation in connection with the sale of products or parts of products. Tyco Fire Products shall not be responsible for sprinkler system design errors or inaccurate or incomplete information supplied by Buyer or Buyer’s representatives. IN NO EVENT SHALL TYCO FIRE PRODUCTS BE LIABLE, IN CONTRACT, TORT, STRICT LIABILITY OR UNDER ANY OTHER LEGAL THEORY, FOR INCIDENTAL, INDIRECT, SPECIAL OR CONSEQUENTIAL DAMAGES, INCLUDING BUT NOT LIMITED TO LABOR CHARGES, REGARDLESS OF WHETHER TYCO FIRE PRODUCTS WAS INFORMED ABOUT THE POSSIBILITY OF SUCH DAMAGES, AND IN NO EVENT SHALL TYCO FIRE PRODUCT’S LIABILITY EXCEED AN AMOUNT EQUAL TO THE SALES PRICE. THE FOREGOING W ARRANTY IS MADE IN LIEU OF ANY AND ALL OTHER W ARRANTIES EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF MERCHANT ABILITY AND FITNESS FOR A PARTICULAR PURPOSE. Vail Fire & Emergency Services 07/14/15 SPRINKLER SYSTEMS SPRINKLER SYSTEMS Freeze Protection Fluid Propylene Glycol solutions for most wet fire sprinkler systems FireFighter™ PG Freeze Protection Fluid Glycerine solutions for CPVC wet fire sprinkler systems ANTIFREEZEfor WET Fire Easy to Use Available in 5 gallon containers, 55 gallon drums, totes or tank trucks. • Ready to use or concentrates • Custom blends available Easy to Maintain Instruments necessary to test the fluids and maintain the protection 800-878-5788 www.noblecompany.com Digital Refractometer Hydrometer Refractometer Time Tested...15 years and millions of gallons installed FireFighter™ GL ANTIFREEZE FireFighter is a trademark of The Noble Company. Vail Fire & Emergency Services 07/14/15 PRODUCT DESCRIPTION FireFighter GL and FireFighter PG are non-toxic*¹ anti-freezes designed specifically for fire protection systems. These products are used in place of water and other wa-ter-like fluids in sprinkler systems where freezing may either cause damage or interfere with the functioning of systems or equipment, and/or toxicity to humans or ani-mals is a concern. ______________________________________________ FireFighter GL FireFighter GL is a Glycerine based material which is compatible with all approved types of pipe, including BlazeMaster® CPVC sprinkler pipe and fittings. Active Ingredient: USP or CP Glycerine Other ingredients: Water Viscosity Reduction Agent Dye ______________________________________________ FireFighter PG FireFighter PG is a Propylene Glycol based material which is compatible with all approved types of sprinkler systems, with the exception of CPVC. Active Ingredient: Propylene Glycol Other Ingredients: Water Viscosity Reduction Agent Inhibitor Dye ______________________________________________ Flammability FireFighter GL and FireFighter PG are not flammable since they have no measurable flash point; however, both products can flash or burn if the water content is evapo- rated off. No harmful fumes are produced. ______________________________________________ Toxicological, Environmental and Health Information FireFighter GL and FireFighter PG are virtually harmless to animals or plants; however, the disposal of these mate-rials should be in conformance with national, state and local health codes. FDA References GRAS: FireFighter GL and FireFighter PG are consid-ered “Generally Regarded as Safe” (GRAS) by the Fed-eral Food and Drug Administration. ______________________________________________ Typical Physical Properties of “Ready-to-Use” FireFighter GL and FireFighter PG “Ready-to-Use” FireFighter GL FireFighter PG Color: Orange Red Density @ 77°F: 1.137 1.026 (grams/ml) Viscosity @ 77°F: 7.05 6.15 (Centipoise) pH: 7.0 8.0-9.6 Boiling Point @ Atmospheric Pressure: (760 mm) 212°F 222°F Minimum Flow Temperature: -15°F -15°F Minimum Burst Temperature: -50°F -50°F (Hard Freeze) Flash Point 350°F 214°F Fire Point 400°F 220°F Concentrate (Pensky-Martens Closed Cup) ______________________________________________ Other FireFighter Antifreeze Products xFireFighter GL Concentrate xFireFighter PG Concentrate (New Formula) xGL and PG Custom Blends For specifications on these products please contact us. ______________________________________________ *FireFighter is a Trademark of The Noble Company *BlazeMaster is a Registered Trademark of Noveon *¹Non-Toxic is used to describe extremely low chronic and acute toxic-ity. No maximum safe intake for humans has been established. The product is considered GRAS by The Food and Drug Administration. Vail Fire & Emergency Services 07/14/15 Sizes FireFighter GL and FireFighter PG are available in: x1 gallon plastic bottles (6 per case, PG Ready-to-Use only) x5 gallon pails x30 gallon drums x55 gallon drums x275 or 330 gallon totes x5000 gallon tank truck ___________________________________________ System Requirements and Limitations All fire protection sprinkler systems that use Fire-Fighter GL and FireFighter PG should conform to local, state and NFPA requirements. The use of an-tifreeze within these systems should also conform to NFPA requirements. Use of antifreeze solutions should also be in confor-mance with any state or local health codes. Please contact your local health authorities if you have any questions concerning the codes in your area. ___________________________________________ Maintenance Chemicals which compose FireFighter GL and Fire-Fighter PG can break down over time. NFPA 25 re-quires that the freezing point of the system should be tested at least once a year. Periodic testing of systems is critical to maintaining the proper con-centration and freeze point of the fluid. Leaks, pressure surges and temperature changes to the system can cause antifreeze to flow out of the sys-tem or water to flow into the system changing the freeze temperature. ___________________________________________ Testing To test the freeze protection level of FireFighter GL or FireFighter PG the correct instrument must be used. For testing FireFighter GL we have two instruments. A lab grade hydrometer or a digital refractometer. For testing FireFighter PG we have three instru-ments for test. A lab grade hydrometer, an analog refractometer or a digital refractometer. When testing indicates that the solution has weak-ened, empty the system and replace with fresh FireFighter GL or FireFighter PG, according to the installation instructions. For further information concerning correct testing procedures and test instruments, contact our tech-nical services department and ask for “How to Choose the Correct Antifreeze Loop Tester”. ___________________________________________ RECOMMENDED CONCENTRATIONSFireFighter GL Ready-to-UseFireFighter PG Ready-to-UseFireFighter GL ConcentrateSpecific Gravity @ 77° F Freeze Point Burst Point 1.141 -15° F -50° F 1.116 -5° F -45° F 1.102 0° F -40° F 1.096 10° F -35° F @ 77° F Freeze Point Burst Point GL Concentrate Freeze Point Specific Gravity @60 °F 40% +5° F 1.100 50% -15° F 1.133 60% -22° F 1.151 70% -40° F 1.165 Specific Gravity1.033 0° F -50° F 1.028 +10° F -20° F 1.024 +15° F 0° F 1.020 +20° F +10 ° F Vail Fire & Emergency Services 07/14/15 RECOMMENDED CONCENTRATIONS FireFighter PG Concentrate (New Formula) __________________________________________ ACCESSORIES xLab Grade Hydrometer xAnalog Refractometer xDigital Refractometer __________________________________________ AVAILABILITY FireFighter GL and Firefighter PG are available throughout the U.S. through wholesale distributors. Please contact The Noble Company for your local representa-tive and wholesaler. __________________________________________ TECHNICAL SUPPORT Specifications, installation design, instal-lation techniques and unique applications will be reviewed upon request. Address inquiries ATTN: FireFighter Technical Support, Email: www.noblecompany.com or phone us at: 800-878-5788 Field services are available through fac-tory representatives and Noble Company staff. Contact The Noble Company for local representatives. Additional product information and MSDS are available immediately through our website at www.noblecompany.com or our Fast Fax service at 1-800-272-1519. These are available 24 hours a day, 7 days a week. __________________________________________ FF PG Concentrate Freeze Point Specific Gravity @ 60° F 60% -60° F 1.045 50% -26° F 1.041 40% -6° F 1.034 30% +9° F 1.027 P.O. Box 350 Grand Haven, MI 49417-0350 www.noblecompany.com Phone: (231) 799-8000 (800) 878-5788 Fax: (231) 799-8850 Fast Fax: (800) 272-1519 © 2004 Form #FFPIG 1004 Supercedes 0604 Vail Fire & Emergency Services 07/14/15 Page 1 of 2 a company DOCUMENT #: REVISION: WXT-WXTP 4/05 Model WXTP Water Thermal Expansion Tank SPECIFICATION SUBMITTAL SHEET FEATURES DIMENSIONS & WEIGHTS (do not include pkg.) MATERIALS APPLICATION ACCESSORIES STANDARDS COMPLIANCE Designed for installation on potable water lines between the backflow preventer or pressure reducing valve and the water heater to protect against water thermal expansion. When system pressure increases, water enters the tank’s bladder which expands into the pre-charged air chamber, keeping system pressure below the relief valve setting. y IAPMO® Listed y NSF® Listed Outer shell High Grade Steel Coatings Epoxy finish (outer shell) Connection Brass (sizes: 8 thru 32) Stainless Steel (sizes: 50V thru 320V) Bladder Butyl Rubber (FDA approved) A B B C A C WXTP 50V-320V WXTP 8-32 BR4 - water pressure reducing valve TP1100A - temperature & pressure relief valve P1000A - pressure relief valve 975XL - reduced pressure backflow preventer Sizes (liters): 8 18 32 50V 75V 120V 165V 320V (V = vertical, free-standing) Maximum working water pressure 150 PSI End connections Threaded NPT ANSI B1.20.1 Precharge (adjustable) 40 PSI 5 year warranty R UPC NSFR Certified toANSI/NSF 61 NOTE: Model WXTP tanks are certified to NSF Standard 61 cold, but are suitable for temperatures up to 200°F. in. mm in. mm lbs. kg WXTP-8 150 PSIG 2.1 0.84 40 8 1/2 216 11 1/2 292 3/4" MNPT 7 3.2 WXTP-18 150 PSIG 4.5 1.8 40 10 254 15 381 3/4" MNPT 10 4.5 WXTP-32 150 PSIG 8.5 3.4 40 12 1/2 318 19 3/16 487 3/4" MNPT 15 6.8 WXTP-50V 150 PSIG 14 5.6 40 16 406 21 11/16 551 1" FNPT 32 14.5 WXTP-75V 150 PSIG 20 8.0 40 16 406 28 13/16 732 1" FNPT 39 17.7 WXTP-120V 150 PSIG 32 12.8 40 21 533 27 13/16 706 1" FNPT 60 27.2 WXTP-165V 150 PSIG 44 17.6 40 21 533 36 3/16 919 1 1/4" FNPT 72 32.7 WXTP-320V 150 PSIG 85 34.0 40 26 660 44 7/16 1129 1 1/4" FNPT 140 63.4 TANK SPECIFICATIONS MODEL NUMBER MAXIMUM WORKING PRESSURE TOTAL VOLUME GALLON S ACCEPTANCE VOLUME WEIGHT SYSTEM CONNECTION HEIGHT DIMENSIONS DIAMETER FACTORY PRECHARGE (PSI) NOTE: RELIEF VALVE MUST BE SET AT 150 PSIG MAXIMUM Vail Fire & Emergency Services 07/14/15 Page 2 of 2 WILKINS a Zurn Company, 1747 Commerce Way, Paso Robles, CA 93446 Phone:805/238-7100 Fax:805/238-5766 IN CANADA: ZURN INDUSTRIES LIMITED, 3544 Nashua Dr., Mississauga, Ontario L4V 1L2 Phone:905/405-8272 Fax:905/405-1292 Product Support Help Line: 1-877-BACKFLOW (1-877-222-5356) · Website: http://www.zurn.com SIZING CHART TYPICAL INSTALLATION Local codes shall govern installation requirements. Unless otherwise specified, the assembly shall be mounted on the cold water supply and at least 18” from the cold water inlet to the heater. Note: If incoming water pressure is above 40 psi, the precharge pressure of the expansion tank should be adjusted to equal the incoming water pressure, not to exceed 80 psi. MODEL WXTP INSTALLATION MODEL WXTP INSTALLATION “V” SERIES T&P VALVE DIRECTION OF FLOW HOT WATER HEATER MODEL WXTP HOSE BIBB MODEL BR4 WATER PRESSURE REDUCING VALVE DRAIN MODEL 975XL T&P VALVE DIRECTION OF FLOW HOT WATER HEATER MODEL WXTP HOSE BIBB MODEL BR4 WATER PRESSURE REDUCING VALVE DRAIN MODEL 975XL The Water Thermal Expansion Tank shall be IAPMO® and NSF® Listed. The outer shell shall be high grade steel with exterior coating. The bladder shall be FDA approved butyl rubber and prevent water from contact with shell interior. The assembly shall incorporate a shrader valve for adjustable air precharge and a lead free bronze system connection. The Water Thermal Expansion Tank shall be a WILKINS Model WXTP. SPECIFICATIONS Based upon 100° F temperature rise (40° F to 140° F) X=multiple tanks required (contact your WILKINS Rep) Supply Pressure (psig) 20 30 40 50 60 80 100 120 150 175 200 40 8 8 8 8 8 18 18 18 32 32 32 50 8 8 8 8 8 18 18 18 32 32 32 55 8 8 8 8 8 18 18 18 32 32 32 60 8 8 8 8 18 18 18 18 32 32 32 70 8 8 8 8 18 18 18 18 32 32 32 80 8 8 8 8 18 18 18 32 32 32 32 90 8 8 8 18 18 18 32 32 32 50V 50V 100 8 8 18 18 18 32 32 32 50V 50V 50V 110 8 18 18 18 32 32 32 50V 50V 75V 75V 120 18 18 32 32 32 50V 50V 50V 120V 120V 120V WATER HEATER CAPACITY (U.S. gal) Supply WATER HEATER CAPACITY (U.S. gal) Pressure (psig) 240 260 280 300 350 400 450 500 600 800 1000 40 50V 50V 50V 50V 50V 75V 75V 75V 120V 120V 165V 50 50V 50V 50V 50V 50V 75V 75V 75V 120V 120V 165V 55 50V 50V 50V 50V 50V 75V 75V 75V 120V 120V 165V 60 50V 50V 50V 50V 50V 75V 75V 75V 120V 120V 165V 70 50V 50V 50V 50V 50V 75V 75V 75V 120V 120V 165V 80 50V 50V 50V 50V 75V 75V 75V 120V 120V 165V 165V 90 50V 50V 50V 75V 75V 75V 120V 120V 120V 165V 320V 100 75V 75V 75V 75V 120V 120V 120V 165V 165V 320V 320V 110 120V 120V 120V 120V 120V 165V 165V 320V 320V 320V X 120 165V 165V 165V 320V 320V 320V 320V 320V X X X Vail Fire & Emergency Services 07/14/15 Office/Manufacturing Facility · 1375 Sampson Ave. · Corona, CA 92879 · Ph: 909.737.5599 · Fax: 909.737.0330 Customer Service · 800.786.5266 www.tolco.com 39 wwwwww..ttoollccoo..ccoomm Revision 5/24/2001™ ® a brand of Size Range — 3/4" thru 2" CPVC pipe Material — Carbon Steel, Pre-Galvanized Function — Intended to perform as a hanger/restrainer to support only CPVC piping used in automatic fire sprinkler systems. Can be installed on the top or on the bottom of a beam. The Fig. 23 can also be installed on the side of a beam. The Fig. 23 can also function as a restrainer to prevent the upward movement of the sprinkler head during activation. Approvals — Underwriters’ Laboratories Listed in the USA (UL) and Canada (cUL) to support fire sprinkler piping. Meets and exceeds the requirements of NFPA 13, 13R and 13D. Features — Fig. 23 incorporates features which protect the pipe and ease installation. The flared edge design* protects the CPVC pipe from any rough surface. It also incorporates snap restrainers allow-ing easier and faster installation. Easily attaches to the building structure using the two UL Listed hex head self threading screws** furnished with the product. It is recommended that rechargeable electric drills fitted with a hex socket attachment be used as installa-tion tools. No impact tools (such as a hammer) or impact fasteners (such as drive screws or nails) are allowed. Damage has been known to result from installations using impact type tools. No pre-drilling of a pilot hole in wood is required. Finish — Pre-Galvanized Order By — Figure number and pipe size * Patent Pending ** Hardened hex head self threading screw is furnished with theproduct and is the minimum fastener size acceptable. Fig. 23 - Hanger for CPVC Plastic PipeDouble Fastener StrapType Dimensions · Weights CPVC Max. Hanger Fastener Hex Approx. Pipe Size A B C Spacing (Ft.) Head Size Wt./100 3/4 31/8 1 9/16 1 3/165 1/25/16 9 1 33/8 111/16 13/16 6 5/16 9 11/4 4 3/16 2 3/32 1 3/16 6 1/25/16 11 11/2 4 7/16 2 7/321 3/167 5/16 12 2 47/8 2 7/161 3/168 5/16 15 Vail Fire & Emergency Services 07/14/15 Main Office/Manufacturing Facility · 1375 Sampson Ave. · Corona, CA 92879 · Ph: 909.737.5599 · Fax: 909.737.0330 Customer Service · 800.786.5266 www.tolco.com 40 wwwwww..ttoollccoo..ccoomm Revision 5/24/2001 ™ ® a brand of Dimensions · Weights CPVC Max. Hanger Fastener Hex Approx. Pipe Size A B C Spacing (Ft.) Head Size Wt./100 3/4 25/16 15/32 13/16 51/2 5/16 9 1 25/8 1 5/161 3/166 5/16 9 11/4 3 1 1/21 3/16 6 1/25/16 11 11/2 3 1/4 1 5/8 1 3/167 5/16 12 2 311/16 1 27/32 1 3/168 5/16 15 Size Range — 3/4" thru 2" CPVC pipe Material — Carbon Steel, Pre-Galvanized Function — Intended to perform as a hanger/restrainer to support onlyCPVC piping used in automatic fire sprinkler systems. Can be installedon the top or on the bottom of a beam. The Fig. 24 can also functionas a restrainer to prevent the upward movement of the sprinkler headduring activation. Approvals — Underwriters’ Laboratories Listed in the USA (UL) andCanada (cUL) to support fire sprinkler piping. Meets and exceeds therequirements of NFPA 13, 13R and 13D. Features — Fig. 24 incorporates features which protect the pipe andease installation. The flared edge design* protects the CPVC pipe fromany rough surface. Easily attaches to the building structure using the twoUL Listed hex head self threading screws** furnished with the product. Itis recommended that rechargeable electric drills fitted with a hex socket attachment be used as installation tools. No impact tools (such as a hammer) or impact fasteners (such as drive screws or nails) are allowed. Damage has been known to result from installations using impact type tools. No pre-drilling of a pilot hole in wood is required. Finish — Pre-Galvanized Order By — Figure number and pipe size * Patent Pending ** Hardened hex head self threading screw is furnished with theproduct and is the minimum fastener size acceptable. Fig. 24 - Hanger for CPVC Plastic PipeDouble Fastener StrapType - Side Mount Vail Fire & Emergency Services 07/14/15 OFFICE/MANUFACTURING FACILITY · 1375 SAMPSON AVE. · CORONA, CA 92879 · PH: 951.737.5599 · FAX: 951.737.0330 CUSTOMER SERVICE · 800.786.5266 www.tolco.com 38 www.tolco.com Revision 5/24/2001 ™ ® a brand of www .tolco .com Revision 4/27/2006 Fig. 28"Stand-Off" Hanger & Restrainer for CPVC Plastic Pipe Size Range — ¾" through 2" Material — Carbon Steel, Pre-Galvanized Function — Designed to be used as a hanger and restrainer for CPVC piping wherethe "stand-off" design will ease installation by eliminating the need for wood blocking. Features:· Flared edge design protects CPVC pipe from any rough or abrasive surfaces. · Unique twist and lock design holds pipe firmly in place and allows retrofit typeof installation. · The "Stand-Off" design eliminates the need for wood block extension. · Can be installed on horizontal or vertical piping regardless of mountingsurface orientation. · Attaches easily to wood structure with two hex head self-threading screwsfurnished with product. · Installs easily using rechargeable electrical driver with 5/16" extension socketeliminating impact tool damage to pipe. · Attaches easily to steel, minimum 18 gauge with (2) 1/4" x 1" tek type self drillingtapping screws. · U.L. Listed as a hanger and a restrainer for fire sprinkler piping. Approvals — Underwriters' Laboratory Listed in the USA (UL) and Canada (cUL) tosupport automatic fire sprinkler systems. May be installed into wood using fastenerssupplied with product, or into minimum 18 gauge steel using (2) 1/4" x 1" tek type screws.Meets and exceeds the requirements of NFPA 13, 13R and 13D. Fig. 28 satisfies the ULvertical restraint requirement where needed. UL Listed as a hanger and vertical restraintwhen installed on 3/8" composite wood material. Use two Fig. 27B Speed Nuts whenused as a hanger and restraint. Use one Fig. 27B Speed Nut on the upper installedscrew when used as a hanger only. Order by — Figure number and pipe size. US AND INTERNATIONAL PATENT APPLICATION IN PROCESS.Dimensions · Weights Pipe Approx. Size A B C Wt. 3/4 31⁄32 2 31⁄2 .180 1 35⁄16 23⁄16 31⁄2 .210 11⁄4 35⁄8 23⁄8 31⁄2 .225 11⁄2 4 21⁄2 31⁄2 .310 2 41⁄2 211⁄16 35⁄8 .340 Vail Fire & Emergency Services 07/14/15 Main Office/Manufacturing Facility · 1375 Sampson Ave. · Corona, CA 92879 · Ph: 909.737.5599 · Fax: 909.737.0330 Customer Service · 800.786.5266 www.tolco.com 38 wwwwww..ttoollccoo..ccoomm Revision 5/24/2001 ™ ® a brand of Size Range — 3/4" thru 2" CPVC pipe Material — Carbon Steel, Pre-Galvanized Function — Designed to support a CPVC pipe awayfrom the corner of a beam. This position allows for easy installation of drops or risers without adding additionalwood blocks. Approvals — Underwriters’ Laboratories Listed in the USA (UL) and Canada (cUL) for use as a combination hanger and restrainer. Finish — Pre-Galvanized Note — Approved UL Listed fastener into wood is furnished with the product. A fastener into light gauge metal may be ordered separately. Minimum acceptable #10 x 1" hardened self threading screw with 5/16" hex washer head. Order By — Fig. 22C application is composed of twostandard Fig. 22 models — order two singles for each hanger and restrainer application required. Fig. 22C - Combination Hanger & Restrainer Application Vail Fire & Emergency Services 07/14/15 FIREDEPT. INLET CONN. FLUSH TYPE 6341-6345SERIES SINGLE INLET An inlet connection with 250 G.P.M. minimum inlet capacity to supplement the fire protection water supply. Provides unobstructed water supply. Flush round design enhances appearance and provides unobstructed passage. STANDARD EQUIPMENT: Cast Brass round plate with double female adapter; plug and chain; branding as selected. SPECIFY THREAD AND BRANDING. BRANDING: "Standpipe", "Auto Spkr." FINISH: Cast Brass OPTIONAL FINISH: PB-Polished Brass PC-Polished Chrome RESIDENTIAL FIRE DEPT. CONNECTION An inlet connection to supplement the water supply to a residential sprinkler system. STANDARD EQUIPMENT: 1 1/2" cast brass round plate assembly with integral pin lug swivel inlet. Hose thread inlet swivel, 1 1/2" NPT female outlet on back of plate. Cast brass plug and brass chain. Overall outside Diameter 4 3/8". SPECIFY THREAD AND BRANDING. U/L LISTED. BRANDING: "Auto Spkr." FINISH: Cast Brass OPTIONAL FINISH: PB-Polished Brass PC-Polished Chrome Figure No. 6341 Figure No. 6342 Figure No. 6345 Page 6-12 Round Plate Figure No. Size 6341 2 1/2 X 2 1/2 6342 3 X 2 1/2 6343 3 X 3 ___________________________________________________ Vail Fire & Emergency Services 07/14/15 NIBCO INC. WORLDHEADQUARTERS • 1516 MIDDLEBURYST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECHSERVICES PH: 1.888.446.4226 • FAX: 1.800.234.0557 • INTERNATIONALOFFICE PH: +1.574.295.3221 • FAX: +1.574.295.3455 www.nibco.com 14 AHEADOF THEFLOW™ www.nibco.com Revised 08/01/03 200 lb. WWPBronze Check Valves Fire Protection Valve • Horizontal Swing • Rubber Disc MATERIAL LIST PART SPECIFICATION 1. Bonnet Bronze ASTM B 62 or B 584 Alloy C84400 2. Body Bronze ASTM B 62 or B 584 Alloy C84400 3. Hinge Pin Bronze ASTM B 140 Alloy C31400 or B 134 Alloy C23000 4. Disc Hanger Bronze ASTM B 62 5. Hanger Nut Bronze ASTM B 97 Alloy C65500 or Brass ASTM B 16 6. Disc Holder Bronze ASTM B 62 7. Seat Disc Buna-N (W) TFE(Y)‡ 8. Seat Disc Nut Brass ASTM B 16 or B 97 Alloy C65500 9. Hinge Pin Plug Bronze ASTM B 140 Alloy C32000 (Not Shown) *10. Seat Disc Washer Stainless Steel *Sizes ³⁄₄" , 1" , 1¹⁄₄" and 1¹⁄₂" only. ‡2¹⁄₂" and 3" size only. 200 PSI/13.8 Bar Non-Shock Cold Water CONFORMS TO MSS SP-80 NIBCO check valves may be installed in both horizontal and vertical lines with upward flow or in any intermediate position. WARNING - Valve must be installed downstream of receiver tank if used in line with reciprocating air compressor. DIMENSIONS—WEIGHTS—QUANTITIES Dimensions Size A B Weight Box Master. In. mm. In. mm. In. mm. Lbs. Kg. Qty. Ctn. Qty. ¹⁄₂ 15 2.44 62 1.69 43 .58 .26 10 50 ³⁄₄ 20 2.94 75 1.88 48 .92 .42 10 50 1 25 3.56 90 2.31 59 1.55 .70 5 30 1¹⁄₄ 32 4.19 106 2.69 68 2.32 1.05 5 20 1¹⁄₂ 40 4.50 114 2.94 75 3.00 1.36 2 10 2 50 5.25 133 3.81 97 4.87 2.21 2 10 2¹⁄₂ 65 8.00 203 5.06 129 11.48 5.22 1 5 3 80 9.25 235 6.25 159 17.53 7.97 1 4 Sizes 2¹⁄₂" and 3" supplied as T-433-Y with TFEseat disc. KT-403-W NPTx NPT KT-403-W Threaded Dezincification Resistant Vail Fire & Emergency Services 07/14/15 Features • One alarm appliance with (8) eight selective signals to provide superior sound penetration for various ambient and wall conditions with two field selectable sound output levels. • Code-3 Horn and Tone meet NFPA/ANSI/ISO temporal pattern for standard emergency evacuation signaling. • Audible and strobe can operate from a single signaling circuit. • Designed to meet or exceed NFPA/ANSI Standards and ADA Accessibility Guidelines. 110 VAC model does not meet ADA requirements. • Low current draw with low temperature compensation to reduce power consumption and wiring costs. • Low cost installation via standard electrical boxes. Attractive flush or surface mounting options available. Wheelock’s MT and MT Strobe Series Multitone Electronic Signals offer a choice of eight (8) nationally and internationally recognized alerting sounds: Horn, Bell, March Time Horn, Code-3 Tone, Code-3 Horn, Slow Whoop, Siren or Hi/Lo Tone. Wheelock’s Code-3 horn and tone patterns are engineered to comply with NFPA/ANSI Temporal Pattern specifications without requiring additional coding means. With MT and MT Strobe Signals, one alarm appliance meets most of your signaling needs. Wheelock’s MT and MT Strobe Signals are UL Listed, FM, CSFM and NYMEA Approved. WHEELOCK SERIES MT AND MT STROBE MULTITONE ELECTRONIC SIGNALS * For outdoor installation use MTWP-2475W-FR with IOB-R backbox. ** See next page for mounting options. PRINTED IN USA PAGE 1 OF 2 MKT. #8850002 - REV H 2/03 Potter Electric Signal Company • 2081 Craig Road, St. Louis, MO, 63146-4161 • Phone: 800-325-3936/Canada 888-882-1833 • www.pottersignal.com MT-24-1575W-FR SHOWN l edoMR F-W575121-TM) nroH/ebortS(1 290161. oNk cotS* *snoitpOg nitnuoMR ,P , O,M,L,F , E,D4 2/21T M) nroH(4 190161. oNk cotS* *snoitpOg nitnuoMR ,P , O,M,L,F , E,D* RF-W5751-42-TMr oodnI) nroH/ebortS(5 190161. oNk cotS* *snoitpOg nitnuoMR ,P , O,M,L,F , E,DR FV-HW-511-4TM) nroH/ebortS(6 120161. oNk cotS* *snoitpOg nitnuoMR ,O,N,K,J,E,Ds gnitaRt nerruCd naA Bde noT) spmA(s gnit a Rt nerruCe garevAsgnit a Rt narebreveRA Bd4 64L Ur ePsgnit a Rc iohcenAA BdC DV42@ C DV21@ C DV42@ C DV21@ C DV42d na2 1@ I HD TSI HD TSI HD TSI HD TSI HD TSn roH8 30.04 20.05 90.09 10.02 97 80 97 79 93 9l leB9 10.02 10.00 30.00 10.06 80 85 89 62 97 8n roHe miTh craM8 30.04 20.05 90.09 10.09 84 89 84 79 93 9n roH3 -edoC8 30.04 20.05 90.09 10.08 83 88 83 79 93 9e noT3 -edoC7 20.06 10.07 50.04 10.05 80 84 80 75 90 9p oohWw olS7 40.05 20.05 90.04 20.00 99 89 85 79 94 9n eriS4 30.02 20.08 70.09 10.09 84 89 85 78 93 9o L/iH0 20.03 10.02 40.01 10.06 81 86 81 73 98 8Vail Fire & Emergency Services 07/14/15 WHEELOCK SERIES MT AND MT STROBE MULTITONE ELECTRONIC SIGNALS PRINTED IN USA PAGE 2 OF 2 MKT. #8850002 - REV H 2/03 MOUNTING ACCESSORIES (D) 4" SQUARE, FLUSH (BO) (F) DOUBLE-GANG, FLUSH (BO) (J) BB BACKBOX (Order Code: 2830) Standard steel backbox with knockouts for interior surface mounting, concealed conduit mounting or semi-flush applications. It is painted to match the signal. (K) WBB WEATHER RESISTANT BACKBOX (Order Code: 2959) Sturdy die-cast housing, threaded conduit hole and knockout for outdoor applications. It is painted to match the signal. (L) ISP SURFACE ADAPTER (Order Code: 5306) Indoor use. (M) IOB BACKBOX (Order Code: 5046) For surface mounting MT products. (O) RP-R RETROFIT PLATE (Order Code: 5042) (R) SFP SEMI-FLUSH PLATE (Order Code: 2957) Stamped aluminum surface wall plate which mounts behind the basic unit and serves to cover recessed backboxes in semi-flush mounting applications. It is painted to match the signal. MAXIMUM NUMBER OF CONDUCTORS AWG. #18 AWG. #16 AWG. #14 AWG. #12 4444 MAXIMUM NUMBER OF CONDUCTORS AWG. #18 AWG. #16 AWG. #14 AWG. #12 4444 MAXIMUM NUMBER OF CONDUCTORS AWG. #18 AWG. #16 AWG. #14 AWG. #12 4444 MAXIMUM NUMBER OF CONDUCTORS AWG. #18 AWG. #16 AWG. #14 AWG. #12 8884 MAXIMUM NUMBER OF CONDUCTORS AWG. #18 AWG. #16 AWG. #14 AWG. #12 8884 (E) 4" SQUARE, DEEP, FLUSH (BO) MAXIMUM NUMBER OF CONDUCTORS AWG. #18 AWG. #16 AWG. #14 AWG. #12 88 84 MAXIMUM NUMBER OF CONDUCTORS AWG. #18 AWG. #16 AWG. #14 AWG. #12 44 44 MOUNTING NOTES CAUTION: The mounting options figures show the maximum number of field wires (conductors) that can enter the backbox used with each mounting option. If these limits are exceeded, there may be insufficient space in the backbox to accommodate the field wires and stresses from the wires could damage the product. Although the limits shown for each mounting option comply with the National Electrical code (NEC), Wheelock recommends use of the largest backbox option and the use of approved stranded field wires whenever possible, to provide additional wiring room for easy installation and minimum stress on the product from wiring. CAUTION: Check that the installed product will have sufficient clearance and wiring room prior to installing backboxes and conduit, especially if sheathed multiconductor cable or 3/4" conduit fittings are used. 1. Mounting hardware for each mounting option is supplied. 2. Conduit entrances to the backbox should be selected to provide sufficient wiring clearance for the installed product. When extension rings are required, conduit should enter through the backbox, not the extension ring. Use Steel City #53151 (1-1/2" deep) or #53171 (2-1/8" deep) extension rings (as noted in the mounting options) or equivalent with the same cut-out area. 3. When terminating field wires, do not use more lead length than required. Excess lead length could result in insufficient wiring space for the appliance. 4. Use care and proper techniques to position the field wires in the backbox so that they use minimum space and produce minimum stress on the product. This is especially important for stiff, heavy gauge wires and wires with thick insulation or sheathing. 5. Do not pass additional wires (used for other than the appliance) through the backbox. Such additional wires could result in insufficient wiring space for the appliance. Vail Fire & Emergency Services 07/14/15 122 Consult factory for guidance in product selection Phone (203) 385-0217, Fax (203) 385-0602 or visit our web site at www.ashcroft.com Fire Protection, Sprinkler Service Gauge Type 1005P, XUL ASME B 40.1 Grade B (±3-2-3% of span) • Underwriters Laboratory listed and Factory Mutual approved • Corrosion-resistant ABS case ABS ABS • Heat-resistant polycarbonate push-in window • Patented PowerFlex™ movement with polyester segment • True Zero™ indication, a unique safety feature Type no.: 1005P, XUL Accuracy: ASME B 40.1 Grade B (±3-2-3% of span) Size: 31⁄112⁄⁄˝ Case: ABS (Polycarbonate blend) Ring: None Window: Polycarbonate, push-in Dial: Black fi gures on white back-ground Pointer: Black, aluminum Bourdon tube: “C” shaped bronze Movement: Patented PowerFlex with polyester segment Socket: Brass Restrictor: None Ashcroft® fi re protection sprinkler ®®gauges are Underwriters Laboratory listed and Factory Mutual approved for fi re protection sprinkler service. The case material on Type 1005P, XUL gauges is ABS. The 0-300 psi pressure range is used on “wet” systems where water is available to the sprinkler heads. The 0-80 retard to 250 psi pressure range is used on dry systems where the lines are fi lled with air pressure until system activation. The patented PowerFlex move-FlexFlexment with polyester segment is designed to provide unequalled shock and vibration resistance resulting in superior performance and extended gauge life. NOTES FM Customized dials Other UL listed ranges on application Operating temperature: –40°F to 150°F Connection: 1⁄114⁄⁄ NPT lower Ranges: 0-300 psi (water) 0-80 retard to 250 psi (air) UL 393 Listed, UL of Canada Listed and FM approved. Equivalent (single or dual scale) metric scales are available TO ORDER THIS TYPE 1005P, XUL GAUGE: Select: 35 W 1005 P H 02L XUL 300# 1. Dial Size: 31⁄112⁄⁄˝ 2. Patented PowerFlex™ Movement FlexFlex3. Case Type Number: 1005 4. Case Type Material: ABS 5. Socket Material: Brass 6. Connection Size/Location: 1⁄114⁄⁄ NPT lower 7. UL listed, FM approved 8. Range: 300 psi True Zero indication, a standard feature on these gauges, reduces the potential risk of installing a dam-aged gauge on your equipment. LISTED U L GAUGE SPECIFICATIONS GAUGE OPTIONS LOOK FOR THESE AGENCY MARKS ON OUR PRODUCTS Vail Fire & Emergency Services 07/14/15 Central Sprinkler Head Cabinets are constructed of a metal enclosure with a hinged cover designed to provide on-site storage of an emergency supply of sprinkler heads and a sprinkler head wrench. NFPA 13 requires a representative number of each type of sprinkler head used in a sprinkler system to be stored in a cabinet on-site to allow for immediate removal and replacement of sprinklers which may have operated or become damaged. Central Sprinkler Head Cabinets are manufactured of heavy gauge steel with knock-outs to accommodate either 1⁄2" or 3⁄4" N.P.T. threaded sprinkler heads and are painted an attractive red enamel. They are available in three (3), six (6) or twelve (12) head capacity. Central Sprinkler Company 451 North Cannon Avenue, Lansdale, Pennsylvania 19446 Sprinkler Head Cabinet Model: Sprinkler Head Cabinet Style: 3, 6 or 12 head Standard Finish: Red enamel Mfgr. Source: Non-domestic Capacity: 3 sprinkler heads 6 sprinkler heads 12 sprinkler heads Dimensions: 3 head - 5" high x 71⁄2" long x 21⁄2" deep 6 head - 5" high x 14" long x 31⁄4" deep 12 head - 5" high x 143⁄4" long x 5" deep Weight: 3 head - 1.5 lbs. 6 head - 2.3 lbs. 12 head - 4 lbs. Hd. Cab. Product Description Technical Data No. 28-6.0 3, 6 & 12 Head Sprinkler Head Cabinet Hd. Cab. 11-94Close Vail Fire & Emergency Services 07/14/15 ©1994 Central Sprinkler Company Printed in U.S.A. Central’s Sprinkler Head Cabinet is designed with two 3⁄16" diameter holes for wall mounting or direct attachment to the system riser with a strap-type hanger. The Cabinet should be installed at or near the system control valve and must be stocked with an adequate supply of spare sprinklers and a sprinkler wrench. The stock of spare sprinklers should include sprinklers of each type and temperature rating as are installed in the sprinkler system, in the following quantities: Sprinklers Spare Sprinklers In System Required under 300 6 300-1000 12 over 1000 24 The Cabinets are designed to accept both 1⁄2" and 3⁄4" N.P.T. threaded sprinklers. For 1⁄2" N.P.T. sprinklers, leave the removable knockout in the hole. For 3⁄4" N.P.T. sprinklers, insert a screwdriver blade from the front top of the shelf and under the near bottom part of the knockout annular ring. Press the screwdriver handle down to remove the knockout ring. The hole, with the knockout ring removed, will accept a 3⁄4" N.P.T. sprinkler. When placing an order, indicate the full product name. Please specify the quantity, model, style, capacity, and size. Sprinklers, wrenches, and hard-ware for hanging are not supplied with the Cabinet. They must be ordered separately. Availability and Service: Central sprinklers, accessories, and other products are available throughout the U.S. and Canada, and internationally through a network of Central Sprinkler distribution centers. You may write directly to Central Sprinkler Company, or call (215) 362-0700 for the distributor nearest you. Guarantee: Central Sprinkler Company will repair and/or replace any products found to be defective in material or workmanship within a period of one year from date of shipment. Please refer to the current Price List for further details of the warranty. Conversion Table: 1 inch = 25.400 mm 1 foot = 0.3048 M 1 pound = 0.4536 kg Conversions are approximate. Central Sprinkler Company 451 North Cannon Avenue, Lansdale, PA 19446 Phone (215) 362-0700 FAX (215) 362-5385 Hd.Cab.2 Ordering Information Installation Care & Maintenance The Cabinet, wrench, and stock of spare sprinklers should be inspected at least quarterly. The following items should be checked: 1. The Cabinet should be readily accessible, and not exposed to a corrosive atmosphere or temperatures in excess of 100oF/38oC. 2. The stock of spare sprinklers should include an adequate number of each type and temperature rating. 3. The stock of sprinklers must be in good condition. 4. A sprinkler wrench of the appropriate type must be included in the Cabinet. Close Vail Fire & Emergency Services 07/14/15 Central's Identification Signs are designed to provide information to the end user about the sprinkler system and it's components. They are available with a variety of wording combinations to meet the signing requirements of NFPA 13. The five basic types of signs are as follows: Type A - Control Valve Sign Type B - Multi-purpose Text Signs Type C - Cold Weather Sign Type D - Fire Alarm Sign Type E - Hydraulic Calculation Sign The Signs are constructed of 18 gauge steel or aluminum with a porcelain enamel or printed mylar facing respectively. The signs have corner holes or slots for easy attach-ment in the field. Sign Type B is available with the following text options: Air control Air control valve Air line Alarm test Alarm line Antifreeze system Auxiliary drain Control Control valve Drain Drain valve Entire system From city main In this building In this section Inspectors test Main control Sign For sprinkler systems & devices 1-95 Identification Signs Product Description Main drain Open sprinkler control Open sprinkler drain Test valve Triangular main drain Water motor Water motor line Technical Data Model: Sign Style: Flat, rectangular Standard Finish: porcelain or mylar Size: Type A - 9" x 7" Type B - 6" x 2" Type C - 73⁄4" x 11⁄4"Type D - 9" x 7" Type E - 5" x 7" Weight: Type A - 4.5 oz.Type B - 0.5 oz.Type C - 2.0 oz.Type D - 4.0 oz.Type E - 1.5 oz.No. 28-9.0 Manufactured by: Central Sprinkler Company 451 North Cannon Avenue, Lansdale, Pennsylvania 19446 The Identification Signs are pro-vided with 1⁄8" diameter or larger holes (or slots) in the corners for easy attachment using standard hardware chain, wire, plastic lock ties, or light gauge metal strap (not included). Installation Signs Close Vail Fire & Emergency Services 07/14/15 ©1995 Central Sprinkler Company Printed in U.S.A. Central Sprinkler Company 451 N. Cannon Avenue, Lansdale, PA 19446 Phone (215) 362-0700 FAX (215) 362-5385 Signs.1 When placing an order, indicate the full product name. Please specify the quantity and type. Hardware for hanging is not supplied with the Sign. It must be ordered separately. Availability and Service: Central sprinklers, accessories, and other products are available throughout the U.S. and Canada, and internationally through a network of Central Sprinkler distribution centers. You may write directly to Central Sprinkler Company, or call (215) 362-0700 for the distributor nearest you. Guarantee: Central Sprinkler Company will repair and/or replace any products found to be defective in material or workmanship within a period of one year from date of shipment. Please refer to the current Price List for further details of the warranty. Conversion Table: 1 inch = 25.400 mm 1 foot = 0.3048 M 1 pound = 0.4536 kg Conversions are approximate. Sign - Type A THIS VALVE CONTROLS AUTOMATIC SPRINKLERS MUST BE AT ALL TIMES OPEN TO BE HANDLED ONLY BY AUTHORIZED PERSON OR BY EMPLOYEE CARING FOR SPRINKLER SYSTEM SUPPLY TO IN CASE OF FIRE DO NOT SHUT VALVE UNTIL FIRE IS ENTIRELY OUT WHEN VALVE IS SHUT FOR EMERGENCY - REPAIRS - OR FIRE-NOTIFY: REQUEST DIRECTIONS -- RESTORE PROTECTION QUICKLY The blank spaces on this sign may be utilized to provide message flexibility. Simply add combinations of sign Type B and Type C as desired. Ordering Information Sign - Type B AUXILIARY DRAIN VALVE SHUT VALVE SHUT MUST BE OPENED IN CASE OF FIRE ALSO DURING SUMMER MONTHS AND MUST BE KEPT OPEN EXCEPT DURING WINTER MONTHS, WHEN VALVE IS TO BE CLOSED AND PIPES DRAINED. FRONT BACK Sign - Type C SPRINKLER FIRE - ALARM WHEN BELL RINGS CALL FIRE DEP'T OR POLICE Sign - Type D HYDRAULIC-SYSTEM This Building is Protected by a Hydraulically Designed Automatic Sprinkler System Location Basis of Design 1. DENSITY 2. DESIGNED AREA OF DISCHARGE No. of Sprinklers System Demand 1. WATER FLOW RATE 2. RESIDUAL PRESSURE AT THE BASE OF THE RISER GPM/SQ.FT. GPM PSI SQ.FT. Sign - Type E Close Vail Fire & Emergency Services 07/14/15 Vail Fire & Emergency Services 07/14/15