HomeMy WebLinkAboutF14-0069_F14-0069 flow pressure info_1418148600.pdfTechnical Data: F1 Res 49 Pendent and Recessed Pendent
Escutcheon*, F1 or F2, Data:
Sprinkler Max. Max. Actual Sprinkler Thread Temp. Ambient
Size Rating Pressure Temp. K Length
OF oc psi (bar) OF oc Factor Inch (mm)
Y," NPT 155 68 175 (12) 100 38 4.9 2.25 (57) -(RXl 175 79 150 66
Adjustment "A" Face of fitting to
Type ceiling lnch(mm) lnch(mm) lnch(mm)
F1 Y. (19.0) Min.= Y." (19.1) % -1Y,6 (4.7 -24.0) Max.= 1 X:" (38.1)
F2 y, (12.7) Min.= 1)\6" (23.8) Y,6 -'X6 (4.7 -17.4) Max.=1X" (38.1)
*Note: Escutcheons F1 or F2 may be used with
Model F1 Res 49 & 58 Recessed Pendent Sprinkler
I **Baseline flows and pressures for 0.05 density
Deflector -to -ceiling
Maximum 1" (25mm) to 4" (100mm)
Max. Sp~inkler Flow S~ac~g gpm (Lpm)
*Deflector -to -ceiling
Maximum 4" (100mm) to 8" (203mm)
Max. Sprinkler
Spacing
ft m
12x 12 3.6x3.6
14 x 14 4.3x4.3
16x 16 4.9x4.9
Flow Pressure
gpm (Lpm) psi (bar)
18x 18 5.5x5.5 15.0 1.0
20 x 20 6.1x6.1 20.2 1.4
Sprinkler
Identification
Number SIN
R3516
*Note: The F1 Res 49 pendent and recessed pendent
residential sprinklers can be installed per NFPA 13 in
beamed ceilings meeting the following criteria:
1. Maximum beam depth= 7" (178mm)
2. Beam spacing at or greater than 7.5 ft. (2.3m) on center.
Technical Data: F1 Res 58 Pendent and Recessed Pendent
Sprinkler Max. Max. Sprinkler Thread Temp. Ambient K
Size Rating Pressure Temo. Factor Length
OF oc psi(bar) OF oc lnch(mm)
W'NPT 155 68 175(12) 100 38 5.8 2.25 (57) (RY2) 175 79 150 66
I **Baseline flows and pressures for 0.05 density
Max. Sprinkler Flow Pressure Spacing gpm(Lpm) psi (bar) ft m
12 x 12 3.6x3.6 16 61
14 x 14 4.3x4.3 16 61
16 x 16 4.9x4.9 16 61
19 72
20 x 20 6.1x6.1
I **Calculate for a .10 density but in no case
go below the baseline flows & pressures
Ceiling -to-
Deflector
Inch mm
1-4
(25-100)
Sprinkler
Identification
Number SI
R3513
4.