EQUIPMENT SUBMITTAL
8/7/2015
Worldwide
Contacts www.tyco-fire.com
RAPID RESPONSE Series LFII Residential Sprinklers
4.9 K-factor Flat-Plate Concealed Pendent
Wet Pipe and Dry Pipe Systems
Page 1 of 6 APRIL 2013 TFP443
Worldwide
Contacts www.tyco-fire.com
General Description
The TYCO RAPID RESPONSE Series LFII Residential Flat-Plate Concealed Pendent Sprinklers (TY2524) are decora-tive, fast response, fusible solder sprin-klers designed for use in residential oc-cupancies such as homes, apartments, dormitories, and hotels.
The Cover Plate/Retainer Assembly con-ceals the sprinkler operating compo-nents above the ceiling. The flat profile of the Cover Plate provides the optimum aesthetically appealing sprinkler design. Additionally, the concealed design of the Series LFII Residential Flat-Plate Con-cealed Pendent Sprinklers provides 1/2 inch (12,7 mm) vertical adjustment. This adjustment provides a measure of flex-ibility when cutting fixed sprinkler drops.
The Series LFII Residential Flat-Plate Concealed Pendent Sprinklers are in-tended for use in the following systems:
• wet and dry pipe residential sprin-kler systems for one- and two-fam-ily dwellings and mobile homes per NFPA 13D
• wet and dry pipe residential sprin-kler systems for residential occu-pancies up to and including four sto-ries in height per NFPA 13R
• wet and dry pipe sprinkler systems for the residential portions of any occupancy per NFPA 13
The Series LFII Residential Sprinklers have been designed with heat sensitiv-ity and water distribution characteristics proven to help in the control of residen-
tial fires and to improve the chance for occupants to escape or be evacuated.
The Series LFII Residential Flat-Plate Concealed Pendent Sprinklers are shipped with a Disposable Protective Cap. The Protective Cap protects the sprinkler during ceiling installation or finish. After ceiling installation is com-plete, the Protective Cap is removed and the Cover Plate/Retainer Assem-bly is installed. Removing the Protec-tive Cap is required for proper sprinkler performance.
Dry Pipe System ApplicationThe Series LFII Residential Flat-Plate Concealed Pendent Sprinkler offers a laboratory approved option for design-ing dry pipe residential sprinkler sys-tems, whereas, most residential sprin-klers are laboratory approved for wet systems only.
Through extensive testing, it has been determined that the number of design sprinklers (hydraulic design area) for the Series LFII Residential Flat-Plate Con-cealed Sprinklers (TY2524) need not be increased over the number of design sprinklers (hydraulic design area) speci-fied for wet pipe sprinkler systems, as is customary for density/area sprinkler systems designed per NFPA 13, 13D, or 13R.
Consequently, the Series LFII Residen-tial Flat-Plate Concealed Sprinklers (TY2524) offer the features of non-wa-ter filled pipe in addition to not having to increase the number of design sprinklers (hydraulic design area) for systems de-signed to NFPA 13, 13D, or 13R. Non-water filled pipe will permit options for areas sensitive to freezing.
NOTICE
The Series LFII Residential Flat-Plate Concealed Pendent Sprinklers (TY2524) described herein must be installed and maintained in compliance with this doc-ument and the applicable standards of the National Fire Protection Association, in addition to the standards of any au-thorities having jurisdiction. Failure to do so may impair the performance of these devices.
The owner is responsible for maintain-ing their fire protection system and de-vices in proper operating condition. The installing contractor or sprinkler manu-facturer should be contacted with any questions.
Sprinkler
Identification
Number (SIN)
TY2524
IMPORTANTAlways refer to Technical Data Sheet TFP700 for the “INSTALLER WARNING” that provides cautions with respect to handling and instal-lation of sprinkler systems and com-ponents. Improper handling and in-stallation can permanently damage a sprinkler system or its components and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely.
TFP443Page 2 of 6
3-3/16" DIA.(81,0 mm)
1/2"NPT
2-1/2" DIA.
(63,5 mm)
MOUNTING
SURFACE3/16"(4,8 mm)
1/8" GAP(3,2 mm)
FACE OFSPRINKLERFITTING
7/8" (22,2 mm)
1-1/8" (28,6 mm)
TIP DEFLECTOR INOPERATED POSITION
1/2" (12,7 mm)THREADEDADJUSTMENT
SPRINKLER-
SUPPORT CUP
ASSEMBLY
OPERATED
SPRINKLER
1-7/8"±1/4"(47,6 mm±6,4 mm)
SPRINKLER-
SUPPORT CUP
ASSEMBLY
COVER-
RETAINER
ASSEMBLY
COVER
PLATE
RETAINER
DISPOSABLEPROTECTIVE CAP
SPRINKLER/SUPPORT CUP
ASSEMBLY
COVER PLATE/RETAINER
ASSEMBLY
COVER
PLATE
EJECTION
SPRING
RETAINER
WITH THREAD
DIMPLES
SOLDER
TAB
SEALINGASSEMBLY
COMPRESSION
SCREW
DEFLECTOR(OPERATEDPOSITION)
SPRINKLERWRENCHINGAREA
SOLDER LINK
ELEMENT
LEVER
DEFLECTOR
CAP
BODY(1/2" NPT)
SADDLE
SUPPORTCUP WITHROLL FORMEDTHREADS
GUIDEPIN
GUIDE PIN
HOUSING
THREAD INTO
SUPPORT
CUP UNTIL
MOUNTING
SURFACE IS
FLUSH WITH
CEILING
WRENCHRECESS
PUSH WRENCH
IN TO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE 3 RAPID RESPONSE SERIES LFII RESIDENTIAL FLAT-PLATE (TY2524) INSTALLATION DIMENSIONS/PROTECTIVE CAP/ACTIVATED DEFLECTOR
FIGURE 1 RAPID RESPONSE SERIES LFII RESIDENTIAL FLAT-PLATE CONCEALED PENDENT SPRINKLER (TY2524)
FIGURE 2 W-TYPE 18 SPRINKLER WRENCH
TFP443 Page 3 of 6
Technical
Data
ApprovalsUL and C-UL Listed
The TYCO RAPID RESPONSE Series LFII Residential Flat-Plate Concealed Pendent Sprinklers are only listed with the Series LFII Concealed Cover Plates having a factory-applied finish.
For details on approvals, refer to the De-sign Criteria section.
Maximum Working Pressure175 psi (12,1 bar)
Discharge CoefficientK=4.9 GPM/psi1/2 (70,6 LPM/bar1/2)
Temperature RatingSprinkler: 160°F (71°C) Cover Plate: 139°F (59°C)
Vertical Adjustment1/2 inch (12,7 mm)
FinishesRefer to the Ordering Procedure section.
Physical CharacteristicsCover Plate/Retainer Assembly:Cover Plate . . . . . . . . . . . . . CopperEjection Spring ....Stainless SteelRetainer ................Brass
Sprinkler/Support Cup Assembly:Body ...................Brass Cap ...................Bronze Saddle . . . . . . . . . . . . . . . . . . Brass Sealing Assembly . . . . . . .Beryllium Nickel w/ TEFLON
Soldered Link Halves . . . . . . NickelLever ..................BronzeCompression Screw . . . . . . . BrassDeflector . . . . . . . . . . . . . . . BronzeGuide Pin Housing........BronzeGuide Pins .............BronzeSupport Cup . . . . . . . . . . . . . . Steel
Operation
When exposed to heat from a fire, the Cover Plate, which is normally soldered to the Retainer at three points, falls away to expose the Sprinkler/Support Cup As-sembly. At this point, the Deflector, sup-ported by the Guide Pins, drops down to its operated position.
The Solder Link Element of the Sprinkler/Support Cup Assembly is comprised of two link halves that are soldered togeth-er with a thin layer of solder. When the rated temperature is reached, the sol-der melts and the two link halves sepa-rate, allowing the sprinkler to activate and flow water.
Design
Criteria
The TYCO RAPID RESPONSE Series LFII Residential Flat-Plate Concealed Pendent Sprinklers (TY2524) are UL and C-UL Listed for installation in ac-cordance with this section:
Residential Sprinkler Design GuideWhen conditions exist that are outside the scope of the provided criteria, re-fer to the Residential Sprinkler Design Guide TFP490 for the manufacturer's recommendations that may be accept-able to the authority having jurisdiction.
System TypePer the UL Listing, wet pipe and dry pipe systems may be utilized. Per the C-UL Listing, only wet pipe systems may be utilized.
Refer to Technical Data Sheet TFP485 about the use of Residential Sprinklers in residential dry pipe systems.
Ceiling TypesSmooth flat horizontal, or beamed, or sloped, in accordance with the 2013 Edition of NFPA 13D, 13R or 13 as applicable.
Hydraulic Design (NFPA 13D and 13R)For systems designed to NFPA 13D or NFPA 13R, the minimum required sprin-kler flow rate are given in Tables A and B as a function of temperature rating and the maximum allowable coverage areas. The sprinkler flow rate is the mini-mum required discharge from each of the total number of “design sprinklers” as specified in NFPA 13D or NFPA 13R. The number of “design sprinklers” spec-ified in NFPA 13D and 13R for wet pipe systems is to be applied when designing dry pipe systems.
Hydraulic Design (NFPA 13)For systems designed to NFPA 13, the number of design sprinklers is to be the four most hydraulically demanding sprinklers. The minimum required dis-charge from each of the four sprinklers is to be the greater of the following:
• The flow rates given in Tables A and B as a function of temperature rating and the maximum allowable cover-age area
• A minimum discharge of 0.1 gpm/ft2. over the “design area” comprised of the four most hydraulically demand-ing sprinklers for the actual coverage areas being protected by the four sprinklers
The number of “design sprinklers” specified in NFPA 13 for wet pipe sys-tems is to be applied when designing dry pipe systems.
Dry Pipe System Water DeliveryWhen using the Series LFII Residential Flat-Plate Concealed Pendent Sprinklers (TY2524) in dry pipe sprinkler systems, the time for water delivery must not ex-ceed 15 seconds for the most remote operating sprinkler.
Obstruction to Water Distribution.Sprinklers are to be located in accor-dance with the obstruction rules of NFPA 13D, 13R, and 13 as applicable for residential sprinklers as well as with the obstruction criteria described within the Technical Data Sheet TFP490.
Operational SensitivityInstall sprinklers relative to the ceiling mounting surface as shown in Figure 3.
The Series LFII Residential Flat-Plate Concealed Pendent Sprinklers must not be used in applications where the air pressure above the ceiling is greater than that below. Down drafts through the Support Cup can delay sprinkler op-eration in a fire situation.
Sprinkler SpacingThe minimum spacing between sprin-klers is 8 feet (2,4 m). The maximum spacing between sprinklers cannot ex-ceed the length of the coverage area (Table A) being hydraulically calculated (e.g., a maximum of 12 feet for a 12 ft. x 12 ft. coverage area or 20 feet for a 20 ft. x 20 ft. coverage area.)
TFP443Page 4 of 6
Maximum Coverage Area (a)
Ft. x Ft. (m x m)
Maximum Spacing
Ft. (m)
WET PIPE SYSTEM
Minimum Flow and Residual Pressure(b, c)
Ordinary Temp Rating 160°F (71°C)Deflector to Ceiling Installation Type
Minimum Spacing Ft. (m)
Flow GPM (L/min)
Pressure PSI (bar)
12 x 12(3,7 x 3,7)12(3,7)13 (49,2)7.0 (0,48)Smooth Ceilings 7/8 to 1-1/8 inches.
Beamed Ceilings per NFPA 13D 13R, or 13 Installed in beam 7/8 to 1-1/8 inches below bottom of beam
Concealed 8 (2,4)
14 x 14(4,3 x 4,3)14(4,3)13 49,2)7.0 (0,48)
16 x 16(4,9 x 4,9)16(4,9)13(49,2)7.0 (0,48)
18 x 18(5,5 x 5,5)18(5,5)17 (64,3)12.0 (0,83)
20 x 20(6,1 x 6,1)20(6,1)20 (75,7)16.7 (1,15)
(a) For coverage area dimensions less than or between those indicated, use the minimum required flow for the next highest coverage area for which Hydraulic Design section under the Design Criteria are stated.
(b) The Minimum Flow requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pres-
sures are calculated using the nominal K-factor. Refer to “Hydraulic Design” in the Design Criteria section for details.
(c) For NFPA 13 residential applications, the greater of 0.1 gpm/ft.2 over the design area or the flow in accordance with the
criteria in this table must be used.
TABLE A WET PIPE SYSTEM SERIES LFII RESIDENTIAL FLAT-PLATE CONCEALED PENDENT SPRINKLER (TY2524) NFPA 13D, 13R, AND 13 HYDRAULIC DESIGN CRITERIA
Maximum Coverage Area (a)
Ft. x Ft. (m x m)
Maximum Spacing
Ft. (m)
DRY PIPE SYSTEM
Minimum Flow and Residual Pressure(b)
Ordinary Temp Rating 160°F (71°C)Deflector to Ceiling Installation Type
Minimum Spacing Ft. (m)
Flow GPM (L/min)
Pressure PSI (bar)
12 x 12(3,7 x 3,7)12(3,7)15 (56,8)9.4 (0,65)Smooth Ceilings 7/8 to 1-1/8 inches.
Beamed Ceilings per NFPA 13D 13R, or 13 Installed in beam 7/8 to 1-1/8 inches below bottom of beam
Concealed 8 (2,4)
14 x 14(4,3 x 4,3)14(4,3)15 (56,8)9.4 (0,65)
16 x 16(4,9 x 4,9)16(4,9)16 (60,6)10,7 (0,74)
18 x 18(5,5 x 5,5)18(5,5)17 (64,3)12.0 (0,83)
20 x 20(6,1 x 6,1)20(6,1)21 (79,5)18,4 (1,27)
(a) For coverage area dimensions less than or between those indicated, use the minimum required flow for the next highest
coverage area for which Hydraulic Design section under the Design Criteria are stated.
(b) The Minimum Flow requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are calculated using the nominal K-factor. Refer to “Hydraulic Design” in the Design Criteria section for details.
(c) For NFPA 13 residential applications, the greater of 0.1 gpm/ft.2 over the design area or the flow in accordance with the criteria in this table must be used.
TABLE B DRY PIPE SYSTEM SERIES LFII RESIDENTIAL FLAT-PLATE CONCEALED PENDENT SPRINKLER (TY2524) NFPA 13D, 13R, AND 13 HYDRAULIC DESIGN CRITERIA
TFP443 Page 5 of 6
Installation
The TYCO RAPID RESPONSE Series LFII Residential Flat-Plate Concealed Pendent Sprinklers must be installed in accordance with this section:
General InstructionsDamage to the Solder Link Element dur-ing installation can be avoided by han-dling the sprinkler by the Support Cup only; that is, do not apply pressure to the Solder Link Element (Figure 1).
A leak-tight 1/2 inch NPT sprinkler joint should be obtained by applying a min-imum-to-maximum torque of 7 to 14 ft.-lbs. (9,5 to 19,0 Nm). Higher levels of torque can distort the sprinkler inlet with consequent leakage or impairment of the sprinkler.
Do not attempt to compensate for insuf-ficient adjustment in the Cover Plate/Retainer Assembly by under- or over-tightening the sprinkler. Re-adjust the position of the sprinkler fitting to suit.
Step 1. Install pendent sprinklers in the pendent position, with the center-line of the sprinkler perpendicular to the mounting surface.
Step 2. Remove the Protective Cap.
Step 3. With pipe-thread sealant ap-plied to the pipe threads, and using the W-Type 18 Wrench shown in Figure 2, install and tighten the Sprinkler/Sup-port Cup Assembly into the fitting. The W-Type 18 Wrench accepts a 1/2 inch ratchet drive.
Step 4. Replace the Protective Cap by pushing it upwards until it bottoms out against the Support Cup. The Protec-tive Cap helps prevent damage to the Deflector and Guide Pins during ceiling installation and/or during application of the finish coating of the ceiling.
NOTICE
As long as the protective Cap remains in place, the system is considered “Out Of Service”.
Step 5. After the ceiling has been com-pleted with the 2-1/2 inch (63 mm) diam-eter hole and in preparation for install-ing the Cover Plate/Retainer Assembly, remove and discard the Protective Cap, and verify that the Deflector moves up and down freely.
If the sprinkler has been damaged and the deflector does not move up and down freely, replace the entire sprinkler assembly. Do not attempt to modify or repair a damaged sprinkler.
Step 6. Screw on the Cover Plate/Re-tainer Assembly until its flange contacts the ceiling. Do not continue to screw on the Cover Plate/Retainer Assembly such that it lifts a ceiling panel out of its normal position.
If the Cover Plate/Retainer Assembly cannot be engaged with the Mounting Cup or the Cover Plate/Retainer Assem-bly cannot be engaged sufficiently to contact the ceiling, the Sprinkler Fitting must be repositioned.
Care and
Maintenance
The TYCO RAPID RESPONSE Series LFII Residential Flat-Plate Concealed Pendent Sprinkler (TY2524) must be maintained and serviced in accordance with ths section:
Before closing a fire protection system main control valve for maintenance work on the fire protection system that it con-trols, obtain permission to shut down the affected fire protection system from the proper authorities and notify all person-nel who may be affected by this action.
Absence of a Cover Plate may delay the sprinkler operation in a fire situation.
The owner must assure that the sprin-klers are not used for hanging any ob-jects and that the sprinklers are only cleaned by means of gently dusting with a feather duster; otherwise, non-opera-tion in the event of a fire or inadvertent operation may result.
When properly installed, there is a nomi-nal 1/8 inch (3,2 mm) air gap between the lip of the Cover Plate and the ceil-ing, as shown in Figure 3. This air gap is necessary for proper operation of the sprinkler by allowing heat flow from a fire to pass below and above the Cover Plate to help assure appropriate release of the Cover Plate in a fire situation. If the ceiling needs repainting after sprinkler installation, exercise care to ensure that the new paint does not seal off any of the air gap. Failure to do so may impair sprinkler operation.
Factory painted Cover Plates must not be repainted. They should be replaced, if necessary, by factory painted units. Non-factory applied paint may adversely delay or prevent sprinkler operation in the event of a fire.
Do not pull the Cover Plate relative to the Retainer. Separation may result.
Sprinklers which are found to be leaking or exhibiting visible signs of corrosion must be replaced.
Automatic sprinklers must never be painted, plated, coated, or otherwise altered after leaving the factory. Modi-fied or overheated sprinklers must be replaced.
Care must be exercised to avoid dam-age to the sprinklers - before, during, and after installation. Sprinklers dam-aged by dropping, striking, wrench twist/slippage, or the like, must be replaced.
The owner is responsible for the in-spection, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the applicable standards of the National Fire Protection Association (e.g., NFPA 25), in addition to the stan-dards of any other authorities having ju-risdiction. Contact the installing contrac-tor or sprinkler manufacturer regarding any questions.
Automatic sprinkler systems are rec-ommended to be inspected, tested, and maintained by a qualified Inspec-tion Service in accordance with local requirements and/or national codes.
A H E A D O F T H E F L O W
®
www.nibco.com
NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227
TECH SERVICES PH: 1.888.446.4226 • FAX: 1.888.234.0557 • INTERNATIONAL OFFICE PH: +1.574.295.3327 • FAX: +1.574.295.3455
www.nibco.com
4
All of the advantages found in copper as a metal have been capitalized to the utmost in the manufacture of NIBCO Fittings. Because
of the accuracy of construc tion and design, copper plumbing is more efficient and less expensive.
NIBCO manufactures nine general types of fittings: Wrot Pressure; Cast Pressure; Wrot Drainage; Cast Drainage; Flanges; Flared
Tube; Threaded Bronze; Insert Fittings for PEX; Barbed Insert Fittings for Polybutylene. Each has its particular place and use and each
offers its own advantages when used for the proper service requirement.
ALLOY AND FINISH — NIBCO Fittings are made from highest quality raw materials available — Cast Fittings are made from Copper
Alloy C84400 which consists of 81% Copper, 7% Lead, 3% Tin, and 9% Zinc per ASTM Specification B584. Wrot Copper Fittings are
made from commercially pure copper mill products per ASTM Specifications B75 Alloy C12200.
NIBCO fittings are produced to meet requirements of applicable standards wherever practicable.
NIBCO brand wrot and cast fittings are manufactured in the U.S.A. and Mexico. The manufacturing plants at Stuarts Draft, VA,
Nacogdoches, TX and Reynosa, Mexico are registered to ISO 9002 quality standards.
Following is suggested phrasing to be incorporated in your specifications or bills of material for
Copper Tube Fittings.
WROT SOLDER JOINT FITTINGS — “Wrot Solder Joint Fittings shall be produced to one of the following specifications:
1. Material and workmanship shall be in accordance with ASME/ANSI B16.22; Wrought Copper and Copper Alloy Solder Joint
Pressure Fittings.”
Specifications
2. The dimensional, material and workmanship shall
meet the requirements of MSS SP-104; Wrought
Copper Solder Joint Pressure Fittings.”
3. The dimensional, material and workmanship of
5"–12" copper fittings shall meet the requirements
of MSS SP-109 “Welded Fabricated Copper Solder
Joint Pressure Fittings.”
4. Certified to ANSI/NSF 61.
CAST COPPER ALLOY SOLDER JOINT FITTINGS
— “Cast Copper Alloy Solder Joint Fittings shall be in
accor dance with ANSI Std. B16.18.”
WROT DRAINAGE FITTINGS — “Wrot Drainage
Fittings shall be in accordance with ASME/ANSI Std.
B16.29.”
CAST COPPER ALLOY SOLDER JOINT DRAINAGE
FITTINGS — “Cast Copper Alloy Solder Joint Drainage
Fittings shall be in accordance with ASME Std.
B16.23.”
CAST COPPER ALLOY FLARED TUBE FITTINGS — “Cast
Copper Alloy Flared Tube Fittings shall be in accor-
dance with ASME/ANSI Std. B16.26.
CAST COPPER ALLOY FLANGES AND FLANGED
FITTINGS—
CLASS 150 — Cast Copper Alloy Flanges and
Flanged Fittings shall meet the requirements
of MSS SP-106 and/or the workmanship and
dimensions of Federal Specifications WW-F-406 or
ASME Std. B16.24.
CLASS 125 — Material, workmanship and
dimensions of flanges shall be in accordance with
MSS SP-106.
CAST BRONZE THREADED FITTINGS —
“Cast Bronze Threaded Fittings shall be in accordance
with ANSI/ASME B16.15.”
POLYBUTYLENE COPPER INSERT TYPE VALVES AND
FITTINGS — “Wrot Copper Insert Fittings shall be
manufactured per the following specifications:
MSS SP-103 or ASTM F1380.”
NIBCO Copper Tube Fittings are all produced to above
Standards. To simplify, write your specifications to
read: “Copper Tube Fittings to be in accordance with
specifications as outlined in NIBCO Catalog c-cf-0602.”
WROT COPPER MEDICAL MEDICAL GAS SYSTEM
COMPONENTS — Wrot copper fittings that are to be
installed in medical gas applications shall be prepared
in accordance with NFPA 99, Health Care Facilities
Gas and Vacuum Systems and the Compressed
Gas Association, Pamphlet G4.1. Packaging shall
be adequately protective and include labeling that
identifies the preparer and states that the product
has been cleaned and bagged for oxygen or med gas
service.
For technical information and dimensions refer to the
engineering section contained in this catalog.
Revision 3/29/04
A H E A D O F T H E F L O W
®
www.nibco.com
NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227
TECH SERVICES PH: 1.888.446.4226 • FAX: 1.888.234.0557 • INTERNATIONAL OFFICE PH: +1.574.295.3327 • FAX: +1.574.295.3455
www.nibco.com
6
703-2
Fitting Adapter Ftg x F – Cast
APPROX. DIM. B NOM. SIZE NET WT./LBS. INCHES
1/2 x 1/4 0.11 17/32
3/4 x 1/2 0.12 19/16
1 x 3/4 0.38 131/32
1 x 1/2 0.15 17/16
2 1/2 1.65 215/16
3 2.47 31/4
703-5 Special
Drop Adapter C x F – Cast
APPROX. DIM. A
NOM. SIZE NET WT./LBS. INCHES
1/2 0.16 3/4
3/4 0.24 31/32
703-5B
Drop Adapter C x F – Cast
APPROX. DIM. A
NOM. SIZE NET WT./LBS. INCHES
1/2 0.15 3/4
ADAPTERS
603
Adapter C x F – Wrot
APPROX. DIM. A NOM. SIZE NET WT./LBS. INCHES
1/8 0.03 13/32
1/8 x 1/4 0.03 1/2
1/4 0.03 5/8
1/4 x 3/8 0.05 21/32
3/8 0.04 11/16
3/8 x 1/2 0.09 29/32
3/8 x 1/4 0.03 9/16
1/2 0.09 27/32
1/2 x 3/4 0.14 1
1/2 x 3/8 0.04 17/32
1/2 x 1/4 0.05 1/2
5/8 x 3/4 0.12 29/32
5/8 x 1/2 0.11 3/4
3/4 0.15 29/32
3/4 x 1 0.21 11/8
3/4 x 1/2 0.10 5/8
1 0.24 31/32
1 x 1 1/4 0.28 17/32
1 x 3/4 0.19 25/32
1 x 1/2 0.24 5/8
1 1/4 0.33 13/32
1 1/4 x 1 1/2 0.40 11/4
1 1/4 x 1 0.27 31/32
1 1/2 0.44 11/8
1 1/2 x 2 0.50 11/32
2 0.63 13/32
2 x 1 1/2 0.74 13/16
2 1/2 1.13 –
3 1.94 –
703
Adapter C x F – Cast
APPROX. DIM. A NOM. SIZE NET WT./LBS. INCHES
1/4 x 1/2 0.13 27/32
1/2 x 1 0.30 1
3/4 x 1 1/4 0.55 11/8
3/4 x 3/8 0.17 3/4
1 x 1 1/2 0.68 13/32
1 1/4 x 1 0.27 31/32
1 1/4 x 3/4 0.29 3/4
1 1/2 x 2 0.78 11/32
1 1/2 x 1 0.37 25/32
1 1/2 x 1 1/4 0.47 11/4
2 x 1 1/4 0.76 27/32
2 1/2 1.62 13/8
3 2.34 11/2
4 4.05 19/16
603-2Fitting Adapter Ftg x F – Wrot
APPROX. DIM. B NOM. SIZE NET WT./LBS. INCHES
1/4 0.03 13/32
3/8 0.06 13/16
1/2 0.09 17/16
1/2 x 3/8 0.05 11/4
3/4 0.13 111/16
1 0.27 21/32
1 1/4 0.31 21/8
1 1/2 0.43 25/16
2 0.61 217/32
Consult price sheet for Made to Order items and
for minimum order quantities.
Revision 2/6/07
A H E A D O F T H E F L O W
®
www.nibco.com
NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227
TECH SERVICES PH: 1.888.446.4226 • FAX: 1.888.234.0557 • INTERNATIONAL OFFICE PH: +1.574.295.3327 • FAX: +1.574.295.3455
www.nibco.com
9
Consult price sheet for Made to Order items and
for minimum order quantities.
CAPS
617
Tube Cap C – Wrot
APPROX. DIM. N NOM. SIZE NET WT./LBS. INCHES
1/8 0.01 1/32
1/4 0.01 3/32
3/8 0.01 3/32
1/2 0.02 3/32
5/8 0.03 1/8
3/4 0.04 1/8
1 0.07 5/32
1 1/4 0.10 3/32
1 1/2 0.16 1/8
2 0.27 5/32
2 1/2 0.50 7/32
3 0.78 7/32
4 1.66 1/4
717
Tube Cap C – Cast
APPROX. DIM. N NOM. SIZE NET WT./LBS. INCHES
5 5.48 7/16
6 9.07 17/32
717-D
Drain Cap – Cast
APPROX. DIM. A NOM. SIZE NET WT./LBS. INCHES
1/2 0.06 21/32
COUPLINGS
600
Reducing Coupling C x C – Wrot
APPROX. DIM. A NOM. SIZE NET WT./LBS. INCHES
1/8 x 3/16 O.D. 0.01 5/32
5/16 O.D. x 1/8 0.01 3/16
1/4 x 5/16 O.D. 0.01 3/16
1/4 x 1/8 0.01 3/16
3/8 x 1/4 0.02 3/16
3/8 x 5/16 O.D. 0.01 1/4
3/8 x 1/8 0.01 1/4
1/2 x 3/8 0.03 3/16
1/2 x 1/4 0.02 1/4
1/2 x 1/8 0.03 11/32
5/8 x 1/2 0.05 3/16
5/8 x 3/8 0.04 11/32
5/8 x 1/4 0.03 13/32
3/4 x 5/8 0.07 3/16
3/4 x 1/2 0.06 9/32
3/4 x 3/8 0.06 3/8
3/4 x 1/4 0.05 11/32
1 x 3/4 0.11 11/32
1 x 5/8 0.09 3/8
1 x 1/2 0.10 11/32
1 x 3/8 0.10 13/32
1 1/4 x 1 0.16 5/16
1 1/4 x 3/4 0.18 17/32
1 1/4 x 5/8 0.18 5/8
1 1/4 x 1/2 0.14 7/16
1 1/2 x 1 1/4 0.23 5/16
1 1/2 x 1 0.22 9/16
1 1/2 x 3/4 0.20 3/8
1 1/2 x 1/2 0.19 1/2
2 x 1 1/2 0.41 9/16
2 x 1 1/4 0.35 11/16
2 x 1 0.37 7/16
2 x 3/4 0.34 17/32
2 x 1/2 0.35 23/32
2 1/2 x 2 0.59 9/16
2 1/2 x 1 1/2 0.65 11/16
2 1/2 x 1 1/4 0.65 13/16
2 1/2 x 1 0.73 29/32
Continues…
APPROX. DIM. A NOM. SIZE NET WT./LBS. INCHES
3 x 2 1/2 0.98 1/2
3 x 2 1.06 15/16
3 x 1 1/2 0.92 11/32
3 1/2 x 3 1.52 1/2
4 x 3 1/2 2.12 19/32
4 x 3 1.92 27/32
4 x 2 1/2 1.77 1
4 x 2 1.92 11/4
5 x 4 3.50 331/32
5 x 3 3.18 115/32
5 x 2 1/2 3.50 13/16
5 x 2 3.09 21/32
6 x 5 5.70 11/8
6 x 4 5.24 11/2
6 x 3 5.04 2
6 x 2 1/2 5.13 21/4
6 x 2 4.89 21/2
8 x 6 13.06 119/32
8 x 4 12.22 219/32
8 x 3 11.79 33/32
8 x 2 1/2 12.64 33/8
600-RS
Coupling with Rolled Tube Stop
C x C – Wrot
APPROX. DIM. A
NOM. SIZE NET WT./LBS. INCHES
1/8 O.D. 0.01 1/16
3/16 O.D. 0.01 3/32
1/8 0.01 1/16
5/16 O.D. 0.01 3/32
1/4 0.01 1/16
3/8 0.01 3/32
1/2 0.03 3/32
5/8 0.04 3/32
3/4 0.06 3/32
7/8 0.09 3/32
1 0.11 3/32
1 1/4 0.16 1/8
1 1/2 0.23 1/8
2 0.41 1/8
2 1/2 0.65 1/8
3 0.93 1/8
3 1/2 1.45 5/32
4 1.93 7/32
Revision 2/6/07
A H E A D O F T H E F L O W
®
www.nibco.com
NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227
TECH SERVICES PH: 1.888.446.4226 • FAX: 1.888.234.0557 • INTERNATIONAL OFFICE PH: +1.574.295.3327 • FAX: +1.574.295.3455
www.nibco.com
12
ELBOWS continued
Consult price sheet for Made to Order items and
for minimum order quantities.
706-2
45° Fitting Elbow Ftg x C – Cast
APPROX. DIM. B DIM. C NOM. SIZE NET WT./LBS. INCHES INCHES
4 4.31 311/32 15/16
607
90° Elbow – Close Rough
C x C – Wrot
APPROX. DIM. C DIM. D NOM. SIZE NET WT./LBS. INCHES INCHES
1/8 0.01 13/32 13/32
1/4 0.02 9/32 9/32
3/8 0.03 1/2 1/2
1/2 0.04 3/8 3/8
1/2 x 3/8 0.04 9/16 21/32
3/4 0.10 17/32 17/32
3/4 x 5/8 0.12 29/32 7/8
3/4 x 1/2 0.10 17/32 3/4
1 0.21 23/32 23/32
1 x 3/4 0.16 23/32 5/8
1 1/4 0.31 11/32 11/32
1 1/4 x 1 0.31 15/8 115/32
1 1/2 0.46 17/32 17/32
1 1/2 x 1 1/4 0.35 15/32 13/32
2 0.84 11/2 11/2
2 x 1 1/2 0.58 17/16 11/4
2 1/2 1.41 127/32 127/32
3 2.07 23/32 23/32
3 1/2 2.94 23/8 23/8
4 4.23 225/32 225/32
5 7.74 27/8 27/8
6 10.95 37/16 37/16
8 29.50 423/32 423/32
707
90° Elbow – Close Rough
C x C – Cast
APPROX. DIM. C DIM. D NOM. SIZE NET WT./LBS. INCHES INCHES
1 1/4 x 1 0.42 15/8 115/32
1 1/4 x 3/4 0.34 9/16 13/16
1 1/4 x 1/2 0.28 15/32 27/32
1 1/2 x 1 0.54 11/16 1
1 1/2 x 3/4 0.42 19/32 31/32
1 1/2 x 1/2 0.40 5/8 29/32
2 x 1 1/4 0.86 7/8 11/4
2 x 1 0.78 3/4 11/4
2 x 3/4 0.69 5/8 11/4
2 1/2 x 2 2.16 13/16 19/32
3 x 2 1/2 2.26 111/16 11/2
3 x 2 2.68 13/8 19/16
4 x 3 5.18 129/32 215/32
607-I
90° Elbow –
Intermediate Radius C x C
– Wrot
APPROX. DIM. C DIM. D
NOM. SIZE NET WT./LBS. INCHES INCHES
1/2 0.06 19/32 19/32
5/8 0.09 7/8 7/8
3/4 0.14 13/16 3/16
1 0.24 11/16 11/16
607-LT
90° Elbow – Long Radius
C x C – Wrot
APPROX. DIM. C DIM. D NOM. SIZE NET WT./LBS. INCHES INCHES
3/16 O.D. 0.01 13/32 13/32
1/8 0.01 13/32 13/32
5/16 O.D. 0.02 9/16 9/16
1/4 0.02 17/32 17/32
1/4 x 1/8 0.01 19/32 1/2
3/8 0.04 23/32 23/32
1/2 0.08 7/8 7/8
1/2 x 3/8 0.06 13/16 13/16
1/2 x 1/4 0.03 25/32 21/32
5/8 0.10 13/32 13/32
5/8 x 1/2 0.09 11/16 11/16
3/4 0.16 11/8 11/8
3/4 x 5/8 0.13 11/4 13/32
3/4 x 1/2 0.10 11/8 11/16
7/8 0.28 119/32 119/32
1 0.28 17/16 17/16
1 x 3/4 0.20 11/4 11/8
1 x 5/8 0.15 113/32 13/32
1 1/4 0.42 17/8 17/8
1 1/4 x 1 0.33 125/32 11/2
1 1/2 0.66 21/4 21/4
2 1.23 215/16 215/16
2 1/2 1.96 311/16 311/16
3 2.93 41/32 41/32
4 5.95 51/4 51/4
Revision 2/7/07
A H E A D O F T H E F L O W
®
www.nibco.com
NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227
TECH SERVICES PH: 1.888.446.4226 • FAX: 1.888.234.0557 • INTERNATIONAL OFFICE PH: +1.574.295.3327 • FAX: +1.574.295.3455
www.nibco.com
15
707-6
90° Union Elbow C x C – Cast
APPROX. DIM. A DIM. C NOM. SIZE NET WT./LBS. INCHES INCHES
3/8 0.17 31/32 5/16
1/2 0.24 1 7/16
3/4 0.39 117/32 9/16
1 0.64 121/32 23/32
1 1/4 1.07 119/32 23/32
708
90° Flanged Sink Elbow
C x F – Cast
NOM. APPROX. DIM. A DIM. C DIM. F SIZE NET WT./LBS. INCHES INCHES INCHES
1/2 0.20 7/8 9/16 13/4
764
90° Double Elbow
C x C x C – Cast
APPROX. DIM. C DIM. D
NOM. SIZE NET WT./LBS. INCHES INCHES
1 x 3/4 x 3/4 0.33 3/4 21/32
ELBOWS continued
Consult price sheet for Made to Order items and
for minimum order quantities.
FITTING REDUCERS
APPROX. DIM. B NOM. SIZE NET WT./LBS. INCHES
4 x 3 1/2 2.09 25/8
4 x 3 2.00 31/32
4 x 2 1/2 1.56 31/32
4 x 2 1.76 313/32
5 x 4 3.30 39/16
5 x 3 2.97 41/16
5 x 2 1/2 3.30 411/32
5 x 2 2.88 411/16
6 x 5 5.56 43/16
6 x 4 5.09 49/16
6 x 3 4.67 51/16
6 x 2 1/2 4.47 511/32
6 x 2 4.51 519/32
8 x 6 12.33 515/32
8 x 5 10.35 515/16
8 x 4 11.10 67/16
8 x 3 10.63 615/16
8 x 2 1/2 11.41 73/16
8 x 2 10.86 77/16
741
Companion Flange C – Cast
NOM. APPROX. DIM. B DIM. F DIM. G DIM. W
SIZE NET WT./LBS. INCHES INCHES INCHES INCHES
1/2 0.55 1/8 31/2 3/16 23/8
3/4 0.71 1/8 37/8 3/16 23/4
1 1.26 1/8 41/4 1/4 31/8
1 1/4 1.42 1/8 45/8 1/4 31/2
1 1/2 1.82 1/8 5 5/16 37/8
2 2.76 1/8 6 3/8 43/4
2 1/2 4.29 1/8 7 3/8 51/2
3 5.26 1/8 71/2 7/16 6
4 7.60 1/8 9 7/16 71/2
5 9.04 1/8 10 7/16 81/2
6 12.68 1/8 11 1/2 91/2
NOTE: Dim. B = Tube Stop to Flange Face
600-2
Fitting Reducer Ftg x C – Wrot
APPROX. DIM. B NOM. SIZE NET WT./LBS. INCHES
1/4 x 1/8 0.01 15/32
3/8 x 1/4 0.01 19/32
3/8 x 1/8 0.01 25/32
1/2 x 3/8 0.03 11/16
1/2 x 1/4 0.02 25/32
5/8 x 1/2 0.04 7/8
5/8 x 3/8 0.04 31/32
5/8 x 1/4 0.03 11/32
3/4 x 5/8 0.06 31/32
3/4 x 1/2 0.06 11/8
3/4 x 3/8 0.05 11/8
3/4 x 1/4 0.05 13/32
1 x 3/4 0.10 17/32
1 x 5/8 0.09 13/8
1 x 1/2 0.09 11/4
1 x 3/8 0.08 19/32
1 1/4 x 1 0.15 15/16
1 1/4 x 3/4 0.16 11/2
1 1/4 x 1/2 0.13 13/8
1 1/2 x 1 1/4 0.23 113/32
1 1/2 x 1 0.21 15/8
1 1/2 x 3/4 0.20 17/8
1 1/2 x 1/2 0.16 119/32
2 x 1 1/2 0.40 131/32
2 x 1 1/4 0.34 23/32
2 x 1 0.35 127/32
2 x 3/4 0.35 127/32
2 x 1/2 0.34 131/32
2 1/2 x 2 0.65 131/32
2 1/2 x 1 1/2 0.65 23/8
2 1/2 x 1 1/4 0.60 27/32
2 1/2 x 1 0.78 29/32
3 x 2 1/2 1.03 21/4
3 x 2 0.99 29/16
3 x 1 1/2 0.81 219/32
3 x 1 1/4 1.29 31/4
3 1/2 x 3 1.48 211/32
Continues…
FLANGES –
CLASS 125
Revision 2/8/07
A H E A D O F T H E F L O W
®
www.nibco.com
NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227
TECH SERVICES PH: 1.888.446.4226 • FAX: 1.888.234.0557 • INTERNATIONAL OFFICE PH: +1.574.295.3327 • FAX: +1.574.295.3455
www.nibco.com
18
APPROX. DIMENSIONS NET WT. INCHES NOM. SIZE LBS. C F G
1 x 1/2 x 1 0.29 11/16 1 21/32
1 x 1/2 x 3/4 0.27 9/16 13/16 3/4
1 x 1/2 x 1/2 0.22 15/32 25/32 23/32
1 1/4 0.43 13/16 3/16 13/16
1 1/4 x 1 1/4 x 2 1.13 130/32 130/32 13/32
1 1/4 x 1 1/4 x 1 1/2 0.60 13/16 13/16 29/32
1 1/4 x 1 1/4 x 1 0.45 25/32 25/32 29/32
1 1/4 x 1 1/4 x 3/4 0.37 21/32 21/32 3/4
1 1/4 x 1 1/4 x 1/2 0.30 1/2 1/2 25/32
1 1/4 x 1 1/4 x 3/8 0.34 23/32 23/32 29/32
1 1/4 x 1 x 1 1/4 0.43 13/16 11/32 13/16
1 1/4 x 1 x 1 0.47 25/32 7/8 29/32
1 1/4 x 1 x 3/4 0.35 21/32 25/32 7/8
1 1/4 x 1 x 1/2 0.30 1/2 5/8 29/32
1 1/4 x 3/4 x 1 1/4 0.42 13/16 11/8 13/16
1 1/4 x 3/4 x 1 0.45 25/32 11/32 29/32
1 1/4 x 3/4 x 3/4 0.37 21/32 15/16 7/8
1 1/4 x 3/4 x 1/2 0.30 1/2 3/4 29/32
1 1/4 x 1/2 x 1 1/4 0.41 13/16 17/32 13/16
1 1/2 0.61 31/32 31/32 29/32
1 1/2 x 1 1/2 x 2 1.11 125/32 125/32 13/32
1 1/2 x 1 1/2 x 1 1/4 0.62 29/32 29/32 11/16
1 1/2 x 1 1/2 x 1 0.55 11/16 11/16 7/8
1 1/2 x 1 1/2 x 3/4 0.45 11/16 11/16 11/32
1 1/2 x 1 1/2 x 1/2 0.40 1/2 1/2 11/32
1 1/2 x 1 1/4 x 1 1/2 0.62 11/32 13/16 29/32
1 1/2 x 1 1/4 x 1 1/4 0.62 31/32 13/32 31/32
1 1/2 x 1 1/4 x 1 0.51 25/32 1 11/32
1 1/2 x 1 1/4 x 3/4 0.49 11/16 13/16 11/32
1 1/2 x 1 1/4 x 1/2 0.41 1/2 25/32 11/32
1 1/2 x 1 x 1 1/2 0.59 11/32 111/32 29/32
1 1/2 x 1 x 1 1/4 0.63 29/32 11/8 11/16
1 1/2 x 1 x 1 0.54 25/32 11/16 11/32
1 1/2 x 1 x 3/4 0.44 11/16 31/32 15/16
1 1/2 x 1 x 1/2 0.39 1/2 25/32 11/32
1 1/2 x 3/4 x 1 1/2 0.62 11/32 17/16 11/16
1 1/2 x 3/4 x 1 1/4 0.58 29/32 111/32 11/16
1 1/2 x 3/4 x 1 0.54 25/32 11/4 11/32
1 1/2 x 3/4 x 3/4 0.47 11/16 13/32 29/32
1 1/2 x 3/4 x 1/2 0.39 1/2 29/32 31/32
1 1/2 x 1/2 x 1 1/2 0.62 11/32 113/32 31/32
Continues…
APPROX. DIMENSIONS
NET WT. INCHES
NOM. SIZE LBS. C F G
2 1.30 19/32 19/32 11/32
2 x 2 x 2 1/2 2.34 2 2 121/32
2 x 2 x 1 1/2 1.17 11/4 11/4 123/32
2 x 2 x 1 1/4 1.12 9/32 9/32 17/8
2 x 2 x 1 0.90 27/32 27/32 11/4
2 x 2 x 3/4 0.88 19/32 19/32 11/4
2 x 2 x 1/2 1.17 11/4 11/4 21/4
2 x 1 1/2 x 2 1.16 19/32 17/8 111/32
2 x 1 1/2 x 1 1/2 1.15 11/4 13/4 123/32
2 x 1 1/2 x 1 1/4 1.15 7/32 13/4 111/32
2 x 1 1/2 x 3/4 0.83 21/32 15/16 17/32
2 x 1 1/2 x 1/2 1.12 11/4 125/32 21/4
2 x 1 1/4 x 2 1.58 19/32 115/32 19/32
2 x 1 1/4 x 1 1/2 1.16 11/4 131/32 123/32
2 x 1 1/4 x 1 1/4 1.19 15/16 111/32 111/32
2 x 1 1/4 x 1 0.90 27/32 19/32 111/32
2 x 1 1/4 x 3/4 0.85 21/32 1 18/27
2 x 1 x 2 1.11 11/8 125/32 11/4
2 x 1 x 1 0.89 27/32 19/32 111/32
2 x 3/4 x 2 1.15 19/32 23/16 11/4
2 x 1/2 x 2 1.15 19/32 23/8 11/4
2 1/2 2.40 15/8 15/8 15/8
2 1/2 x 2 1/2 x 2 1.97 15/16 15/16 121/32
2 1/2 x 2 1/2 x 1 1/2 1.53 13/32 13/32 121/32
2 1/2 x 2 1/2 x 1 1/4 1.72 13/32 13/32 127/32
2 1/2 x 2 1/2 x 1 1.34 25/32 25/32 111/16
2 1/2 x 2 1/2 x 3/4 1.34 25/32 25/32 113/16
2 1/2 x 2 1/2 x 1/2 1.34 25/32 25/32 21/8
2 1/2 x 2 x 2 1/2 1.99 121/32 23/32 121/32
2 1/2 x 2 x 2 1.95 111/32 15/8 123/32
2 1/2 x 2 x 1 1/2 1.57 13/32 213/32 121/32
2 1/2 x 2 x 1 1/4 1.57 13/32 119/32 127/32
2 1/2 x 2 x 1 1.40 25/32 19/32 13/4
2 1/2 x 2 x 3/4 1.35 25/32 19/32 127/32
2 1/2 x 1 1/2 x 1 1/2 1.76 13/32 113/32 13/8
2 1/2 x 1 1/4 x 2 1/2 2.40 121/32 27/16 121/32
2 1/2 x 1 x 2 1/2 2.04 121/32 223/32 121/32
2 1/2 x 3/4 x 2 1/2 2.00 121/32 211/16 121/32
2 1/2 x 1/2 x 2 1/2 2.46 11/2 27/32 11/2
Continues…
APPROX. DIMENSIONS NET WT. INCHES NOM. SIZE LBS. C F G
3 3.15 17/8 17/8 21/32
3 x 3 x 2 1/2 3.55 129/32 129/32 23/8
3 x 3 x 2 3.19 115/32 115/32 131/32
3 x 3 x 1 1/2 3.08 115/32 115/32 29/32
3 x 3 x 1 1/4 3.10 115/32 115/32 27/16
3 x 3 x 1 2.12 27/32 27/32 131/32
3 x 3 x 3/4 2.39 27/32 27/32 23/16
3 x 3 x 1/2 1.82 27/32 27/32 23/8
3 x 2 1/2 x 3 3.08 17/8 23/8 131/32
3 x 2 1/2 x 2 1/2 3.12 129/32 211/32 25/32
3 x 2 1/2 x 2 2.28 115/32 127/32 131/32
3 x 2 x 3 3.62 129/32 217/32 115/16
3 x 2 x 2 1/2 3.56 129/32 29/16 25/16
3 x 2 x 2 3.22 115/32 131/32 131/32
3 x 1 1/2 x 3 3.13 129/32 225/32 23/32
3 x 1 1/4 x 3 3.63 129/32 225/32 115/16
3 x 1 x 3 3.20 131/32 219/32 23/16
3 x 3/4 x 3 3.55 131/32 229/32 23/16
3 1/2 5.20 217/32 217/32 217/32
4 8.12 213/32 213/32 217/32
4 x 4 x 3 6.70 21/32 21/32 221/32
4 x 4 x 2 1/2 6.65 21/32 21/32 35/32
4 x 4 x 2 5.82 115/32 115/32 27/16
4 x 4 x 1 1/2 3.94 111/32 111/32 217/32
4 x 4 x 1 1/4 4.04 111/32 111/32 229/32
4 x 4 x 1 3.72 1 1 29/16
4 x 4 x 3/4 3.70 1 1 211/16
4 x 3 x 4 7.05 225/32 37/32 217/32
4 x 3 x 3 5.03 21/32 215/32 215/32
4 x 3 x 2 1/2 5.04 21/32 215/32 229/32
4 x 3 x 2 5.87 115/32 131/32 27/16
4 x 2 1/2 x 4 7.19 225/32 315/32 227/32
4 x 2 x 4 7.08 225/32 319/32 227/32
Continued on next page.
NOTE: Tee sizes are read Run x Run x Outlet.
611
Tee C x C x C – Wrot continued
TEES continued
Consult price sheet for Made to Order items and
for minimum order quantities.
Revision 2/8/07
A H E A D O F T H E F L O W
®
www.nibco.com
NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227
TECH SERVICES PH: 1.888.446.4226 • FAX: 1.888.234.0557 • INTERNATIONAL OFFICE PH: +1.574.295.3327 • FAX: +1.574.295.3455
www.nibco.com
49
U.S. customary units in this document are the standard; the metric units are provided for
reference only. The values stated in each system are not exact equivalents.
Copper Water Tube continued
DIMENSIONAL DATA – COPPER WATER TUBE – TYPE “M”
TYPE “M” Hard Drawn Only: 20-ft. (6.1m) Straight Lengths
Usage: For general purpose plumbing, heating and
drainage installations.
Tolerances Hard Drawn
(Hard Drawn Only)
Outside Tubing OD Nominal Wall Weight Bursting Safe Working
Nominal Diameter Thickness Per Foot PressureA PressureB
Water Tube Min. Max.
Size (In Inches) Inch (mm) Inch (mm) Inch (mm) Inch (mm) Lb (kg) psi (bars) psi (bars)
1/4 0.375 (9.53) 0.373 (9.47) 0.376 (9.55) N/A N/A N/A N/A N/A N/A N/A N/A
3/8 0.500 (12.70) 0.497 (12.62) 0.501 (12.73) 0.025 (0.64) 0.145 (0.07) N/A N/A 855 (59)
1/2 0.625 (15.88) 0.622 (15.80) 0.626 (15.90) 0.028 (0.71) 0.204 (0.09) 6135 (423) 741 (51)
5/8 0.750 (19.05) 0.747 (18.97) 0.751 (19.08) N/A N/A N/A N/A N/A N/A N/A N/A
3/4 0.875 (22.23) 0.872 (22.15) 0.876 (22.25) 0.032 (0.81) 0.328 (0.15) 4717 (325) 611 (42)
1 1.125 (28.58) 1.122 (28.50) 1.127 (28.63) 0.035 (0.89) 0.465 (0.21) 3865 (266) 506 (35)
1 1/4 1.375 (34.93) 1.372 (34.85) 1.377 (34.98) 0.042 (1.07) 0.682 (0.31) 3875 (267) 507 (35)
1 1/2 1.625 (41.28) 1.621 (41.17) 1.627 (41.33) 0.049 (1.24) 0.940 (0.43) 3550 (245) 497 (34)
2 2.125 (53.98) 2.121 (53.87) 2.127 (54.03) 0.058 (1.47) 1.460 (0.66) 2935 (202) 448 (31)
2 1/2 2.625 (66.68) 2.621 (66.57) 2.627 (66.73) 0.065 (1.65) 2.030 (0.92) 2800 (193) 411 (28)
3 3.125 (79.38) 3.121 (79.27) 3.127 (79.43) 0.072 (1.83) 2.680 (1.22) 2665 (184) 380 (26)
3 1/2 3.625 (92.08) 3.621 (91.97) 3.627 (92.13) 0.083 (2.11) 3.580 (1.62) N/A N/A 378 (26)
4 4.125 (104.78) 4.121 (104.67) 4.127 (104.83) 0.095 (2.41) 4.660 (2.11) 2215 (153) 377 (26)
5 5.125 (130.18) 5.121 (130.07) 5.127 (130.23) 0.109 (2.77) 6.660 (3.02) 2490 (172) 349 (24)
6 6.125 (155.58) 6.121 (155.47) 6.127 (155.63) 0.122 (3.10) 8.920 (4.05) 2000 (138) 328 (23)
8 8.125 (206.38) 8.119 (206.22) 8.127 (206.43) 0.170 (4.32) 16.500 (7.48) 2285 (158) 344 (24)
10 10.125 (257.18) 10.119 (257.02) 10.127 (257.23) 0.212 (5.38) 25.600 (11.61) N/A N/A 344 (24)
12 12.125 (307.98) 12.119 (307.82) 12.127 (308.03) 0.254 (6.45) 36.700 (16.65) N/A N/A 345 (24)
Note: Information and data contained in these charts, as taken from ASTM Specifications B 88.
Rated internal pressure for copper water tube based on the strength of the tube alone and
applicable to systems using suitable mechanical joints.
A Based on actual laboratory test data provided by Copper Development Association, Inc.
B Based upon 150°F (65.6°C) with an allowable stress of 9500 psi (668 kPa).
Revision 5/12/02
A H E A D O F T H E F L O W
®
www.nibco.com
NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227
TECH SERVICES PH: 1.888.446.4226 • FAX: 1.888.234.0557 • INTERNATIONAL OFFICE PH: +1.574.295.3327 • FAX: +1.574.295.3455
www.nibco.com
62
1" TYPE “M” COPPER TUBE — WATER FLOW AND FRICTION LOSS PER 100 FEET
Maximum O.D. = 1.1265 inches (28.613 mm) Nominal O.D. = 1.1250 inches (28.575 mm)
Minimum O.D. = 1.1235 inches (28.537 mm) Nominal I.D. = 1.0558 inches (26.797 mm)
Nominal Wall Thickness = 0.0350 inches (0.889 mm) Flow Area = 0.8742 sq. inches (563.98 sq. mm)
Hazen Williams Formula C Factor = 150
FLOW, Q Pressure Loss Head Loss Velocity FLOW, Q Pressure Loss Head Loss Velocity
(GPM) (psi/100 ft) (ft/100 ft) (ft./sec.) (cu. cm/sec.) (kPa/100 m) (m/100 m) (m/sec.)
2.50 0.18 0.41 0.92 158 0.04 0.41 0.28
5.00 0.64 1.49 1.84 315 0.14 1.49 0.56
7.50 1.36 3.15 2.75 473 0.31 3.15 0.84
10.00 2.31 5.37 3.67 631 0.52 5.37 1.12
12.50 3.49 8.11 4.59 789 0.79 8.11 1.40
15.00 4.90 11.36 5.51 946 1.11 11.36 1.68
17.50 6.52 15.11 6.42 1104 1.47 15.11 1.96
20.00 8.34 19.35 7.34 1262 1.89 19.35 2.24
22.50 10.38 24.06 8.26 1419 2.35 24.06 2.52
25.00 12.61 29.24 9.18 1577 2.85 29.24 2.80
27.50 15.05 34.88 10.09 1735 3.40 34.88 3.08
30.00 17.68 40.97 11.01 1893 4.00 40.97 3.36
32.50 20.51 47.51 11.93 2050 4.64 47.51 3.64
35.00 23.52 54.49 12.85 2208 5.32 54.49 3.92
37.50 26.73 61.91 13.76 2366 6.05 61.91 4.19
40.00 30.12 69.76 14.68 2523 6.81 69.76 4.47
42.50 33.70 78.04 15.60 2681 7.62 78.04 4.75
45.00 37.47 86.74 16.52 2839 8.47 86.74 5.03
47.50 41.41 95.87 17.43 2997 9.37 95.87 5.31
50.00 45.54 105.41 18.35 3154 10.30 105.41 5.59
52.50 49.84 115.37 19.27 3312 11.28 115.37 5.87
55.00 54.33 125.74 20.19 3470 12.29 125.74 6.15
1 1/4" TYPE “K” COPPER TUBE — WATER FLOW AND FRICTION LOSS PER 100 FEET
Maximum O.D. = 1.3765 inches (34.963 mm) Nominal O.D. = 1.3750 inches (34.925 mm)
Minimum O.D. = 1.3735 inches (34.887 mm) Nominal I.D. = 1.2450 inches (31.623 mm)
Nominal Wall Thickness = 0.0650 inches (1.651 mm) Flow Area = 1.2174 sq. inches (785.41 sq. mm)
Hazen Williams Formula C Factor = 150
FLOW, Q Pressure Loss Head Loss Velocity FLOW, Q Pressure Loss Head Loss Velocity
(GPM) (psi/100 ft) (ft/100 ft) (ft./sec.) (cu. cm/sec.) (kPa/100 m) (m/100 m) (m/sec.)
5.00 0.29 0.67 1.32 315 0.06 0.67 0.40
10.00 1.03 2.40 2.64 631 0.23 2.40 0.80
15.00 2.19 5.08 3.95 946 0.49 5.08 1.20
20.00 3.73 8.65 5.27 1262 0.84 8.65 1.61
25.00 5.64 13.06 6.59 1577 1.27 13.06 2.01
30.00 7.90 18.30 7.91 1893 1.79 18.30 2.41
35.00 10.51 24.34 9.22 2208 2.38 24.34 2.81
40.00 13.46 31.17 10.54 2523 3.04 31.17 3.21
45.00 16.74 38.75 11.86 2839 3.79 38.75 3.61
50.00 20.35 47.09 13.18 3154 4.60 47.09 4.02
55.00 24.27 56.18 14.49 3470 5.49 56.18 4.42
60.00 28.52 65.99 15.81 3785 6.45 65.99 4.82
65.00 33.07 76.52 17.13 4101 7.48 76.52 5.22
70.00 37.94 87.76 18.45 4416 8.58 87.76 5.62
75.00 43.11 99.71 19.77 4732 9.75 99.71 6.02
80.00 48.58 112.35 21.08 5047 10.99 112.35 6.43
U.S. customary units in this document are the standard; the metric units are provided for
reference only. The values stated in each system are not exact equivalents.
Revision 5/12/02
A H E A D O F T H E F L O W
®
www.nibco.com
NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227
TECH SERVICES PH: 1.888.446.4226 • FAX: 1.888.234.0557 • INTERNATIONAL OFFICE PH: +1.574.295.3327 • FAX: +1.574.295.3455
www.nibco.com
63
1 1/4" TYPE “L” COPPER TUBE — WATER FLOW AND FRICTION LOSS PER 100 FEET
Maximum O.D. = 1.3765 inches (34.963 mm) Nominal O.D. = 1.375 inches (34.925 mm)
Minimum O.D. = 1.3735 inches (34.887 mm) Nominal I.D. = 1.265 inches (32.131 mm)
Nominal Wall Thickness = 0.0550 inches (1.397 mm) Flow Area = 1.2568 sq. inches (810.85 sq. mm)
Hazen Williams Formula C Factor = 150
FLOW, Q Pressure Loss Head Loss Velocity FLOW, Q Pressure Loss Head Loss Velocity
(GPM) (psi/100 ft) (ft/100 ft) (ft./sec.) (cu. cm/sec.) (kPa/100 m) (m/100 m) (m/sec.)
5.00 0.26 0.62 1.28 315 0.06 0.62 0.39
10.00 0.96 2.22 2.55 631 0.22 2.22 0.78
15.00 2.02 4.70 3.83 946 0.46 4.70 1.17
20.00 3.45 8.00 5.11 1262 0.78 8.00 1.56
25.00 5.22 12.09 6.38 1577 1.18 12.09 1.95
30.00 7.31 16.94 7.66 1893 1.65 16.94 2.33
35.00 9.73 22.53 8.93 2208 2.20 22.53 2.72
40.00 12.45 28.84 10.21 2523 2.82 28.84 3.11
45.00 15.49 35.86 11.49 2839 3.50 35.86 3.50
50.00 18.83 43.58 12.76 3154 4.26 43.58 3.89
55.00 22.46 51.98 14.04 3470 5.08 51.98 4.28
60.00 26.39 61.06 15.32 3785 5.97 61.06 4.67
65.00 30.61 70.81 16.59 4101 6.92 70.81 5.06
70.00 35.11 81.21 17.87 4416 7.94 81.21 5.45
75.00 39.89 92.27 19.15 4732 9.02 92.27 5.84
80.00 44.96 103.97 20.42 5047 10.17 103.97 6.22
1 1/4" TYPE “M” COPPER TUBE — WATER FLOW AND FRICTION LOSS PER 100 FEET
Maximum O.D. = 1.3765 inches (34.963 mm) Nominal O.D. = 1.3750 inches (34.925 mm)
Minimum O.D. = 1.3735 inches (34.887 mm) Nominal I.D. = 1.2910 inches (32.7914 mm)
Nominal Wall Thickness = 0.0420 inches (1.067 mm) Flow Area = 1.3090 sq. inches (844.52 sq. mm)
Hazen Williams Formula C Factor = 150
FLOW, Q Pressure Loss Head Loss Velocity FLOW, Q Pressure Loss Head Loss Velocity
(GPM) (psi/100 ft) (ft/100 ft) (ft./sec.) (cu. cm/sec.) (kPa/100 m) (m/100 m) (m/sec.)
5.00 0.24 0.56 1.23 315 0.05 0.56 0.37
10.00 0.87 2.01 2.45 631 0.20 2.01 0.75
15.00 1.83 4.26 3.68 946 0.41 4.26 1.12
20.00 3.12 7.25 4.90 1262 0.71 7.25 1.49
25.00 4.72 10.95 6.13 1577 1.07 10.95 1.87
30.00 6.62 15.34 7.35 1893 1.50 15.34 2.24
35.00 8.81 20.40 8.58 2208 1.99 20.40 2.61
40.00 11.28 26.12 9.80 2523 2.55 26.12 2.99
45.00 14.03 32.48 11.03 2839 3.17 32.48 3.36
50.00 17.05 39.47 12.25 3154 3.86 39.47 3.74
55.00 20.34 47.08 13.48 3470 4.60 47.08 4.11
60.00 23.90 55.31 14.71 3785 5.41 55.31 4.48
65.00 27.72 64.14 15.93 4101 6.27 64.14 4.86
70.00 31.80 73.56 17.16 4416 7.19 73.56 5.23
75.00 36.13 83.57 18.38 4732 8.17 83.57 5.60
80.00 40.72 94.17 19.61 5047 9.21 94.17 5.98
U.S. customary units in this document are the standard; the metric units are provided for
reference only. The values stated in each system are not exact equivalents.
Revision 5/12/02
A H E A D O F T H E F L O W
®
www.nibco.com
NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227
TECH SERVICES PH: 1.888.446.4226 • FAX: 1.888.234.0557 • INTERNATIONAL OFFICE PH: +1.574.295.3327 • FAX: +1.574.295.3455
www.nibco.com
65
1 1/2" TYPE “M” COPPER TUBE — WATER FLOW AND FRICTION LOSS PER 100 FEET
Maximum O.D. = 1.6270 inches (41.326 mm) Nominal O.D. = 1.6250 inches (41.275 mm)
Minimum O.D. = 1.6230 inches (41.224 mm) Nominal I.D. = 1.5270 inches (38.7858 mm)
Nominal Wall Thickness = 0.0490 inches (1.2446 mm) Flow Area = 1.8313 sq. inches (1181.50 sq. mm)
Hazen Williams Formula C Factor = 150
FLOW, Q Pressure Loss Head Loss Velocity FLOW, Q Pressure Loss Head Loss Velocity
(GPM) (psi/100 ft) (ft/100 ft) (ft./sec.) (cu. cm/sec.) (kPa/100 m) (m/100 m) (m/sec.)
5.00 0.11 0.25 0.88 315 0.02 0.25 0.27
10.00 0.38 0.89 1.75 631 0.09 0.89 0.53
15.00 0.81 1.88 2.63 946 0.18 1.88 0.80
20.00 1.38 3.20 3.50 1262 0.31 3.20 1.07
25.00 2.09 4.84 4.38 1577 0.47 4.84 1.33
30.00 2.93 6.78 5.26 1893 0.66 6.78 1.60
35.00 3.89 9.02 6.13 2208 0.88 9.02 1.87
40.00 4.98 11.54 7.01 2523 1.13 11.54 2.14
45.00 6.20 14.35 7.88 2839 1.40 14.35 2.40
50.00 7.53 17.44 8.76 3154 1.70 17.44 2.67
55.00 8.99 20.80 9.64 3470 2.03 20.80 2.94
60.00 10.56 24.44 10.51 3785 2.39 24.44 3.20
65.00 12.25 28.34 11.39 4101 2.77 28.34 3.47
70.00 14.05 32.50 12.26 4416 3.18 32.50 3.74
75.00 15.96 36.92 13.14 4732 3.61 36.92 4.00
80.00 17.99 41.61 14.02 5047 4.07 41.61 4.27
85.00 20.13 46.55 14.89 5362 4.55 46.55 4.54
90.00 22.38 51.74 15.77 5678 5.06 51.74 4.81
95.00 24.73 57.18 16.64 5993 5.59 57.18 5.07
100.00 27.20 62.87 17.52 6309 6.15 62.87 5.34
105.00 29.77 68.81 18.40 6624 6.73 68.81 5.61
110.00 32.45 74.99 19.27 6940 7.34 74.99 5.87
115.00 35.23 81.42 20.15 7255 7.97 81.42 6.14
2" TYPE “K” COPPER TUBE — WATER FLOW AND FRICTION LOSS PER 100 FEET
Maximum O.D. = 2.1270 inches (54.026 mm) Nominal O.D. = 2.1250 inches (53.975 mm)
Minimum O.D. = 2.1230 inches (53.924 mm) Nominal I.D. = 1.9590 inches (49.7586 mm)
Nominal Wall Thickness = 0.0830 inches (2.1082 mm) Flow Area = 3.0141 sq. inches (1944.58 sq. mm)
Hazen Williams Formula C Factor = 150
FLOW, Q Pressure Loss Head Loss Velocity FLOW, Q Pressure Loss Head Loss Velocity
(GPM) (psi/100 ft) (ft/100 ft) (ft./sec.) (cu. cm/sec.) (kPa/100 m) (m/100 m) (m/sec.)
10 0.11 0.26 1.06 631 0.03 0.26 0.32
20 0.41 0.95 2.13 1262 0.09 0.95 0.65
30 0.87 2.02 3.19 1893 0.20 2.02 0.97
40 1.48 3.43 4.26 2523 0.34 3.43 1.30
50 2.24 5.19 5.32 3154 0.51 5.19 1.62
60 3.14 7.27 6.39 3785 0.71 7.27 1.95
70 4.18 9.67 7.45 4416 0.95 9.67 2.27
80 5.35 12.38 8.52 5047 1.21 12.38 2.60
90 6.66 15.39 9.58 5678 1.51 15.39 2.92
100 8.09 18.71 10.64 6309 1.83 18.71 3.24
110 9.66 22.32 11.71 6940 2.18 22.32 3.57
120 11.34 26.21 12.77 7570 2.57 26.21 3.89
130 13.16 30.40 13.84 8201 2.98 30.40 4.22
140 15.09 34.86 14.90 8832 3.41 34.86 4.54
150 17.15 39.61 15.97 9463 3.88 39.61 4.87
160 19.33 44.63 17.03 10094 4.37 44.63 5.19
170 21.62 49.93 18.10 10725 4.89 49.93 5.52
180 24.04 55.50 19.16 11356 5.44 55.50 5.84
190 26.57 61.34 20.22 11986 6.01 61.34 6.16
200 29.22 67.44 21.29 12617 6.61 67.44 6.49
U.S. customary units in this document are the standard; the metric units are provided for
reference only. The values stated in each system are not exact equivalents.
Revision 5/12/02
A H E A D O F T H E F L O W
®
www.nibco.com
NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227
TECH SERVICES PH: 1.888.446.4226 • FAX: 1.888.234.0557 • INTERNATIONAL OFFICE PH: +1.574.295.3327 • FAX: +1.574.295.3455
www.nibco.com
66
2" TYPE “L” COPPER TUBE — WATER FLOW AND FRICTION LOSS PER 100 FEET
Maximum O.D. = 2.1270 inches (54.026 mm) Nominal O.D. = 2.1250 inches (53.975 mm)
Minimum O.D. = 2.1230 inches (53.924 mm) Nominal I.D. = 1.9850 inches (50.419 mm)
Nominal Wall Thickness = 0.0700 inches (1.778 mm) Flow Area = 3.0946 sq. inches (1996.54 sq. mm)
Hazen Williams Formula C Factor = 150
FLOW, Q Pressure Loss Head Loss Velocity FLOW, Q Pressure Loss Head Loss Velocity
(GPM) (psi/100 ft) (ft/100 ft) (ft./sec.) (cu. cm/sec.) (kPa/100 m) (m/100 m) (m/sec.)
10 0.11 0.25 1.04 631 0.02 0.25 0.32
20 0.39 0.89 2.07 1262 0.09 0.89 0.63
30 0.82 1.89 3.11 1893 0.18 1.89 0.95
40 1.39 3.22 4.15 2523 0.31 3.22 1.26
50 2.10 4.87 5.18 3154 0.48 4.87 1.58
60 2.95 6.82 6.22 3785 0.67 6.82 1.90
70 3.92 9.07 7.26 4416 0.89 9.07 2.21
80 5.02 11.61 8.29 5047 1.14 11.61 2.53
90 6.24 14.44 9.33 5678 1.41 14.44 2.84
100 7.59 17.55 10.37 6309 1.72 17.55 3.16
110 9.06 20.93 11.40 6940 2.05 20.93 3.48
120 10.64 24.58 12.44 7570 2.41 24.58 3.79
130 12.34 28.51 13.48 8201 2.79 28.51 4.11
140 14.15 32.70 14.51 8832 3.20 32.70 4.42
150 16.08 37.15 15.55 9463 3.64 37.15 4.74
160 18.13 41.86 16.59 10094 4.10 41.86 5.06
170 20.28 46.83 17.62 10725 4.59 46.83 5.37
180 22.54 52.05 18.66 11356 5.10 52.05 5.69
190 24.92 57.53 19.70 11986 5.64 57.53 6.00
200 27.40 63.25 20.73 12617 6.20 63.25 6.32
2" TYPE “M” COPPER TUBE — WATER FLOW AND FRICTION LOSS PER 100 FEET
Maximum O.D. = 2.1270 inches (54.026 mm) Nominal O.D. = 2.1250 inches (53.975 mm)
Minimum O.D. = 2.1230 inches (53.924 mm) Nominal I.D. = 2.0090 inches (51.0286 mm)
Nominal Wall Thickness = 0.0580 inches (1.4732 mm) Flow Area = 3.1699 sq. inches (2045.11 sq. mm)
Hazen Williams Formula C Factor = 150
FLOW, Q Pressure Loss Head Loss Velocity FLOW, Q Pressure Loss Head Loss Velocity
(GPM) (psi/100 ft) (ft/100 ft) (ft./sec.) (cu. cm/sec.) (kPa/100 m) (m/100 m) (m/sec.)
10 0.10 0.23 1.01 631 0.02 0.23 0.31
20 0.36 0.84 2.02 1262 0.08 0.84 0.62
30 0.77 1.78 3.04 1893 0.17 1.78 0.93
40 1.31 3.04 4.05 2523 0.30 3.04 1.23
50 1.98 4.59 5.06 3154 0.45 4.59 1.54
60 2.78 6.43 6.07 3785 0.63 6.43 1.85
70 3.70 8.55 7.08 4416 0.84 8.55 2.16
80 4.74 10.95 8.10 5047 1.07 10.95 2.47
90 5.89 13.62 9.11 5678 1.33 13.62 2.78
100 7.16 16.55 10.12 6309 1.62 16.55 3.08
110 8.54 19.74 11.13 6940 1.93 19.74 3.39
120 10.03 23.19 12.15 7570 2.27 23.19 3.70
130 11.64 26.89 13.16 8201 2.63 26.89 4.01
140 13.35 30.84 14.17 8832 3.02 30.84 4.32
150 15.17 35.04 15.18 9463 3.43 35.04 4.63
160 17.10 39.48 16.19 10094 3.87 39.48 4.94
170 19.13 44.17 17.21 10725 4.33 44.17 5.24
180 21.26 49.09 18.22 11356 4.81 49.09 5.55
190 23.50 54.26 19.23 11986 5.32 54.26 5.86
200 25.84 59.66 20.24 12617 5.85 59.66 6.17
U.S. customary units in this document are the standard; the metric units are provided for
reference only. The values stated in each system are not exact equivalents.
Revision 5/12/02
A H E A D O F T H E F L O W
®
www.nibco.com
NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227
TECH SERVICES PH: 1.888.446.4226 • FAX: 1.888.234.0557 • INTERNATIONAL OFFICE PH: +1.574.295.3327 • FAX: +1.574.295.3455
www.nibco.com
81
Copper Water Tube continued
COPPER TUBE – TYPES, STANDARDS, APPLICATIONS, TEMPERS AND LENGTHS
Commercially Available Lengths
Tube Type Color Code Standard Application Nominal or Standard Sizes Drawn Annealed
Type K Green ASTM B 88 Domestic Water Service Distribution Straight Lengths: 1/4-inch to 8-inch 20 ft. (6.1m) 20 ft. (6.1m)
Fire Protection 10-inch 18 ft. (5.5m) 18 ft. (5.5m)
Solar 12-inch 12 ft. (3.7m) 12 ft. (3.7m)
Fuel/Fuel Oil Coils: 1/4-inch to 1-inch – 60 ft. (18.3m)
HVAC – 100 ft. (30.5m)
Snow Melting 11/4-inch & 11/2-inch – 60 ft. (18.3m)
2-inch – 40 ft. (12.2m)
– 45 ft. (13.7m)
Type L Blue ASTM B 88 Domestic Water Service Distribution Straight Lengths: 1/4-inch to 10-inch 20 ft. (6.1m) 20 ft. (6.1m)
Fire Protection 12-inch 18 ft. (5.5m) 18 ft. (5.5m)
Solar
Fuel/Fuel Oil
Natural Gas Coils: 1/4-inch to 1-inch – 60 ft. (18.3m)
Liquified Petroleum (LP) Gas – 100 ft. (30.5m)
HVAC 11/4-inch & 11/2-inch – 60 ft. (18.3m)
Snow Melting 2-inch – 40 ft. (12.2m)
– 45 ft. (13.7m)
Type M Red ASTM B 88 Domestic Water Service Distribution Straight Lengths: 1/4-inch to 12-inch 20 ft. (6.1m) N/A
Fire Protection
Solar
Fuel/Fuel Oil
HVAC
Snow Melting
DWV Yellow ASTM B 306 Drain Straight Lengths: 11/4-inch to 8-inch 20 ft. (6.1m) N/A
Waste
Vent
HVAC
Solar
ACR Blue ASTM B 280 Air Conditioning Straight Lengths: 1/4-inch to 41/8-inch 20 ft. (6.1m) 20 ft. (6.1m)1
Refrigeration
Natural Gas Coils: 1/8-inch to 15/8-inch – 50 ft. (15.3m)1
Liquified Petroleum (LP) Gas
OXY Type K ASTM B 819 Medical Gas Straight Lengths: 1/4-inch to 8-inch 20 ft. (6.1m) N/A
MED Green
OXY/MED
OXY/ACR Type L
ACR/MED Blue
Type G Yellow ASTM B 837 Natural Gas Straight Lengths: 3/8-inch to 11/8-inch 12 ft. (3.7m) 12 ft. (3.7m)1
Liquified Petroleum (LP) Gas 20 ft. (6.1m) 20 ft. (6.1m)1
Coils: 3/8-inch to 7/8-inch – 60 ft. (18.3m)1
– 100 ft. (30.5m)1
1 Available as special order only.
U.S. customary units in this document are the standard; the metric units are provided for
reference only. The values stated in each system are not exact equivalents.
Revision 5/12/02
Main Office/Manufacturing Facility •1375 Sampson Ave. •Corona, CA 92879 •Ph: 909.737.5599 •Fax: 909.737.0330
Customer Service •800.786.5266
www.tolco.com
36
wwwwww..ttoollccoo..ccoomm
Revision 5/24/2001
™
®a brand of
Dimensions • Weights
Data Table for Fig. 20S
Pipe Hole Max. Rec. Approx.
Sizes A BCDSize Load Lbs. Wt./100
1/2 4
1/8 5/16 2
7/8 3/4 7/16 410 21
3/4 4
5/16 7/16 3 15/16 7/16 410 24
149/16 9/16 3
3/8 11/8 7/16 410 26
11/4 415/16 11/16 3
3/4 11/2 7/16 410 30
11/2 53/16 13/16 4
1/4 15/8 7/16 410 33
253/4 11/16 43/4 21/4 7/16 410 38
21/2 61/4 19/16 51/4 23/4 7/16 610 102
367/8 15/8 57/8 33/8 7/16 610 118
31/2 73/8 17/8 63/8 37/8 7/16 610 130
483/8 21/8 743/8 9/16 725 159
597/16 25/8 77/8 53/8 9/16 725 191
6101/2 33/16 87/8 67/16 9/16 725 234
81441/4 111/2 83/8 11/16 900 446
Size Range — 1/2" thru 8" pipe
Material — Carbon Steel
Function — Recommended for supporting pipe
with fittings vertically or horizontally to walls or
ceiling. Fig. 20S will support pipe flush with
mounting surface.
Approvals — Conforms to Federal Specification
WW-H-171E, Type 26 and Manufacturers
Standardization Society SP-69, Type 26.
Finish — Plain
Note — Available in Electro-Galvanized and HDG
finish or Stainless Steel materials.
Order By — Figure number, pipe size, material
and finish
Size Range — 1/2" thru 2" pipe
Material — Carbon Steel
Function — Light duty strap that attaches pipe or copper
tubing to horizontal or vertical structure.
Finish — Pre-Galvanized
Note — Available with felt lining, order TOLCO™ Fig. 21F.
Order By — Figure number and pipe size
Fig. 20 - Standard Pipe Strap
Fig. 20S - Flush Mount Pipe Strap
Fig. 21 - “Tin Strap”
Dimensions • Weights
Data Table for Fig. 20
Pipe Hole Max. Rec. Approx.
Sizes A BCDSize Load Lbs. Wt./100
1/2 3
7/8 3/4 3
1/16 15/32 7/16 410 16
3/4 4 13/16 3
1/8 15/16 7/16 410 21
149/16 7/8 3
3/8 11/2 7/16 410 26
11/4 415/16 133/4 17/8 7/16 410 30
11/2 53/16 13/16 41/4 21/8 7/16 410 33
253/4 17/16 43/4 25/8 7/16 410 38
21/2 61/4 111/16 51/4 31/8 7/16 610 102
367/8 257/8 33/4 7/16 610 118
31/2 73/8 21/4 63/8 41/4 7/16 610 130
483/8 21/2 743/4 9/16 725 159
597/16 31/16 77/8 513/16 9/16 725 191
6101/2 35/8 87/8 67/8 9/16 725 234
81445/8 111/2 9 11/16 900 446
Main Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92870 • Ph: 909.737.5599 • Fax: 909.737.0330
Distribution Center • 8790 Fruitridge Road • Sacramento, CA 95826 • Ph: 916.388.7800 • Fax: 916.388.1401
Manufacturing Facility • 4851 Homestead Road, Bldg. 118 • Houston, TX 77028 • Ph: 713.672.0058 • Fax: 713.672.0074
www.tolco.com
31
Fig. 200
“Trimline” Adjustable Band Hanger
Size Range – 1/2 thru 8 inch pipe.
Material – Carbon Steel, Mil. Galvanized to G-90
specifications.
Function – For fire sprinkler and other general piping
purposes. Knurled swivel nut design permits hanger
adjustment after installation.
Features
· (1/2 thru 2 inch) Flared edges ease installation for all
pipe types and protect CPVC plastic pipe from
abrasion. Captured design keeps adjusting nut from
separating with hanger. Hanger is easily installed
around pipe.
· (2-1/2 thru 8 inch) Spring tension on nut holds it
securely in hanger before installation. Adjusting nut is
easily removed.
Approvals – Underwriters' Laboratories Listed (1/2”
thru 8”) in the U.S. (UL) and Canada (cUL) for steel
and CPVC plastic pipe and Factory Mutual
Engineering Approved (3/4” thru 8”). Conforms to
Federal Specifications WW-H-171E, Type 10, and
Manufacturers Standardization Society SP-69, type 10.
Maximum Temperature - 650°F.
Finish – Mil. Galvanized, for Stainless Steel materials
order TOLCO™ Fig. 200WON.
Order By – Figure number and pipe size.
Pipe Size Rod Size
Inch Metric* B Max. Rec.
Load bs.
Approx.
Wt./100
1/2 3/8 8mm or 10mm 3-1/8 2-5/8 400 11
3/4 3/8 8mm or 10mm 3-1/8 2-1/2 400 11
1 3/8 8mm or 10mm 3-3/8 2-5/8 400 12
1-1/4 3/8 8mm or 10mm 3-3/4 2-7/8 400 13
1-1/2 3/8 8mm or 10mm 3-7/8 2-7/8 400 14
2 3/8 8mm or 10mm 4-1/2 3 400 15
2-1/2 3/8 10mm 5-5/8 4-1/8 600 27
3 3/8 10mm 5-7/8 4 600 29
3-1/2 3/8 10mm 7-3/8 5-1/4 600 34
4 3/8 10mm 7-3/8 5 1000 35
5 1/2 12mm 9-1/8 6-1/4 1250 66
6 1/2 12mm 10-1/8 6-3/4 1250 73
8 1/2 12mm 13-1/8 8-3/4 1250 136
*Order Fig. 200M
Revision 5/24/2001
5 To find a distributor near you, call 800-BUILDEX
Not less than 2” nominal width (1-1/2”) up to 3-1/2” pipe; not less than 3” (2-1/2”) nominal width 4” & 5” pipe
Minimum 2-1/2” from bottom for branch lines. Minimum 3” from bottom for main lines. Exception: This requirement shall not apply to 2” or thicker nailing strips resting on top of steel beams.
Floor Joist
HORIZONTAL MOUNT
WOOD WOOD WOOD WOOD WOODSIDEWINDERS® for Wood Installs HORIZONTALLY into the side of wood structures easily and quickly!
Approvals Rod Size Part Number Model Screw Descriptions Ultimate Pullout (lbs)UL Test Load (lbs)Box Qty Case Qty
1/4"8018957 SWG 100 1/4 x 1"622 (Fir)25 125
1/4"8019957 SWG 200 1/4 x 2"1725 (Fir)25 125
3/8"8020957 SWG 10 1/4 x 1"622 (Fir)300 25 125
3/8"8021957 SWG 20 1/4 x 2"1725 (Fir)1050 25 125
3/8"8073925 SWG 20-SS 1/4 x 2"1725 (Fir)850 25 125
3/8"8022925 SWG 25-380 3/8 x 2-1/2"2249 (Fir)1500 25 125
3/8"8023925 SWG 30 1/4 x 3"1884 (Fir)25 125#14 SW Red Nut Driver Part # 8114910
SPECIAL NUT DRIVER SYSTEM: The nut drivers were designed with a unique spin-off feature which provides a fast and safe installation each time. When the face of the driver comes into contact with the material you are installing into, continue drilling until nut driver spins free. Installation is then complete. Warranty requires the use of the appropriate nut driver for installations.
INSTALLATION STEPS - VERTICAL INTO WOOD & STEEL: 1. Insert the appropriate nut driver into a 3/8” or 1/2” portable drill.
2. Insert the SAMMYS into the #14 (black) nut driver (p/n 8113910). Drill should be in a vertical position.
3. Push the face of the nut driver tight to the member. When the nut driver spins freely on the SAMMYS, stop drill and remove.
4. The SAMMYS is now ready to receive 1/4”, 3/8”, 1/2” or metric
all thread rod, bolt stock. (The 1/2” requires the #14SW red nut driver)
Note: When installing DSTR, follow the above instructions,
then add retainer nut and torque to 20 foot lbs. for maximumpullout in purlin steel.
INSTALLATION STEPS - HORIZONTAL INTO WOOD & STEEL: 1. Insert the appropriate nut driver into a 3/8” or 1/2” portable drill.
2. Insert the SAMMYS into the #14SW (red) nut driver (p/n 8114910). With drill unit in a horizontal position and at a right angle to the structural member, begin installation.
3. When the nut driver spins free on the SAMMYS, stop the drill and remove.
4. The unit is now ready to receive 1/4”, 3/8” or metric all thread rod or bolt stock.
Note: When installing SWDR, follow the above instructions, then add retainer nut and torque to 20 foot lbs. for maximum pullout in purlin steel.
Composite/TrussConsult truss manufacturer for recommended installation point.
*Pre-drilling may be required for Model SWG 25-380 (tools available on pg 10 )
Product Features
• No pre-drilling required.
• Quick to install using the Sammy Nut Driver with an 18V cordless drill/driver.
• Saves time from traditional methods.
• Reduces installation cost.
• Made in the U.S.A.
Installs VERTICALLY and swivels up to 17° in wood structure
Main Office/Manufacturing Facility •1375 Sampson Ave. •Corona, CA 92879 •Ph: 909.737.5599 •Fax: 909.737.0330
Customer Service •800.786.5266
www.tolco.com
68
wwwwww..ttoollccoo..ccoomm
Revision 5/24/2001
™
®a brand of
Fig. 98 - Rod Stiffener
Size Range — Secures 3/8" thru 7/8" hanger rod
Material — Carbon Steel
Function — Secures channel to hanger rod for vertical seismic bracing.
Finish — Electro Galvanized
Note — Available in HDG finish or Stainless Steel materials.
Order By — Figure number
Fig. 99 - All Thread Rod Cut to Length
Size Range — Secures 3/8" thru 7/8" rod in
1" increments
Material — Carbon Steel
Maximum Temperature — 750°F
Finish — Plain
Note — Available in Electro-Galvanized and
HDG finish or Stainless Steel materials.
Order By — Figure number, rod diameter, rod
length and finish
Fig. 100 - All Thread Rod Full Lengths
Size Range — Secures 3/8" thru 7/8" rod in
10’ lengths
Material — Carbon Steel
Maximum Temperature — 750°F
Finish — Plain
Note — Available in Electro-Galvanized and
HDG finish or Stainless Steel materials.
Order By — Figure number, rod diameter
and finish
Dimensions • Weights
Rod Max. Rec. Load Lbs.
Size For Service Temps
650°F 750°F
3/8 610 540
1/2 1130 1010
5/8 1810 1610
3/4 2710 2420
7/8 3770 3360
Dimensions • Weights
Max Rec. Load Lbs.
Rod For Service Temps Approx.
Size 650°F 750°F Wt./100
1/4 240 215 12
3/8 610 540 29
1/2 1130 1010 53
5/8 1810 1610 84
3/4 2710 2420 123
7/8 3770 3360 169
1 4960 4420 222
11/4 8000 7140 360
11/2 11630 10370 510
Series 4000B Reduced Pressure Zone Assemblies are designed to protect
drinking water supplies from dangerous cross-connections in accordance
with national plumbing codes and water authority requirements for health-
hazard non-potable service applications such as irrigation, fire line, or indus-
trial processing.
This series features two in-line, independent check valves, cap tured springs
and replaceable check seats with an in ter me di ate relief valve. Its compact
modular de sign facilitates easy main te nance and as sem bly ac cess. Sizes
1⁄2"- 1" (15-25mm) shutoffs have tee handles.
Specifications
A Reduced Pressure Zone Assembly shall be in stalled at each potential
health hazard location to pre vent back flow due to backsiphonage and/or
back pres sure. The as sem bly shall con sist of an in ter nal pres sure differential
relief valve lo cat ed in a zone be tween two pos i tive seating check mod ules
with cap tured springs and silicone seat discs. Seats and seat discs shall
be re place able in both check modules and the re lief valve. There shall be
no threads or screws in the wa ter way ex posed to line fluids. Ser vice of all
in ter nal com po nents shall be through a sin gle ac cess cover se cured with
stain less steel bolts. The as sem bly shall also in clude two re sil ient seat ed iso-
la tion valves, four re sil ient seat ed test cocks and an air gap drain fitting. The
as sem bly shall meet the re quire ments of: USC Man u al 8th Edition†; ASSE
Std. 1013; AWWA Std. C511; CSA B64.4. The assembly shall be an Ames
Com pa ny Series 4000B.
ES-A-4000B
2" (50mm) 4000B-HC
Series 4000B
Reduced Pressure Zone Assemblies
Sizes: 1⁄2" – 2" (15 – 50mm)
Job Name ________________________________________________Contractor ______________________________________________
Job Location ______________________________________________Approval _______________________________________________
Engineer _________________________________________________Contractor’s P.O. No. ______________________________________
Approval _________________________________________________Representative ___________________________________________
Ames product specifications in U.S. customary units and metric are ap prox i mate and are pro vid ed for ref er ence only. For precise mea sure ments, please contact Ames Technical Ser vice. Ames re serves the right to change or modify prod uct de sign, con struc tion, spec i fi ca tions, or ma te ri als with out prior notice and without in cur ring any ob li ga tion to make such chang es and mod i fi ca tions on Ames products previously or sub se quent ly sold.amesfirewater.com
Features
• Single access cover and
modular check construction
for ease of maintenance
• Top entry - all internals
im me di ate ly accessible
• Captured springs for safe
maintenance
• Internal relief valve for reduced
installation clearances
• Replaceable seats for
economical repair
• Bronze body construction for
durability - 1⁄2" to 2" (15-50mm)
• Ball valve test cocks -
screw driv er slotted -1⁄2" to 2"
(15-50mm)
• Large body passages provides
low pressure drop
• Compact, space saving design
• No special tools required for
servicing
1/2" (15mm) 4000B
NOTICE
The information contained herein is not
intended to replace the full product instal-
lation and safety information available or
the experience of a trained product install-
er. You are required to thoroughly read all
installation instructions and product safety
information before beginning the installa-
tion of this product.
2
Pressure — Temperature
Suitable for supply pressures up to 175psi (12.06 bar)
and water temperature to 180°F (75°C) continuous.
Available Models
Suffix:
B - quarter-turn ball valves
LBV - less ball valves
SH - stainless steel ball valve handles
HC - 21⁄2" inlet/outlet fire hydrant fitting (2" valve)
S - bronze strainer
Prefix:
U - union connections
Model Size (dN) diMeNSioNS StraiNer diMeNSioNS WeigHt
A B C D L M N
in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm lbs. kg.
4000B** 1⁄2 15 10 250 45⁄8 117 33⁄8 86 11⁄4 32 51⁄2 140 3 76 2 51 4.50 2.0
4000B M3** 3⁄4 20 103⁄4 273 5 127 31⁄2 89 11⁄2 38 63⁄4 171 35⁄16 84 25⁄16 59 5.75 2.6
4000B M2** 1 25 141⁄2 368 51⁄2 140 3 76 21⁄2 64 91⁄2 241 41⁄2 114 25⁄16 59 12.25 5.6
4000B** 11⁄4 32 173⁄8 441 6 150 31⁄2 89 21⁄2 64 113⁄8 289 51⁄8 130 31⁄8 79 14.62 6.6
4000B** 11⁄2 40 177⁄8 454 6 150 31⁄2 89 21⁄2 64 111⁄8 283 57⁄8 149 33⁄4 95 16.32 7.4
4000B** 2 50 213⁄8 543 73⁄4 197 41⁄2 114 31⁄4 83 131⁄2 343 63⁄16 157 47⁄8 124 30.00 13.6
**Approved by the Foundation for Cross-Connection Control and Hydraulic Research at the University of Southern Cal i for nia.
Suffix HC - Fire Hydrant Fittings dimension "A" = 251⁄16 (637mm)
M
C
B
N
l
Weights — Dimensions
Strainer sold separately
Materials
Bronze body construction, silicone rubber disc ma te ri al in the
first and sec ond check plus the re lief valve. Re place able poly-
mer check seats for first and sec ond checks. Re mov able stain-
less steel re lief valve seat. Stain less steel cover bolts.
Standardly furnished with NPT body connections. For op tion al
bronze union inlet and outlet connections, spec i fy pre fix U
(1⁄2" - 2")(15-50mm). Series 4000B furnished with quar ter turn,
full port, re sil ient seated, bronze ball valve shutoffs.
Standards
AWWA C511-92, USC Manual 8th Edition, IAPMO File No.
1563
Approvals
Approved by the Foundation for Cross-Connection Con trol
and Hydraulic Research at the University of South ern
Cal i for nia.
Approval models QT, U.
1013 B64.4 3⁄4" - 2" (20-50mm)
(lBV models only)
d
a
NOTICE
Inquire with governing authorities for local installation requirements
It is illegal to use this product in any plumbing system providing water for human consumption, such as drinking or dishwashing, in the United States. Before installing standard material product, consult your local water authority, building and plumbing codes.
WARNING!
3
Capacity
Performance as established by an independent testing laboratory.
∆Typical maximum system flow rate (7.5 feet/sec., 2.3 meters/sec.)
1⁄4" (8mm) kPa psi
138 20
117 17
96 14
76 11
55 8
35 5 0 .25 .50 .75 1 1.17 gpm0 .95 1.9 2.9 3.8 4.5 lpm
3⁄8" (10mm)
0 .25 .50 .75 1 1.25 1.50 2.5 3.1 gpm0 .95 1.9 2.9 3.8 4.8 5.7 9.5 11.8 lpm
1⁄2" (15mm)
3⁄4" (20mm)
1" (25mm)
11⁄4" (32mm)
11⁄2" (40mm)
2" (50mm)
kPa psi
138 20
117 17
96 14
76 11
55 8
35 5
kPa psi
172 25
138 20
103 15
69 10
35 5
0 1 2.5 5 7.5 10 12.5 15 gpm 0 3.8 9.5 19 28.5 38 47.5 57 lpm 5 7.5 15 fps 1.5 2.3 4.6 mps
∆P
∆P
∆P
kPa psi 207 30
165 24
124 18
83 12
41 6
0 0
0 2 6 10 14 18 22 26 30 34 38 42 46 gpm 0 7.6 23 38 53 68 84 99 114 129 144 160 175 lpm 7.5 15 fps 2.3 4.6 mps
∆P
kPa psi
207 30
172 25
138 20
103 15
69 10
34 5
0 0 0 5 10 20 30 40 50 60 70 80 gpm 0 19 38 76 114 152 190 228 266 304 lpm
7.5 15 fps 2.3 4.6 mps
kPa psi
172 25
138 20
103 15
69 10
34 5
0 0
0 10 20 30 40 50 60 70 80 gpm 0 38 76 114 152 190 228 266 304 lpm
5 7.5 10 15 fps 1.5 2.3 3.0 4.6 mps
∆P
∆P
kPa psi 207 30
172 25
138 20
103 15
69 10
34 5
0 0
∆P 0 10 20 30 40 50 60 70 80 90 100 110 120 gpm 0 38 76 114 152 190 228 266 304 342 380 418 456 lpm 5 7.5 10 15 fps 1.5 2.3 3.0 4.6 mps
kPa psi
207 30
172 25
138 20
103 15
69 10
34 5
0 0∆P 0 20 40 60 80 100 120 140 160 180 200 gpm 0 76 152 228 304 380 456 532 608 684 760 lpm 5 7.5 10 15 fps 1.5 2.3 3.0 4.6 mps
∆
∆
∆
∆
∆∆
Flow Rate
Flow Rate
Flow Rate
Flow Rate
Flow Rate
Flow Rate
Flow Rate
Flow RatePressure LossPressure LossPressure LossPressure LossPressure LossPressure LossPressure LossPressure Loss
PRINTED IN USA MKT. #8800003 - REV X
MFG. #5400802 - 12/01
VSR-SF
VANE TYPE WATERFLOW
ALARM SWITCH WITH RETARD
FOR SMALL PIPE
PAGE 1 OF 2
UL, ULC, CSFM Listed and NYMEA Accepted, CE Marked
Service Pressure: Up to 250 PSI (17,2 BAR)
Minimum Flow Rate for Alarm: 8-10 GPM (30-38 Lpm)
Maximum Surge: 18 FPS (10 m/s)
Enclosure:Die-cast, red enamel finish
Cover held in place with tamper resistant screws
Contact Ratings:Two sets of SPDT (Form C)
15.0 Amps at 125/250 VAC
2.0 Amps at 30 VDC
Conduit Entrances: Two knockouts provided for 1/2" conduit.
Usage:Listed plastic, copper and schedule 40 iron pipe.
Fits pipe sizes - 1" (25mm), 1 1/4" (32mm), 1 1/2"
(38mm) and 2" (50mm)
Note: 12 paddles are furnished with each unit, one for
each pipe size of threaded and sweat TEE, one for 1"
(25mm) CPVC, one for 1" (25mm) CPVC (Central),
one for 1 1/2" (38mm) polybutylene and one for 1 1/2"
(38mm) threaded (Japan).
(CTS-Copper tubing size)
Environmental Specifications:
• Suitable for indoor or outdoor use with factory installed
gasket and die-cast housing.
• NEMA 4/IP55 rated enclosure - use with appropriate conduit
fitting.
• Temperature range: 40° F to 120° F, 4,5° C to 49° C)
Caution:This device is not intended for applications in
explosive environments.
Service Use:
Automatic Sprinkler NFPA-13
One or two family dwelling NFPA-13D
Residential occupancy up to four stories NFPA-13R
National Fire Alarm Code NFPA-72
Optional: Cover Tamper Switch Kit, Stock No. 0090018
Stock No. 1113000
U.S. Pat. No. 3921989, Canadian Pat. No. 1009680
Other Patents Pending
The Model VSR-SF is a vane type waterflow switch for use on wet
sprinkler systems that use 1" (25mm), 1 1/4" (32mm), 1 1/2"
(38mm) or 2" (50mm) pipe size. The unit may also be used as
a sectional waterflow detector on large systems.
The unit contains two single pole double throw snap action
switches and an adjustable, instantly recycling pneumatic re-
tard. The switches are actuated when a flow of 8-10 gallons per
minute (30-38 Lpm) or more occurs downstream of the device.
The flow condition must exist for a period of time necessary to
overcome the selected retard period.
INSTALLATION: These devices may be mounted in horizontal
or vertical pipe. On horizontal pipe they should be installed on
the top side of the pipe where they will be accessible. The units
should not be installed within 6" (15cm) of a valve, drain or fitting
which changes the direction of the waterflow. The unit has a 1"
NPT bushing for threading into a non-corrosive TEE. See Fig.
2 for proper TEE size, type and installation.
Screw the device into the TEE fitting as shown in Fig. 2. Care
must be taken to properly orient the device for the direction of
waterflow.
The vane must not rub the inside of the TEE or bind in any way.
The stem should move freely when operated by hand.
The device can also be used in copper or plastic pipe installa-
tions with the proper adapters so that the specified TEE fitting
may be installed on the pipe run.
INSPECTION AND TESTING: Check the operation of the unit by
opening the inspector’s test valve at the end of the sprinkler line
or the drain and test connection, if an inspector’s test valve is not
provided.
If there are no provisions for testing the operation of the flow
detection device on the system, application of the VSR-SF is not
recommended or advisable
The frequency of the inspection and testing and its associated
protective monitoring system should be in accordance with the
applicable NFPA Codes and Standards and/or authority having
jurisdiction (manufacturer recommends quarterly or more fre-
quently).
Potter Electric Signal Company • 2081 Craig Road, St. Louis, MO, 63146-4161 • Phone: 800-325-3936/Canada 888-882-1833 • www.pottersignal.com
PRINTED IN USA MKT. #8800003 - REV X
MFG. #5400802 - 12/01
VSR-SF
VANE TYPE WATERFLOW
ALARM SWITCH WITH RETARD
FOR SMALL PIPE
PAGE 2 OF 2
CAUTION:
An uninsulated section of a single conductor should not be looped around
the terminal and serve as two separate connections. The wire must be
severed, thereby providing supervision of the connection in the event that
the wire becomes dislodged from under the terminal.
FIG. 1
Important:
There are 12 paddles fur-
nished with each unit. One for
each size of threaded, sweat or
plastic TEE as described in
Fig. 2. These paddles have
raised lettering that shows the
pipe size and type of TEE that
they are to be used with. The
proper paddle must be used.
The paddle must be properly
attached (see drawing) and
the screw that holds the pad-
dle must be securely tight-
ened.
FIG. 2
NOTES:
1. The model VSR-SF has two
switches, one can be used to
operate a central station,
proprietary or remote signal-
ing unit, while the other is
used to operate a local au-
dible or visual annunciator.
2. For supervised circuits see
“Switch Terminal Connec-
tions” drawing and caution
note (Fig. 3).
FIG. 4 TYPICAL ELECTRICAL CONNECTIONS
Retard Adjustment:
To change time, turn knob
(either direction) for desired
time delay. Use the minimum
amount of retard necessary to
prevent false alarms. A “B”
setting is usually adequate for
this. Factory set at “B”.
FIG. 3
SWITCH TERMINAL CONNECTIONS CLAMPING PLATE TERMINAL
FIG. 5
To remove knockouts: Place
screwdriver at edge of knock-
outs, not in the center.
APPLICATION WARNING!
Due to the possibility of unintended discharges caused by pressure surges, trapped air, or short retard times, waterflow switches
that are monitoring wet pipe sprinkler systems should not be used as the sole initiating device to discharge AFFF, deluge, or
chemical suppression systems.
Screw the device into the tee fitting as shown. Care must be taken to
properly orient the device for the direction of waterflow. On sweat tees, no
threaded bushings, inserts, or adapters are permitted, unless they comply
with the dimensions listed in the chart below.
Important - The depth to the inside bottom of the tee should have the
following dimensions:
PRINTED IN USA
RBVS
UNIVERSAL BALL
VALVE SWITCH
PAGE 1 OF 2MFG.# 5401086 - REV U
5/08
US Patent No. 6,945,509
General
The Model RBVS is designed to monitor the fully open position of a ball valve
installed in a sprinkler system. The unit will fi t on most ball valves installed on
back-fl ow-preventers and alarm trim lines of dry, alarm, and deluge sprinkler
valves. The switch operates if the ball valve handle is moved from the open
position. However, the switch does not track the position of the handle or ball.
When the ball valve handle is in the open position, a spring-loaded switch button
will contact the valve handle. When the handle is moved from the open position,
this switch button extends to the tripped position, and the RBVS contacts change
state, thereby opening or closing a circuit. A cover tamper switch is available and
is activated by the removal of the RBVS housing cover. If an attempt is made
to remove the RBVS by the removal of the mounting brackets, the unit will be
set into the tripped mode by this action.
The RBVS can be mounted to the hex portion of the ball valve or back-fl ow-
preventer or to the adjoining pipe via two clamps. The RBVS is shipped with two
sets of mounting clamps to accommodate various pipe and valve sizes, refer to
Table 1. An "L" shaped and offset bracket for mounting the switch enclosure and
an extension bracket add to the mounting fl exibility of the RBVS. See "Typical
Mounting Diagram" and "Installation and Operation" on following page.
Testing
The RBVS and its associated protective monitoring system should be tested
in accordance with applicable NFPA codes and standards and/or the authority
having jurisdiction (manufacturer recommends quarterly or more frequently).
UL and cUL Listed, FM, CSFM Approved
Dimensions: (including mounting clamps)
Large Clamps: 6" L x 5" W x 5.2" H
15,2 cm L x 12,7 cm W x 13,2 cm H
Small Clamps: 6" L x 4" W x 5.2" H
15,2 cm L x 10,2 cm W x 13,2 cm H
Weight: With Large Clamps: 13.6 oz. (386,9 g.)
With Small Clamps: 11.0 oz. (311,2 g.)
Enclosure: Non-Corrosive Composite Material
Environmental Limitations:
• NEMA 4 rated enclosure when proper electrical
fi ttings are used. (IP67)
• Temperature range: -40°F to 150°F (-40°C to 65°C)
• Not for use in hazardous locations
Housing Cover Tamper: Activated by housing cover removal
(Stock No. 1000035 only)
Contact Ratings:
SPDT Contacts: 10A at 125/250 VAC
2A at 30 VDC
SPDT Cover Tamper: 3A at 250 VAC
Fig.1 Internal Components
Potter Electric Signal Company, LLC • 2081 Craig Road, St. Louis, MO, 63146-4161 • Phone: 800-325-3936/Canada 888-882-1833 • www.pottersignal.com
RBVS Stock No. 1000040 (w/o Cover Tamper)
RBVS-T Stock No. 1000035 (w/Cover Tamper)
Installation On Lever Handle (See Fig. 2)
1. Select clamps and clamping bolts based upon pipe/valve size, see Table 1.
2. Insert rubber clamp grippers into clamps, see Fig. 2.
3. Place one clamp on top of pipe/ball valve near the valve handle and
insert clamping bolts through it.
4. Place other clamp over clamping bolts from beneath the installation and
thread hex nuts onto the clamping bolts, but do not fully tighten, (be sure
hex nuts seat properly in clamp hex recesses). (NOTE: Some installations
may require one of the mounting bolts to be inserted from the bottom of
the brackets and then trimmed to allow the extension bracket to clear.
See Fig. 4)
5. Attach extension bracket (if necessary to use for positioning) to top clamp
using ¼-20 X ¾" Hex bolt and washer, but do not fully tighten.
6. Attach "L" bracket (RBVS switch enclosure is loosely attached to "L"
bracket) to extension bracket using ¼-20 X ¾" Hex bolt and washer, but
do not fully tighten.
7. Be sure ball valve is in the fully open position.
8. Slide loosely assembled RBVS switch enclosure to a position that permits
the switch button to contact the valve handle approximately 1" from its
inside end. See Fig. 1 for approximate location. Cut and remove the plastic
coating from the ball valve handle to allow the RBVS switch button to
contact (and be activated by) the metal of the handle.
9. Tighten clamping screws alternately to an eventual 30 in-lbs. (minimum)
of torque.
10. Maintain position of switch enclosure over valve handle and secure bolt
that holds the extension bracket to the clamping assembly. It may be
necessary to close valve to access this bolt.
11. Position "L" bracket so that it contacts the back edge of the valve handle, and
secure its bolt. It may be necessary to close valve to access this bolt.
12. With the actuator fully retracted, position RBVS switch enclosure to
contact the valve handle squarely, see Fig. 1.
13. With RBVS switch enclosure held squarely in contact with valve handle,
securely tighten the two tamper resistant screws on the backside of the
enclosure.
14. Close and open the valve to verify operation. The actuator should easily
retract when the valve handle is in the open position.
15. Fully open the valve.
16. Remove the cover and wire main switch and tamper switch if applicable.
Carefully route tamper switch wires through strain relief channel in switch
enclosure. Fully seat the wires into the bottom of the channel. See Fig. 1.17. Replace RBVS switch enclosure cover and securely tighten cover screw.
PRINTED IN USA
RBVS
UNIVERSAL BALL
VALVE SWITCH
MFG.# 5401086 - REV U
5/08
PAGE 2 OF 2
OUTG
O
I
N
G
INCO
M
I
N
G
DWG# 923-3
Installation on Tee Handle (See Fig. 3)1. Select clamps and clamping bolts based upon pipe/valve size, see Table 1.
2. Insert rubber clamp grippers into clamps, See Fig. 3.3. Place one clamp on top of pipe/ball valve near the valve handle and
insert clamping bolts through it.4. Place other clamp over clamping bolts from beneath the installation
and thread hex nuts onto the clamping bolts, but do not fully tighten, (be sure hex nuts seat properly in clamp hex recesses).
5. Loosely attach "L" bracket to the "offset" bracket and "offset" bracket to the RBVS housing.
6. Be sure ball valve is in the fully open position.7. Slide loosely assembled RBVS switch enclosure to a position that
permits the switch button to contact the valve handle approximately 1/2" from the end of the handle. Cut and remove the plastic coating
from the ball valve handle to allow the RBVS switch button to contact (and be activated by) the metal of the handle.
8. Tighten clamping screws alternately and ¼-20 X ¾" bolt to 30 in-lbs. (minimum) of torque.
9. With the valve handle fully open, slide the RBVS housing down until the switch operates plus 1/8 inch. Tighten the screws holding
the RBVS to the "offset" bracket.10. Remove the RBVS switch enclosure cover.
11. Close and open the valve to verify operation. The actuator should easily retract up when the valve handle is in the open position.
12. Fully open the valve.13. Wire main switch and tamper switch (if applicable). Carefully route
tamper switch wires through strain relief channel in switch enclosure. Fully seat the wires into the bottom of the channel. See Fig. 1.
14. Replace RBVS switch enclosure cover and securely tighten cover screw.
Fig. 3
Typical Electrical Connections
Fig. 2 Typical Mounting Diagram
Tamper Switch Connections
Switch Terminal Connections, Clamping Plate Terminal
Table 1 Clamp Sizing
Fig. 4
SOME INSTALLATIONS MAY
CAUSE INTERFERENCE
BETWEEN MOUNTING BOLT AND
OFFSET BRACKET. INSTALL BOLT
FROM BOTTOM AND TRIM AS
NEEDED TO CORRECT.
RBVS
PIPE
DWG# 1086-6
Pipe Valve/Size Clamp Clamping Bolts
1/2" to 3/4" (12,5 to 19mm) Small 10-32 x 2 1/2
1" to 2" (25 to 50mm) Large 1/4-20 x 4"
An uninsulated section of single conductor
should not be looped around the terminal
and serve as two seperate connections. The
wire must be severed, thereby providing
supervision of the connection in the event
that the wire becomes dislodged from
under the terminal.
MFG. #5400930 - REV D
1/08
PRINTED IN USA PAGE 1 OF 3
PS40 SERIES
PRESSURE SWITCH
Installation
The Potter PS40 Series Pressure Actuated Switches are designed primarily to
detect an increase and/or decrease from normal system pressure in automatic
fi re sprinkler systems. Typical applications are: Dry pipe system, pre-action
air/nitrogen supervision, pressure tanks, air supplies, and water supplies.
The PS40 switch is factory set for 40 PSI (2,8 BAR) normal system pressure.
The switch marked with the word LOW is set to operate at a pressure decrease
of 10 PSI (,7 BAR) at 30 PSI (2,1 BAR). The switch marked with the word
HIGH is set to operate at a pressure increase of 10 PSI (,7 BAR) at 50 PSI
(3,5 BAR). See section heading Adjustments and Testing if other than
factory set point is required.
1. Connect the PS40 to the system side of any shutoff or check valve.
2. Apply Tefl on tape to the threaded male connection on the device.
(Do not use pipe dope)
3. Device should be mounted in the upright position.
(Threaded connection down)
4. Tighten the device using a wrench on the fl ats on the device.
Wiring Instructions
1. Remove the tamper resistant screw with the special key provided.
2. Carefully place a screwdriver on the edge of the knockout and sharply
apply a force suffi cient to dislodge the knockout plug. See Fig. 9
3. Run wires through an approved conduit connector and affi x the
connector to the device. A NEMA-4 rated conduit fi tting is
required for outdoor use.
(UL, cUL, and CSFM Listed, FM and LPC Approved, NYMEA Accepted, CE Marked Pending)
Dimensions: 3.78" (9,6cm)W x 3.20" (8,1cm)D x 4.22" (10,7cm)H
Conduit Entrance: Two knockouts provided for 1/2" conduit. Individual
switch compartments and ground screw suitable for
dissimilar voltages
Enclosure: Cover- Die-cast with textured red powdercoat fi nish, single
cover screw and rain lip.
Base- Die-cast
Pressure Connection: Nylon 1/2" NPT male
Factory Adjustment: PS40-1 operates on decrease at 30 PSI (2,1 BAR)
PS40-2 operates in increase at 50 PSI (3,5 BAR)
and on decrease at 30 PSI (2,1 BAR)
Pressure Range: 10-60 PSI (,7 - 4,1 BAR)
Differential: Typical 1 lb. at 10 PSI (,07 at ,7 BAR) 4 lbs at 60 PSI (,28 at 4,1 BAR)
Maximum System Pressure: 300 PSI (20,68 BAR)
Switch Contacts: SPDT (Form C)
10.1 Amps at 125/250VAC, 2.0 Amps at 30VDC
One SPDT in PS40-1, Two SPDT in PS40-2
Environmental Specifi cations:
NEMA 4/IP55 Rated Enclosure - indoor or outdoor when used
with NEMA 4 conduit fi ttings.
Temperature range: -40°F to 140°F (-40°C to 60°C)
Tamper: Cover incorporates tamper resistant fastener that requires a
special key for removal. One key is supplied with each device.
For optional cover tamper switch kit, order Stock No. 0090200.
See bulletin #5401200 PSCTSK.
Service Use:
Automatic Sprinkler NFPA-13
One or two family dwelling NFPA-13D
Residential Occupancy up to four stories NFPA-13R
National Fire Alarm Code NFPA-72
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 866-956-0988/Canada 888-882-1833 • www.pottersignal.com
Ordering Information
Model Description Stock No.
PS40-1 Pressure switch with one set SPDT contacts 1340403
PS40-2 Pressure switch with two sets SPDT contacts 1340404
Hex Key 5250062
Cover Tamper Switch Kit 0090200
BVL Bleeder valve 1000018
4. Connect the wires to the appropriate terminal connections for the
service intended. See Figures 2,4,5,6, and 8
Adjustment And Testing
The operation of the pressure supervisory switch should be tested upon
completion of installation and periodically thereafter in accordance with
the applicable NFPA codes and standards and/or the authority having
jurisdiction (manufacturer recommends quarterly or more frequently).
Note: Testing the PS40 may activate other system connected devices.
The use of a Potter BVL (see product bulletin 8900067 for details) is
recommended to facilitate setting and testing of the PS40 pressure switch.
When a BVL (bleeder valve) is used, the pressure to the switch can be
isolated and bled from the exhaust port on the BVL without effecting the
supervisory pressure of the entire system. See Fig. 3
The operation point of the PS40 Pressure Switch can be adjusted to any
point between 10 and 60 PSI (0,7 - 4,11 BAR) by turning the adjustment
knob(s) clockwise to raise the actuation point and counter clockwise to
lower the actuation point. In the case of the PS40-2, both switches operate
independent of each other. Each switch may be independently adjusted to
actuate at any point acrosss the switch adjustment range. Initial adjustment
can be made with a visual reference from the top of the adjustment knob
across to the printed scale on the switch bracket. Final adjustments should
be verifi ed with a pressure gauge.
MFG. #5400930 - REV D
1/08
PRINTED IN USA PAGE 2 OF 3
PS40 SERIES
PRESSURE SWITCH
Typical Sprinkler Applications
Switch Clamping Plate TerminalDimensions
OUTG
OI
N
G INCOM
I
N
G
DWG# 923-3
Fig. 1 Fig. 2
Fig. 3
GONG
MOTOR
WATER
TEST
BY-PASS
WATER
VALVE
OS & Y
VALVE
ALARM
PRESSURE
SWITCH
PS10
CHECK
VALVE
VALVE
CHECK
BVL
VALVE
TEST
BLEEDER
AIR LINE
SHUT-OFF
VALVE
PS40
DWG. #924-1A
RBVS
DRY PIPE
VALVE
Typical Connections
Fig. 4
An uninsulated section of a single conductor
should not be looped around the terminal and
serve as two separate connections. The wire
must be severed, thereby providing supervision
of the connection in the event that the wire
becomes dislodged from under the terminal.
Closing of any shutoff valves between the
alarm check valve and the PS10 will render
the PS10 inoperative. To comply with NFPA-
72 any such valve shall be electrically
supervised with a supervisory switch such as
Potter Model RBVS.
NOTE: To prevent leakage, apply Teflon tape sealant to male threads only.
2.87
[72.97]
4.22
[107.19]
2.48
[62.87]
3.78
[95.89]
3.20
[81.28]
1.60
[40.64]
GROUND
SCREWS
DWG# 930-1
1/2" NPT
ADJUSTMENT
KNOB
COM 1 2
EOLRTO FIRE
ALARM
PANEL
TO FIRE
ALARM
PANEL
COM12
21COM
HIGH
AIR
LOW
AIR
PS40-1 PS40-2WITH NORMAL SYSTEM PRES-
SURE APPLIED LOW -TERMINAL 2
CLOSES ON PRESSURE DROP.
WITH NORMAL SYSTEM
PRESSURE APPLIED HIGH
- TERMINAL 1 WILL CLOSE
ON PRESSURE INCREASE.
EOLR
DWG# 930-2
MFG. #5400930 - REV D
1/08
PRINTED IN USA PAGE 3 OF 3
PS40 SERIES
PRESSURE SWITCH
DWG# 928-4
Break out thin section of divider to provide path for wires
when wiring both switches from one conduit entrance.
One Conduit Wiring
Fig. 6
Fig. 8
DWG#928-5
Fig. 9
Removing Knockouts
NC
NC
NO
NO
C
C
C 12
C 12
LOW PRESSURE SWITCH
HIGH PRESSURE SWITCH
DWG# 930-3
Changing Pressure
Low Pressure Signal Connection
EOLR
TO FIRE ALARM PANEL
DWG# 928-1
EOLR
TO FIRE ALARM PANEL
DWG# 928-2
High Pressure Signal Connection
Fig. 5 Fig. 7
(With normal system pressure)
Engineer/Architect Specifi cations Pressure Type Waterfl ow Switch
Pressure type supervisory switches; shall be a Model PS40 as manufactured by
Potter Electric Signal Company, St. Louis, MO., and shall be installed on the fi re
sprinkler system as shown and or specifi ed herein.
Switches shall be provided with a 1/2" NPT male pressure connection to be
connected into the air supply line on the system side of any shut-off valve. A
Model BVL bleeder valve as supplied by Potter Electric Signal Company of St.
Louis, MO., or equivalent shall be connected in line with the PS40 to provide a
means of testing the operation of the supervisory switch. (See Fig. 3)
The switch unit shall contain SPDT (Form C) switch(es). One switch shall be
set to operate at a pressure decrease of 10 PSI (0,7 BAR) from normal. If two
switches are provided, the second switch shall be set to operate at a pressure
increase of 10 PSI (0,7 BAR) from normal.
Switch contacts shall be rated at 10.1 Amps at 125/250VAC and 2.0 Amps at
30VDC. The units shall have a maximum pressure rating of 300 PSI (20,68 BAR)
and shall be adjustable from 10 to 60 PSI (0,7 to 4,1 BAR).
Pressure switches shall have two conduit entrances, one for each individual switch
compartment to facilitate the use of dissimilar voltages for each individual switch.
The cover of the pressure switch shall be zinc die-cast with rain lip and shall attach
with one tamper resistant screw. The pressure switch shall be suitable for indoor or
outdoor service with a NEMA-4/IP55 rating.
The pressure switch shall be UL, ULC, and CSFM listed, FM and LPC approved
and NYMEA accepted.
•Installation must be performed by qualifi ed personnel and in accordance with all
national and local codes and ordinances.
•Shock hazard. Disconnect power source before servicing. Serious injury or death
could result.
•Read all instructions carefully and understand them before starting installation.
Save instructions for future use. Failure to read and understand instructions could
result in improper operation of device resulting in serious injury or death.
•Risk of explosion. Not for use is hazardous locations. Serious injury or death could result.
•Do not tighten by grasping the switch enclosure. Use wrenching fl ats on the bushing
only. Failure to install properly could damage the switch and cause improper operation
resulting in damage to equipment and property.
•To seal threads, apply Tefl on tape to male threads only. Using joint compounds or
cement can obstruct the pressure port inlet and result in improper device operation and
damage to equipment.
•Do not over tighten the device, standard piping practices apply.
Terminal
C: Common1: Closed when installed
under normal system pressure.
2: Open when installed under normal system
pressure. Closes on pressure drop. Use for
low air signal.
Terminal
1: Open when installed
under normal system
pressure. Closes on
increase in pressure.
Use for high air signal.
2: Closed under normal
system pressure.
Model 1011A
TESTa n DRaIn®
Di m e n s i o n s
Orifice Size Available: 3⁄8", 7⁄16", 1⁄2", 17⁄32", ELO (5⁄8")*, ESFR (3⁄4")*, & K25**
SIZE A B C D E F G H
¾"79⁄16"(191 mm)11⁄2"(37.5 mm)23⁄16"(57 mm)35⁄8"(93 mm)33⁄8"(86 mm)113⁄16"(46 mm)49⁄16"(117 mm)63⁄8"(162.5 mm)
1"79⁄16"
(191 mm)
11⁄2"
(37.5 mm)
23⁄16"
(57 mm)
35⁄8"
(93 mm)
33⁄8"
(86 mm)
113⁄16"
(46 mm)
49⁄16"
(117 mm)
63⁄8"
(162.5 mm)
11⁄4"715⁄16"
(201 mm)
111⁄16"
(43 mm)
29⁄16"
(65 mm)
41⁄4"
(108 mm)
35⁄8"
(91 mm)
115⁄16"
(51 mm)
59⁄16"
(141 mm)
51⁄2"
(192 mm)
1½"815⁄16"
(227 mm)
113⁄16"
(45 mm)
31⁄4"
(81.5 mm)
51⁄16"
(127 mm)
37⁄8"
(99 mm)
25⁄8"
(67 mm)
81⁄4"
(207 mm)
107⁄8"
(274 mm)
2"815⁄16"
(227 mm)
113⁄16"
(45 mm)
31⁄4"
(81.5 mm)
51⁄16"
(127 mm)
37⁄8"
(99 mm)
25⁄8"
(67 mm)
81⁄4"
(207 mm)
107⁄8"
(274 mm)
* Available on 11⁄4" to 2" size units only ** Available on 11⁄2" and 2" size units only
TO DRAIN
TO
DRAIN
H
F
G
E A
A
INLET
D
B
C
Ap p r o v A l s
UL and ULC Listed: (EX4019
& EX4533)
FM Approved
NYC-BSA No. 720-87-SM
Job Name:__________________________________
Architect: ___________________________________
Engineer: ___________________________________
Contractor: _________________________________
USA Patent # 4741361 and Other Patents Pending
mA t e r i A l s
Handle: Steel
Stem: Rod Brass
Ball: C.P. Brass
Body: Bronze
Valve Seat: Impregnated Teflon®
Indicator Plate: Steel
Relief Valve: Bronze
Bypass Fittings: Brass
Bypass Tubing: Nylobraid
mo D e l 1011A - Fr o n t vi e w
mo D e l 1011A - pl A n vi e w
AGF Manufacturing Inc.
100 Quaker Lane, Malvern, PA 19355
Phone: 610-240-4900
Fax: 610-240-4906
www.testandrain.com
Model 1011A 300 PSI Bronze Ball Valve, Model 7000 Pressure Relief Valve
Factory Rated at 175 PSI with other settings available
th e mo D e l 1011A p r o v i D e s A l l o F t h e F o l l o w i n g …
From the 2007 Edition of NFPA 13
Chapter 8.16.2.4.1* Provisions shall be made to properly drain all parts of the system.
Chapter 8.16.2.4.2 Drain connections, interior sectional or floor control valve(s) –
shall be provided with a drain connection having a minimum size
as shown in Table 8.16.2.4.2.
Chapter 8.16.2.4.4 Drains shall discharge outside or to a drain capable of handling
the flow of the drain.
Chapter A.8.17.4.2 (Wet Pipe System) test connection is permitted to terminate into
a drain capable of accepting full flow… using an approved sight
test connection containing a smooth bore corrosion-resistant
orifice giving a flow equivalent to one sprinkler…
Chapter 8.17.4.2.2 The test connection valve shall be readily accessible.
Chapter 8.17.4.2.4 shall be permitted to be installed in any location… downstream
of the waterflow alarm.
Chapter 8.17.4.3.1 (Dry Pipe System) a trip test connection not less than 1" in
diameter, terminating in a smooth bore corrosion-resistant orifice,
to provide a flow equivalent to one sprinkler…
Chapter 8.17.4.3.2 The trip test connection… with a shutoff valve and plug not less
than 1", at least one of which shall be brass.
Chapter 7.1.2 - a gridded wet pipe system shall be provided with a relief valve
set to operate at 175 PSI or 10 PSI in excess of the maximum
system pressure, whichever is greater.
Chapter 8.16.1.2.3* A relief valve of not less than ½" in size shall be provided on the
discharge side of the pressure-reducing valve set to operate at a
pressure not exceeding 175 PSI.
Chapter A.8.16.1.2.3 - consideration should be given to piping the discharge from the
(pressure relief) valve
& 8.16.2.4.3
Specifications · Material List
Size 1 in
C - Height Closed 4.38 in
B - Diameter 2.75 in
A - Length 1.47 in
Ship Weight 1.76 lb
Quantity Unit Pack 6
Quantity per Case 36
Valve Type Angle Valve
Pressure Class
125 psi
200 WOG
125 WSP
Specifications
Item # Model 126SUL - 1", Model 126SUL Angle Valve
Soft Disc
UL Listed for Fire Sprinkler Service at 250 WOG
200 WOG at 180 ° Max
100% Pressure Tested
Threaded Ends
Rising Stem
Integral Seat
*Contains lead. Not for use in water systems intended for human consumption*
larger image larger image
United Brass Works, Inc.
714 South Main Street
Randleman, NC 27317 USA
Phone: 336-498-2661
Fax: 336-498-4267
Toll-free: 800-334-3035
Email: sales@ubw.com
Website: http://www.ubw.com
All Categories > Fire Protection Valves & Products > Fire Protection Products - Angle Valves > Model 126SUL Angle
Valve > Item # Model 126SUL - 1"
United Brass Works, Inc. - Item # Model 126SUL - 1", Model 126SUL ... http://ubw.thomasnet.com/printitem/fire-protection-products-angle-valve...
1 of 2 10/29/2011 2:59 PM
End Connection Threaded
Application
Gas
Oil
Water
Stem Type Rising
Bonnet Type Screwed
UL Listed Yes
FM Approved No
MEA Approved No
MSS Compliant No
Canadian Registration No
Pressing Machine Part No
Material List
United Brass Works, Inc. - Item # Model 126SUL - 1", Model 126SUL ... http://ubw.thomasnet.com/printitem/fire-protection-products-angle-valve...
2 of 2 10/29/2011 2:59 PM
Specifications · Material List
Size 1 in
A - Total Length 2.97 in
C - Height Closed 4.25 in
B - Diameter 2.75 in
Ship Weight 1.76 lb
Quantity Unit Pack 6
Quantity per Case 36
Valve Type Globe Valve
Pressure Class
125 psi
200 WOG
125 WSP
Specifications
Item # Model 125SUL - 1", Model 125SUL Globe Valve
Soft Disc
UL Listed for Fire Sprinkler Service at 250 WOG
200 WOG at 180 ° Max
100% Pressure Tested
Threaded Ends
Integral Seat
Rising Stem
Swivel Disc Holder
*Contains lead. Not for use in water systems intended for human consumption*
larger image larger image
United Brass Works, Inc.
714 South Main Street
Randleman, NC 27317 USA
Phone: 336-498-2661
Fax: 336-498-4267
Toll-free: 800-334-3035
Email: sales@ubw.com
Website: http://www.ubw.com
All Categories > Fire Protection Valves & Products > Fire Protection Products - Globe Valves > Model 125SUL Globe
Valve > Item # Model 125SUL - 1"
United Brass Works, Inc. - Item # Model 125SUL - 1", Model 125SUL ... http://ubw.thomasnet.com/printitem/fire-protection-products-globe-valv...
1 of 2 10/29/2011 3:01 PM
End Connection Threaded
Application
Gas
Oil
Water
Stem Type Rising
Bonnet Type Screwed
UL Listed Yes
FM Approved No
MEA Approved No
MSS Compliant No
Canadian Registration No
Pressing Machine Part No
Material List
United Brass Works, Inc. - Item # Model 125SUL - 1", Model 125SUL ... http://ubw.thomasnet.com/printitem/fire-protection-products-globe-valv...
2 of 2 10/29/2011 3:01 PM
Specifications · Material List
Size 1-1/4 in
A 3.45 in
B 2.20 in
Ship Weight 1.81 lb
Quantity per Carton 6
Quantity per Case 18
Valve Type Check Valve
Pressure Class 200 WOG
End Connection Threaded
Application
Gas
Oil
Water
UL Listed No
FM Approved No
MEA Approved No
MSS Compliant No
Specifications
Item # Model 99S 11/4", Model 99S Swing Check Valve
larger image larger image
United Brass Works, Inc.
714 South Main Street
Randleman, NC 27317 USA
Phone: 336-498-2661
Fax: 336-498-4267
Toll-free: 800-334-3035
Email: sales@ubw.com
Website: http://www.ubw.com
All Categories > Fire Protection Valves & Products > Fire Protection Products - Swing Check Valves > Model 99S Swing
Check Valve > Item # Model 99S 11/4"
United Brass Works, Inc. - Item # Model 99S 11/4", Model 99S Swing C... http://ubw.thomasnet.com/printitem/fire-protection-products-swing-chec...
1 of 2 10/29/2011 3:02 PM
Canadian Registration No
Material List
United Brass Works, Inc. - Item # Model 99S 11/4", Model 99S Swing C... http://ubw.thomasnet.com/printitem/fire-protection-products-swing-chec...
2 of 2 10/29/2011 3:02 PM
FIRE DEPT. INLET CONN. FLUSH TYPE
6341-6345 SERIES
SINGLE INLET
An inlet connection with 250 G.P.M. minimum inlet capacity
to supplement the fire protection water supply. Provides
unobstructed water supply. Flush round design enhances
appearance and provides unobstructed passage.
STANDARD EQUIPMENT:Cast Brass round plate with double
female adapter; plug and chain; branding as selected.
SPECIFY THREAD AND BRANDING.
BRANDING:"Standpipe", "Auto Spkr."
FINISH:Cast Brass
OPTIONAL FINISH:PB-Polished Brass
PC-Polished Chrome
RESIDENTIAL FIRE DEPT. CONNECTION
An inlet connection to supplement the water supply to a
residential sprinkler system.
STANDARD EQUIPMENT:1 1/2" cast brass round plate
assembly with integral pin lug swivel inlet. Hose thread inlet
swivel, 1 1/2" NPT female outlet on back of plate. Cast brass
plug and brass chain. Overall outside Diameter 4 3/8".
SPECIFY THREAD AND BRANDING.
U/L LISTED.
BRANDING:"Auto Spkr."
FINISH:Cast Brass
OPTIONAL FINISH:PB-Polished Brass
PC-Polished Chrome
Figure No. 6341 Figure No. 6342
Figure No. 6345
Page 6-12
Round Plate
Figure No. Size
6341 21/2X21/2
6342 3X21/2
6343 3X3
___________________________________________________
Submittal data sheets can ONLY be ordered as a "Submittal Data Sheet Pack", using MC# 4400. They are not available to order on an indi-
vidual basis, however each data sheet is available on the Amtrol Web Site and can be downloaded and printed for use as needed.
Rev. 03/06 18
FIRE-X-TROL®
FPT Series, Fire Protection Expansion Tanks (ASME)
B
A FPT-5-C
FPT-12-C
CHARGING
VALVE
SYSTEM CONNECTION
MODELS:
B
A
FPT-20V-C
-30V-C
-42V-C
-60V-C
CHARGING
VALVE
c
-70V-C
FPT
FPT
FPT
FPT
SYSTEM CONNECTION
MODELS:
In-Line Models
Model Tank A B Sys. Ship
No. Vol. Height Diameter Conn. Wt.
Lit. Gal. mm ins. mm ins. ins. kg lbs.
FPT-5-C 15 2.1 264 10
3⁄8 254 10
3⁄4 NPTF 9.5 21
FPT-12-C 24 6.4 397 15
5⁄8 305 12
3⁄4 NPTF 15.4 36
Maximum Operating Conditions
Operating Temperature -20°F (-29°C) to 200°F (93°C)
Working Pressure 175 PSIG (12 bar)
Specifications
Description Standard Construction
Standard Factory Pre-charge 25 PSIG (1.7 bar)
System Connection Stainless Steel
Diaphragm Material High-Performance Rubber Compound
Liner Material Polypropylene
Shell Steel
Coating FPT Red
Fluid Compatibility With or Without Antifreeze Per NFPA 13
Stand Models
Model Tank A B C Sys. Ship
No. Vol. Height Diameter Dim. Conn. Wt.
Lit. Gal. mm ins. mm ins. mm ins. ins. kg lbs.
FPT-20V-C 30 8.0 495 19
1⁄2 305 12 273 10
3⁄4 3⁄4 NPTF 23.6 52
FPT-30V-C 53 14.0 486 19
1⁄8 419 16
1⁄4 324 12
3⁄4 3⁄4 NPTF 44 97
FPT-42V-C 66 17.5 616 24
1⁄4 419 16
1⁄4 324 12
3⁄4 3⁄4 NPTF 52.7 116
FPT-60V-C 95 25.0 838 33 419 16
1⁄4 324 12
3⁄4 3⁄4 NPTF 70 154
FPT-70V-C 129 34.0 1054 41
1⁄2 419 16
1⁄4 324 12
3⁄4 3⁄4 NPTF 90 197
FPT-80V-C 200 53.0 908 35
3⁄4 610 24 406 16 1
1⁄4 NPTF 114 251
FPT-120V-C 250 66.0 1111 43
3⁄4 610 24 406 16 1
1⁄4 NPTF 127.6 281
FPT-180V-C 292 77.0 1235 48
5⁄8 610 24 406 16 1
1⁄4 NPTF 160.3 353
FPT-210V-C 341 90.0 1410 55
1⁄2 610 24 406 16 1
1⁄4 NPTF 173.4 382
Job Name___________________________________________
Location ____________________________________________
____________________________________________
____________________________________________
Engineer ____________________________________________
Contractor __________________________________________
Contractor P.O. No.___________________________________
Sales Representative _________________________________
Model No. Ordered ___________________________________
Constructed per ASME Code Section VIII, Division 1.
All dimensions and weights are approximate.
175 PSIG Working Pressure
2
GOULDS PUMPSCommercial Water
A Full Range of Product Features
Una Gama Total de Características del Producto
Superior Materials of
Construction: Complete AISI
316L stainless steel liquid handling
components and mounting bracket
for corrosion resistance, quality
appearance, and improved strength
and ductility.
High Efficiency Impeller:
Enclosed impeller with unique
floating seal ring design maintains
maximum efficiencies over the life
of the pump without adjustment.
Casing and Adapter Features:
Stainless steel construction with
NPT threaded, centerline connec-
tions, easily accessible vent, prime
and drain connections with stain-
less steel plugs. Optional seal face
vent/flush available.
Mechanical Seal: Standard
John Crane Type 21 with carbon
versus silicon-carbide faces, Viton
elastomers, and 316 stainless metal
parts. Optional high temperature
and chemical duty seals available.
Motors: NEMA standard open
drip-proof, totally enclosed fan
cooled or explosion proof enclo-
sures. Rugged ball bearing design
for continuous duty under all
operating conditions.
Materiales Superiores de
Construcción: Componentes
completos para manejo de líqui-
dos en acero inoxidable AISI 316L
y consola para el montaje para
resistencia a la corrosión,
apariencia de calidad, y fuerza y
ductilidad mejoradas.
Impulsor de Eficiencia Supe-
rior: El impulsor encerrado con
un diseño único de anillo del sello
flotante, mantiene sin ajustes, la
eficiencia máxima sobre la vida
de la bomba.
Características de la
Carcasa y del Adaptador:
Construcción en acero inoxidable
con NPT roscado, conexiones
centrales, válvulas de fácil acceso,
conexiones de cebado y drenaje
con enchufes de acero inoxid-
able. Cara del sello válvula/chorro
opcional disponible.
Sello Mecánico: Estándar John
Crane Tipo 21 con carbón en con-
traste con caras de silicón-carbide,
elastómeros de Viton, y partes
metálicas de acero inoxidable
316. Sellos de alta temperatura
y productos químicos están dis-
ponibles.
Motores: Estándar NEMA a
prueba de goteo, ventilador
totalmente encerrado o recintos
a prueba de explosión. Diseño
robusto de balineras de bolas
para trabajo continuo en todas las
condiciones de funcionamiento.
Las diferentes versiones de la NPE
se identifican con un número de
código del producto en la etiqueta
de la bomba. Este número es
también el número del catálogo
para la bomba. El significado
de cada dígito en el número de
código del producto se muestra a
la izquierda.
The various versions of the NPE are
identified by a product code number
on the pump label. This number
is also the catalog number for the
pump. The meaning of each digit in
the product code number is shown
at left.
Example Product Code, Ejemplo Código del Producto
NPE Product Line Numbering System
Línea de Producto NPE Sistema de Numeración
1 ST 2 C 1 A 4 F
Seal Vent/Flush Option,Opción de Sello Válvula/ChorroSeal Ven
Mechanical Seal and O-ring
4 = Pre-engineered standard
For optional mechanical seal modify catalog order no.
with seal code listed below.
Sello Mecánico y Anillo ‘O’
4 = Estándar aprobado
Para sello mecánico opcional modificar el número de orden
del catálogo con el código del sello anotado abajo.
Impeller Option . . . No Adder Required
For optional impeller diameters modify catalog order no.
with impeller code listed. Select optional impeller diameter from
pump performance curve.
Código del Impulsor Opcional
Para impulsores con diámetros opcionales modificar el número de
orden del catálogo con el código del impulsor anotado. Escoger el im-
pul con diámetro opcional de la curva de funcionamiento de la bomba.
Driver, Conductor
1 = 1 PH, ODP 7 = 3 PH, XP
2 = 3 PH, ODP 8 = 575 V, XP
3 = 575 V, ODP 9 = 3 PH, TEFC
4 = 1 PH, TEFC Premium Eff.
5 = 3 PH, TEFC 0 = 1 PH, XP
6 = 575 V, TEFC
HP Rating, HP Potencia
C = ½ HP E = 1 HP G = 2 HP J = 5 HP
D = ¾ HP F = 1½ HP H = 3 HP
Driver: Hertz/Pole/RPM,Conductor: Hercios/Polo/RPM
1 = 60 Hz, 2 pole, 3500 RPM
2 = 60 Hz, 4 pole, 1750 RPM
3 = 60 Hz, 6 pole, 1150 RPM
4 = 50 Hz, 2 pole, 2900 RPM
5 = 50 Hz, 4 pole, 1450 RPM
Material
ST = Stainless steel, Acero inoxidable
Pump Size, Tamaño de la Bomba
1 = 1 x 1¼ – 6 2 = 1¼ x 1½ – 6 3 = 1½ x 2 – 6
Pump Size, Tamaño de la Bomba
1 x 1¼ – 6 1¼ x 1½ – 6 1½ x 2 – 6
Diameter Diameter Diameter
K – 61⁄8 –
G – 515⁄16 53⁄8
H – 5½ 5
A 61⁄8 5¼ 4¾
B 5¾ 51⁄16 45⁄8
C 53⁄16 47⁄8 43⁄8
D 4¾ 45⁄8 41⁄16
E 47⁄16 4¼ 35⁄8
F 41⁄16 37⁄8 –
Impeller Code,Código del Impulsor
John Crane Type 21 Mechanical Seal (5⁄8” seal),
Sello Mecánico John Crane Tipo 21 (sello de 5⁄8”)
Seal
Code,
Código
del
Sello
2 Carbon EPR 10K18
4 Viton 316 SS 10K55
5 EPR 10K81
6 Viton 10K62SiliconCarbide
Silicon
Carbide
Metal Part
Rotary, Stationary, Elastomers, Parts, No.,
Rotativo Estacionario Elastómeros Partes Pieza
Metálicas Número
For frame mounted version, substitute the letters “FRM” in these positions.
Para la versión con el armazón montado, sustituya las letras “FRM” en estas posiciones.
3
GOULDS PUMPSCommercial Water
Performance Coverage (60 Hz)
Alcance de Funcionamiento (60 Hz)
NoTES:
Not recommended for operation
beyond printed H-Q curve.
For critical application conditions
consult factory.
Not all combinations of motor,
impeller and seal options are
available for every pump model.
Please check with G&L on non-
cataloged numbers.
All standard 3500 RPM ODP and
TEFC motors supplied by Goulds
Pumps, have minimum of 1.15
service factor. Standard catalog
units may utilize available service
factor. Any motors supplied other
than Goulds Pumps check avail-
able service factor.
NOTAS:
No se recomienda para funciona-
miento superior al impreso en la
curva H-Q.
Para condiciones de aplicaciones
críticas consultar con la fábrica.
No todas las combinaciones de
las opciones de motor, impulsor y
sello están disponibles para cada
modelo de bombas. Por favor
verifique con G&L en los números
no catalogados.
Todos los motores estándar
de 3500 RPM, ODP (abiertos
resguardados) y TEFC (totalmente
encerrados con enfriamiento
forzado) provistos por Goulds
Pumps tienen un factor mínimo
de servicio de 1,15. Las unidades
estándar de catálogo pueden
utilizar el factor de servicio
disponible. Verificar el factor de
servicio disponible de todo motor
no provisto por Goulds Pumps.
CAPACITY (CAPACIDAD) Q
METERSMETROS FEETPIES
TOTAL DYNAMIC HEAD (CARGA DINAMICA TOTAL) H0
160
140
120
100
80
60
40
20
50
40
30
20
10
0 0 20 40 60 80 100 120 140 160 U.S. GPM
0 5 10 15 20 25 30 35 m3/hr
2ST11⁄4" x 11⁄2" – 63⁄4–5 HP3500 RPM
1ST1" x 11⁄4" – 61⁄2–3 HP3500 RPM
3ST11⁄2" x 2" – 61–5 HP3500 RPM
3ST 1750 RPM2ST 1750 RPM
1ST1750 RPM
4
GOULDS PUMPSCommercial Water
NPE Close Coupled Pump Major Components: Materials of Construction
Bomba Cerrada Acoplada NPE Componentes Principales: Materiales de Construcción
184A
108A
Seal Face Vent/Flush Option,
Opción Cara del Sello Válvula/Chorro
Item No., Description, Materials, Parte No. Descripción Materiales
100 Casing; Carcasa
101 Impeller; Impulsor AISI 316L SS;
108 Motor adapter; Adaptador del motor AISI 316L
108A Motor adapter seal vent/flush; Acero inoxidable
Sello válvula/chorro del adaptador del motor
123 Deflector; Deflector BUNA-N
184 Seal housing; Alojamiento del sello AISI 316L SS;
184 A Seal housing seal vent/flush; AISI 316L
Sello válvula/chorro del alojamiento del sello Acero inoxidable347 Guidevane; Difusor
349 Seal ring, guidevane; Anillo del sello, difusor Viton
370 Socket head screws, casing; AISI 410 SS;
Encajes cabezas de tornillos, carcasa AISI 410 Acero inoxidable
371 Bolts, motor; Plated steel;
Tornillos, motor Acero chapeado
383 Mechanical seal; Sello mecánico **see chart, ver tabla
408 Drain and vent plug, casing; AISI 316L SS;
Enchufes de drenaje y válvula, carcasa AISI 316L Acero inoxidable
412B O-ring, drain and vent plug; Viton (Standard, estándar)
Anillo ‘O’, enchufe de drenaje y válvula
513 O-ring, casing; Anillo ‘O’, carcasa EPR (Optional, Opcional)
Motor NEMA standard, 56J flange;
Motor NEMA estándar, brida 56J
100 101 347 370 513 184 108 383 123
349
412B 408 371
1½, 2 and 3 HP
1½, 2 y 3 HP
½, ¾ and 1 HP
½, ¾ y 1 HP
Footed motor for 5 HP ODP and TEFC, all explosion
proof motors, see page 13.
Motor con pie para 5 HP ODP y TEFC, a prueba de
explosiones motores, en la página 13.
5
GOULDS PUMPSCommercial Water
NPE Frame Mounted Pump Major Components: Materials of Construction
Bomba NPE de Armazón Montado Componentes Principales: Materiales de Construcción
Item No., Description, Materials,
Parte No. Descripción Materiales
100 Casing; Carcasa
101 Impeller; Impulsor AISI 316L SS;
108 Adapter; Adaptador AISI 316L
108A Motor adapter seal vent/flush; Acero inoxidable
Sello válvula/chorro del adaptador del motor
109 Bearing cover; Cubierta de balineras Cast iron; Hierro fundido
112 Ball bearing (outboard); Steel;
Balineras de bolas (exterior) Acero
122 Shaft; Eje AISI 316 SS;
AISI 316 Acero inoxidable
138 Lip-seal (inboard); Sello cubierto (interior) BUNA/steel; BuNA/acero
139 Lip-seal (outboard); Sello cubierto (exterior) BUNA/steel; BuNA/acero
168 Ball bearing (inboard); Steel;
Balineras de bolas (interior) Acero
184 Seal housing; Alojamiento del sello AISI 316L SS;
184 A Seal housing seal vent/flush; AISI 316L Acero inoxidable
Sello válvula/chorro del alojamiento del sello
228 Bearing frame; Armazón de balineras Cast iron, Hierro fundido
Item No., Description, Materials,
Parte No. Descripción Materiales
304 Impeller locknut; Contratuerca del impulsor AISI 316 SS;
347 Guidevane; Difusor AISI 316 Acero inoxidable
349 Seal ring, guidevane; Anillo del sello, difusor Viton
361 Retaining ring; Anillo de retención Steel; Acero
370 Socket head screws, casing; AISI 410 SS;
Encaje cabeza del tornillo, carcasa AISI 410 Acero inoxidable
Hex head screw, bearing cover; Plated steel;
370C Tornillo de cabeza hexagonal, Acero chapeado cubierta de balineras
Hex head screw, bearing frame; Plated steel;
371 Tornillo de cabeza hexagonal, Acero chapeado armazón de balineras
383 Mechanical seal; Sello mecánico **see chart; ver tabla
400 Shaft key; Llave del eje Steel; Acero
408 Drain and vent plug, casing; AISI 316 SS;
Enchufes de drenaje y válvula, carcasa AISI 316 Acero inoxidable
412B O-ring, drain and vent plug; Viton (Standard, estándar)
Anillo ‘O’, enchufe de drenaje y válvula
513 O-ring, casing; Anillo ‘O’, carcasa EPR (Optional, Opcional)
Seal Face Vent/Flush Option,
Opción Cara del Sello Válvula/Chorro
228371138
408
412B
304
383
349
101
100
347 370 513 184 108 168 122 112 370C
361
109
139
184A
108A
6
GOULDS PUMPSCommercial Water
Performance Curves – 60 Hz, 3500 RPM
Curvas de Funcionamiento – 60 Hz, 3500 RPM
Ordering Standard
Code, HP Rating, Imp.
Código Estándar HP Dia.
de Pedido Potencia
E ½ 47⁄16”
D ¾ 4¾
C 1 53⁄16
B 1½ 5¾
A 2 61⁄8
m3⁄ hr
0
20
40
60
80
100
120
140
0
10
20
30
40
50
6050403020100
1050
160
Model NPE / 1ST Size (Tamaño) 1 x 11⁄4-6
RPM 3500 Curve (Curva) CN0231R01
NOTE: Not recommended for operation beyond printed H-Q curve.NOTA: No se recomienda para funcionamiento superior al impreso en la curva H-Q.
Impeller Selections for Exp. Proof Motors
Selecciones del Impulsor para Motores Exp. Proof
45 48 50
50 48
51
5152
53
1⁄2 HP
10'
8’6'
5'
12'
EFF %
3⁄4 HP
11⁄2 HP
1 HP
2 H
P
8'
10'12'
U.S. GPM
3 H
P
B 53⁄4"
C 53⁄16"
D 43⁄4"
E 47⁄16"
F 41⁄16"Spec.
A 61⁄8" DIA.
METERSMETROS FEETPIES
TOTAL DYNAMIC HEAD (CARGA DINAMICA TOTAL) HCAPACITY (CAPACIDAD) Q
NPSHR – FEET (PIES)
m3⁄ hr
Model NPE / 1ST Size (Tamaño) 1 x 11⁄4-6
RPM 3500 Curve (Curva) CN0231R01
0
20
40
60
80
100
120
140
0
10
20
30
40
50
METERSMETROS FEETPIES
TOTAL DYNAMIC HEAD (CARGA DINAMICA TOTAL) H6050403020100
1050CAPACITY (CAPACIDAD) Q
U.S. GPM
45 48
50
50 48
51
5152
53
1⁄2 HP
10'
8'6'5'
12'
EFF %
NPSHR – FEET (PIES)
160
3⁄4 HP
11⁄2 HP1 HP
2 HP
3
H
P
A 61⁄8" DIA.
B 53⁄4"
C 53⁄16"
D 43⁄4"
E 47⁄16"
NOTE: Not recommended for operation beyondprinted H-Q curve.NOTA: No se recomienda para funcionamiento
superior al impreso en la curva H-Q.
Impeller Selections for ODP & TEFC Motors
Selecciones del Impulsor para
Motores ODP & TEFC
Ordering Standard Code, HP Rating, Imp. Código Estándar HP Dia. de Pedido Potencia
F ½
E ¾ 47⁄16
D 1 4¾
C 1½ 53⁄16
B 2 5¾
A 3 61⁄8
41⁄16”spec.
NoTE: Although not
recommended, the pump
may pass a 1⁄16” sphere.
NOTA: Si bien no se reco-
mienda, la bomba puede pasar
una esfera de 1⁄16”.
NoTE: Although not
recommended, the pump
may pass a 1⁄16” sphere.
NOTA: Si bien no se
recomienda, la bomba puede
pasar una esfera de 1⁄16”.
14
GOULDS PUMPSCommercial Water
41⁄4
X
51⁄4
2
FILL AND VENTCARGA Y VÁLVULA Y
DISCHARGEDESCARGA
L 31⁄4
1⁄2
4 HOLES 3⁄8 DIA.4 AGUJEROS 3⁄8 DIA.
SUCTIONSUCCIÓN KEYWAY 3⁄32 x 3⁄16CHAVETERO 3⁄32 x 3⁄162
DRAINDRENAJE
2
4
311⁄16MAX.
W
9⁄16
7/8
CP MAX.
41⁄2
413⁄16
NPE Frame Mounted – Dimensions, Weights and Specifications
NPE Armazón Montado – Dimensiones, Pesos y Especificaciones
Motor specifications:
T-frame single and three phase.
Open drip-proof, TEFC or explosion
proof enclosures are available
for 60 Hz, 3500 and 1750 RPM
operation.
For three phase motors, overload
protection must be provided in
starter unit. Starter and heaters
must be ordered separately.
Capacities to:
85 GPM (322L/min) at 1750 RPM
170 GPM (643L/min) at 3500 RPM
Heads to:
39 feet (12 m) at 1750 RPM
150 feet (47 m) at 3500 RPM
Working pressures to:
125 PSIG (9 bars)
Maximum temperatures to:
250°F (121°C)
Direction of rotation:
Clockwise when viewed from
motor end.
Motores:
Armazón T- monofásico y
trifásico. A prueba de goteo, TEFC
o recintos a prueba de explosión
están disponibles para funciona-
miento de 60 Hz, 3500 y 1750
RPM.
Para motores trifásicos se debe de
proporcionar la protección térmica
contra sobrecarga en la unidad
de arranque. El arrancador y los
calentadores se deben pedir por
separado.
Capacidades:
85 GPM (322L/min) a 1750 RPM
170 GPM (643L/min) a 3500 RPM
Cargas:
39 pies (12 m) a 1750 RPM
150 pies (47 m) a 3500 RPM
Presión de trabajo:
125 PSIG (9 baras)
Temperatura máxima:
250°F (121°C)
Dirección de rotación:
En dirección de las agujas del reloj
visto desde el extremo final del
motor.
Specifications
Especificaciones
FILL AND VENTCARGA Y VÁLVULA
41/4
DISCHARGEDESCARGA
4 HOLES 3⁄8 DIA.4 AGUJEROS 3⁄8 DIA.
SUCTIONSUCCIÓN
DRAINDRENAJE
YW
31/2 C. MAX.SPACER COUPLING (ACOPLE DEL ESPACIADOR)
COUPLING GUARDGUARDA ACOPLE
LOCATION FORSINGLE PHASE ONLYUBICACIÓN PARAMONOFÁSICOS SOLAMENTE
KEYWAY 3/32 X 3/16CHAVETERO 3/32 X 3/16
2
7/8X
HD
HG
4 311/16MAX.
HL HF
HB
HPHEHE
HA
CP
77/8 MAX.
31/8 MAX.
NPE-F
15
GOULDS PUMPSCommercial Water
Dimensions and Weights – Determined by Pump,
Dimensiones y Pesos – Determinados por la Bomba
Dim. “HL” Determined
by Pump and Motor,
Dim. “HL” Determinadas por la Bomba y el Motor
Suct. NPT, Disch. NPT,
Succión Descarga
NPT NPT
1ST 11⁄4 1 1215⁄16 67⁄16 35/16 43⁄8 2 221⁄2 49⁄16 67⁄16
2ST 11⁄2 11⁄4 41⁄2
3ST 2 11⁄2 45⁄8
Pump,Bomba CP L W X Y Wt.,Peso
56 1⁄2 – 11⁄2 1⁄2 – 11⁄2 1⁄2 – 1 1⁄2 – 1 13 45
143T — — 11⁄2 11⁄2 133⁄8 45
145T 2 2 11⁄2 – 3 11⁄2 – 2 141⁄4 52
182T 3 3 5 3 165⁄8 63
184T 5 5 — 5 181⁄8 112
3500 RPM
Horsepower, Fuerza
Single Phase, Monofásicos Three Phase, Trifásicos
ODP TEFC ODP TEFC
FrameSize,Tamaño del Armazón
Available Motor and Bedplate Dimensions and Weights, Pesos y Dimensiones Disponibles de la Fundación y del Motor
56
143T 8 26 67⁄8 31⁄8 223⁄8 23⁄8 1 30 1”
145T
182T
184T
Shims,
Deflec-
tor
Wt.Max.,Peso Máx.
C Max.
NOTES:1. Pump will be shipped with top
vertical discharge position as standard. For other orientations,
remove casing bolts, rotate discharge to desired position,
replace and tighten 6mm bolts to 5 – 6 lbs.-ft.
2. Motor dimensions may vary with motor manufacturers.
3. Dimensions in inches, weights in pounds.
4. For explosion proof motor dimensions consult factory for
information.
5. Not to be used for construction
purposes unless certified.
NOTAS:
1. Las bombas se transportarán
con la descarga vertical superior
como estándar. Para otras orien-
taciones, retirar los tornillos de
la carcasa, rotar la descarga a la
posición deseada, y reemplazar y
apretar los tornillos de 6mm a 5
– 6 libras-pies.
2. Las dimensiones del motor
puede que varíen con los
fabricantes.
3. Dimensiones en pulgadas, pesos
en libras.
4. Para las dimensiones de los
motores a prueba de explosión
consultar con la fábrica para
información.
5. No usar para propósitos de
construcción sin certificar.
HA HB HD HE HF HG HP
Wt.Max.,PesoMáx
131⁄2 7 33⁄4 21/8 23 51⁄8 7
10 26 71⁄4 33⁄4 24 23⁄4 7⁄8 43 —
Frame, Armazón
Motor Frame,Armazón del Motor
56 140 180
Dimensions and Weights
Dimensiones y Pesos