F15-0088_Hydraulic Calcs_1450110960.pdf
O t/i Western States Fire Protection Co. pozotezeie, Iicte4 aea pow/zero 7026 South Tucson Way Centennial, CO 80112 (303) 792-0022 Fax (303) 792-9049 Fire Protection System Hydraulic Calculations and Equipment Sebastian Penthouse Fire Sprinkler System 16 Vail Rd Vail, Colorado 81657 Prepared by: Zack Hinson Project Manager Phone: (303)792-0022 Cell: (720)346-3113 Fax: (303)792-9049 Email: Zachary.hinson@wsfp.us December 10,2015 } Hydraulic Summary Job Number:CS2787 Re.ort Descri.tion:Livin. Room Job Job Number Design Engineer CS2787 Zack Hinson Job Name: State Certification/License Number Sebastian Penthouse 032 Address l Mat 16 Vail Rd. Vail Fire Address 2 Job Site/Building Vail,CO 81657 Sebastian Penthouse Address 3 Drawing Name CS2787-Sebastian Penthouse-Design System Remote Area(s) Most Demanding Sprinkler Data Occupancy Job Suffix 4.9 K-Factor 25.6 at 27.3 Living Room Hose Allowance At Source Density Area of Application 100.0 0.10gpm/ft2 576.00ft2(Actual 236.21ft2) Additional Hose Supplies Number Of Sprinklers Calculated Coverage Per Sprinkler Node Flow(aom) 4 144.00ft2 AutoPeak Results:Pressure For Remote Area(s)Adjacent To Most Remote Area Total Hose Streams 100.0 System Flow Demand Total Water Required(Including Hose Allowance) 101.2 201.2 Maximum Pressure Unbalance In Loops 0.0 Maximum Velocity Above Ground 24.80 between nodes 4 and 5 Maximum Velocity Under Ground Volume capacity of Wet Pipes Volume capacity of Dry Pipes 469.6gal Supplies Hose Flow Static Residual Flow Available Total Demand Required Safety Margin Node Name (gpm) (psi) (psi) @ (gpm) (psi) @ (gpm) (psi) (psi) 1 Water Supply 100.0 155.0 124.8 287.3 139.4 201.2 121.7 17.6 Contractors 11 Contractor Number Contact Name Contact Title Zack Hinson PM Name of Contractor. Phone Extension Western States Fire Protection 720-346-3133 Address l FAX 274 Center Drive Address 2 E-mail Glenwood Springs,CO.81601 zachary.hinson@wsfp.us Address 3 Web-Site ©M.E.P.CAD,Inc. AutoSPRINK®VR11 v11.0.30.0 12/10/2015 3:18:29PM Page 1 +- Hydraulic Graph Job Number:CS2787 Report Description:Living Room Water Supply at Node 1 200 180 160 Static Pressure 155.0 140 287.3 @ 124.8 120 201.2 with hose streams Ul Q 100 fA to N System demand curve 80 60 40 20 0 mmiii 111111111 111111111 1111 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 00 200 300 400 500 600 700 800 900 1000 Water flow,gpm Hydraulic Graph Water Supply at Node 1 Static:Pressure 155.0 Residual:Pressure 124.8@287.3 Available Pressure at Time of Test 139.4 @ 201.2 System Demand 121.7 @ 101.2 System Demand(Including Hose Allowance at Source) 121.7 @ 201.2 iL� ©M.E.P.CAD,Inc. 1 AutoSPRINK®VR11 v11.0.30.0 12/10/2015 3:18:31PM Page 2 iii -Summary Of Outflowing Devices I Job Number:CS2787 Report Description:Living Room Actual Flow Minimum Flow K-Factor Pressure Device (qpm) (qpm) (K) (psi) Sprinkler 101 26.3 25.6 4.9 28.8 Sprinkler 102 22.1 15.0 4.2 27.7 Sprinkler 103 27.2 25.6 4.9 30.8 b Sprinkler 104 25.6 25.6 4.9 27.3 b Most Demanding Sprinkler Data E,©M.E.P.CAD,Inc. in AutoSPRINK®VR11 v11.0.30.0 12/10/2015 3:18:32PM Page 3 go ydraulic Analysis Job Number:CS2787 Report Description:Living Room Pipe Type Diameter Flow Velocity HWC Friction Loss Length Pressure Downstream Elevation Discharge K-Factor Pt Pn Fittings Eq.Length Summary Upstream Total Length OF Route 1 AO 1.055 25.6 9.40 150 0.132243 6'-111h Pf 1.2 104 16-0 25.6 4.9 27.3 Sprinkler, 2'-0 Pe 11 16-0 28.5 E(2'-0) 8'-111h Pv AO 1.055 47.7 17.51 150 0.418183 9'-91/< Pf 4.1 11 16-0 22.1 28.5 Flow(q)from Route 3 Pe 9 16-0 32.6 9'-91/< Pv AO 1.291 101.2 24.80 150 0.629176 4'-6% Pf 4.8 9 16'-0 53.5 32.6 Flow(q)from Route 2 3'-0 Pe 8 16'-0 37.3 T(3'-0) 7-6% Pv CM 1.291 35.7 8.74 150 0.091375 68'-7-3/8 Pf 8.6 8 16'-0 37.3 26-0 Pe 10 16'-0 46.0 8E(2'-0),7Tr(1'-0),C(3'-0) 94'-7-3/8 Pv FR 1.291 56.3 13.79 150 0.212497 16-0 Pf 4.0 10 16'-0 20.6 46.0 Flow(q)from Route 5 3'-0 Pe 6.9 6 0'-0 56.9 T(3'-0) 19'-0 Pv CM 1.291 56.3 13.79 150 0.212497 12'-8-5/8 Pf 3.3 6 0'-0 56.9 3'-0 Pe 5 0'-0 60.3 T(3'-0) 15'-8-5/8 Pv CM 1.291 101.2 24.80 150 0.629176 14'-8-7/8 Pf 11.2 5 0'-0 44.9 60.3 Flow(q)from Route 4 3'-0 Pe 4 0'-0 71.4 2Tr(1'-0),cplg(1'-0) 17'-8-7/8 Pv CM 2.009 101.2 10.24 150 0.073025 198'-0 Pf 15.5 4 0'-0 71.4 14'-0 Pe 3 0'-0 86.9 4E(3'-6) 212'-0 Pv CM 2.157 101.2 8.89 120 0.078058 5'-0 Pf 0.9 3 0'-0 86.9 6'-1-7/8 Pe 2 0'-0 87.8 E(6'-1-7/8) 11'-1-7/8 Pv FR 6.357 101.2 1.02 120 0.000404 231'-0 Pf 0.1 2 0'-0 87.8 70'-4-7/8 Pe 33.8 1 -78'-0 121.7 4E(17'-714),S 301'-4-7/8 Pv 100.0 Hose Allowance At Source 1 201.2 OF Route 2 AO 1.055 26.3 9.66 150 0.139176 7'-11-3/8 Pf 1.9 101 16'-0 26.3 4.9 28.8 Sprinkler, 6-0 Pe 103 16'-0 30.8 3E(2'-0) 13'-11-3/8 Pv AO 1.055 53.5 19.64 150 0.517203 1'-51/a Pf 1.8 103 16-0 27.2 4.9 30.8 Sprinkler, 2'-0 Pe 9 16-0 32.6 T(2'-0) 3'-51/a Pv OF Route 3 AO 1.055 22.1 8.11 150 0.100741 5'-10% Pf 0.8 102 16'-0 22.1 4.2 27.7 Sprinkler, 2'-0 Pe 11 16'-0 28.5 T(2'-0) 7'-10% Pv - Route 4 FR 1.291 44.9 11.01 150 0.140020 16-0 Pf 2.2 12 16'-0 43.4 Pe 6.9 7 0'-0 52.6 16'-0 Pv CM 1.291 44.9 11.01 150 0.140020 43'-11h Pf 7.7 7 0'-0 52.6 12'-0 Pe 5 0'-0 60.3 2T(3'-0),6Tr(1'-0) 55'-11% Pv OF Route 5 CM 1.291 65.5 16.06 150 0.281623 11'-6Yz Pf 6.1 8 16-0 37.3 10'-0 Pe 12 16-0 43.4 2T(3'-0),Tr(1'-0),C(3'-0) 21'-6Yz Pv CM 1.291 20.6 5.05 150 0.033149 55'-9-7/8 Pf 2.6 12 16'-0 43.4 C(3'-0) 22'-0 Pe 10 16'-0 46.0 5E(2'-0),9Tr(1'-0) 77'-9-7/8 Pv Equivalent Pipe Lengths of Valves and Fittings(C=120 only) a C Value Multiplier= Actual Inside Diameter 4'87 Value Of C 100 130 140 150 Schedule 40 Steel Pipe Inside Diameter ) =Factor Multiplying Factor 0.713 1.16 1.33 1.51 ©M.E.P.CAD,Inc. 111 AutoSPRINK®VR11 v11.0.30.0 12/10/2015 3:18:34PM Page 4 111 ydraulic Analysis Job Number:CS2787 Report Description:Living Room Pipe Type Diameter Flow Velocity HWC Friction Loss Length Pressure Downstream Elevation Discharge K-Factor Pt Pn Fittings Eq.Length Summary Upstream (Total Length Pipe Type Legend 1 Units Legend IF r -Fittings Legend AO Arm-Over Diameter Inch ALV Alarm Valve BL Branch Line Elevation Foot AngV Angle Valve CM Cross Main Flow gpm b Bushing DN Drain Discharge gpm BaIV Ball Valve DR Drop Velocity fps BFP Backflow Preventer DY Dynamic Pressure psi BV Butterfly Valve FM Feed Main Length Foot C Cross Flow Turn 90° FR Feed Riser Friction Loss psi/Foot cplg Coupling MS Miscellaneous HWC Hazen-Williams Constant Cr Cross Run OR Outrigger Pt Total pressure at a point in a pipe CV Check Valve RN Riser Nipple Pn Normal pressure at a point in a pipe DeIV Deluge Valve SP Sprig Pf Pressure loss due to friction between points DPV Dry Pipe Valve ST Stand Pipe E 90°Elbow Pe Pressure due to elevation difference between indicated points UG Underground Pv Velocity pressure at a point in a pipe EE 45°Elbow Eel 11W Elbow Ee2 221/ Elbow Flow Device fd Flex Drop FDC Fire Department Connection fE 90°FireLock(TM)Elbow fEE 45°FireLock(TM)Elbow flg Flange FN Floating Node fT FireLock(TM)Tee g Gauge GIoV Globe Valve GV Gate Valve Ho Hose Hose Hose HV Hose Valve Hyd Hydrant LtE Long Turn Elbow mecT Mechanical Tee Noz Nozzle P1 Pump In P2 Pump Out PIV Post Indicating Valve PO Pipe Outlet PRV Pressure Reducing Valve PrV Pressure Relief Valve red Reducer/Adapter S Supply sCV Swing Check Valve Spr Sprinkler St Strainer T Tee Flow Turn 90° Tr Tee Run U Union WirF Wirsbo WMV Water Meter Valve Z Cap ©M.E.P.CAD,Inc. ,111 AutoSPRINK®VR11 v11.0.30.0 12/10/2015 3:18:34PM Page 5 } Hydraulic Summary Job Number:CS2787 Re.ort Descri.tion:Kitchen/Dinin. Job Job Number Design Engineer CS2787 Zack Hinson Job Name: State Certification/License Number Sebastian Penthouse 032 Address l AHJ 16 Vail Rd. Vail Fire Address 2 Job Site/Building Vail,CO 81657 Sebastian Penthouse Address 3 Drawing Name CS2787-Sebastian Penthouse-Design System Remote Area(s) Most Demanding Sprinkler Data Occupancy Job Suffix 4.9 K-Factor 25.6 at 27.3 Kitchen/Dining Hose Allowance At Source Density Area of Application 100.0 0.10gpm/ft2 1088.00ft2(Actual 302.96ft2) Additional Hose Supplies Number Of Sprinklers Calculated Coverage Per Sprinkler Node Flow(aum) 4 256.00ft2 AutoPeak Results:Pressure For Remote Area(s)Adjacent To Most Remote Area Total Hose Streams 100.0 System Flow Demand Total Water Required(Including Hose Allowance) 107.1 207.1 Maximum Pressure Unbalance In Loops 0.0 Maximum Velocity Above Ground 26.26 between nodes 4 and 5 Maximum Velocity Under Ground Volume capacity of Wet Pipes Volume capacity of Dry Pipes 469.6gal Supplies Hose Flow Static Residual Flow Available Total Demand Required Safety Margin Node Name (gpm) (psi) (psi) @ (gpm) (psi) @ (gpm) (psi) (psi) 1 Water Supply 100.0 155.0 124.8 287.3 138.5 207.1 116.2 22.3 Contractors 11 Contractor Number Contact Name Contact Title Zack Hinson PM Name of Contractor. Phone Extension Western States Fire Protection 720-346-3133 Address l FAX 274 Center Drive Address 2 E-mail Glenwood Springs,CO.81601 zachary.hinson@wsfp.us Address 3 Web-Site ©M.E.P.CAD,Inc. AutoSPRINK®VR11 v11.0.30.0 12/10/2015 3:18:04PM Page 1 Hydraulic Graph Job Number:CS2787 Report Description:Kitchen/Dining Water Supply at Node 1 200 180 160 Static Pressure 155.0 140 287.3 @ 124.8 120 107.1 @ 116.2 r • I � 207.1 with hose streams N Q J100 80 System demand curve 60 40 20 — 0 uamm111111111111111111111 111111111 111111111 11111111 111111111 111111111 111111111 00 200 300 400 500 600 700 800 900 1000 Water flow,gpm Hydraulic Graph Water Supply at Node 1 Static:Pressure 155.0 Residual:Pressure 124.8@287.3 Available Pressure at Time of Test 138.5 @ 207.1 System Demand 116.2 @ 107.1 System Demand(Including Hose Allowance at Source) 116.2 @ 207.1 iL� ©M.E.P.CAD,Inc. 1 AutoSPRINK®VR11 v11.0.30.0 12/10/2015 3:18:05PM Page 2 iii -Summary Of Outflowing Devices I Job Number:CS2787 Report Description:Kitchen/Dining Actual Flow Minimum Flow K-Factor Pressure Device (qpm) (qpm) (K) (psi) Sprinkler 201 25.8 25.6 4.9 27.8 Sprinkler 202 25.7 25.6 4.9 27.6 b Sprinkler 203 25.6 25.6 4.9 27.3 Sprinkler 204 30.0 23.0 5.8 26.7 b Most Demanding Sprinkler Data E,©M.E.P.CAD,Inc. in AutoSPRINK®VR11 v11.0.30.0 12/10/2015 3:18:07PM Page 3 Job Number: 787 go ydraulic Analysis Report Description:Kitchen/Dining Pipe Type Diameter Flow Velocity HWC Friction Loss Length Pressure Downstream Elevation Discharge K-Factor Pt Pn Fittings Eq.Length Summary Upstream Total Length OF Route 1 AO 1.055 25.6 9.40 150 0.132243 5'-0% Pf 0.9 203 16-0 25.6 4.9 27.3 Sprinkler, 2'-0 Pe 13 16-0 28.2 PO(Z-0) 7-0% Pv CM 1.291 16.2 3.97 150 0.021256 10'-81/4 Pf 0.3 13 16-0 28.2 3'-0 Pe 14 16-0 28.5 3Tr(1'-0) 13'-81/4 Pv CM 1.291 41.9 10.28 150 0.123353 44'-1% Pf 7.8 14 16'-0 25.7 28.5 Flow(q)from Route 2 19'-0 Pe 10 16'-0 36.3 7E(2'-0),2Tr(1'-0),C(3'-0) 63'-1% Pv FR 1.291 60.6 14.86 150 0.243893 16-0 Pf 4.6 10 16'-0 18.7 36.3 Flow(q)from Route 6 3'-0 Pe 6.9 6 0'-0 47.9 T(3'-0) 19'-0 Pv CM 1.291 60.6 14.86 150 0.243893 12'-8-5/8 Pf 3.8 6 0'-0 47.9 3'-0 Pe 5 0'-0 51.7 T(3'-0) 15'-8-5/8 Pv CM 1.291 107.1 26.26 150 0.699212 14'-8-7/8 Pf 12.4 5 0'-0 46.5 51.7 Flow(q)from Route 3 3'-0 Pe 4 0'-0 64.1 2Tr(1'-0),cplg(1'-0) 17'-8-7/8 Pv CM 2.009 107.1 10.84 150 0.081154 198'-0 Pf 17.2 4 0'-0 64.1 14'-0 Pe 3 0'-0 81.3 4E(3'-6) 212'-0 Pv CM 2.157 107.1 9.41 120 0.086747 5'-0 Pf 1.0 3 0'-0 81.3 6'-1-7/8 Pe 2 0'-0 82.3 E(6'-1-7/8) 11'-1-7/8 Pv FR 6.357 107.1 1.08 120 0.000449 231'-0 Pf 0.1 2 0'-0 82.3 70'-4-7/8 Pe 33.8 1 -78'-0 116.2 4E(17'-71/4),S 301'-4-7/8 Pv 100.0 Hose Allowance At Source 1 207.1 - Route 2 AO 1.055 25.7 9.44 150 0.133507 5'-0% Pf 0.9 202 16-0 25.7 4.9 27.6 Sprinkler, 2'-0 Pe 14 16'-0 28.5 P0(2'-0) 7-0% Pv Route 3 AO 1.055 25.8 9.49 150 0.134623 1'-1-5/8 Pf 0.4 201 16'-0 25.8 4.9 27.8 Sprinkler, 2'-0 Pe 15 16-0 28.2 P0(2'-0) 3'-1-5/8 Pv CM 1.291 35.2 8.64 150 0.089335 16-6% Pf 1.9 15 16-0 9.4 28.2 Flow(q)from Route 5 5'-0 Pe 16 16'-0 30.2 E(2'-0),T(3'-0) 21'-6'% Pv CM 1.291 65.2 15.98 150 0.278933 7-3'/z Pf 4.0 16 16'-0 30.0 30.2 Flow(q)from Route 4 7'-0 Pe 12 16'-0 34.2 T(3'-0),Tr(1'-0),C(3'-0) 14'-3'% Pv FR 1.291 46.5 11.40 150 0.149321 16'-0 Pf 2.4 12 16'-0 34.2 Pe 6.9 7 0'-0 43.5 16-0 Pv CM 1.291 46.5 11.40 150 0.149321 43'-11/4 Pf 8.2 7 0'-0 43.5 12'-0 Pe 5 0'-0 51.7 2T(3'-0),6Tr(1'-0) 55'-11/4 Pv - Route 4 AO 1.055 30.0 11.00 150 0.176960 7'-10'% Pf 1.7 204 20'-0 30.0 5.8 26.7 Sprinkler, 2'-0 Pe 1.7 16 16'-0 30.2 E(2'-0) 9'-10'% Pv Route 5 CM 1.291 9.4 2.30 150 0.007730 1'-5% Pf 0.0 13 16'-0 28.2 1'-0 Pe 15 16'-0 28.2 Tr(1'-0) 2'-5% Pv OF Route 6 CM 1.291 18.7 4.58 150 0.027642 55'-9-7/8 Pf 2.2 12 16'-0 34.2 C(3'-0) 22'-0 Pe 10 16'-0 36.3 5E(2'-0),9Tr(1'-0) 77'-9-7/8 Pv Equivalent Pipe Lengths of Valves and Fittings(C=120 only) C Value Multiplier Actual Inside Diameter 487 Value Of C 100 130 140 150 Schedule 40 Steel Pipe Inside Diameter ) =Factor Multiplying Factor 0.713 1.16 1.33 1.51 ©M.E.P.CAD,Inc. i;il AutoSPRINK®VR11 v11.0.30.0 12/10/2015 3:18:08PM Page 4 c Job Number:CS2787 111 ydra _ Analysis Report Description:Kitchen/Dining Pipe Type Diameter Flow Velocity HWC Friction Loss Length Pressure Downstream Elevation Discharge K-Factor Pt Pn Fittings Eq.Length Summary Upstream (Total Length Pipe Type Legend 1 Units Legend IF r -Fittings Legend AO Arm-Over Diameter Inch ALV Alarm Valve BL Branch Line Elevation Foot AngV Angle Valve CM Cross Main Flow gpm b Bushing DN Drain Discharge gpm BaIV Ball Valve DR Drop Velocity fps BFP Backflow Preventer DY Dynamic Pressure psi BV Butterfly Valve FM Feed Main Length Foot C Cross Flow Turn 90° FR Feed Riser Friction Loss psi/Foot cplg Coupling MS Miscellaneous HWC Hazen-Williams Constant Cr Cross Run OR Outrigger Pt Total pressure at a point in a pipe CV Check Valve RN Riser Nipple Pn Normal pressure at a point in a pipe DeIV Deluge Valve SP Sprig Pf Pressure loss due to friction between points DPV Dry Pipe Valve ST Stand Pipe E 90°Elbow Pe Pressure due to elevation difference between indicated points UG Underground Pv Velocity pressure at a point in a pipe EE 45°Elbow Eel 11W Elbow Ee2 221/ Elbow Flow Device fd Flex Drop FDC Fire Department Connection fE 90°FireLock(TM)Elbow fEE 45°FireLock(TM)Elbow flg Flange FN Floating Node fT FireLock(TM)Tee g Gauge GIoV Globe Valve GV Gate Valve Ho Hose Hose Hose HV Hose Valve Hyd Hydrant LtE Long Turn Elbow mecT Mechanical Tee Noz Nozzle P1 Pump In P2 Pump Out PIV Post Indicating Valve PO Pipe Outlet PRV Pressure Reducing Valve PrV Pressure Relief Valve red Reducer/Adapter S Supply sCV Swing Check Valve Spr Sprinkler St Strainer T Tee Flow Turn 90° Tr Tee Run U Union WirF Wirsbo WMV Water Meter Valve Z Cap ©M.E.P.CAD,Inc. ,111 AutoSPRINK®VR11 v11.0.30.0 12/10/2015 3:18:08PM Page 5 } - Hydraulic Summary Job Number:CS2787 Re ort Descri tion:Master Bedroom Job Job Number Design Engineer CS2787 Zack Hinson Job Name: State Certification/License Number Sebastian Penthouse 032 Address l AHJ 16 Vail Rd. Vail Fire Address 2 Job Site/Building Vail,CO 81657 Sebastian Penthouse Address 3 Drawing Name CS2787-Sebastian Penthouse-Design System Remote Area(s) Most Demanding Sprinkler Data Occupancy Job Suffix 4.9 K-Factor 32.4 at 43.7 Master Bedroom Hose Allowance At Source Density Area of Application 100.0 0.10gpm/ft2 836.00ft2(Actual 486.95ft2) Additional Hose Supplies Number Of Sprinklers Calculated Coverage Per Sprinkler Node Flow(aom) 3 256.00ft2 AutoPeak Results:Pressure For Remote Area(s)Adjacent To Most Remote Area Total Hose Streams 100.0 System Flow Demand Total Water Required(Including Hose Allowance) 98.3 198.3 Maximum Pressure Unbalance In Loops 0.0 Maximum Velocity Above Ground 24.09 between nodes 4 and 5 Maximum Velocity Under Ground Volume capacity of Wet Pipes Volume capacity of Dry Pipes 469.6gal Supplies Hose Flow Static Residual Flow Available Total Demand Required Safety Margin Node Name (gpm) (psi) (psi) @ (gpm) (psi) @ (gpm) (psi) (psi) 1 Water Supply 100.0 155.0 124.8 287.3 139.8 198.3 124.2 15.5 Contractors 11 Contractor Number Contact Name Contact Title Zack Hinson PM Name of Contractor. Phone Extension Western States Fire Protection 720-346-3133 Address l FAX 274 Center Drive Address 2 E-mail Glenwood Springs,CO.81601 zachary.hinson@wsfp.us Address 3 Web-Site ©M.E.P.CAD,Inc. AutoSPRINK®VR11 v11.0.30.0 12/10/2015 3:17:45PM Page 1 +- Hydraulic Graph Job Number:CS2787 Report Description:Master Bedroom Water Supply at Node 1 200 180 160 Static Pressure 155.0 140 ♦ 287.3 @ 124.8 120 198.3 with hose streams N Q 100 N fA N 80 [System demand curve 60 40 20 0 dIuuuwii 111111111 I I I I I I I i I 1 1 1 1 1 1 1 1 1 I I I I I I I I Q100 i i i i i i i i '100 200 300 400 500 600 700 800 900 1000 Water flow,gpm Hydraulic Graph Water Supply at Node 1 Static:Pressure 155.0 Residual:Pressure 124.8@287.3 Available Pressure at Time of Test 139.8 @ 198.3 System Demand 124.2 @ 98.3 System Demand(Including Hose Allowance at Source) 124.2 @ 198.3 iL� ©M.E.P.CAD,Inc. 1 AutoSPRINK®VR11 v11.0.30.0 12/10/2015 3:17:46PM Page 2 iii -Summary Of Outflowing Devices I Job Number:CS2787 Report Description:Master Bedroom Actual Flow Minimum Flow K-Factor Pressure Device (qpm) (qpm) (K) (psi) Sprinkler 301 32.2 25.6 4.9 43.1 Sprinkler 302 33.7 25.6 4.9 47.3 * Sprinkler 303 32.4 32.4 4.9 43.7 E> Most Demanding Sprinkler Data E,©M.E.P.CAD,Inc. in AutoSPRINK®VR11 v11.0.30.0 12/10/2015 3:17:48PM Page 3 go ydraulic Analysis Job Number:CS2787 Report Description:Master Bedroom Pipe Type Diameter Flow Velocity HWC Friction Loss Length Pressure Downstream Elevation Discharge K-Factor Pt Pn Fittings Eq.Length Summary Upstream Total Length OF Route 1 AO 1.055 32.4 11.89 150 0.204474 9'-2'/= Pf 2.3 303 0'-0 32.4 4.9 43.7 Sprinkler, 2'-0 Pe 18 0'-0 46.0 E(2'-0) 11'-21/ Pv AO 1.291 64.6 15.82 150 0.273880 4'-10'% Pf 1.3 18 0'-0 32.2 46.0 Flow(q)from Route 2 Pe 302 0'-0 47.3 4'-10'% Pv CM 1.291 98.3 24.09 150 0.595902 8'-11'% Pf 6.5 302 0'-0 33.7 4.9 47.3 Sprinkler, 2'-0 Pe 17 0'-0 53.9 2Tr(1'-0) 10'-11'% Pv CM 1.291 56.9 13.96 150 0.217155 38'-9-7/8 Pf 10.4 17 0'-0 53.9 9'-0 Pe 5 0'-0 64.3 6Tr(1'-0),T(3'-0) 47'-9-7/8 Pv CM 1.291 98.3 24.09 150 0.595902 14'-8-7/8 Pf 10.6 5 0'-0 41.3 64.3 Flow(q)from Route 3 3'-0 Pe 4 0'-0 74.8 2Tr(1'-0),cplg(1'-0) 17'-8-7/8 Pv CM 2.009 98.3 9.95 150 0.069163 198'-0 Pf 14.7 4 0'-0 74.8 14'-0 Pe 3 0'-0 89.5 4E(3'-6) 212'-0 Pv CM 2.157 98.3 8.63 120 0.073930 5'-0 Pf 0.8 3 0,-0 89.5 6'-1-7/8 Pe 2 0'-0 90.3 E(6'-1-7/8) 11'-1-7/8 Pv FR 6.357 98.3 0.99 120 0.000383 231'-0 Pf 0.1 2 0'-0 90.3 70'-4-7/8 Pe 33.8 1 -78'-0 124.2 4E(17'-7%),S 301'-4-7/8 Pv 100.0 Hose Allowance At Source 1 198.3 Route 2 AO 1.055 32.2 11.80 150 0.201652 12'-7% Pf 2.9 301 0,-0 32.2 4.9 43.1 Sprinkler, 2'-0 Pe 18 0'-0 46.0 T(2'-0) 14'-7% Pv OF Route 3 CM 1.291 41.3 10.13 150 0.120010 4'-3'/z Pf 0.9 17 0'-0 53.9 T(3'-0) 3'-0 Pe 7 0'-0 54.8 7-3% Pv FR 1.291 41.3 10.13 150 0.120010 16-0 Pf 2.3 7 0'-0 54.8 3'-0 Pe -6.9 12 16-0 50.1 C(3'-0) 19'-0 Pv CM 1.291 18.2 4.47 150 0.026373 80'-13/4 Pf 3.1 12 16-0 50.1 C(3'-0) 36-0 Pe 10 16-0 53.2 8Tr(1'-0),2T(3'-0),8E(2'-0), 116-1% Pv C(3'-0) FR 1.291 41.3 10.13 150 0.120010 16-0 Pf 2.3 10 16-0 23.1 53.2 Flow(q)from Route 4 3'-0 Pe 6.9 6 0'-0 62.4 T(3'-0) 19'-0 Pv CM 1.291 41.3 10.13 150 0.120010 12'-8-5/8 Pf 1.9 6 0'-0 62.4 3'-0 Pe 5 0'-0 64.3 T(3'-0) 15'-8-5/8 Pv s-. Route 4 CM 1.291 23.1 5.66 150 0.040939 55'-9-7/8 Pf 3.1 12 16'-0 50.1 19'-0 Pe 10 16'-0 53.2 5E(2'-0),9Tr(1'-0) 74'-9-7/8 Pv Equivalent Pipe Lengths of Valves and Fittings(C=120 only) C Value Multiplier 1 Actual Inside Diameter 4.87 Value Of C 100 130 140 150 Schedule 40 Steel Pipe Inside Diameter ) =Factor Multiplying Factor 0.713 1.16 1.33 1.51 ©M.E.P.CAD,Inc. ,111 AutoSPRINK®VR11 v11.0.30.0 12/10/2015 3:17:49PM Page 4 111 ydraulic Analysis Job Number:CS2787 Report Description:Master Bedroom Pipe Type Diameter Flow Velocity HWC Friction Loss Length Pressure Downstream Elevation Discharge K-Factor Pt Pn Fittings Eq.Length Summary Upstream Total Length Pipe Type Legend 1 Units Legend IF r -Fittings Legend AO Arm-Over Diameter Inch ALV Alarm Valve BL Branch Line Elevation Foot AngV Angle Valve CM Cross Main Flow gpm b Bushing DN Drain Discharge gpm BaIV Ball Valve DR Drop Velocity fps BFP Backflow Preventer DY Dynamic Pressure psi BV Butterfly Valve FM Feed Main Length Foot C Cross Flow Turn 90° FR Feed Riser Friction Loss psi/Foot cplg Coupling MS Miscellaneous HWC Hazen-Williams Constant Cr Cross Run OR Outrigger Pt Total pressure at a point in a pipe CV Check Valve RN Riser Nipple Pn Normal pressure at a point in a pipe DeIV Deluge Valve SP Sprig Pf Pressure loss due to friction between points DPV Dry Pipe Valve ST Stand Pipe E 90°Elbow Pe Pressure due to elevation difference between indicated points UG Underground Pv Velocity pressure at a point in a pipe EE 45°Elbow Eel 11W Elbow Ee2 221/ Elbow Flow Device fd Flex Drop FDC Fire Department Connection fE 90°FireLock(TM)Elbow fEE 45°FireLock(TM)Elbow flg Flange FN Floating Node fT FireLock(TM)Tee g Gauge GIoV Globe Valve GV Gate Valve Ho Hose Hose Hose HV Hose Valve Hyd Hydrant LtE Long Turn Elbow mecT Mechanical Tee Noz Nozzle P1 Pump In P2 Pump Out PIV Post Indicating Valve PO Pipe Outlet PRV Pressure Reducing Valve PrV Pressure Relief Valve red Reducer/Adapter S Supply sCV Swing Check Valve Spr Sprinkler St Strainer T Tee Flow Turn 90° Tr Tee Run U Union WirF Wirsbo WMV Water Meter Valve Z Cap ©M.E.P.CAD,Inc. AutoSPRINK®VR11 v11.0.30.0 12/10/2015 3:17:49PM Page 5 Bulletin 006 Rev. I Model RFC30 (SIN RA0611) °J R eia ® M (S Modelodel RFC49RFC43 (SININ RA0616)RA0612) . Residential Flat Concealed a Sprinklers A Residential Flat Concealed Sprinkler engineered for a minimum design density of 0.05 gpm/ft2 with low GPM requirements. Features 1 . Very low water flow requirements. 2. Cover plate attachment (Plain or Perforated) with 1/2" (13mm)Total adjustment. 3. Thread-On/Thread-Off or Push-On/Thread Off cover attachment option. 4. Smooth aesthetic ceiling profile. 5. Available in brass, chrome and black plated or painted finishes. Plain Cover Plate Listings & Approval 1. Listed by Underwriters Laboratories, and �. -' . • certified by UL for Canada (cULus) _ --.2-7-...„ . • UL Listing Categories Residential Automatic Sprinklers UL Guide Number - - - " VKKW =__- -_ '- -- -__- --_ -_ - Product Description -- - --- -- ------ Model RFC30, RFC43 and RFC49 Concealed Residen- - --- -- _-_ _ - tial Sprinklers are fast response residential fusible solder link automatic sprinklers. Residential sprinklers differ from standard sprinklers primarily in their response time and water distribution patterns. Perforated Cover Plate Model RFC30, RFC43 and RFC49 sprinklers discharge water in a hemispherical pattern below the sprinkler de- and positively attached and blends into the ceiling, con- flector. Residential distribution patterns are higher and cealing the most dependable fire protection available, an generally contain a finer droplet size than standard sprin- automatic sprinkler system. kler patterns. The RFC30, RFC43 and RFC49 are UL Listed Residen- The combination of speed of operation and high dis- tial Sprinklers to be installed in the residential portions charge pattern required for residential sprinklers has of any occupancy in accordance with NFPA 13, 13R, & demonstrated, in fire testing, an ability for controlling 13D. residential fires, and thereby providing significant evacu- The RFC30, RFC43 and RFC49 can reduce the need ation time for occupants. for precise cutting of drop nipples. The threaded cover The RFC30, RFC43 and RFC49 Sprinklers provide the plate assembly can be adjusted without tools to fit ac- best form of fire protection by combining an attractive ap- curately against the ceiling. The fire protection system pearance and 1/2" (13mm) of cover adjustment for ease need not be shut down to adjust or remove the cover of installation. The small diameter cover plate is easily plate assembly. Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523 Application and Installation The RFC30, RFC43 and RFC49, for residential instal- When inserting or removing the wrench from the sprin- lations, use a 165°F (74°C) fusible solder link in a tun- kler/cup assembly, care should be taken to prevent darn- ing fork style sprinkler frame with a drop-down deflector. age to the sprinkler. DO NOT WRENCH ON ANY OTHER This assembly is recessed into the ceiling and concealed PART OF THE SPRINKLER/CUP ASSEMBLY. MODEL by a flat cover plate. The cover plate is attached to the RFC30, RFC43 AND RFC49 CONCEALED SPRINKLERS skirt, using 135°F(57°C)ordinary temperature classifica- MUST BE INSTALLED ONLY WITH 135°F RATED COV- tion solder.When the ceiling temperature rises,the solder ERS. holding the cover plate releases the cover allowing the Note:A leak tight 1/2" NPT(R1/2)sprinkler joint can be ob- deflector to drop into position and exposing the sprinkler tained with a torque of 8-18 ft-lbs (10,8- 24,4 N-m). Do not inside to ceiling temperature. The subsequent operation tighten sprinklers over maximum recommended torque. It of the solder link opens the waterway and causes the de- may cause leakage or impairment of the sprinklers. flector to drop into position to distribute the discharging Cover assemblies provide up to 1/2" (13mm) of adjust- water in a hemispherical pattern below the sprinkler de- ment. Turn the cover clockwise until the flange is in con- flector. Any adjustment of thread engagement between tact with the ceiling. For the push-on/thread-off option, the cover plate and cup will assure that the drop-down the cover assembly is pushed onto the cup and final ad- deflector is properly located below the ceiling. The resi- justment is made by turning the cover clockwise until the dential distribution pattern contains a finer droplet size skirt flange makes full contact with the ceiling. Cover re- than a standard sprinkler, and the pattern produces sig- moval requires turning in the counter-clockwise direction. nificantly higher wall wetting. In ceilings that have a plenum space above the After a 25/s inch diameter hole is cut in the ceiling, the sprinkler,the plenum space may have neutral or neg- sprinkler is to be installed with the Model FC Wrench. ative pressurization but must not be positively pres- When installing a sprinkler, the wrench is first positioned surized. Inspect all sprinklers after installation to en- into the sprinkler/cup assembly and around the hexago- sure that the gap between the cover plate and ceiling nal body of the sprinkler frame. The Wrench must bottom and the 4 slots in the cup are all open and free from out against the cup in order to ensure proper, safe instal- any air flow impediment. lation. The sprinkler is then tightened into the pipe fitting. Sprinkler CCP AssemblyMax. Thread Nominal p Ambientient K Max.MModel Temp Rating Temp. Pressure reSize Orifice Temp. Factor(SIN) Inch(mm) Inch (mm) PF /C rF rC /F pC psi (bar) RFC 30 1/2„(15) 21/64(8,2) 165 74 135 57 100 38 3.0(43.2) 175(12) (RA0611) RFC 43 1/2"(15) 3/8(10) 165 74 135 57 100 38 4.3(62) 175(12) (RA0612) RFC 49 1/"(15) 7/6(11) 165 74 135 57 100 38 4.9(70.6) 175(12) (RA0616) Note: 1 bar= 100 Kpa RFC 30 Ordinary Temp. Rating Max. Coverage ?F/74r'C) Top of Deflector Minimum area Max. Spacing (165to Ceiling Installation Spacing Ft x Ft(m x m) Ft(m) Flow Pressure Inch (mm) Type Ft(m) GPM (Umin) PSI(bar) 12 x 12(3,6 x 3,6) 12(3,6) 9(34,1) 9.0(0,62) Smooth Ceilings 1/2 to 1(13 to 25.4) Beamed Ceilings per NFPA 13D, 13R or Concealed 8(2,4) 14 x 14(4,3 x 4,3) 14(4,3) 10(37,8) 11.0(0,76) 13 installed in beams 1/2 to 1(13 to 25.4) For Ceiling types refer to NFPA 13, 13R or 13D 2. RFC 43 Ordinary Temp. Rating Max. Coverage Max. Spacing (165PF/74PC) Top of Deflector Installation Minimum area to Ceiling Spacing Ft x Ft(m x m) Ft(m) Flow Pressure Inch (mm) Type Ft(m) GPM (Vmin) PSI(bar) 12 x 12(3,6 x 3,6) 12(3,6) 12(4,5) 7.8(0,54) 14 x 14(4,3 x 4,3) 14(4,3) 13(49) 9.1 (0,63) — Smooth Ceilings 1/2 to 1(13 to 25.4) 16 x 16(4,9 x 4,9) 16(4,9) 13(49) 9.1 (0,63) Beamed Ceilings per NFPA 13D, 13R or Concealed 8(2,4) 13 installed in beams'to 1(13 to 25.4) 18 x 18(5,5 x 5,5) 18(5,5) 18(68) 17.5(1,21) 20x20(6,1 x6,1) 20(6,1) 21 (79) 23.8(1,64) For Ceiling types refer to NFPA 13, 13R or 13D RFC 49 Ordinary Temp. Rating Max.Coverage Max. Spacing (165WF/74/C) Top of Deflector Installation Minimum area Ft(m) Flow Pressure to Ceiling Type Spacing Ft x Ft(m x m) GPM(1../min) PSI(bar) Inch (mm) Ft(m) 12 x 12(3,6 x 3,6) 12(3,6) 13(49) 7.0(0,48) 14 x 14(4,3 x 4,3) 14(4,3) 13(49) 7.0(0,48) Smooth Ceilings 1 to 1(13 to 25.4) 16 x 16(4,9 x 4,9) 16(4,9) 13(49) 7.0(0,48) Beamed Ceilings per NFPA 13D, 13R or Concealed 8(2,4) 13 installed in beams 1 to 1(13 to 25.4) 18 x 18(5,5 x 5,5) 18(5,5) 17(64,3) 12.0(0,83) 20x20(6,1 x6,1) 20(6,1) 20(75,73) 16.7(1,14) For Ceiling types refer to NFPA 13, 13R or 13D Maintenance Model RFC30, RFC43 and RFC49 Concealed Sprin- symmetric lever mechanism, maintaining a Teflon-coated klers should be inspected and the sprinkler system Belleville spring washer and machined brass cap water maintained in accordance with NFPA 25. Do not clean seal assembly containing no plastic parts. Sprinkler K- sprinklers with soap and water, ammonia or any other factor shall be nominal 3.0 (43.2), 4.3(62), and 4.9(70.6) cleaning fluids. Remove dust by using a soft brush or having a 5/6", 3/" and 7/16" orifice. Temperature rating gentle vacuuming. Remove any sprinkler cover plate as- shall be Ordinary 165°F(74°C); cover plate temperature sembly which has been painted (other than factory ap- rating to be 135°F(57°C). Cover plate assembly shall plied) or damaged in any way. A stock of spare sprin- consist of a brass cover plate and copper alloy retainer klers should be maintained to allow quick replacement flange allowing a'/2" cover plate adjustment. Any secure of damaged or operated sprinklers. Prior to installation, engagement between the cover plate and the cup will sprinklers should be maintained in the original cartons assure that the drop-down deflector is properly located and packaging until used to minimize the potential for below the ceiling. A plastic protective cap shall be damage to sprinklers that would cause improper opera- provided and factory installed inside the sprinkler cup tion or non-operation. to protect the drop-down sprinkler deflector from dam- age, which could occur during construction before the Model RFC30, RFC43 and RFC49 Residential cover plate is installed. Standard cover finish: [Chrome] Concealed Sprinkler Specification [White] [Specialty—specify]. Residential concealed sprinklers shall be Reliable Model RFC30, SIN RA0611 Sprinklers shall be cULus Listed low flow residential con- (Bulletin 006), Model RFC43, SIN RA0612(Bulletin 006) cealed sprinklers with drop-down deflector and adjust- or Model RFC49, SIN RA0616(Bulletin 006). able flat cover plate engineered for a minimum design density of 0.05 gpm/ft2. Sprinkler frame and deflector shall be of bronze frame construction having a'/2" NPT thread. Thermal element shall consist of an approved black-painted beryllium-nickel fusible solder link with 3. Ordering Information Cover Plate Finishesf1 Specify: Standard Finishes 1. Sprinkler Model Chrome 2. Cover Plate Finish White Paint 3. Thread-On or Special Application Push-On Feature Finishes/21 Bright Brass Finished Bronze Black Plating li Black Paint Off White Satin Chrome I r,....J (1) Other finishes and colors are available on special order. Consult factory for details. Coverplate custom paint is semi-gloss, unless specified • otherwise. 00 (2) For the perforated style cover- plate, consult factory for avail- ability on these and other cus- tom finishes. 1— t"x 1/2"REDUCING TEE OR ELBOW I --T-- II -- —b7-- :--- i ---: --- 2i"[66.55mm] 27 "[58.42mm] D/A I Lam-__1 OLE IN CEILING F CUP 2"[50.8mm] MAX. ji FACE OF FITTING i"[12.70mm] MAX. 1\\\\\\\N"— TO FACE OF CEILING COVER ADJUSTMENT \\\\\\\, ) \\\\\\\ DIMENSION \\\\\\\\ Ili 1/2"[12.7Omm]MIN. TO CEILING2 //////// 1"[25.4mm]MAX. i l I. , „„„, i DROPPED DEFLECTOR le it :_ --�� TO CEILINGi CEILING _# tis A"[4.96mm]—f FLAT COVER PLATE 3i"[84.21 mm] DIA. - ASSEMBLY SPRINKLER COVER PLATE: 1/2" [12.7mm] ADJUSTMENT IC The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association,Factory Mutual Research Corporation,or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Products manufactured and distributed by Reliable have been protecting life and property for over 90 years,and are installed and serviced by the most highly qualified and reputable sprinkler contractors located throughout the United States,Canada and foreign countries. Manufactured by ReiReliable Automatic Sprinkler Co.,Inc. ® Recycled ® (800)431-1588 Sales Offices ' (800)848-6051 Sales Fax Revision lines indicate updated or new data. (914)829-2042 Corporate Offices www.reliablesprinkler.com Internet Address EG.Printed in U.S.A.11/14 P/N 9999970261 VicoWorldwide Fire Protection Contacts www.tyco-fire.com Products RAPID RESPONSE Series LFII Residential Sprinklers 4.2 K-factor Flush Pendent Wet Pipe and Dry Pipe Systems General of residential fires and to improve the chance for occupants to escape or be Description evacuated. The TYCO RAPID RESPONSE Series Dry Pipe System Application TheII CO Flush The Series LFII Residential Flush SprinklersLR (TY2284)lare decorative,Pendent Pendent Sprinklers offers a laboratory fast response,fusible solder sprinklers approved option for systems, designingdry pipe residential sprinkler whereas, designed for use in residential occu- most residential sprinklers are labora- pancies such as homes, apart- tory approved for wet systems only. ments, dormitories, and hotels. When aesthetics is the major consideration, Through extensive testing, it has been the Series LFII Residential Sprinklers determined that the number of design (TY2284)should be the first choice. sprinklers (hydraulic design area) The Series LFII Residential Sprinklers for the Series LFII Residential Flush are intendedSeries for usin the following Pendent Sprinklers (TY2284) need cenntios: not be increased over the number of Sprinkler sdesign sprinklers (hydraulic design • wet and dry pipe residential sprinkler area)as specified for wet pipe sprinkler Identification systems for one- and two-family systems, as is customary for density/ dwellings and mobile homes per area sprinkler systems designed per Number (SIN) NFPA 13D NFPA 13. • wet and dry pipe residential sprinkler Consequently, the Series LFII TY2284 systems for residential occupancies Residential Sprinklers (TY2284) offer up to and including four stories in the features of non-water filled pipe in height per NFPA 13R addition to not having to increase the • wet and dry pipe sprinkler systems number of design sprinklers(hydraulic fordesign area) for systems designed to the residential portions of any occupancy per NFPA 13 NFPA 13, 13D,or 13R. The flush design of the Series LFII NOTICE Residential Sprinklers features a The Series LFII Residential Flush separable escutcheon providing 3/8 Pendent Sprinklers(TY2284)described inch (9,5 mm)vertical adjustment.This herein must be installed and maintained adjustment reduces the accuracy to in compliance with this document and which the pipe drops to the sprinklers the applicable standards of the National must be cut. Fire Protection Association, in addition The Series LFII Residential Sprinklers to the standards of any authorities have been designed with heat sensi- having jurisdiction. Failure to do so tivity and water distribution charac- may impair the performance of these teristics proven to help in the control devices. The owner is responsible for main- taining their fire protection system and devices in proper operating condition. IMPORTANT Contact the installing contractor Always refer to Technical Data or sprinkler manufacturer with any Sheet TFP700 for the "INSTALLER questions. WARNING"that provides cautions with respect to handling and instal- lation of sprinkler systems and components.Improper handling and installation can permanently damage a sprinkler system or its compo- nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Page 1 of 6 FEBRUARY 2014 TFP420 TFP420 Page 2 of 6 I 3/32"(2,4 mm)TYP. FACE OF WRENCH DO NOT SPRINKLER *-----k4 RECESS f.� OVER TIGHTEN FITTING W #4948 WRENCH&SOCKET il �f11_11 COMBINATIONII � I ��� 29/32±3/16" II liI I �.� (23,0±4,8 mm) �� 441,461116ACEPTS WRENCH \\\\\ \\\ 1 3/8"SOCKET #4947 DRIVE \ SOCKET CEILING LEVEL MOUNTING - TOLERANCE SURFACE LIMIT i� SPRINKLER WRENCHING FIGURE 2 PROTECTIVE CAP AREA SPRINKLER SOCKET 1A WRENCH&SOCKET 2"(50 mm)DIA. - COMBINATION I Niku-....... tiney 29/32±3/16" _ _ (..------=------- -1 2-1/4" (23,0±4,8 mm) 11I1 (57,2 mm) 11-1,7 jz = HEAT -- COLLECTOR 1 1 2-15/16"(75 mm)DIA. 1B a 1/2" NPT r 7/16"(11,1 mm) FIGURE 3 _ NOMINAL MAKE-IN PROTECTIVE CAP REMOVAL 9/16"(14,2 mm) _1 TOOL 15/16"(23,6 mm) I,�I: \\\\� \\ DEFLECTOR ligig _.-- IN OPERATED POSITION 1C FIGURE 1 RAPID RESPONSE SERIES LFII RESIDENTIAL FLUSH PENDENT SPRINKLER(TY2284) TFP42O Page 3 of 6 Technical System Types Operational Sensitivity Per the UL Listing, wet pipe and dry The sprinklers are to be installed in Data pipe systems may be utilized. Per the the flush position per Figure 1 with the C-UL Listing, only wet pipe systems provided escutcheon. may be utilized. Approvals Sprinkler Spacing UL Listed for use with wet pipe and dry Ceiling Types The minimum spacing between sprin- pipe systems Smooth flat horizontal, or beamed, or klers is 8 feet (2,4 m). The maximum C-UL Listed for use only with wet pipe sloped, in accordance with the 2013 spacing between sprinklers cannot systems Edition of NFPA 13D, 13R, or 13 as exceed the length of the coverage applicable. area(Table A or B) being hydraulically For details on approvals, refer to the calculated (e.g., maximum 12 feet for a Design Criteria section. Hydraulic Design 12 ft. x 12 ft. coverage area, or 20 feet (NFPA 13D and 13R) for a 20 ft.x 20 ft. coverage area). Maximum Working Pressure For systems designed to NFPA 13D 175 psi (12,1 bar) or NFPA 13R, the minimum required Precautionary Warnings for sprinkler flow rate are given in Tables Corrosive Environments Discharge Coefficient A and B as a function of temperature The Series LFII Residential Flush K=4.2 GPM/psif12(60,5 LPM/barlI2) rating and the maximum allowable Sprinkler (TY2284) must be installed Temperature Rating coverage areas.The sprinkler flow rate in a non-corrosive environment. The 162°F(72°C) is the minimum required discharge from improper use of corrosive agents such each of the total number of "design as flux, or other products that contain Vertical Adjustment sprinklers" as specified in NFPA 13D chloride ions,whether applied internally 3/8 inch (9,5 mm) or NFPA 13R. The number of"design or externally to the sprinkler system, sprinklers" specified in NFPA 13D may result in corrosion of the sprinkler Finishes and 13R for wet pipe systems is to heads, or stress corrosion cracking, Antique Brass be applied when designing dry pipe which in turn may cause the sprinkler Signal White systems. heads to develop leaks, operate unex- Jet Black pectedly or improperly. Chrome Hydraulic Design (NFPA 13) Accordingly, it is essential that the Physical Characteristics For systems designed to NFPA 13, the Series LFII Residential Flush Sprinkler Body Copper Alloy number of design sprinklers is to be (TY2284) be installed only by expe- Deflector Copper the four most hydraulically demanding rienced fire sprinkler engineers, who Valve Cap Copper Alloy sprinklers. The minimum required comply fully with NFPA 13, 13D, 13R Orifice Seal PTFE discharge from each of the four and 25, ASTM B 813, ASTM B 828 Heat Collectors Copper sprinklers is to be the greater of the and Copper Development Association following: (CDA). Operation •The flow rates given in Tables A Copper Sprinkler System Piping The sprinkler assembly contains a small and B as a function of temperature Any time copper piping is used in fusible solder element.When exposed rating and the maximum allowable any part of a fire sprinkler system, to sufficient heat from a fire,the solder coverage area. the copper piping must be installed melts and enables the internal compo- •A minimum discharge of 0.1 in conformance with all applicable nents of the sprinkler to fall away. At gpm/ft2 over the "design area" standards and requirements for copper this point the sprinkler activates with comprised of the four most hydrau- piping, including: NFPA 13, 13D, 13R the deflector dropping into its operated lically demanding sprinklers for and 25, ASTM B 813, ASTM B 828, position (Figure 1C), permitting water the actual coverage areas being and Copper Development Association to flow. protected by the four sprinklers. (CDA). Any soldering in any part of a sprinkler system, either internally or The number of "design sprinklers" externally, must be done with use of Design specified in NFPA 13 for wet pipe only an ASTM B 813 approved flux. systems is to be applied when Residual flux must be thoroughly Criteria designing dry pipe systems. removed from both the interior and The TYCO RAPID RESPONSE Series Dry Pipe System Water Delivery exterior sure sprinklerces of the had pipingbefore LFII Residential Flush Pendent When using the Series LFII Residential of impropertalling the heads.The use Sprinklers(TY2284)are UL and C-UL Pendent Sprinklers(TY2284)in drypipe of vflex, or the failure, maytthort oughly remove proper flux, result Listed for installation in accordance sprinkler systems, the time for water in corrosion of the sprinkler heads or with this section. delivery must not exceed 15 seconds stress corrosion cracking, which in Residential Sprinkler Design Guide for the most remote operating sprinkler. turn may cause the sprinkler heads to When conditions exist that are outside Obstruction to Water Distribution develop leaks,operate unexpectedly or the scope of the provided criteria, refer Sprinklers are to be located in accor- improperly. to the Residential Sprinkler Design dance with the obstruction rules of Guide TFP490 for the manufacturer's NFPA 13D, 13R, and 13 as applicable recommendations that may be accept- for residential sprinklers as well as with able to any local authority having the obstruction criteria described within jurisdiction. the Technical Data Sheet TFP490. TFP420 Page 4 of 6 WET PIPE SYSTEM Maximum Minimum Flow and Residual Pressure(I),c) Coverage Maximum Ordinary Temp Rating Area(a) Spacing 162°F(72°C) Minimum Ft.x Ft. Ft. Heat Collector Installation Spacing (m x m) (m) Flow Pressure to Ceiling Type Ft. 1 GPM PSI (m) (L/min) (bar) 12 x 12 12 13 9.6 Smooth (3,7 x 3,7) (3,7) (49,2) (0,66) Ceilings 14 x 14 14 13 9.6 23/32 to 1-3/32 (4,3 x 4,3) (4,3) (49,2) (0,66) inches 16 x 16 16 14 11.1 Beamed Flush 8 (4,9 x 4,9) (4,9) (53,0) (0,77) Ceilings per (2,4) 18x18 18 18 18.4 NFPA 13D (5,5 x 5,5) (5,5) (68,1) (1,27) or 1 inches inches 20 x 20 20 22 27.4 below bottom (6,1 x 6,1) (6,1) (83,3) (1,89) of beam (a) For coverage area dimensions less than or between those indicated,use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. (b) Requirement is based on minimum flow in GPM(LPM)from each sprinkler.The associated residual pressures are calculated using the nominal K-factor.Refer to Hydraulic Design under the Design Criteria section. (c) For NFPA 13 residential applications,the greater of 0.1 gpm/ft2 over the design area or the flow in accordance with the criteria in this table must be used. TABLE A WET PIPE SYSTEM SERIES LFII RESIDENTIAL 4.2 K-FACTOR FLUSH PENDENT SPRINKLERS(TY2284) NFPA 13D, 13R,AND 13 HYDRAULIC DESIGN CRITERIA DRY PIPE SYSTEM Maximum Minimum Flow and Residual Pressure(b,c) Coverage Maximum Area(a) Spacing Ordinary Temp Rating Minimum Ft. 162°F(72°C) Ft.x Ft. Heat Collector Installation Spacing (m x m) (m) Flow Pressure to Ceiling Type Ft. GPM PSI (m) (L/min) (bar) 12 x 12 12 13 9.6 Smooth (3,7 x 3,7) (3,7) (49,2) (0,66) Ceilings 14 x 14 14 13 9.6 23/32 to 1-3/32 (4,3 x 4,3) (4,3) (49,2) (0,66) inches 16 x 16 16 13 9.6 Beamed Flush 8 (4,9 x 4,9) (4,9) (49,2) (0,66) Ceilings per (2,4) 18x18 18 17 16.4 NFPA 13D (5,5 x 5,5) (5,5) (64,4) (1,13) or 23/32 inches 20 x 20 20 20 22.7 below bottom (6,1 x 6,1) (6,1) (75,7) (1,56) of beam (a) For coverage area dimensions less than or between those indicated,use the minimum required flow for the next highest coverage area for which hydraulic design criteria are stated. (b) The Minimum Flow requirement is based on minimum flow in GPM(LPM)from each sprinkler.The associated residual pressures are calculated using the nominal K-factor.Refer to Hydraulic Design under the Design Criteria section. (c) For NFPA 13 residential applications,the greater of 0.1 gpm/ft2 over the design area or the flow in accordance with the criteria in this table must be used. TABLE B DRY PIPE SYSTEM SERIES LFII RESIDENTIAL 4.2 K-FACTOR FLUSH PENDENT SPRINKLERS(TY2284) NFPA 13D, 13R,AND 13 HYDRAULIC DESIGN CRITERIA TFP42O Page 5 of 6 Installation with the ceiling. Do not continue Automatic sprinkler systems are to push the Escutcheon such that recommended to be inspected, The TYCO RAPID RESPONSE Series it lifts a ceiling panel out of its tested, and maintained by a qualified LFII Residential Flush Pendent normal position. If the Escutcheon Inspection Service in accordance with Sprinklers(TY2284) must be installed cannot be engaged with the sprinkler, local requirements and/or national in accordance with this section. or the Escutcheon cannot be engaged codes. sufficiently to contact the ceiling, General Instructions relocate the sprinkler fitting as Limited The Protective Cap is to remain on necessary. the sprinkler during installation until Warranty the ceiling installation is complete. Care and The Protective Cap must be removed For warranty terms and conditions,visit to place the sprinkler in service. Maintenance www.tyco-fire.com. A leak-tight 1/2 inch NPT sprinkler joint should be obtained by applying a The TYCO RAPID RESPONSE Series Ordering minimum-to-maximum torque of 7 to 14 LFII Residential Flush Pendent ft.-lbs. (9,5 to 19,0 Nm). Higher levels Sprinklers (TY2284) must be main- Procedure of torque can distort the sprinkler Inlet tained and serviced in accordance with with consequent leakage or impairment this section. Contact your local distributor for avail- of the sprinkler. Before closing a fire protection system ability.When placing an order, indicate Do not attempt to compensate for main control valve for maintenance the full product name and Part Number insufficient adjustment in the sprinkler work on the fire protection system (P/N). by under- or over-tightening the that it controls, obtain permission to Sprinkler/Support Cup Assembly. Re- shut down the affected fire protection Sprinkler Assembly adjust the position of the sprinkler systems from the proper authorities Specify: Series LFII (TY2284), K=4.2, fitting to suit. and notify all personnel who may be Residential Flush Pendent Sprinkler affected by this action. without Escutcheon and having a Each sprinkler must be inspected (specify)finish, P/N(specify): before installation. Do not use any Absence of the outer piece of an sprinkler that exhibits any deformations escutcheon, which is used to cover Antique Brass P/N 51-123-1-162 or cracks, including cracks on the a clearance hole, can delay sprinkler Signal White(RAL9003) P/N 51-123-4-162 protective cap. operation in a fire situation. Jet Black(RAL9005) P/N 51-123-6-162 Chrome Plated P/N 51-123-0-162 Step 1.The sprinkler must be installed The owner must assure that the sprin- only in the pendent position and with klers are not used for hanging any Escutcheon the sprinkler waterway centerline objects and that the sprinklers are only Specify: Escutcheon for Series LFII perpendicular to the mounting surface. cleaned by means of gently dusting (TY2284), K = 4.2, Residential Flush with a feather duster; otherwise, non- Pendent Sprinkler with(specify)finish, Step 2. Install the sprinkler fitting so operation in the event of a fire or inad- P/N (specify): that the distance from the face of the vertent operation may result. Antique Brass P/N 56-123-1-001 fitting to the mounting surface will be Signal White(RAL9003) P/N 56-123-4-001 nominally 29/32 inches (23,0 mm) as Sprinklers which are found to be shown in Figure 1A. leaking or exhibiting visible signs of Jet Black(RAL9005) P/N 56-123-6-001 g Chrome P/N 56-123-9-001 Step 3. With pipe thread sealant corrosion must be replaced. applied to the pipe threads, hand- Automatic sprinklers must never be Accessories tighten the sprinkler into the sprinkler painted, plated, coated, or otherwise Specify:Wrench and Socket for Series fitting. altered after leaving the factory. LFII (TY2284)Residential Flush Pendent Modified or overheated sprinklers must Sprinkler, P/N 56-000-4-948 Step 4.Tighten the sprinkler using only be replaced. Specify:Socket for Series LFII(TY2284) the Sprinkler Socket or Wrench Residential Flush Pendent Sprinkler, & Socket Combination (Figure 2). Care must be exercised to avoid P/N 56-000-4-947 The wrench recess of the socket is to damage to the sprinklers - before, be applied to the sprinkler wrenching during, and after installation.Sprinklers Specify: Protective Cap Removal area(Figure 1A). damaged by dropping,striking,wrench Tool for Series LFII Residential twist/slippage, or the like, must be Flush Pendent Sprinkler (TY2284), Step 5. Use the"ceiling level tolerance replaced. P/N 56-000-4-300 limit" indicator on the Protective Cap to check for proper installation The owner is responsible for the height. Relocate the sprinkler fitting as inspection,testing,and maintenance of necessary. If desired, the Protective their fire protection system and devices Cap may also be used to locate the in compliance with this document, as center of the clearance hole by gently well as with the applicable standards of pushing the ceiling material against the the National Fire Protection Association center point of the Cap. (e.g., NFPA 25), in addition to the Step 6. After the ceiling has been standards of any authorities having completed with the 2 inch (50 jurisdiction. Contact the installing contractor or sprinkler manufacturer mm diameter clearance hole, use the Protective Cap Removal Tool regarding any questions. (Figure 3) to remove the Protective Cap and then push on the Escutcheon until its flange just comes in contact TFP420 Page 6 of 6 GLOBAL HEADQUARTERS 11400 Pennbrook Parkway,Lansdale,PA 19446 I Telephone+1-215-362-0700 Copyright©2014 Tyco Fire Products,LP. All rights reserved. t co TEFLON is trademark of The DuPont Corporation. Fire Protection Products Bulletin 135 Rev. M CIJ® Model Fl Residential Sprinklers for CO Design Density of .05 gpmfft2 Model Fl Res Sprinklers engineered for the lowest flows to meet the minimum design density of.05 gpmfft2 Types: 1. Fl Res 30 Pendent . 2. Fl Res 30 Recessed Pendent/F2 3. Fl Res 30 Recessed Pendent/FP is fetid r r� 4. Fl Res 49 Pendent r; ' 5. Fl Res 49 Recessed Pendent/F1 _ - u= `{ , a 6. Fl Res 49 Recessed Pendent/FP 7. Fl Res 58 Pendent Fl Res 30, 49, 58&76 Fl Res 30, 49, 58&76 8. Fl Res 58 Recessed Pendent/F1 Recessed Pendent/Fl Recessed Pendent/FP Fl Res 58 HSWX 9. Fl Res 58 Recessed Pendent/FP 10. Fl Res 76 Pendent 11. Fl Res 76 Recessed Pendent/F1 12. Fl Res 76 Recessed Pendent/FP 13. Fl Res 30 CCP Pendent ! a ‘11-1. 'i!1) 14. Fl Res 49 CCP Pendent \ ./ :+' 15. Fl Res 58 CCP Pendent 16. Fl Res 76 CCP Pendent 17. Fl Res 44 HSW Fl Res 30, 49, 58& 76 Fl Res 44&58 Fl Res 44 SWC 18. Fl Res 44 Recessed HSW/F2 CCP Pendent Recessed HSW/F2 19. Fl Res 58 HSW 20. Fl Res 58 HSWX Horizontal Sidewall sprinklers(Figs. 5, 6&7)are equally attrac- 21. KRes58 HSWX tive when above ceiling piping cannot be used. 22. Fl Res 58 HSW Recessed HSW/F2 The 3mm glass-bulb pendent sprinklers permit the efficient use 23. Fl Res 44 SWC of residential water supplies for sprinkler coverage in residential Listings & Approvals fire protection design. The low flow Fl Res sprinklers are specially engineered for fast 1. Listed by Underwriters Laboratories Inc. and thermal response to meet the sensitive fire protection applica- UL Certified for Canada (cULus) tion needs of the latest residential market standards (UL 1626 Standard). Upon fire conditions, rising heat causes a sprinkler's Sprinklers for .10 Density: Refer to Bulletin 176 heat-sensitive element,glass bulb or link to actuate,releasing the UL Listing Category waterway for water flow onto the deflector,evenly distributing the Residential Automatic Sprinkler discharged water to control a fire. UL Guide Number Technical Data: VKKW • Thermal Sensor: Soldered Element (Link) or Nominal 3mm glass-bulb Patents • Sprinkler Frame : Brass Casting US Patent No. 6,516,893 applies to the Model Fl Res 49 • Sprinklers' Pressure Rating : 175 psi & 58 Pendent Sprinklers Factory Hydrostatically Tested to 500 psi US Patent No. 7,353,882 applies to Model Fl Res 44&58 • Thread Size: 1/2" NPT(R'/2) HSW Sprinklers • K-Factor: 3.0(43.2)(Actual)-Fl Res 30 Pendent Sprinkler US Patent No. 7,784,555 applies to Model Fl Res 44 SWC 4.9(70.6)(Actual) Fl Res 49 Pendent Sprinkler Sprinklers 5.8 (83.5)(Actual)-Fl Res 58 Pendent&HSW Sprinkler Product Description 7.6(109)(Actual)-Fl Res 76 Pendent Sprinkler Model Fl Res Pendent sprinklers (Figs. 1, 2, 3, &4) are fast 4.4(63)(Actual)-Fl Res 44 HSW Sprinkler response sprinklers combining excellent durability,high sensitiv- • Density: Minimum 0.05 gpm/ft2 ity glass-bulb and low profile decorative design. The Fl Res Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523 Application Model Fl Res Sprinklers are used for Residential Fire Pro- the only recessed escutcheons to be used with Model Fl Res tection according to UL 1626 Standard*. For ceiling types: sprinklers. Use of any other recessed escutcheon will void all Smooth Flat Horizontal,or beamed,or sloped, in accordance approvals and warranties. For installing Model Fl Res Pen- with NFPA 13D, 13R,or 13 2013 editions. Be sure that orifice dent sprinklers use only the Model D sprinkler Wrench; for size,temperature rating,deflector style and sprinkler type are installing Models Fl Res Recessed Pendent, CCP & SWC in accordance with the latest published standards of The Na- sprinklers use only the Model GFR2 sprinkler wrench; for in- tional Fire Protection Association or the approving authority stalling Model Fl Res Recessed HSW sprinklers use only the having jurisdiction. Model GFR2 Sprinkler Wrench. Use of wrenches other than Installation those specified may damage these sprinklers. Install Fl Res Models Fl Res sprinklers are to be installed as shown. 44 with a ceiling to deflector distance of 4" 12". Flow arrow Model F1, F2 and FP Escutcheons, illustrated herewith, are on deflector must point away from near wall and "Top" mark - Model must face ceiling. Escutcheon*, Fl or F2, Data: Adjustment "A" Face of fitting to ceiling B Type Inch(mm) Inch(mm) Inch(mm) Deflector Distance below bottom of beam Inch(mm) F1 3/4(19.0) Min.Recessed=15/8(41.3) 3/8(9.5) 13/4(44.4) Max.Recessed=7/8(22.2) 11/8(28.6) 1 (25.4) F2 /2(12.7) Min.Recessed=15/8(41.3) 3/6(9.5) 13/4(44.4) Max.Recessed=11/8(28.6) 7/6(22.2) 11/4(31.7) *Note:Escutcheons F1 or F2 may be used with Model F1 Res 49,58&76 Recessed Pendent Sprinkler • Model Fl Res 30 Recessed Pendent/F2 • Model Fl Res 30, 49, 58 &76 Pendent • Model Fl Res 49, 58 &76 Recessed Pendent/Fl f I, .r �J . .r F1 escutcheon, 3/4" (19mm) adjustment �— 2 1/4"HOLE DIA. � [57.2mm] _ 1 15/16"DIA. [49.2mm] TURN COLLAR UNTIL I rt 1"X 1/2"REDUCER TIGHT AGAINST SPRINKLER 1 FACE OF FITTING TO .=--- --1 WRENCH BOSS. r 1 CEILING DIMENSION.. _ 3/8"-1 1/8"(F1 ESCUTCHEON) /, ' =i 3/8"-7/8"(F2 ESCUTCHEON) II ®�wl IIp �� =KJ. III!'111!1_ ..I ADJUSTMENT El!l-Willi 1%//. Ii'u NIli } I�i 1 'i l ] 1 1 Vit _nit �il AN iHi, [.31. 78//V 1 1 ••.•�� _ .... 2 27/32"DIA. I3sFt;o.3 1 +asFroie [72.2mm] Fig. 1 Fig. 2 Technical Data: F1 Res 30 Pendent and Recessed Pendent (SIN R3511) Thread Nominal Orifice Max.Pressure Sprinkler Temp.Rating Max.Ambient Temp. Actual K Sprinkler Length Size Inch(mml psi(bar) PF PC PF PC Factor Inch(mm) /(RN�T 8 21/64"(8.2) 175(12) 175 155 7g 100 38 3.0(43.2) 2.25(57) Ordinary Temp.Rating Intermediate Temp.Rating Max.Coverage area Max. Minimum g (155PF/68PC) (175PF/79°C) Top of Deflector to Ceiling Ft x Ft(m x m) Spacing Flow Pressure Flow Pressure Inch(mm) Spacing Ft(m) GPM(L/min) PSI(bar) GPM(L/min) PSI(bar) Ft(m) 12 x 12(3,6 x 3,6) 12(3,6) 8(30,3) 7.0(0,48) 8(30,3) 7.0(0,48) Smooth Ceilings 11/4 to 4(31.7 to 102) using F2 escutcheon. 14 x 14(4,3 x 4,3) 14(4,3) 10(37,8) 11 (0,76) 10(37,8) 11 (0,76) Beamed Ceilings per NFPA 13D, 13R 8(2,4) or 13 installed in beams 11/4 to 13/4 16 x 16(4,9 x 4,9) 16(4,9) 13(49) 18.8(1,3) 13(49) 18.8(1,3) (31.7 to 44.4)using F2 escutcheon For Ceiling types refer to NFPA 13, 13R or 13D 2. Technical Data: F1 Res 49 Pendent and Recessed Pendent(SIN R3516) Thread Nominal Orifice Max. Sprinkler Max. Actual Sprinkler Size Inch(mm) Pressure Temp.Rating Ambient Temp. K Length psi(bar) PF rC 1°F wC Factor Inch(mm) /z"NPT7/16"(11) 175(12) 155 68 100 38 4.9(70.6) 2.25(57) (R1/2) 175 79 150 66 Ordinary Temp.Rating Intermediate Temp.Rating Top of Deflector Minimum Max.Coverage area Max.Spacing (155PF/681C) (1751F/791C) Ft x Ft(m x m) Ft(m) Flow Pressure Flow Pressure to Ceiling Spacing GPM(L/min) PSI(bar) GPM(L/min) PSI(bar) Inch(mm) Ft(m) 12 x 12(3,6 x 3,6) 12(3,6) 13(49) 7.0(0,48) 13(49) 7.0(0,48) Smooth Ceilings 11/4 to 4(31.7 to 102)using F2 escutcheon. 14 x 14(4,3 x 4,3) 14(4,3) 13(49) 7.0(0,48) 13(49) 7.0(0,48) 1 to 4(25.4 to 102)using F1 escutcheon. 16 x 16(4,9 x 4,9) 16(4,9) 13(49) 7.0(0,48) 13(49) 7.0(0,48) Beamed Ceilings per NFPA 8(2,4) 13D, 13R or 13 installed in 18 x 18(5,5 x 5,5) 18(5,5) 17(64,3) 12(0,83) 17(64,3) 12(0,83) beams 11/4 to 13/4 (31.7 to 44.4)using F2 escutcheon, 1 20 x 20(6,1 x 6,1) 20(6,1) 20(75,7) 16.7(1,14) 20(75,7) 16,7(1,14) to 13/4(25.4 to 44.4)using F1 escutcheon For Ceiling types refer to NFPA 13, 13R or 13D Ordinary Temp.Rating Intermediate Temp.Rating Top of Deflector Minimum Max.Coverage area Max.Spacing (1551F/68WC) (1751F/791C) Ft x Ft(m x m) Ft(m) Flow Pressure Flow Pressure to Ceiling Spacing GPM(L/min) PSI(bar) GPM(L/min) PSI(bar) Inch(mm) Ft(m) 12 x 12(3,6 x 3,6) 12(3,6) 15(57) 9.4(0,65) 15(57) 9.4(0,65) Smooth Ceilings 4 to 8(100 to 203)using F2 escutcheon. 14 x 14(4,3 x 4,3) 14(4,3) 16(60,5) 10.6(0,73) 16(60,5) 10.6(0,73) 4 to 8(100 to 203)using F1 escutcheon. 16 x 16(4,9 x 4,9) 16(4,9) 17(64,3) 12.0(0,83) 17(64,3) 12.0(0,83) Beamed Ceilings per NFPA 13D, 8(2,4) 13R or 13 installed in beams 18 x 18(5,5 x 5,5) 18(5,5) 19(72) 15.0(1,0) 19(72) 15.0(1,0) 41/4 to 8(108 to 203)using F2 escutcheon,4 to 8(100 to 203) 20 x 20(6,1 x 6,1) 20(6,1) 22(83,2) 20.2(1,4) 22(83,2) 20.2(1,4) using F1 escutcheon Technical Data: F1 Res 58 Pendent and Recessed Pendent(SIN R3513) Thread Nominal Orifice Max. Sprinkler Max. Actual Sprinkler Pressure Temp.Rating Ambient Temp. Length Size Inch(mm) psi(bar) WF PC PF pC K Factor Inch(mm) /z"NPT1/"(13) 175(12) 155 68 100 38 5.8(83.5) 2.25(57) (R1/) 175 79 150 66 Ordinary Temp.Rating Intermediate Temp.Rating Top of Deflector Minimum Max.Coverage area Max.Spacing (155rF/68WC) (175"F7791C) Ft x Ft(m x m) Ft(m) Flow Pressure Flow Pressure to Ceiling Spacing GPM(L/min) PSI(bar) GPM(L/min) PSI(bar) Inch(mm) Ft(m) 12 x 12(3,6 x 3,6) 12(3,6) 16(61) 7.6(0,53) 16(61) 7.6(0,53) Smooth Ceilings 11/4 to 4(31.7 to 102)using F2 escutcheon. 14 x 14(4,3 x 4,3) 14(4,3) 16(61) 7.6(0,53) 16(61) 7.6(0,53) 1 to 4(25.4 to 102)using F1 escutcheon. 16 x 16(4,9 x 4,9) 16(4,9) 16(61) 7.6(0,53) 16(61) 7.6(0,53) Beamed Ceilings per NFPA 13D, 8(2,4) 13R or 13 installed in beams 18 x 18(5,5 x 5,5) 18(5,5) 19(72) 10.8(0,75) 19(72) 10.8(0,75) 11/4 to 13/4 (31.7 to 44.4)using F2 escutcheon, 1 to 13/4(25.4 to 20 x 20(6,1 x 6,1) 20(6,1) 22(83,3) 14.4(1,0) 22(83,3) 14.4(1,0) 44.4)using F1 escutcheon For Ceiling types refer to NFPA 13, 13R or 13D 3. Technical Data: Fl Res 76 Pendent and Recessed Pendent(SIN R7618) Thread Nominal Orifice Max. Sprinkler Max. K Sprinkler Pressure Temp.Rating Ambient Temp. Length Size Inch(mm) psi(bar) PF PC PF PC Factor Inch(mm) 3/4NPT 17/32"(13.5) 175(12) 155 68 100 38 7.6(109) 2.25(57) (R3/4) 175 79 150 66 Ordinary Temp.Rating Intermediate Temp.Rating Max.Coverage area Max.Spacing (155,7/68°C) (175PF/79PC) Top of Deflector to Ceiling Minimum Ft x Ft(m x m) Ft(m) Flow Pressure Flow GPM Pressure Inch(mm) Spacing GPM(L/min) PSI(bar) (L/min) PSI(bar) Ft(m) 12 x 12(3,6 x 3,6) 12(3,6) 21 (79,5) 7.6(0,53) 21 (79,5) 7.6(0,53) Smooth Ceilings 41/4 to 8(108 to 203)using F2 escutcheon. 14 x 14(4,3 x 4,3) 14(4,3) 21 (79,5) 7.6(0,53) 21 (79,5) 7.6(0,53) 4 to 8(100 to 203)using F1 escutcheon. 16 x 16(4,9 x 4,9) 16(4,9) 21 (79,5) 7.6(0,53) 21 (79,5) 7.6(0,53) Beamed Ceilings per NFPA 8(2,4) 13D, 13R or 13 installed in 18 x 18(5,5 x 5,5) 18(5,5) 21 (79,5) 7.6(0,53) 21 (79,5) 7.6(0,53) beams 41/4 to 8(108 to 203)us- ing F2 escutcheon,4 to 8(100 20 x 20(6,1 x 6,1) 20(6,1) 23(87,1) 9.2(0,63) 23(87,1) 9.2(0,63) to 203)using F1 escutcheon For Ceiling types refer to NFPA 13, 13R or 13D • Model Fl Res 30, 49, 58 & 76 CCP Pendent* • Model Fl Res 30, 49, 58 & 76 Recessed Pendent/FP Zoo) ___74r.,. "411 " roe # _ t `Not listed for corrosion resistance. FP push-on/thread-off escutcheon 2 5/8"[66.7mm] DIA. 2 5/8" DIA. [66.7mm] 2 5/16" DIA. HOLE IN CEILING —HOLE IN CEILING [58.7mm] CUP ----+__ '),, 2 5/16" DIA. k,_4_`__-s [58.7mm] T ------__ CUP_ k1/2" REDUCER r CUP \ / I IT 1 I 1" X 1/2" REDUCER CEILING t,==,,� 1 1/4"[3/.5mm] \� 1I[F �II�j MAX. FACE OF FITTING — ;;; ` 1 _TO FACE OF CEILING CEILING —J DIMENSION t #.� \Q� � ��� � ��' 1 1/2" [38.7mm] MAX. "'C" �� �P/ t� ` I �lIll �e= Ilp�l� FACE OF FITTING A" _ -�i , i,. 7-0 FACE OF CEILING COVER ADJUSTMENT HEIGHT �. ��I11 �� lir��� D�MENSION " A_;i a 1 1/2 [13mm] MAX. /j• I I FP ADJUSTMENT `411V' 3 5/16"DIA. ...._ _�__.... I I 7 35FC04E [84.1 mm] Mo 113 Fl RES 30, 49, 58 & 76 CCP PEND. Fl RES 49 PENDENT/FP Fig. 3 Fig. 4 Note: The F1 Res 76 will use a 1"x%"reducer. CCP Cover Plate Data: FP Escutcheon Data: "C„ "B" Deflector Distance below bottom "A" Deflector Distance below bottom Cover Adjustment CCP Height of beam FP Position Inch(mm) of beam Inch(mm) Inch(mm) Inch(mm) Inch(mm) 1/2(12.7) 15/16(24) 1/2(13)-1 (25.4) Max.Recessed 7/16(11) 1/2(12.7) 5/16(7.9) 3/4(19) 1/2(13)-1 (25.4) Min.Recessed 15/16(24) 1 (25.4) Note: Sprinklers shown in Fig. 3 and Fig. 4 are not suitable for installation in ceilings which have positive pressure in the space above. 4. Technical Data: F1 Res 30 CCP Pendent and Recessed Pendent/FP (SIN R3511) Thread Nominal Max. CCP Assembly Max. K Sprinkler Orifice Pressure Temp.Rating Ambient Temp. Length Size Inch(mm) psi(bar) PF PC PF PC Factor Inch(mm) '/z"NPT 21 (R1/2) /64"(8.2) 175(12) 135 57 100 38 3.0(43.2) 2.25(57) Ordinary Temp. Rating Minimum Max.Coverage area Max.Spacing (155PF/68PC) Top of Deflector to Ceiling Spacing Ft x Ft(m x m) Ft(m) Flow Pressure Inch(mm) GPM(Umin) PSI(bar) Ft(m) 12 x 12(3,6 x 3,6) 12(3,6) 8(30,3) 7.0(0,48) Smooth Ceilings Y to 1 (13 to 25.4)using CCP. /z to 1 (13 to 25.4)using FP escutcheon. Beamed Ceilings per NFPA 13D,13R or 13 installed in 8(2,4) 14 x 14(4,3 x 4,3) 14(4,3) 11 (37,8) 13.4(0,92) beams 1/2 to 1 (13 to 25.4)using CCP. /z to 1 (13 to 25.4)using FP escutcheon. For Ceiling types refer to NFPA 13, 13R or 13D Technical Data: F1 Res 49 CCP Pendent and Recessed Pendent/FP (SIN 3516) CCP Nominal I Max. Assembly Max. Sprinkler Thread Orifice Ambient K Size Inch Pressure Temp. Temp. Factor Length psi(bar) Rating Inch(mm) (mm) PF PC PF PC 1"NPT 'h (RYz) s"(11) 175(12) 135 57 100 38 4.9(70.6) 2.25(57) Max.Coverage Ordinary Temp.Rating Minimum Max.Spacing (155r'F/68r'C) Top of Deflector to Ceiling area Ft(m) Flow Pressure Inch(mm) Spacing Ft x Ft(m x m) GPM(Umin) PSI(bar) Ft(m) 12 x 12(3,6 x 3,6) 12(3,6) 13(49) 7.0(0,48) Smooth Ceilings Y to 1 (13 to 25.4)using 14 x 14(4,3 x 4,3) 14(4,3) 13(49) 7.0(0,48) CCP. '/z to 1 (13 to 25.4)using FP escutcheon. 16 x 16(4,9 x 4,9) 16(4,9) 14(53) 8.2(0,56) Beamed Ceilings per NFPA 13D,13R or 13 8(2,4) installed in beams Y to 1 (13 to 25.4)using 18 x 18(5,5 x 5,5) 18(5,5) 18(68,1) 13.5(0,93) CCP. '/z to 1 (13 to 25.4)using FP escutcheon. 20 x 20(6,1 x 6,1) 20(6,1) 20(75,7) 16.7(1,14) For Ceiling types refer to NFPA 13, 13R or 13D Technical Data: F1 Res 58 CCP Pendent and Recessed Pendent/FP(SIN R3513) Thread Nominal Max. CCP Assembly Max. K Sprinkler Orifice Pressure Temp. Rating Ambient Temp. Length Size Inch(mm) psi(bar) PF PC PF )''C Inch Inch(mm) Y"NPT (R1/2) '/2"(13) 175(12) 135 57 100 38 5.8(83.5) 2.25(57) Max.Coverage Ordinary Temp.Rating Minimum Max.Spacing (1557'F/68PC) Top of Deflector to Ceiling area Ft(m) Flow Pressure Inch(mm) Spacing Ft x Ft(m x m) GPM(1../min) PSI(bar) Ft(m) 12 x 12(3,6 x 3,6) 12(3,6) 16(61) 7.6(0,53) 14 x 14(4,3 x 4,3) 14(4,3) 16(61) 7.6(0,53) Smooth Ceilings Y to 1 (13 to 25.4)using CCP. '/z to 1 (13 to 25.4)using FP escutcheon. 16 x 16(4,9 x 4,9) 16(4,9) 16(61) 7.6(0,53) Beamed Ceilings per NFPA 13D,13R or 13 installed in beams 1/2 to 8(2,4) 1 (13 to 25.4)using CCP. 18 x 18(5,5 x 5,5) 18(5,5) 19(72) 10.8(0,75) '/z to 1 (13 to 25.4)using FP escutcheon. 20 x 20(6,1 x 6,1) 20(6,1) 22(83,3) 14.4(1,0) For Ceiling types refer to NFPA 13, 13R or 13D 5. Technical Data: F1 Res 76 CCP Pendent and Recessed Pendent/FP (SIN R7618) Thread Nominal Max. CCP Assembly Max. K Sprinkler Size Orifice Pressure Temp.Rating Ambient Temp. Factor Length Inch(mm) psi(bar) PF PC PF PC Inch(mm) 3/4"NPT17/32"(13.5) 175(12) 135 57 100 38 7.6(109) 2.25(57) (R3/4) 150 66 Max.Coverage Ordinary Temp.Rating Minimum Max.Spacing (155PF/68PC) Top of Deflector to Ceiling area Ft(m) Flow Pressure Inch(mm) Spacing Ft x Ft(m x m) GPM(L/min) PSI(bar) Ft(m) 12 x 12(3,6 x 3,6) 12(3,6) 21 (79,5) 7.6(0,53) 14 x 14(4,3 x 4,3) 14(4,3) 21 (79,5) 7.6(0,53) Smooth Ceilings 1/2 to 1 (13 to 25.4)using CCP. 1/2 to 1 (13 to 25.4)using FP escutcheon. 16 x 16(4,9 x 4,9) 16(4,9) 21 (79,5) 7.6(0,53) Beamed Ceilings per NFPA 13D, 13R or 13 installed in beams Y 8(2,4) to 1 (13 to 25.4)using CCP. 18 x 18(5,5 x 5,5) 18(5,5) 22(83,3) 8.4(0,58) 1/2 to 1 (13 to 25.4)using FP escutcheon. 20 x 20(6,1 x 6,1) 20(6,1) 25(94,6) 10.8(0,74) For Ceiling types refer to NFPA 13, 13R or 13D • Model Fl Res 44&58 HSW r ' k FACE OF FITTING TO WALL DIMENSION 1 1/4"MIN. 2 1/4"HOLE DIA. [31.8mm] A [57.2mm] f7/g CEILING TO [3.2mm] DEFLECTOR 7"X 1/2"REDUCER 1 //'/ DIMENSION f .� Model Fl Res 44 &58 Recessed HSW/F2 gi ; IRI ��i 7 15/76"DIA.I/no _ _ I i.� `_N` I [49.2mm] ) 1701 1�—"�" e 2 27/32"DIA. wn 1__,I. [72.2mm] 1 1 . , TURN COLLAR UNTIL4., TIGHT AGAINST i WRENCH BOSS.SPRINKLER ' ., —NH ] \ 135FC06—D il IAD""SJUSTMENTTMENT 1 AD Fl RES 58 & 44 HSW/F2 F2 escutcheon, Fig. 5 1/2" (13mm) adjustment Technical Data: F1Res 44 HSW & HSW/F2 (SIN R3531) Escutcheon, F2, Data: Nominal Max. Sprinkler Max. p Sprinkler rinkler Thread Ambient K Adjustment Face of Fitting Size Orifice Pressure Temp.Rating Temp. Factor Length Type Inch(mm) to wall Inch(mm) psi(bar) PF PC PF PC Inch(mm) Inch(mm) /2"NPT3/3„(10) 175(12) 155 68 100 38 4.4(63) 2.45(62) F2 1/2(13) 3/16-"/l6 (R'/2) 175 79 150 66 (4.7-17.4) 6. Ordinary Temp.Rating Intermediate Temp.Rating Top of Deflector to Minimum Max.Coverage area Max.Spacing (155PF/68PC) (175PF/799C) Ceiling Spacing Ft x Ft(m x m) Ft(m) Flow Pressure Flow Pressure GPM(L/min) PSI(bar) GPM(L/min) PSI(bar) Inch(mm) Ft(m) 12 x 12(3,6 x 3,6) 12(3,6) 12(45,4) 7.5(0,52) 12(45,4) 7.5(0,52) 14 x 14(4,3 x 4,3) 14(4,3) 14(53,0) 10.2(0,71) 14(53,0) 10.2(0,71) 16 x 16(4,9 x 4,9) 16(4,9) 16(60,6) 13.3(0,92) 16(60,6) 13.3(0,92) 4 to 6(100 to 152); 1/2(13)recessed 16 x 18(4,9 x 5,5) 16(4,9) 18(68,1) 16.8(1,16) 18(68,1) 16.8(1,16) using F2 escutcheon 18 x 18(5,5 x 5,5) 18(5,5) 19(72,0) 18.7(1,29) 19(72,0) 18.7(1,29) 16 x 20(4,9 x 6,1) 16(4,9) 23(87,1) 27.4(1,89) 23(87,1) 27.4(1,89) 8(2,4) 12 x 12(3,6 x 3,6) 12(3,6) 14(53,0) 10.2(0,71) 14(53,0) 10.2(0,71) 14 x 14(4,3 x 4,3) 14(4,3) 16(60,6) 13.3(0,92) 16(60,6) 13.3(0,92) 6 to 12(152 to 305); 16 x 16(4,9 x 4,9) 16(4,9) 17(64,4) 15.0(1,04) 17(64,4) 15.0(1,04) 1/2(13)recessed using F2 escutcheon 16 x 18(4,9 x 5,5) 16(4,9) 20(75,7) 20.7(1,43) 20(75,7) 20.7(1,43) 16 x 20(4,9 x 6,1) 16(4,9) 23(87,1) 27.4(1,89) 23(87,1) 27.4(1,89) For Ceiling types refer to NFPA 13, 13R or 13D Technical Data: Fl Res 58 HSW & HSW/F2 (SIN R3533) Escutcheon, F2, Data: Nominal Max. Sprinkler Face of Fitting Max. Sprinkler Adjustment Thread Orifice Pressure Temp.Rating Ambient K Length Type Inch mm to wall Size Inch psi(bar) Temp. Factor Inch ( ) Inch(mm) (mm) PF PC PF PC (mm) '/z 3/7 -11/1, (R1/2) 1/z"(13) 175(12) 175 79 150 66 5.8(83.5) 2.45(62) (4.7-17.4) Ordinary Temp.Rating Intermediate Temp.Rating Top of Deflector to Minimum Max.Coverage area Max.Spacing (155PF/68PC) (175PF/79PC) Ceiling Spacing Ft x Ft(m x m) Ft(m) Flow Pressure Flow Pressure Inch(mm) Ft(m) GPM(L/min) PSI(bar) GPM(L/min) PSI(bar) 12 x 12(3,6 x 3,6) 12(3,6) 16(60,6) 7.6(0,53) 16(60,6) 7.6(0,53) 14 x 14(4,3 x 4,3) 14(4,3) 18(68,2) 9.7(0,69) 18(68,2) 9.7(0,69) 4 to 6(100 to 152); 16 x 16(4,9 x 4,9) 16(4,9) 21 (79,5) 13.2(0,91) 21 (79,5) 13.2(0,91) 1/2(13)recessed using F2 escutcheon 16 x 18(4,9 x 5,5) 16(4,9) 25(94,7) 18.6(1,28) 25(94,7) 18.6(1,28) 16 x 20(4,9 x 6,1) 16(4,9) 29(109,8) 25.0(1,73) 29(109,8) 25.0(1,73) 8(2,4) 12 x 12(3,6 x 3,6) 12(3,6) 22(83,3) 14.4(1,0) 22(83,3) 14.4(1,0) 14 x 14(4,3 x 4,3) 14(4,3) 22(83,3) 14.4(1,0) 22(83,3) 14.4(1,0) 6 to 12(152 to 305); 1/2(13)recessed 16 x 16(4,9 x 4,9) 16(4,9) 26(98,4) 20.1 (1,39) 26(98,4) 20.1 (1,39) using F2 escutcheon 16 x 18(4,9 x 5,5) 16(4,9) 31 (117,4) 28.6(1,97) 31 (117,4) 28.6(1,97) For Ceiling types refer to NFPA 13, 13R or 13D 7. • Model Fl Res 44 SWC* 11 , "Not listed for corrosion resistance. 4"to 12" A [101.60mm To 1 1/4"[31.75mm]Maximum 304.80mm] Face Of Fitting PUSH ON COVER, THEN To Wal/Dimension TURN TO ADJUST UNTIL r TIGHT AGAINST WALL. 1"X 1/2"Reducer 'It RecommendedJPIPPIPIWill mm �i , uuiI Wall Hole 2 5/76" �`/nI�nY ///� /_/ 2 5/8" [58.74mm] „ --- l g--1.1=1 �-to - 3 5/16" [66.68mm] Dia. � nio 'r�// , [84.14mm] Dia. TURN COLLAR UNTIL j I RET AGAINST SPRINKLER INKLER WRENCH BOSS. 1 21/32" [42.07mm7mmJ 135F007 1/2"[12.70mm] Adjustment F1 RES 44 SWC Fig. 6 Technical Data: F1 Res 44 SWC 'SIN R3531) Nominal Max. Cover Max. Sprinkler Thread Temp. Ambient K Size Orifice Pressure Rating Temp. Factor Length Inch(mm) psi(bar) PF pC pF pC Inch(mm) /2"NPT 3/5"(10) 175(12) 135 57 100 38 4.4(63) 2.45(62) (R/) Ordinary Temp.Rating Top of Deflector to Minimum Max.Coverage area Max.Spacing (155?F/68r'C) Ft x Ft(m x m) Ft(m) Flow Pressure Ceiling Spacing GPM(L/min) PSI(bar) Inch(mm) Ft(m) 12 x 12(3,6 x 3,6) 12(3,6) 13(49,2) 8.7(0,60) 14 x 14(4,3 x 4,3) 14(4,3) 14(53,0) 10.2(0,71) 4 to 6(100 to 152); 16 x 16(4,9 x 4,9) 16(4,9) 17(64,3) 15.0(1,1) 1(13)recessed using F2 escutcheon 16 x 18(4,9 x 5,5) 16(4,9) 19(71,8) 18.7(1,13) 16 x 20(4,9 x 6,1) 16(4,9) 23(87,1) 27.4(1,89) 8(2,4) 12 x 12(3,6 x 3,6) 12(3,6) 14(52,9) 10.2(0,71) 14 x 14(4,3 x 4,3) 14(4,3) 15(56,7) 11.7(0,81) 6 to 12(152 to 305); 1(13)recessed 16 x 16(4,9 x 4,9) 16(4,9) 18(68,1) 16.8(1,16) using F2 escutcheon 16 x 18(4,9 x 5,5) 16(4,9) 20(75,6) 20.7(1,43) For Ceiling types refer to NFPA 13, 13R or 13D 8. Technical Data: Fl Res 58 HSWX (SIN RA3533) Nominal Max. Sprinkler Max. Sprinkler Sprinkler Thread Ambient K Size Orifice Pressure Temp.Rating Temp. Factor Length Identification Inch(mm) psi(bar) pF rc PF I'DInch(mm) Number(SIN) Bulb /z NPT 1/2"(13) 175(12) 155 68 100 38 5.8(83.5) 2.45(62) RA3533 (R1/2) 175 79 150 66 1 Ordinary Temp.Rating Intermediate Temp.Rating Top of Deflector to Minimum Max.Coverage area Max.Spacing (155?F/68r'C) (175PFl79)*C) Ceiling Spacing Ft x Ft(m x m) Ft(m) Flow Pressure Flow Pressure Inch(mm) Ft(m) GPM(Umin) PSI(bar) GPM(Umin) PSI(bar) 18 x 20(5,5 x 6,1) 18(5,5) 30(114) 26.8(1,85) 30(114) 26.8(1,85) 20 x 20(6,1 x 6,1) 20(6,1) 30(114) 26.8(1,85) 30(114) 26.8(1,85) 4 to 6(100 to 152); 16 x 22(4,9 x 6,7) 16(4,9) 33(125) 32.4(2,23) 33(125) 32.4(2,23) 1/2(13)recessed using F2 escutcheon 16 x 24(4,9 x 7,3) 16(4,9) 38(144) 42.9(2,96) 38(144) 42.9(2,96) 14 x 26(4,3 x 7,9) 14(4,3) 42(160) 52.4(3,75) 42(160) 52.4(3,75) 8(2,4) 18 x 20(5,5 x 6,1) 18(5,5) 35(133) 36.4(2,5) 35(133) 36.4(2,5) 16 x 22(4,9 x 6,7) 16(4,9) 38(144) 42.9(2,96) 38(144) 42.9(2,96) 6 to 12(152 to 305); 1/2(13)recessed 16 x 24(4,9 x 7,3) 16(4,9) 42(160) 52.4(3,6) 42(160) 52.4(3,6) using F2 escutcheon 14 x 26(4,3 x 7,9) 14(4,3) 46(174) 62.9(4,34) 46(174) 62.9(4,34) For Ceiling types refer to NFPA 13, 13R or 13D • Model Fl Res 58 HSWX(Bulb) 4 FACE OF FITTING TO — - WALL DIMENSION 1 11/16" MIN. [31.8mm] , - 2 1/4" HOLE DIA. y f1/8", •A [57.2mm] [3.2mm] CEILING TO r+ DEFLECTOR :.s 1 1 , . 7"X 1/2"REDUCER ,(/ \ DIMENSION 4- _irAlre _ 1 ,"/IlINi -lr- 71 Jr* nii 1 75/16" DIA.\11nn I ,.. `- I [49.2mm] a I jS`1" c"� 2 27/32" DIA. nn / /% r_ Ilio r -I,��0 [72.2mm] L-omL i_-��� .• I TURN COLLAR UNTIL �� • TIGHT AGAINST SPRINKLER `\`! Model KRes58 HSWX(Link) WRENCH BOSS. f 1/2"[73mm] - . . 135FG08 ADJUSTMENT / F1 RES 58 HSWX f Fig. 7 d - t Its r , I 9. Technical Data: KRes58 HSWX (RA3593) Nominal Max. Max. Sprinkler Sprinkler Thread Ambient K Size Orifice Pressure Temp. Factor Length Identification Inch(mm) psi(bar) WF rc Inch(mm) Number(SIN) Link /z NPT" 1/2"(13) 175(12) 100 38 5.8(83.5) 2.45(62) RA3593 (R1) Ordinary Temp.Rating Top of Deflector to Minimum Max.Coverage area Max.Spacing (165PF/74PC) Ft x Ft(m x m) Ft(m) Flow Pressure Ceiling Spacing GPM(L/min) PSI(bar) Inch(mm) Ft(m) 18 x 20(5,5 x 6,1) 18(5,5) 29(109) 25(1,72) 20 x 20(6,1 x 6,1) 20(6,1) 30(114) 26.8(1,85) 4 to 6(100 to 152); 16 x 22(4,9 x 7,3) 16(4,9) 33(125) 32.4(2,23) 1/2(13)recessed using F2 escutcheon 16 x 24(4,9 x 7,3) 16(4,9) 38(144) 42.9(2,96) 14 x 26(4,3 x 7,9) 14(4,3) 42(160) 52.4(3,75) 8(2,4) 18 x 20(5,5 x 6,1) 18(5,5) 35(133) 36.4(2,5) 16 x 22(4,9 x 6,7) 16(4,9) 38(144) 42.9(2,96) 6 to 12(152 to 305); 1/2(13)Recessed 16 x 24(4,9 x 7,3) 16(4,9) 42(160) 52.4(3,6) using F2 escutcheon 14 x 26(4,3 x 7,9) 14(4,3) 46(174) 62.9(4,34) For Ceiling types refer to NFPA 13, 13R or 13D Maintenance Model Fl Res 30, 49, Fl Res 58, Fl Res 76 and Fl Res ter seal assembly shall consist of a Teflon* coated Bel- 44 Sprinklers should be inspected and the sprinkler sys- leville spring washer with top-loaded extruded or cold tern maintained in accordance with NFPA 25, 13, 13D, head cup with 3 mm glass bulb containing no plastic and 13R. Do not clean sprinkler with soap and water,Am- parts, and having a temperature rating of [155°F (68°C)] monia or any other cleaning fluids. Remove dust by using [175°F (79°C)]. Sprinklers shall have a nominal K-factor a soft brush or gentle vacuuming. Remove any sprinkler of 3.0, 4.9 and 5.8. Standard finish: [Bronze] [Chrome- which has been painted (other than factory applied) or plated] [White Polyester] [Special finish- specify]. Resi- damaged in any way. A stock of spare sprinklers should dential pendent sprinklers shall be Reliable Model Fl Res be maintained to allow quick replacement of damaged or 30, 49 &58, SIN R3511, R3516& R3513 (Bulletin 135). operated sprinklers. Prior to installation, sprinklers should Model F1 Res 49 & 58 Recessed Pendent/F1, remain in the original cartons and packaging until used. Model F1 Res 30, 49 & 58 Recessed Pendent/ This will minimize the potential for damage to sprinklers F2, Model F1 Res 30, 49&58 Recessed Pendent/ that could cause improper operation or non-operation. FP Model F1 Res 30, 49 & 58 Pendent Sprinklers shall be [cULus Listed] [New York City MEA Sprinkler Specifications Approved (258-93-E)] low flow residential recessed pen- Sprinklers shall be [cULus Listed] [New York City MEA dent sprinklers engineered to provide a minimum design Approved (258-93-E)] low flow residential pendent sprin- density of 0.05 gpm/ft2 over the listed coverage area. klers engineered to provide a minimum design density of Listed flows as specified by the manufacturer's technical 0.05 gpm/ft2 over the listed coverage area. Listed flows data sheets are to be used. Residential sprinklers shall as specified by the manufacturer's technical data sheets be installed in conformance with the manufacturer's in- are to be used. Residential sprinklers shall be installed stallation guidelines and the applicable installation stan- in conformance with the manufacturer's installation guide- dard. Deflector-to-ceiling distance listing shall be 1"to 8" lines and the applicable installation standard. Deflector- maximum, only for Fl Res 49. Sprinkler frame and deflec- to-ceiling distance listing shall be 1" to 8" maximum, only tor shall be of bronze frame construction having a'/2" NPT for F1 Res 49. Sprinkler frame and deflector shall be of thread. Water seal assembly shall consist of a Teflon* bronze frame construction having a 1/2" NPT thread. Wa- coated Belleville spring washer with top-loaded extruded *DuPont Registered Trademark 10. or cold head cup with 3 mm glass bulb containing no leville spring washer with top-loaded extruded or cold plastic parts, and having a temperature rating of [155°F head cup with 3 mm glass bulb containing no plastic (68°C)] [175°F (79°C)]. Sprinklers shall have a nomi- parts, and having a temperature rating of [155°F (68°C)] nal K-factor of 3.0, 4.9 & 5.8. Standard finish: [Bronze] [175°F (79°C)]. The solder element (Link) version, the [Chrome-plated] [White Polyester] [Special finish— spec- water seal consist of a cap with a bellville spring washer ify]. Recessed escutcheon assembly shall be a steel, and a temperature rating of 165°F (74°C). The recessed two-piece escutcheon [with 1/2" adjustment (Model F2)] assembly forthe HSWX (Bulb & Link) should be a steel [with 3/4" adjustment (Model F1)] [of push-on and thread two pieces escutcheon with 1/2" adjustment (Model F2) off design with 1/2" adjustment (Model FP)]. Standard fin- standard finish should be Bright Chrome and white paint- ish shall be [brass][bright chrome] [white painted]. Resi- ed. The Fl Res 58 HSW is also available with low lead dential recessed pendent sprinklers shall be Reliable frame. Fl Res 58 HSW and HSWX sprinklers shall have a [Model Fl Res 30, 49&58 Recessed Pendent/F1] [Model nominal K Factor of 5.8 and Fl Res 44 a nominal K factor Fl Res 30, 49&58 Recessed Pendent/F2] [Model Fl Res of 4.4. Standard finish: [Bronze] [Chrome-plated] [White 30, 49 & 58 Recessed Pendent/FP] SIN R3511, R3516 & Polyester] [Special finish—specify]. Residential horizontal R3513 (Bulletin 135). sidewall sprinklers shall be Reliable Model Fl Res 44, Fl Model Fl Res 30, 49 & 58 CCP Pendent Res 58, Fl Res 58 HSWX & Model KRes58 HSWX, SIN (Concealed) R3531, RA3533 & RA3593 (Bulletin 135). Sprinklers shall be [cULus Listed] [New York City MEA Model Fl Res 44 Recessed Approved (258-93-E)] low flow residential concealed Horizontal Sidewall Sprinkler sprinklers engineered to provide a minimum design den- Use description for the Model Fl Res 44 horizontal side- sity of 0.05 gpm/ft2 over the listed coverage area. Listed wall sprinkler with the following modifications: Replace flows as specified by the manufacturer's technical data "horizontal sidewall sprinkler" with "recessed horizontal sheets are to be used. Residential sprinklers shall be in- sprinkler." Add: Recessed escutcheon assembly shall be stalled in conformance with the manufacturer's installa- steel, two-piece escutcheon with 1/2" adjustment(Model tion guidelines and the applicable installation standard. F2). Standard finish shall be [brass][bright chrome] [white Sprinkler frame and deflector shall be of bronze frame painted] [Special finish— specify]. Residential recessed construction having a 1/2" NPT thread. Water seal as horizontal sidewall sprinklers shall be Reliable Model Fl sembly shall consist of a Teflon* coated Belleville spring Res 44/F2, SIN R3531 (Bulletin 135). washer with top-loaded extruded or cold head cup with 3 Model Fl Res 76 Pendent mm glass bulb containing no plastic parts, and having a Sprinklers shall be [cULus Listed] low flow residential temperature rating of 155°F (68°C). Cover plate assem- pendent sprinklers engineered to provide a minimum bly shall consist of a brass cover plate and copper alloy design density of 0.05 gpm/ft2 over the listed coverage retainer flange. Method of attaching the cover plate to the area. Listed flows as specified by the manufacturer's sprinkler cup shall be a push-on and thread-off design technical data sheets are to be used. Residential sprin- allowing a '/2" cover plate adjustment. Cover plate tem- klers shall be installed in conformance with the manufac- perature rating shall be 135°F (57°C). A plastic protec- turer's installation guidelines and the applicable installa- tive cap shall be provided and factory installed inside the tion standard. Sprinkler frame and deflector shall be of sprinkler cup to protect the sprinkler from damage, which bronze frame construction having a 3/4" NPT thread. Wa- could occur during construction before the cover plate ter seal assembly shall consist of a Teflon* coated Bel- is installed. Standard cover plate finish: [White] [Custom leville spring washer with machined or cold head cup with Color— specify]. ]. Concealed pendent sprinklers shall 3 mm glass bulb containing no plastic parts, and having be Reliable Model Fl Res 30, 49 & 58 CCP, SIN R3511, a temperature rating of [155°F (68°C)] [175°F (79°C)]. R3516& R3513 (Bulletin 135). Sprinklers shall have a nominal K-factor of 7.6. Standard Model Fl Res 44, Fl Res 58 Horizontal finish: [Bronze] [Chrome-plated] [White Polyester] [Spe- Sidewall, Fl Res 58 HSWX & KRes58 HSWX cial finish— specify]. Residential pendent sprinklers shall Residential Sprinkler Specifications be Reliable Model Fl Res 76, SIN R7618 (Bulletin 135). Sprinklers shall be [cULus Listed] low flow residential horizontal sidewall sprinklers engineered to provide a minimum design density of 0.05 gpm/ft2 over the listed coverage area. Listed flows as specified by the manu- facturer's technical data sheets are to be used. Residen- tial sprinklers shall be installed in conformance with the manufacturer's installation guidelines and the applicable installation standard. Sprinkler frame and deflector shall be of bronze frame construction having a'/2" NPT thread. Water seal assembly shall consist of a Teflon*coated Bel- "Dupont Registered Trademark 11. Model F1 Res 76 Recessed Pendent/F1, Model F1 Res 76 Recessed Pendent/F2, a temperature rating of 155°F(68°C). Cover plate assem- Model F1 Res 76 Recessed Pendent/FP bly shall consist of a brass cover plate and copper alloy Sprinklers shall be [cULus Listed] low flow residential retainer flange. Method of attaching the cover plate to the recessed pendent sprinklers engineered to provide a sprinkler cup shall be a push-on and thread-off design minimum design density of 0.05 gpm/ft2 over the listed allowing a 1" cover plate adjustment. Cover plate tem- coverage area. Listed flows as specified by the manu- perature rating shall be 135°F (57°C). A plastic protec- facturer's technical data sheets are to be used. Residen- tive cap shall be provided and factory installed inside the tial sprinklers shall be installed in conformance with the sprinkler cup to protect the sprinkler from damage, which manufacturer's installation guidelines and the applicable could occur during construction before the cover plate installation standard. Sprinkler frame and deflector shall is installed. Standard cover plate finish: [White] [Custom be of bronze frame construction having a 3/4" NPT thread. Color—specify]. ]. Concealed pendent sprinklers shall be Water seal assembly shall consist of a Teflon*coated Bel- Reliable Model Fl Res 76 CCP, SIN R7618 (Bulletin 135). leville spring washer with machined or cold head cup with Finishes (1) 3 mm glass bulb containing no plastic parts, and hav- Standard Finishes ing a temperature rating of [155°F(68°C)] [175°F(79°C)]. Sprinklers shall have a nominal K-factor of 7.6. Standard Sprinkler Fl,F2,FP Cover Plates finish: [Bronze] [Chrome-plated] [White Polyester] [Spe Escutcheons cial finish— specify]. Recessed escutcheon assembly Bronze Brass White Painted shall be a steel, two-piece escutcheon [with '/2" adjust Chrome Plated Bright Chrome Plated Chrome White and Black White Painted ment (Model F2)] [with 3/4" adjustment (Model F1)] [of Polyester(2)Coated push-on and thread off design with t/" adjustment (Mod- _ el FP)]. Standard finish shall be [brass][bright chrome] Special Application Finishes [white painted]. Residential recessed pendent sprinklers Sprinkler Fi,F2,FP shall be Reliable [Model Fl Res 76 Recessed Pendent/ Escutcheons F1] [Model Fl Res 76 Recessed Pendent/F2] [Model Fl Electroless Nickel PTFE(Teflon®)(2) Electroless Nickel PTFE(Teflon®) Res 76 Recessed Pendent/FP] SIN R7618 (Bulletin 135). Bright Brass Bright Brass Model Fl Res 76 CCP Pendent (Concealed) Black Plated Black Plated Black Paint Black Paint Sprinklers shall be [cULus Listed] low flow residential Off White Off White concealed sprinklers engineered to provide a minimum Chrome Dull Chrome Dull design density of 0.05 gpm/ft2 over the listed coverage (1)Other finishes and colors are available on special order. area. Listed flows as specified by the manufacturer's Consult factory for details. technical data sheets are to be used. Residential sprin 12)cULus listed corrosion Resistant Note: Paint or any other coating applied over the factory finish will void klers shall be installed in conformance with the manufac- all approvals and warranties. turer's installation guidelines and the applicable installa- Ordering Information tion standard. Sprinkler frame and deflector shall be of bronze frame construction having a 3/4" NPT thread. Wa- Specify: ter seal assembly shall consist of a Teflon* coated Bel 1. Sprinkler Model leville spring washer with machined or cold head cup with 2. Sprinkler Type 3 mm glass bulb containing no plastic parts, and having 3. Temperature Rating 4. Sprinkler Finish 5. Escutcheon Finish 6. Cover Plate Finish "DuPont Registered Trademark The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association,Factory Mutual Research Corporation,or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Products manufactured and distributed by Reliable have been protecting life and property for over 90 years,and are installed and serviced by the most highly qualified and reputable sprinkler contractors located throughout the United States,Canada and foreign countries. Manufactured by Reliable Automatic Sprinkler Co.,Inc. ® Recycled ® (800)431-1588 Sales Offices Paper eIiabI (800)848 6051 Sales Fax (914)829-2042 Corporate Offices Revision lines indicate updated or new data. www.reliablesprinkler.com Internet Address EG.Printed in U.S.A.06/15 P/N 9999970235