Loading...
HomeMy WebLinkAboutF15-0086_Hydraulic calcs_1449253860.pdf 7026 South Tucson Way Centennial, CO 80112 (303) 792-0022 Fax (303) 792-9049 Fire Protection System Hydraulic Calculations and Equipment Village Inn Plaza Unit 501 Fire Sprinkler System 68 E. Meadow Dr. Vail, Colorado 81657 Prepared by: Zack Hinson Project Manager Phone: (303) 792-0022 Cell: (720) 346-3113 Fax: (303) 792-9049 Email: Zachary.hinson@wsfp.us September 15, 2015 Hydraulic Summary Report Description: Light Hazard Job Number: CS2747 Node Flow(gpm) Total Hose Streams 0.0 Safety MarginRequiredAvailable Node Hose Flow Static Residual Flow Total Demand (gpm)(psi)(psi)(gpm)(psi)(gpm)(psi)(psi)@@Name 1 144.1 114.8 29.3721.015.1150.0 132.6Water Supply Design EngineerJob Number Total Water Required (Including Hose Allowance) 132.6 Maximum Pressure Unbalance In Loops 0.0 Additional Hose Supplies 0.0 Hose Allowance At Source Supplies 471.2gal Residential 1.00gpm/ft² 324.00ft² 1296.00ft² 4 Occupancy Area of Application Coverage Per SprinklerNumber Of Sprinklers Calculated Density Manually Flowing Job Suffix AutoPeak Results: Pressure For Remote Area(s) Adjacent To Most Remote Area Volume capacity of Dry PipesVolume capacity of Wet Pipes Maximum Velocity Under Ground 24.16 between nodes 8 and 101 Maximum Velocity Above Ground 4.9 K-Factor 32.4 at 43.7 Most Demanding Sprinkler Data System 68 East Meadows Dr. Job Site/Building Vail Fire Department68 East Meadow Dr. AHJ 032Village Inn Plaza Unit #501 Job State Certification/License NumberJob Name: Zack HinsonCS2747 Contractor Contractor Number Name of Contractor: Western States Fire Protection Address 1 274 Center Drive Address 2 Glenwood Springs, CO. 81601 Contact Name Contact TitlePM ExtensionPhone 720-346-3133 FAX E-mail zachary.hinson@wsfp.us Web-Site Zack Hinson Address 3 Address 1 Address 2 Drawing Name Village Inn #501 Remodel System Flow Demand 132.6 Remote Area(s) Address 3 12/4/2015© M.E.P.CAD, Inc.Page 1AutoSPRINK® VR11 v11.0.30.0 10:38:43AM Hydraulic Graph Report Description: Light Hazard Job Number: CS2747 System Demand (Including Hose Allowance at Source) System Demand 15.1 @ 721.0 Residual: Pressure 150.0 Static: Pressure Water Supply at Node 1 Hydraulic Graph Water Supply at Node 1 114.8 @ 132.6 114.8 @ 132.6 Available Pressure at Time of Test 144.1 @ 132.6 © M.E.P.CAD, Inc.12/4/2015 Page 2AutoSPRINK® VR11 v11.0.30.0 10:38:44AM Device (gpm) Actual Flow Minimum Flow (gpm)(K) K-Factor (psi) Pressure Summary Of Outflowing Devices Report Description: Light Hazard Job Number: CS2747 Sprinkler 101 33.4 32.4 4.9 46.5 Sprinkler 102 32.4 32.4 4.9 43.7 Sprinkler 103 33.9 32.4 4.9 47.8 Sprinkler 104 32.9 32.4 4.9 45.0 Most Demanding Sprinkler Data © M.E.P.CAD, Inc.12/4/2015 Page 3AutoSPRINK® VR11 v11.0.30.0 10:38:46AM Pipe Type Diameter Flow Velocity Friction Loss Length Pressure Downstream Elevation Discharge K-Factor Pt Pn Fittings Eq. Length Summary Upstream Total Length HWC Hydraulic Analysis Job Number: CS2747 Report Description: Light Hazard • • • • • Route 1 • • • • • Pf Pe Pv AO 1.055 32.4 11.89 0.204474 13'-10 2.8 102 10'-0 32.4 4.9 43.7 101 10'-0 46.5 13'-10 150 Sprinkler Pf Pe Pv AO 1.055 65.8 24.16 0.758966 1'-11½3.0 101 10'-0 33.4 4.9 46.5 2'-0 8 10'-0 49.5 3'-11½ 150 Sprinkler, T(2'-0) Pf Pe Pv BL 1.527 132.6 23.23 0.457959 22'-9 12.0 8 10'-0 66.8 49.5 3'-6 7 10'-0 61.6 26'-3 150 Flow (q) from Route 2 E(2'-6), cplg(1'-0) Pf Pe Pv BL 2.067 132.6 12.68 0.158379 33'-9 7.6 7 10'-0 61.6 14'-0 10 10'-0 69.1 47'-9 120 2EE(2'-0), 2E(5'-0) Pf Pe Pv BL 1.610 132.6 20.90 0.534766 2'-0½3.2 10 10'-0 69.1 4'-0 11 10'-0 72.4 6'-0½ 120 E(4'-0) Pf Pe Pv FM 4.026 132.6 3.34 0.006161 266'-5½17.1 11 10'-0 72.4 884'-4½29.7 3 -58'-6 119.1 1150'-10 120 55E(10'-0), 14T(20'-0), 8fE(6'-9½), BFP(-10.0) Pf Pe Pv BL 6.065 132.6 1.47 0.000838 9'-8½0.0 3 -58'-6 119.1 30'-0 1.3 2 -61'-6 120.5 39'-8½ 120 PRV, 3fE(10'-0) Pf Pe Pv BL 6.280 132.6 1.37 0.000531 161'-6 0.2 2 -61'-6 120.5 179'-8 -5.9 1 -48'-0 114.8 341'-2 140 6E(22'-1), T(47'-3½), S 132.6 0.0 Hose Allowance At Source 1 • • • • • Route 2 • • • • • Pf Pe Pv AO 1.055 32.9 12.07 0.210152 9'-0 2.7 104 10'-0 32.9 4.9 45.0 4'-0 9 10'-0 47.8 13'-0 150 Sprinkler, E(2'-0), T(2'-0) Pf Pe Pv BL 1.291 32.9 8.06 0.078625 1'-0 0.1 9 10'-0 47.8 103 10'-0 47.8 1'-0 150 Pf Pe Pv BL 1.291 66.8 16.37 0.291555 5'-9½1.7 103 10'-0 33.9 4.9 47.8 8 10'-0 49.5 5'-9½ 150 Sprinkler 1.51 4.87 )(150 1.33 140 1.16 130 0.713 100 Equivalent Pipe Lengths of Valves and Fittings (C=120 only) Actual Inside Diameter Schedule 40 Steel Pipe Inside Diameter = Factor C Value Multiplier Value Of C Multiplying Factor © M.E.P.CAD, Inc.12/4/2015 Page 4AutoSPRINK® VR11 v11.0.30.0 10:38:47AM Pipe Type Diameter Flow Velocity Friction Loss Length Pressure Downstream Elevation Discharge K-Factor Pt Pn Fittings Eq. Length Summary Upstream Total Length HWC Hydraulic Analysis Job Number: CS2747 Report Description: Light Hazard Pipe Type Legend AO Arm-Over BL Branch Line CM Cross Main DN Drain DR Drop DY Dynamic FM Feed Main FR Feed Riser MS Miscellaneous OR Outrigger RN Riser Nipple SP Sprig ST Stand Pipe UG Underground Units Legend Diameter Inch Elevation Foot Flow gpm Discharge gpm Velocity fps Pressure psi Length Foot Friction Loss psi/Foot HWC Hazen-Williams Constant Pt Total pressure at a point in a pipe Pn Normal pressure at a point in a pipe Pf Pressure loss due to friction between points Pe Pressure due to elevation difference between indicated points Pv Velocity pressure at a point in a pipe Fittings Legend ALV Alarm Valve AngV Angle Valve b Bushing BalV Ball Valve BFP Backflow Preventer BV Butterfly Valve C Cross Flow Turn 90° cplg Coupling Cr Cross Run CV Check Valve DelV Deluge Valve DPV Dry Pipe Valve E 90° Elbow EE 45° Elbow Ee1 11¼° Elbow Ee2 22½° Elbow f Flow Device fd Flex Drop FDC Fire Department Connection fE 90° FireLock(TM) Elbow fEE 45° FireLock(TM) Elbow flg Flange FN Floating Node fT FireLock(TM) Tee g Gauge GloV Globe Valve GV Gate Valve Ho Hose Hose Hose HV Hose Valve Hyd Hydrant LtE Long Turn Elbow mecT Mechanical Tee Noz Nozzle P1 Pump In P2 Pump Out PIV Post Indicating Valve PO Pipe Outlet PRV Pressure Reducing Valve PrV Pressure Relief Valve red Reducer/Adapter S Supply sCV Swing Check Valve Spr Sprinkler St Strainer T Tee Flow Turn 90° Tr Tee Run U Union WirF Wirsbo WMV Water Meter Valve Z Cap © M.E.P.CAD, Inc.12/4/2015 Page 5AutoSPRINK® VR11 v11.0.30.0 10:38:47AM Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523 Bulletin 135 Rev. MBulletin 135 Rev. M Model F1 Residential Sprinklers for Design Density of .05 gpm/ft2 Types: 1. F1 Res 30 Pendent 2. F1 Res 30 Recessed Pendent/F2 3. F1 Res 30 Recessed Pendent/FP 4. F1 Res 49 Pendent 5. F1 Res 49 Recessed Pendent/F1 6. F1 Res 49 Recessed Pendent/FP 7. F1 Res 58 Pendent 8. F1 Res 58 Recessed Pendent/F1 9. F1 Res 58 Recessed Pendent/FP 10. F1 Res 76 Pendent 11. F1 Res 76 Recessed Pendent/F1 12. F1 Res 76 Recessed Pendent/FP 13. F1 Res 30 CCP Pendent 14. F1 Res 49 CCP Pendent 15. F1 Res 58 CCP Pendent 16. F1 Res 76 CCP Pendent 17. F1 Res 44 HSW 18. F1 Res 44 Recessed HSW/F2 19. F1 Res 58 HSW 20. F1 Res 58 HSWX 21. KRes58 HSWX 22. F1 Res 58 HSW Recessed HSW/F2 23. F1 Res 44 SWC Listings & Approvals 1. Listed by Underwriters Laboratories Inc. and UL Certified for Canada (cULus) Sprinklers for .10 Density: Refer to Bulletin 176 UL Listing Category Residential Automatic Sprinkler UL Guide Number VKKW Patents US Patent No. 6,516,893 applies to the Model F1 Res 49 & 58 Pendent Sprinklers US Patent No. 7,353,882 applies to Model F1 Res 44 & 58 HSW Sprinklers US Patent No. 7,784,555 applies to Model F1 Res 44 SWC Sprinklers Product Description Model F1 Res Pendent sprinklers (Figs. 1, 2, 3, & 4) are fast response sprinklers combining excellent durability, high sensitiv- ity glass-bulb and low profile decorative design. The F1 Res F1 Res 30, 49, 58 & 76 Recessed Pendent / FP F1 Res 30, 49, 58 & 76 Recessed Pendent / F1 F1 Res 44 & 58 Recessed HSW/F2 F1 Res 30, 49, 58 & 76 CCP Pendent F1 Res 44 SWC Horizontal Sidewall sprinklers (Figs. 5, 6 & 7) are equally attrac- tive when above ceiling piping cannot be used. The 3mm glass-bulb pendent sprinklers permit the efficient use of residential water supplies for sprinkler coverage in residential fire protection design. The low flow F1 Res sprinklers are specially engineered for fast thermal response to meet the sensitive fire protection applica- tion needs of the latest residential market standards (UL 1626 Standard). Upon fire conditions, rising heat causes a sprinkler’s heat-sensitive element, glass bulb or link to actuate, releasing the waterway for water flow onto the deflector, evenly distributing the discharged water to control a fire. Technical Data: • Thermal Sensor: Soldered Element (Link) or Nominal 3mm glass-bulb • Sprinkler Frame : Brass Casting • Sprinklers’ Pressure Rating : 175 psi Factory Hydrostatically Tested to 500 psi • Thread Size: ½” NPT (R½) • K-Factor: 3.0 (43.2) (Actual) - F1 Res 30 Pendent Sprinkler 4.9 (70.6) (Actual) - F1 Res 49 Pendent Sprinkler 5.8 (83.5) (Actual) - F1 Res 58 Pendent & HSW Sprinkler 7.6 (109)(Actual) - F1 Res 76 Pendent Sprinkler 4.4 (63) (Actual) - F1 Res 44 HSW Sprinkler• Density: Minimum 0.05 gpm/ft2 Model F1 Res Sprinklers engineered for the lowest fl ows to meet the minimum design density of .05 gpm/ft2 F1 Res 58 HSWX 2. Application Model F1 Res Sprinklers are used for Residential Fire Pro- tection according to UL 1626 Standard*. For ceiling types: Smooth Flat Horizontal, or beamed, or sloped, in accordance with NFPA 13D, 13R, or 13 2013 editions. Be sure that orifice size, temperature rating, deflector style and sprinkler type are in accordance with the latest published standards of The Na- tional Fire Protection Association or the approving authority having jurisdiction. Installation Models F1 Res sprinklers are to be installed as shown. Model F1, F2 and FP Escutcheons, illustrated herewith, are the only recessed escutcheons to be used with Model F1 Res sprinklers. Use of any other recessed escutcheon will void all approvals and warranties. For installing Model F1 Res Pen- dent sprinklers use only the Model D sprinkler Wrench; for installing Models F1 Res Recessed Pendent, CCP & SWC sprinklers use only the Model GFR2 sprinkler wrench; for in- stalling Model F1 Res Recessed HSW sprinklers use only the Model GFR2 Sprinkler Wrench. Use of wrenches other than those specified may damage these sprinklers. Install F1 Res 44 with a ceiling to deflector distance of 4” - 12”. Flow arrow on deflector must point away from near wall and “Top” mark- ing must face ceiling. Technical Data: F1Res 30 Pendent and Recessed Pendent (SIN R3511) Thread Size Nominal Orifi ce Inch (mm) Max. Pressure psi (bar) Sprinkler Temp. Rating Max. Ambient Temp. Actual K Factor Sprinkler Length Inch (mm)°F °C °F °C ½” NPT (R½)21/64” (8.2) 175 (12) 155175 6879 100 38 3.0 (43.2) 2.25 (57) Max. Coverage area Ft x Ft (m x m) Max. Spacing Ft (m) Ordinary Temp. Rating (155°F/68°C) Intermediate Temp. Rating (175°F/79°C)Top of Defl ector to Ceiling Inch (mm) Minimum Spacing Ft (m)Flow GPM (L/min) Pressure PSI (bar) Flow GPM (L/min) Pressure PSI (bar) 12 x 12 (3,6 x 3,6) 12 (3,6) 8 (30,3) 7.0 (0,48) 8 (30,3) 7.0 (0,48) Smooth Ceilings 1¼ to 4 (31.7 to 102) using F2 escutcheon. Beamed Ceilings per NFPA 13D, 13R or 13 installed in beams 1¼ to 1¾ (31.7 to 44.4) using F2 escutcheon 8 (2,4)14 x 14 (4,3 x 4,3) 14 (4,3) 10 (37,8) 11 (0,76) 10 (37,8) 11 (0,76) 16 x 16 (4,9 x 4,9) 16 (4,9) 13 (49) 18.8 (1,3) 13 (49) 18.8 (1,3) For Ceiling types refer to NFPA 13, 13R or 13D • Model F1 Res 30, 49, 58 & 76 Pendent • Model F1 Res 30 Recessed Pendent / F2 • Model F1 Res 49, 58 & 76 Recessed Pendent / F1 Fig. 1 Fig. 2 F1 escutcheon, 3/4” (19mm) adjustment Escutcheon*, F1 or F2, Data: Type Adjustment Inch (mm) “A” Inch (mm) Face of fi tting to ceiling Inch (mm) “B” Defl ector Distance below bottom of beam Inch (mm) F1 ¾ (19.0) Min. Recessed = 15/8 (41.3)Max. Recessed = 7/8 (22.2) 3/8 (9.5)11/8 (28.6)13/4 (44.4)1 (25.4) F2 ½ (12.7) Min. Recessed = 15/8 (41.3) Max. Recessed = 11/8 (28.6) 3/8 (9.5) 7/8 (22.2) 13/4 (44.4) 1¼ (31.7) * Note: Escutcheons F1 or F2 may be used with Model F1 Res 49, 58 & 76 Recessed Pendent Sprinkler 3. Technical Data: F1Res 49 Pendent and Recessed Pendent (SIN R3516) Thread Size Nominal Orifi ce Inch (mm) Max. Pressure psi (bar) Sprinkler Temp. Rating Max. Ambient Temp. Actual K Factor Sprinkler Length Inch (mm)°F °C °F °C ½” NPT (R½)7/16” (11) 175 (12) 155 175 68 79 100 150 38 66 4.9 (70.6) 2.25 (57) Max. Coverage area Ft x Ft (m x m) Max. Spacing Ft (m) Ordinary Temp. Rating (155°F/68°C) Intermediate Temp. Rating (175°F/79°C)Top of Defl ector to Ceiling Inch (mm) Minimum Spacing Ft (m)Flow GPM (L/min) Pressure PSI (bar) Flow GPM (L/min) Pressure PSI (bar) 12 x 12 (3,6 x 3,6) 12 (3,6) 13 (49) 7.0 (0,48) 13 (49) 7.0 (0,48) Smooth Ceilings 1¼ to 4 (31.7 to 102) using F2 escutcheon. 1 to 4 (25.4 to 102) using F1 escutcheon. Beamed Ceilings per NFPA 13D, 13R or 13 installed in beams 1¼ to 1¾ (31.7 to 44.4) using F2 escutcheon, 1 to 1¾ (25.4 to 44.4) using F1 escutcheon 8 (2,4) 14 x 14 (4,3 x 4,3) 14 (4,3) 13 (49) 7.0 (0,48) 13 (49) 7.0 (0,48) 16 x 16 (4,9 x 4,9) 16 (4,9) 13 (49) 7.0 (0,48) 13 (49) 7.0 (0,48) 18 x 18 (5,5 x 5,5) 18 (5,5) 17 (64,3) 12 (0,83) 17 (64,3) 12 (0,83) 20 x 20 (6,1 x 6,1) 20 (6,1) 20 (75,7) 16.7 (1,14) 20 (75,7) 16,7 (1,14) For Ceiling types refer to NFPA 13, 13R or 13D Max. Coverage area Ft x Ft (m x m) Max. Spacing Ft (m) Ordinary Temp. Rating (155°F/68°C) Intermediate Temp. Rating (175°F/79°C)Top of Defl ector to Ceiling Inch (mm) Minimum Spacing Ft (m)Flow GPM (L/min) Pressure PSI (bar) Flow GPM (L/min) Pressure PSI (bar) 12 x 12 (3,6 x 3,6) 12 (3,6) 15 (57) 9.4 (0,65) 15 (57) 9.4 (0,65)Smooth Ceilings 4 to 8 (100 to 203) using F2 escutcheon.4 to 8 (100 to 203) using F1 escutcheon. Beamed Ceilings per NFPA 13D, 13R or 13 installed in beams 4¼ to 8 (108 to 203) using F2 escutcheon, 4 to 8 (100 to 203) using F1 escutcheon 8 (2,4) 14 x 14 (4,3 x 4,3) 14 (4,3) 16 (60,5) 10.6 (0,73) 16 (60,5) 10.6 (0,73) 16 x 16 (4,9 x 4,9) 16 (4,9) 17 (64,3) 12.0 (0,83) 17 (64,3) 12.0 (0,83) 18 x 18 (5,5 x 5,5) 18 (5,5) 19 (72) 15.0 (1,0) 19 (72) 15.0 (1,0) 20 x 20 (6,1 x 6,1) 20 (6,1) 22 (83,2) 20.2 (1,4) 22 (83,2) 20.2 (1,4) Technical Data: F1Res 58 Pendent and Recessed Pendent (SIN R3513) Thread Size Nominal Orifi ce Inch (mm) Max. Pressure psi (bar) Sprinkler Temp. Rating Max. Ambient Temp.Actual K Factor Sprinkler Length Inch (mm)°F °C °F °C ½” NPT (R½)½” (13) 175 (12) 155 175 68 79 100 150 38 66 5.8 (83.5) 2.25 (57) Max. Coverage area Ft x Ft (m x m) Max. Spacing Ft (m) Ordinary Temp. Rating (155°F/68°C) Intermediate Temp. Rating (175°F/79°C)Top of Defl ector to Ceiling Inch (mm) Minimum Spacing Ft (m)Flow GPM (L/min) Pressure PSI (bar) Flow GPM (L/min) Pressure PSI (bar) 12 x 12 (3,6 x 3,6) 12 (3,6) 16 (61) 7.6 (0,53) 16 (61) 7.6 (0,53)Smooth Ceilings 1¼ to 4 (31.7 to 102) using F2 escutcheon. 1 to 4 (25.4 to 102) using F1 escutcheon. Beamed Ceilings per NFPA 13D, 13R or 13 installed in beams 1¼ to 1¾ (31.7 to 44.4) using F2 escutcheon, 1 to 1¾ (25.4 to 44.4) using F1 escutcheon 8 (2,4) 14 x 14 (4,3 x 4,3) 14 (4,3) 16 (61) 7.6 (0,53) 16 (61) 7.6 (0,53) 16 x 16 (4,9 x 4,9) 16 (4,9) 16 (61) 7.6 (0,53) 16 (61) 7.6 (0,53) 18 x 18 (5,5 x 5,5) 18 (5,5) 19 (72) 10.8 (0,75) 19 (72) 10.8 (0,75) 20 x 20 (6,1 x 6,1) 20 (6,1) 22 (83,3) 14.4 (1,0) 22 (83,3) 14.4 (1,0) For Ceiling types refer to NFPA 13, 13R or 13D Note: The F1 Res 76 will use a 1” x ¾” reducer. FP push-on/thread-off escutcheon Fig. 3 Fig. 4 4. • Model F1 Res 30, 49, 58 & 76 CCP Pendent*• Model F1 Res 30, 49, 58 & 76 Recessed Pendent / FP Technical Data: F1 Res 76 Pendent and Recessed Pendent (SIN R7618) Thread Size Nominal Orifi ce Inch (mm) Max. Pressure psi (bar) Sprinkler Temp. Rating Max. Ambient Temp.K Factor Sprinkler Length Inch (mm)°F °C °F °C 3/4” NPT (R3/4)17/32” (13.5) 175 (12) 155175 6879 100150 3866 7.6 (109) 2.25 (57) Max. Coverage area Ft x Ft (m x m) Max. Spacing Ft (m) Ordinary Temp. Rating (155°F/68°C) Intermediate Temp. Rating (175°F/79°C)Top of Defl ector to Ceiling Inch (mm) Minimum Spacing Ft (m)Flow GPM (L/min) Pressure PSI (bar) Flow GPM (L/min) Pressure PSI (bar) 12 x 12 (3,6 x 3,6) 12 (3,6) 21 (79,5) 7.6 (0,53) 21 (79,5) 7.6 (0,53)Smooth Ceilings 4¼ to 8 (108 to 203) using F2 escutcheon.4 to 8 (100 to 203) using F1 escutcheon. Beamed Ceilings per NFPA 13D, 13R or 13 installed in beams 4¼ to 8 (108 to 203) us-ing F2 escutcheon, 4 to 8 (100 to 203) using F1 escutcheon 8 (2,4) 14 x 14 (4,3 x 4,3) 14 (4,3) 21 (79,5) 7.6 (0,53) 21 (79,5) 7.6 (0,53) 16 x 16 (4,9 x 4,9) 16 (4,9) 21 (79,5) 7.6 (0,53) 21 (79,5) 7.6 (0,53) 18 x 18 (5,5 x 5,5) 18 (5,5) 21 (79,5) 7.6 (0,53) 21 (79,5) 7.6 (0,53) 20 x 20 (6,1 x 6,1) 20 (6,1) 23 (87,1) 9.2 (0,63) 23 (87,1) 9.2 (0,63) For Ceiling types refer to NFPA 13, 13R or 13D CCP Cover Plate Data: “A” Cover Adjustment Inch (mm) “B” CCP Height Inch (mm) “C” Defl ector Distance below bottom of beam Inch (mm) ½ (12.7)15/16 (24) ½ (13) - 1 (25.4) 5/16 (7.9)3/4 (19) ½ (13) - 1 (25.4) FP Escutcheon Data: FP Position “A” Inch (mm) “B” Defl ector Distance below bottom of beam Inch (mm) Max. Recessed 7/16 (11) ½ (12.7) Min. Recessed 15/16 (24) 1 (25.4) Note: Sprinklers shown in Fig. 3 and Fig. 4 are not suitable for installation in ceilings which have positive pressure in the space above. * Not listed for corrosion resistance. 5. Technical Data: F1Res 30 CCP Pendent and Recessed Pendent/FP (SIN R3511) Thread Size Nominal Orifi ce Inch (mm) Max. Pressure psi (bar) CCP Assembly Temp. Rating Max. Ambient Temp.K Factor Sprinkler Length Inch (mm)°F °C °F °C ½” NPT (R½)21/64” (8.2) 175 (12) 135 57 100 38 3.0 (43.2) 2.25 (57) Max. Coverage area Ft x Ft (m x m) Max. Spacing Ft (m) Ordinary Temp. Rating (155°F/68°C)Top of Defl ector to Ceiling Inch (mm) Minimum Spacing Ft (m)Flow GPM (L/min) Pressure PSI (bar) 12 x 12 (3,6 x 3,6) 12 (3,6) 8 (30,3) 7.0 (0,48) Smooth Ceilings ½ to 1 (13 to 25.4) using CCP. ½ to 1 (13 to 25.4) using FP escutcheon. Beamed Ceilings per NFPA 13D, 13R or 13 installed in beams ½ to 1 (13 to 25.4) using CCP.½ to 1 (13 to 25.4) using FP escutcheon. 8 (2,4) 14 x 14 (4,3 x 4,3) 14 (4,3) 11 (37,8) 13.4 (0,92) For Ceiling types refer to NFPA 13, 13R or 13D Technical Data: F1Res 49 CCP Pendent and Recessed Pendent/FP (SIN 3516) Thread Size Nominal Orifi ce Inch (mm) Max. Pressure psi (bar) CCP Assembly Temp. Rating Max. Ambient Temp. K Factor Sprinkler Length Inch (mm) °F °C °F °C ½” NPT (R½)7/16” (11) 175 (12) 135 57 100 38 4.9 (70.6) 2.25 (57) Max. Coverage area Ft x Ft (m x m) Max. Spacing Ft (m) Ordinary Temp. Rating (155°F/68°C)Top of Defl ector to Ceiling Inch (mm) Minimum Spacing Ft (m)Flow GPM (L/min) Pressure PSI (bar) 12 x 12 (3,6 x 3,6) 12 (3,6) 13 (49) 7.0 (0,48)Smooth Ceilings ½ to 1 (13 to 25.4) using CCP. ½ to 1 (13 to 25.4) using FP escutcheon. Beamed Ceilings per NFPA 13D, 13R or 13 installed in beams ½ to 1 (13 to 25.4) using CCP. ½ to 1 (13 to 25.4) using FP escutcheon. 8 (2,4) 14 x 14 (4,3 x 4,3) 14 (4,3) 13 (49) 7.0 (0,48) 16 x 16 (4,9 x 4,9) 16 (4,9) 14 (53) 8.2 (0,56) 18 x 18 (5,5 x 5,5) 18 (5,5) 18 (68,1) 13.5 (0,93) 20 x 20 (6,1 x 6,1) 20 (6,1) 20 (75,7) 16.7 (1,14) For Ceiling types refer to NFPA 13, 13R or 13D Technical Data: F1Res 58 CCP Pendent and Recessed Pendent/FP (SIN R3513) Thread Size Nominal Orifi ce Inch (mm) Max. Pressure psi (bar) CCP Assembly Temp. Rating Max. Ambient Temp.K Factor Sprinkler Length Inch (mm)°F °C °F °C ½” NPT (R½)1/2” (13) 175 (12) 135 57 100 38 5.8 (83.5) 2.25 (57) Max. Coverage area Ft x Ft (m x m) Max. Spacing Ft (m) Ordinary Temp. Rating (155°F/68°C)Top of Defl ector to Ceiling Inch (mm) Minimum Spacing Ft (m)Flow GPM (L/min) Pressure PSI (bar) 12 x 12 (3,6 x 3,6) 12 (3,6) 16 (61) 7.6 (0,53) Smooth Ceilings ½ to 1 (13 to 25.4) using CCP. ½ to 1 (13 to 25.4) using FP escutcheon.Beamed Ceilings per NFPA 13D, 13R or 13 installed in beams ½ to 1 (13 to 25.4) using CCP. ½ to 1 (13 to 25.4) using FP escutcheon. 8 (2,4) 14 x 14 (4,3 x 4,3) 14 (4,3) 16 (61) 7.6 (0,53) 16 x 16 (4,9 x 4,9) 16 (4,9) 16 (61) 7.6 (0,53) 18 x 18 (5,5 x 5,5) 18 (5,5) 19 (72) 10.8 (0,75) 20 x 20 (6,1 x 6,1) 20 (6,1) 22 (83,3) 14.4 (1,0) For Ceiling types refer to NFPA 13, 13R or 13D 6. • Model F1 Res 44 & 58 HSW • Model F1 Res 44 & 58 Recessed HSW/F2 F2 escutcheon, 1/2” (13mm) adjustment Escutcheon, F2, Data: Type Adjustment Inch (mm) Face of Fitting to wall Inch (mm) F2 1/2 (13)3/16 - 11/16 (4.7 - 17.4) Fig. 5 Technical Data: F1Res 76 CCP Pendent and Recessed Pendent/FP (SIN R7618) Thread Size Nominal Orifi ce Inch (mm) Max. Pressure psi (bar) CCP Assembly Temp. Rating Max. Ambient Temp.K Factor Sprinkler Length Inch (mm)°F °C °F °C 3/4” NPT (R3/4)17/32” (13.5) 175 (12) 135 57 100150 3866 7.6 (109) 2.25 (57) Max. Coverage area Ft x Ft (m x m) Max. Spacing Ft (m) Ordinary Temp. Rating (155°F/68°C)Top of Defl ector to Ceiling Inch (mm) Minimum Spacing Ft (m)Flow GPM (L/min) Pressure PSI (bar) 12 x 12 (3,6 x 3,6) 12 (3,6) 21 (79,5) 7.6 (0,53) Smooth Ceilings ½ to 1 (13 to 25.4) using CCP. ½ to 1 (13 to 25.4) using FP escutcheon. Beamed Ceilings per NFPA 13D, 13R or 13 installed in beams ½ to 1 (13 to 25.4) using CCP. ½ to 1 (13 to 25.4) using FP escutcheon. 8 (2,4) 14 x 14 (4,3 x 4,3) 14 (4,3) 21 (79,5) 7.6 (0,53) 16 x 16 (4,9 x 4,9) 16 (4,9) 21 (79,5) 7.6 (0,53) 18 x 18 (5,5 x 5,5) 18 (5,5) 22 (83,3) 8.4 (0,58) 20 x 20 (6,1 x 6,1) 20 (6,1) 25 (94,6) 10.8 (0,74) For Ceiling types refer to NFPA 13, 13R or 13D Technical Data: F1Res 44 HSW & HSW/F2 (SIN R3531) Thread Size Nominal Orifi ce Inch (mm) Max. Pressure psi (bar) Sprinkler Temp. Rating Max. Ambient Temp. K Factor Sprinkler Length Inch (mm)°F °C °F °C ½” NPT (R½)3/8” (10) 175 (12) 155 175 68 79 100 150 38 66 4.4 (63) 2.45 (62) 7. Max. Coverage area Ft x Ft (m x m) Max. Spacing Ft (m) Ordinary Temp. Rating (155°F/68°C) Intermediate Temp. Rating (175°F/79°C)Top of Defl ector to Ceiling Inch (mm) Minimum Spacing Ft (m)Flow GPM (L/min) Pressure PSI (bar) Flow GPM (L/min) Pressure PSI (bar) 12 x 12 (3,6 x 3,6) 12 (3,6) 12 (45,4) 7.5 (0,52) 12 (45,4) 7.5 (0,52) 4 to 6 (100 to 152);½ (13) recessed using F2 escutcheon 8 (2,4) 14 x 14 (4,3 x 4,3) 14 (4,3) 14 (53,0) 10.2 (0,71) 14 (53,0) 10.2 (0,71) 16 x 16 (4,9 x 4,9) 16 (4,9) 16 (60,6) 13.3 (0,92) 16 (60,6) 13.3 (0,92) 16 x 18 (4,9 x 5,5) 16 (4,9) 18 (68,1) 16.8 (0,53) 18 (68,1) 16.8 (0,53) 18 x 18 (5,5 x 5,5) 18 (5,5) 19 (72,0) 18.7 (1,29) 19 (72,0) 18.7 (1,29) 16 x 20 (4,9 x 6,1) 16 (4,9) 23 (87,1) 27.4 (1,89) 23 (87,1) 27.4 (1,89) 12 x 12 (3,6 x 3,6) 12 (3,6) 14 (53,0) 10.2 (0,71) 14 (53,0) 10.2 (0,71) 6 to 12 (152 to 305); ½ (13) recessedusing F2 escutcheon 14 x 14 (4,3 x 4,3) 14 (4,3) 16 (60,6) 13.3 (0,92) 16 (60,6) 13.3 (0,92) 16 x 16 (4,9 x 4,9) 16 (4,9) 17 (64,4) 15.0 (1,04) 17 (64,4) 15.0 (1,04) 16 x 18 (4,9 x 5,5) 16 (4,9) 20 (75,7) 20.7 (1,43) 20 (75,7) 20.7 (1,43) 16 x 20 (4,9 x 6,1) 16 (4,9) 23 (87,1) 27.4 (1,89) 23 (87,1) 27.4 (1,89) For Ceiling types refer to NFPA 13, 13R or 13D Escutcheon, F2, Data: Type Adjustment Inch (mm) Face of Fitting to wall Inch (mm) F2 1/2 (13)3/16 - 11/16 (4.7 - 17.4) Technical Data: F1Res 58 HSW & HSW/F2 (SIN R3533) Thread Size Nominal Orifi ce Inch (mm) Max. Pressure psi (bar) Sprinkler Temp. Rating Max. Ambient Temp. K Factor Sprinkler Length Inch (mm)°F °C °F °C ½” NPT (R½)1/2” (13) 175 (12) 155 175 68 79 100 150 38 66 5.8 (83.5) 2.45 (62) Max. Coverage area Ft x Ft (m x m) Max. Spacing Ft (m) Ordinary Temp. Rating (155°F/68°C) Intermediate Temp. Rating (175°F/79°C)Top of Defl ector to Ceiling Inch (mm) Minimum Spacing Ft (m)Flow GPM (L/min) Pressure PSI (bar) Flow GPM (L/min) Pressure PSI (bar) 12 x 12 (3,6 x 3,6) 12 (3,6) 16 (60,6) 7.6 (0,53) 16 (60,6) 7.6 (0,53) 4 to 6 (100 to 152); ½ (13) recessed using F2 escutcheon 8 (2,4) 14 x 14 (4,3 x 4,3) 14 (4,3) 18 (68,2) 9.7 (0,69) 18 (68,2) 9.7 (0,69) 16 x 16 (4,9 x 4,9) 16 (4,9) 21 (79,5) 13.2 (0,91) 21 (79,5) 13.2 (0,91) 16 x 18 (4,9 x 5,5) 16 (4,9) 25 (94,7) 18.6 (1,28) 25 (94,7) 18.6 (1,28) 16 x 20 (4,9 x 6,1) 16 (4,9) 29 (109,8) 25.0 (1,73) 29 (109,8) 25.0 (1,73) 12 x 12 (3,6 x 3,6) 12 (3,6) 22 (83,3) 14.4 (1,0) 22 (83,3) 14.4 (1,0) 6 to 12 (152 to 305); ½ (13) recessed using F2 escutcheon 14 x 14 (4,3 x 4,3) 14 (4,3) 22 (83,3) 14.4 (1,0) 22 (83,3) 14.4 (1,0) 16 x 16 (4,9 x 4,9) 16 (4,9) 26 (98,4) 20.1 (1,39) 26 (98,4) 20.1 (1,39) 16 x 18 (4,9 x 5,5) 16 (4,9) 31 (117,4) 28.6 (1,97) 31 (117,4) 28.6 (1,97) For Ceiling types refer to NFPA 13, 13R or 13D • Model F1 Res 44 SWC* Fig. 6 Technical Data: F1Res 44 SWC (SIN R3531) Thread Size Nominal Orifi ce Inch (mm) Max. Pressure psi (bar) Cover Temp. Rating Max. Ambient Temp. K Factor Sprinkler Length Inch (mm)°F °C °F °C ½” NPT (R½)3/8” (10) 175 (12) 135 57 100 38 4.4 (63) 2.45 (62) Max. Coverage area Ft x Ft (m x m) Max. Spacing Ft (m) Ordinary Temp. Rating (155°F/68°C)Top of Defl ector to Ceiling Inch (mm) Minimum Spacing Ft (m)Flow GPM (L/min) Pressure PSI (bar) 12 x 12 (3,6 x 3,6) 12 (3,6) 13 (49,2) 8.7 (0,60) 4 to 6 (100 to 152);½ (13) recessed using F2 escutcheon 8 (2,4) 14 x 14 (4,3 x 4,3) 14 (4,3) 14 (53,0) 10.2 (0,71) 16 x 16 (4,9 x 4,9) 16 (4,9) 17 (64,3) 15.0 (1,1) 16 x 18 (4,9 x 5,5) 16 (4,9) 19 (71,8) 18.7 (1,13) 16 x 20 (4,9 x 6,1) 16 (4,9) 23 (87,1) 27.4 (1,89) 12 x 12 (3,6 x 3,6) 12 (3,6) 14 (52,9) 10.2 (0,71) 6 to 12 (152 to 305); ½ (13) recessed using F2 escutcheon 14 x 14 (4,3 x 4,3) 14 (4,3) 15 (56,7) 11.7 (0,81) 16 x 16 (4,9 x 4,9) 16 (4,9) 18 (68,1) 16.8 (1,16) 16 x 18 (4,9 x 5,5) 16 (4,9) 20 (75,6) 20.7 (1,43) For Ceiling types refer to NFPA 13, 13R or 13D 8. * Not listed for corrosion resistance. 9. Technical Data: F1Res 58 HSWX (SIN RA3533) Thread Size Nominal Orifi ce Inch (mm) Max. Pressure psi (bar) Sprinkler Temp. Rating Max. Ambient Temp. K Factor Sprinkler Length Inch (mm) Sprinkler Identifi cation Number (SIN)°F °C °F °C Bulb ½” NPT (R½)1/2” (13) 175 (12) 155 175 68 79 100 150 38 66 5.8 (83.5) 2.45 (62) RA3533 Max. Coverage area Ft x Ft (m x m) Max. Spacing Ft (m) Ordinary Temp. Rating (155°F/68°C) Intermediate Temp. Rating (175°F/79°C)Top of Defl ector to Ceiling Inch (mm) Minimum Spacing Ft (m)Flow GPM (L/min) Pressure PSI (bar) Flow GPM (L/min) Pressure PSI (bar) 18 x 20 (5,5 x 6,1) 18 (5,5) 30 (114) 26.8 (1,85) 30 (114) 26.8 (1,85) 4 to 6 (100 to 152);½ (13) recessed using F2 escutcheon 8 (2,4) 20 x 20 (6,1 x 6,1) 20 (6,1) 30 (114) 26.8 (1,85) 30 (114) 26.8 (1,85) 16 x 22 (4,9 x 7,3) 16 (4,9) 33 (125) 32.4 (2,23) 33 (125) 32.4 (2,23) 16 x 24 (4,9 x 7,3) 16 (4,9) 38 (144) 42.9 (2,96) 38 (144) 42.9 (2,96) 14 x 26 (4,3 x 7,9) 14 (4,3) 42 (160) 52.4 (3,75) 42 (160) 52.4 (3,75) 18 x 20 (5,5 x 6,1) 18 (5,5) 35 (133) 36.4 (2,5) 35 (133) 36.4 (2,5) 6 to 12 (152 to 305); ½ (13) recessed using F2 escutcheon 16 x 22 (4,9 x 6,7) 16 (4,9) 38 (144) 42.9 (2,96) 38 (144) 42.9 (2,96) 16 x 24 (4,9 x 7,3) 16 (4,9) 42 (160) 52.4 (3,6) 42 (160) 52.4 (3,6) 14 x 26 (4,3 x 7,9) 14 (4,3) 46 (174) 62.9 (4,34) 46 (174) 62.9 (4,34) For Ceiling types refer to NFPA 13, 13R or 13D • Model F1 Res 58 HSWX (Bulb) • Model KRes58 HSWX (Link) Fig. 7 10. Maintenance Model F1 Res 30, 49, F1 Res 58, F1 Res 76 and F1 Res 44 Sprinklers should be inspected and the sprinkler sys- tem maintained in accordance with NFPA 25, 13, 13D, and 13R. Do not clean sprinkler with soap and water, Am- monia or any other cleaning fluids. Remove dust by using a soft brush or gentle vacuuming. Remove any sprinkler which has been painted (other than factory applied) or damaged in any way. A stock of spare sprinklers should be maintained to allow quick replacement of damaged or operated sprinklers. Prior to installation, sprinklers should remain in the original cartons and packaging until used. This will minimize the potential for damage to sprinklers that could cause improper operation or non-operation. Model F1 Res 30, 49 & 58 Pendent Sprinkler Specifi cations Sprinklers shall be [cULus Listed] [New York City MEA Approved (258-93-E)] low flow residential pendent sprin- klers engineered to provide a minimum design density of 0.05 gpm/ft2 over the listed coverage area. Listed flows as specified by the manufacturer’s technical data sheets are to be used. Residential sprinklers shall be installed in conformance with the manufacturer’s installation guide- lines and the applicable installation standard. Deflector- to-ceiling distance listing shall be 1” to 8” maximum, only for F1Res 49. Sprinkler frame and deflector shall be of bronze frame construction having a ½” NPT thread. Wa- ter seal assembly shall consist of a Teflon* coated Bel- leville spring washer with top-loaded extruded or cold head cup with 3 mm glass bulb containing no plastic parts, and having a temperature rating of [155°F (68°C)] [175°F (79°C)]. Sprinklers shall have a nominal K-factor of 3.0, 4.9 and 5.8. Standard finish: [Bronze] [Chrome- plated] [White Polyester] [Special finish– specify]. Resi- dential pendent sprinklers shall be Reliable Model F1 Res 30, 49 & 58, SIN R3511, R3516 & R3513 (Bulletin 135). Model F1 Res 49 & 58 Recessed Pendent/F1, Model F1 Res 30, 49 & 58 Recessed Pendent/ F2, Model F1 Res 30, 49 & 58 Recessed Pendent/ FP Sprinklers shall be [cULus Listed] [New York City MEA Approved (258-93-E)] low flow residential recessed pen- dent sprinklers engineered to provide a minimum design density of 0.05 gpm/ft2 over the listed coverage area. Listed flows as specified by the manufacturer’s technical data sheets are to be used. Residential sprinklers shall be installed in conformance with the manufacturer’s in- stallation guidelines and the applicable installation stan- dard. Deflector-to-ceiling distance listing shall be 1” to 8” maximum, only for F1Res 49. Sprinkler frame and deflec- tor shall be of bronze frame construction having a ½” NPT thread. Water seal assembly shall consist of a Teflon* coated Belleville spring washer with top-loaded extruded Technical Data: KRes58 HSWX (RA3593) Thread Size Nominal Orifi ce Inch (mm) Max. Pressure psi (bar) Max. Ambient Temp. K Factor Sprinkler Length Inch (mm) Sprinkler Identifi cation Number (SIN)°F °C Link ½” NPT (R½)1/2” (13) 175 (12) 100 38 5.8 (83.5) 2.45 (62) RA3593 Max. Coverage area Ft x Ft (m x m) Max. Spacing Ft (m) Ordinary Temp. Rating (165°F/74°C)Top of Defl ector to Ceiling Inch (mm) Minimum Spacing Ft (m)Flow GPM (L/min) Pressure PSI (bar) 18 x 20 (5,5 x 6,1) 18 (5,5) 29 (109) 25 (1,72) 4 to 6 (100 to 152);½ (13) recessed using F2 escutcheon 8 (2,4) 20 x 20 (6,1 x 6,1) 20 (6,1) 30 (114) 26.8 (1,85) 16 x 22 (4,9 x 7,3) 16 (4,9) 33 (125) 32.4 (2,23) 16 x 24 (4,9 x 7,3) 16 (4,9) 38 (144) 42.9 (2,96) 14 x 26 (4,3 x 7,9) 14 (4,3) 42 (160) 52.4 (3,75) 18 x 20 (5,5 x 6,1) 18 (5,5) 35 (133) 36.4 (2,5) 6 to 12 (152 to 305); ½ (13) Recessedusing F2 escutcheon 16 x 22 (4,9 x 6,7) 16 (4,9) 38 (144) 42.9 (2,96) 16 x 24 (4,9 x 7,3) 16 (4,9) 42 (160) 52.4 (3,6) 14 x 26 (4,3 x 7,9) 14 (4,3) 46 (174) 62.9 (4,34) For Ceiling types refer to NFPA 13, 13R or 13D *DuPont Registered Trademark 11. or cold head cup with 3 mm glass bulb containing no plastic parts, and having a temperature rating of [155°F (68°C)] [175°F (79°C)]. Sprinklers shall have a nomi- nal K-factor of 3.0, 4.9 & 5.8. Standard finish: [Bronze] [Chrome-plated] [White Polyester] [Special finish– spec- ify]. Recessed escutcheon assembly shall be a steel, two-piece escutcheon [with ½” adjustment (Model F2)] [with ¾” adjustment (Model F1)] [of push-on and thread off design with ½” adjustment (Model FP)]. Standard fin- ish shall be [brass][bright chrome] [white painted]. Resi- dential recessed pendent sprinklers shall be Reliable [Model F1 Res 30, 49 & 58 Recessed Pendent/F1] [Model F1 Res 30, 49 & 58 Recessed Pendent/F2] [Model F1 Res 30, 49 & 58 Recessed Pendent/FP] SIN R3511, R3516 & R3513 (Bulletin 135). Model F1 Res 30, 49 & 58 CCP Pendent (Concealed) Sprinklers shall be [cULus Listed] [New York City MEA Approved (258-93-E)] low flow residential concealed sprinklers engineered to provide a minimum design den- sity of 0.05 gpm/ft2 over the listed coverage area. Listed flows as specified by the manufacturer’s technical data sheets are to be used. Residential sprinklers shall be in- stalled in conformance with the manufacturer’s installa- tion guidelines and the applicable installation standard. Sprinkler frame and deflector shall be of bronze frame construction having a ½” NPT thread. Water seal as- sembly shall consist of a Teflon* coated Belleville spring washer with top-loaded extruded or cold head cup with 3 mm glass bulb containing no plastic parts, and having a temperature rating of 155°F (68°C). Cover plate assem- bly shall consist of a brass cover plate and copper alloy retainer flange. Method of attaching the cover plate to the sprinkler cup shall be a push-on and thread-off design allowing a ½” cover plate adjustment. Cover plate tem- perature rating shall be 135°F (57°C). A plastic protec- tive cap shall be provided and factory installed inside the sprinkler cup to protect the sprinkler from damage, which could occur during construction before the cover plate is installed. Standard cover plate finish: [White] [Custom Color– specify]. ]. Concealed pendent sprinklers shall be Reliable Model F1 Res 30, 49 & 58 CCP, SIN R3511, R3516 & R3513 (Bulletin 135). Model F1 Res 44, F1 Res 58 Horizontal Sidewall, F1 Res 58 HSWX & KRes58 HSWX Residential Sprinkler Specifi cations Sprinklers shall be [cULus Listed] low flow residential horizontal sidewall sprinklers engineered to provide a minimum design density of 0.05 gpm/ft2 over the listed coverage area. Listed flows as specified by the manu- facturer’s technical data sheets are to be used. Residen- tial sprinklers shall be installed in conformance with the manufacturer’s installation guidelines and the applicable installation standard. Sprinkler frame and deflector shall be of bronze frame construction having a ½” NPT thread. Water seal assembly shall consist of a Teflon* coated Bel- leville spring washer with top-loaded extruded or cold head cup with 3 mm glass bulb containing no plastic parts, and having a temperature rating of [155°F (68°C)] [175°F (79°C)]. The solder element (Link) version, the water seal consist of a cap with a bellville spring washer and a temperature rating of 165°F (74°C). The recessed assembly forthe HSWX (Bulb & Link) should be a steel two pieces escutcheon with 1/2” adjustment (Model F2) standard finish should be Bright Chrome and white paint- ed. The F1 Res 58 HSW is also available with low lead frame. F1 Res 58 HSW and HSWX sprinklers shall have a nominal K Factor of 5.8 and F1 Res 44 a nominal K factor of 4.4. Standard finish: [Bronze] [Chrome-plated] [White Polyester] [Special finish– specify]. Residential horizontal sidewall sprinklers shall be Reliable Model F1 Res 44, F1 Res 58, F1 Res 58 HSWX & Model KRes58 HSWX, SIN R3531, RA3533 & RA3593 (Bulletin 135). Model F1 Res 44 Recessed Horizontal Sidewall Sprinkler Use description for the Model F1 Res 44 horizontal side- wall sprinkler with the following modifications: Replace “horizontal sidewall sprinkler” with “recessed horizontal sprinkler.” Add: Recessed escutcheon assembly shall be a steel, two-piece escutcheon with ½” adjustment (Model F2). Standard finish shall be [brass][bright chrome] [white painted] [Special finish– specify]. Residential recessed horizontal sidewall sprinklers shall be Reliable Model F1 Res 44/F2, SIN R3531 (Bulletin 135). Model F1 Res 76 Pendent Sprinklers shall be [cULus Listed] low flow residential pendent sprinklers engineered to provide a minimum design density of 0.05 gpm/ft2 over the listed coverage area. Listed flows as specified by the manufacturer’s technical data sheets are to be used. Residential sprin- klers shall be installed in conformance with the manufac- turer’s installation guidelines and the applicable installa- tion standard. Sprinkler frame and deflector shall be of bronze frame construction having a ¾” NPT thread. Wa- ter seal assembly shall consist of a Teflon* coated Bel- leville spring washer with machined or cold head cup with 3 mm glass bulb containing no plastic parts, and having a temperature rating of [155°F (68°C)] [175°F (79°C)]. Sprinklers shall have a nominal K-factor of 7.6. Standard finish: [Bronze] [Chrome-plated] [White Polyester] [Spe- cial finish– specify]. Residential pendent sprinklers shall be Reliable Model F1 Res 76, SIN R7618 (Bulletin 135). *DuPont Registered Trademark Reliable Automatic Sprinkler Co., Inc.(800) 431-1588 Sales Offices (800) 848-6051 Sales Fax (914) 829-2042 Corporate Offices www.reliablesprinkler.com Internet Address Manufactured by Recycled Paper Revision lines indicate updated or new data. EG. Printed in U.S.A. 07/14 P/N 9999970235 The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Products manufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries. a temperature rating of 155°F (68°C). Cover plate assem- bly shall consist of a brass cover plate and copper alloy retainer flange. Method of attaching the cover plate to the sprinkler cup shall be a push-on and thread-off design allowing a ½” cover plate adjustment. Cover plate tem- perature rating shall be 135°F (57°C). A plastic protec- tive cap shall be provided and factory installed inside the sprinkler cup to protect the sprinkler from damage, which could occur during construction before the cover plate is installed. Standard cover plate finish: [White] [Custom Color– specify]. ]. Concealed pendent sprinklers shall be Reliable Model F1 Res 76 CCP, SIN R7618 (Bulletin 135). Finishes (1) Standard Finishes Sprinkler F1, F2, FP Escutcheons Cover Plates Bronze Chrome Plated White and Black Polyester(2) Coated Brass Bright Chrome Plated White Painted White Painted Chrome Special Application Finishes Sprinkler F1, F2, FP Escutcheons Electroless Nickel PTFE(Teflon®)(2) Bright Brass Black PlatedBlack Paint Off White Chrome Dull Electroless Nickel PTFE (Teflon®) Bright Brass Black PlatedBlack Paint Off White Chrome Dull (1) Other finishes and colors are available on special order. Consult factory for details. (2) cULus listed Corrosion Resistant Note: Paint or any other coating applied over the factory finish will void all approvals and warranties. Ordering Information Specify: 1. Sprinkler Model 2. Sprinkler Type 3. Temperature Rating 4. Sprinkler Finish 5. Escutcheon Finish 6. Cover Plate Finish Model F1 Res 76 Recessed Pendent/F1, Model F1 Res 76 Recessed Pendent/F2, Model F1 Res 76 Recessed Pendent/FP Sprinklers shall be [cULus Listed] low flow residential recessed pendent sprinklers engineered to provide a minimum design density of 0.05 gpm/ft2 over the listed coverage area. Listed flows as specified by the manu- facturer’s technical data sheets are to be used. Residen- tial sprinklers shall be installed in conformance with the manufacturer’s installation guidelines and the applicable installation standard. Sprinkler frame and deflector shall be of bronze frame construction having a ¾” NPT thread. Water seal assembly shall consist of a Teflon* coated Bel- leville spring washer with machined or cold head cup with 3 mm glass bulb containing no plastic parts, and hav- ing a temperature rating of [155°F (68°C)] [175°F (79°C)]. Sprinklers shall have a nominal K-factor of 7.6. Standard finish: [Bronze] [Chrome-plated] [White Polyester] [Spe- cial finish– specify]. Recessed escutcheon assembly shall be a steel, two-piece escutcheon [with ½” adjust- ment (Model F2)] [with ¾” adjustment (Model F1)] [of push-on and thread off design with ½” adjustment (Mod- el FP)]. Standard finish shall be [brass][bright chrome] [white painted]. Residential recessed pendent sprinklers shall be Reliable [Model F1 Res 76 Recessed Pendent/ F1] [Model F1 Res 76 Recessed Pendent/F2] [Model F1 Res 76 Recessed Pendent/FP] SIN R7618 (Bulletin 135). Model F1 Res 76 CCP Pendent (Concealed) Sprinklers shall be [cULus Listed] low flow residential concealed sprinklers engineered to provide a minimum design density of 0.05 gpm/ft2 over the listed coverage area. Listed flows as specified by the manufacturer’s technical data sheets are to be used. Residential sprin- klers shall be installed in conformance with the manufac- turer’s installation guidelines and the applicable installa- tion standard. Sprinkler frame and deflector shall be of bronze frame construction having a ¾” NPT thread. Wa- ter seal assembly shall consist of a Teflon* coated Bel- leville spring washer with machined or cold head cup with 3 mm glass bulb containing no plastic parts, and having *DuPont Registered Trademark Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523 Bulletin 006 Rev. IBulletin 006 Rev. I Model RFC30 (SIN RA0611) Model RFC43 (SIN RA0612) Model RFC49 (SIN RA0616) Residential Flat Concealed Sprinklers A Residential Flat Concealed Sprinkler engineered for a minimum design density of 0.05 gpm/ft2 with low GPM requirements. Features 1. Very low water flow requirements. 2. Cover plate attachment (Plain or Perforated) with ½” (13mm) Total adjustment. 3. Thread-On/Thread-Off or Push-On/Thread Off cover attachment option. 4. Smooth aesthetic ceiling profile. 5. Available in brass, chrome and black plated or painted finishes. Listings & Approval 1. Listed by Underwriters Laboratories, and certified by UL for Canada (cULus) UL Listing Categories Residential Automatic Sprinklers UL Guide Number VKKW Product Description Model RFC30, RFC43 and RFC49 Concealed Residen- tial Sprinklers are fast response residential fusible solder link automatic sprinklers. Residential sprinklers differ from standard sprinklers primarily in their response time and water distribution patterns. Model RFC30, RFC43 and RFC49 sprinklers discharge water in a hemispherical pattern below the sprinkler de- flector. Residential distribution patterns are higher and generally contain a finer droplet size than standard sprin- kler patterns. The combination of speed of operation and high dis- charge pattern required for residential sprinklers has demonstrated, in fire testing, an ability for controlling residential fires, and thereby providing significant evacu- ation time for occupants. The RFC30, RFC43 and RFC49 Sprinklers provide the best form of fire protection by combining an attractive ap- pearance and ½” (13mm) of cover adjustment for ease of installation. The small diameter cover plate is easily and positively attached and blends into the ceiling, con- cealing the most dependable fire protection available, an automatic sprinkler system. The RFC30, RFC43 and RFC49 are UL Listed Residen- tial Sprinklers to be installed in the residential portions of any occupancy in accordance with NFPA 13, 13R, & 13D. The RFC30, RFC43 and RFC49 can reduce the need for precise cutting of drop nipples. The threaded cover plate assembly can be adjusted without tools to fit ac- curately against the ceiling. The fire protection system need not be shut down to adjust or remove the cover plate assembly. Plain Cover Plate Perforated Cover Plate 2. Application and Installation The RFC30, RFC43 and RFC49, for residential instal- lations, use a 165°F (74°C) fusible solder link in a tun- ing fork style sprinkler frame with a drop-down deflector. This assembly is recessed into the ceiling and concealed by a flat cover plate. The cover plate is attached to the skirt, using 135°F (57°C) ordinary temperature classifica- tion solder. When the ceiling temperature rises, the solder holding the cover plate releases the cover allowing the deflector to drop into position and exposing the sprinkler inside to ceiling temperature. The subsequent operation of the solder link opens the waterway and causes the de- flector to drop into position to distribute the discharging water in a hemispherical pattern below the sprinkler de- flector. Any adjustment of thread engagement between the cover plate and cup will assure that the drop-down deflector is properly located below the ceiling. The resi- dential distribution pattern contains a finer droplet size than a standard sprinkler, and the pattern produces sig- nificantly higher wall wetting. After a 25/8 inch diameter hole is cut in the ceiling, the sprinkler is to be installed with the Model FC Wrench. When installing a sprinkler, the wrench is first positioned into the sprinkler/cup assembly and around the hexago- nal body of the sprinkler frame. The Wrench must bottom out against the cup in order to ensure proper, safe instal- lation. The sprinkler is then tightened into the pipe fitting. When inserting or removing the wrench from the sprin- kler/cup assembly, care should be taken to prevent dam- age to the sprinkler. DO NOT WRENCH ON ANY OTHER PART OF THE SPRINKLER/CUP ASSEMBLY. MODEL RFC30, RFC43 AND RFC49 CONCEALED SPRINKLERS MUST BE INSTALLED ONLY WITH 135°F RATED COV- ERS. Note: A leak tight ½” NPT (R1/2) sprinkler joint can be ob- tained with a torque of 8-18 ft-lbs (10,8 - 24,4 N-m). Do not tighten sprinklers over maximum recommended torque. It may cause leakage or impairment of the sprinklers. Cover assemblies provide up to 1/2” (13mm) of adjust- ment. Turn the cover clockwise until the flange is in con- tact with the ceiling. For the push-on/thread-off option, the cover assembly is pushed onto the cup and final ad- justment is made by turning the cover clockwise until the skirt flange makes full contact with the ceiling. Cover re- moval requires turning in the counter-clockwise direction. In ceilings that have a plenum space above the sprinkler, the plenum space may have neutral or neg- ative pressurization but must not be positively pres- surized. Inspect all sprinklers after installation to en- sure that the gap between the cover plate and ceiling and the 4 slots in the cup are all open and free from any air fl ow impediment. Model (SIN) Thread Size Inch (mm) Nominal Orifi ce Inch (mm) Sprinkler Temp Rating CCP Assembly Temp. Rating Max. Ambient Temp. K Factor Max. Pressure psi (bar)°F °C °F °C °F °C RFC 30 (RA0611)½” (15)21/64 (8,2) 165 74 135 57 100 38 3.0 (43.2) 175 (12) RFC 43 (RA0612)½” (15)3/8 (10) 165 74 135 57 100 38 4.3 (62) 175 (12) RFC 49 (RA0616)½” (15)7/16 (11) 165 74 135 57 100 38 4.9 (70.6) 175 (12) Note: 1 bar = 100 Kpa RFC 30 Max. Coverage area Ft x Ft (m x m) Max. Spacing Ft (m) Ordinary Temp. Rating (165°F/74°C)Top of Defl ector to Ceiling Inch (mm) Installation Type Minimum Spacing Ft (m)Flow GPM (L/min) Pressure PSI (bar) 12 x 12 (3,6 x 3,6) 12 (3,6) 9 (34,1) 9.0 (0,62) Smooth Ceilings ½ to 1 (13 to 25.4) Beamed Ceilings per NFPA 13D, 13R or13 installed in beams ½ to 1 (13 to 25.4)Concealed 8 (2,4) 14 x 14 (4,3 x 4,3) 14 (4,3) 10 (37,8) 11.0 (0,76) For Ceiling types refer to NFPA 13, 13R or 13D 3. Maintenance Model RFC30, RFC43 and RFC49 Concealed Sprin- klers should be inspected and the sprinkler system maintained in accordance with NFPA 25. Do not clean sprinklers with soap and water, ammonia or any other cleaning fluids. Remove dust by using a soft brush or gentle vacuuming. Remove any sprinkler cover plate as- sembly which has been painted (other than factory ap- plied) or damaged in any way. A stock of spare sprin- klers should be maintained to allow quick replacement of damaged or operated sprinklers. Prior to installation, sprinklers should be maintained in the original cartons and packaging until used to minimize the potential for damage to sprinklers that would cause improper opera- tion or non-operation. Model RFC30, RFC43 and RFC49 Residential Concealed Sprinkler Specifi cation Sprinklers shall be cULus Listed low flow residential con- cealed sprinklers with drop-down deflector and adjust- able flat cover plate engineered for a minimum design density of 0.05 gpm/ft2. Sprinkler frame and deflector shall be of bronze frame construction having a ½” NPT thread. Thermal element shall consist of an approved black-painted beryllium-nickel fusible solder link with symmetric lever mechanism, maintaining a Teflon-coated Belleville spring washer and machined brass cap water seal assembly containing no plastic parts. Sprinkler K- factor shall be nominal 3.0 (43.2), 4.3 (62), and 4.9 (70.6) having a 5/16”, 3/8” and 7/16” orifice. Temperature rating shall be Ordinary 165°F (74°C); cover plate temperature rating to be 135°F (57°C). Cover plate assembly shall consist of a brass cover plate and copper alloy retainer flange allowing a ½” cover plate adjustment. Any secure engagement between the cover plate and the cup will assure that the drop-down deflector is properly located below the ceiling. A plastic protective cap shall be provided and factory installed inside the sprinkler cup to protect the drop-down sprinkler deflector from dam- age, which could occur during construction before the cover plate is installed. Standard cover finish: [Chrome] [White] [Specialty – specify]. Residential concealed sprinklers shall be Reliable Model RFC30, SIN RA0611 (Bulletin 006), Model RFC43, SIN RA0612 (Bulletin 006) or Model RFC49, SIN RA0616 (Bulletin 006). RFC 43 Max. Coverage area Ft x Ft (m x m) Max. Spacing Ft (m) Ordinary Temp. Rating (165°F/74°C)Top of Defl ector to Ceiling Inch (mm) Installation Type Minimum Spacing Ft (m)Flow GPM (L/min) Pressure PSI (bar) 12 x 12 (3,6 x 3,6) 12 (3,6) 12 (4,5) 7.8 (0,54) Smooth Ceilings ½ to 1 (13 to 25.4) Beamed Ceilings per NFPA 13D, 13R or 13 installed in beams ½ to 1 (13 to 25.4) Concealed 8 (2,4) 14 x 14 (4,3 x 4,3) 14 (4,3) 13 (49) 9.1 (0,63) 16 x 16 (4,9 x 4,9) 16 (4,9) 13 (49) 9.1 (0,63) 18 x 18 (5,5 x 5,5) 18 (5,5) 18 (68) 17.5 (1,21) 20 x 20 (6,1 x 6,1) 20 (6,1) 21 (79) 23.8 (1,64) For Ceiling types refer to NFPA 13, 13R or 13D RFC 49 Max. Coverage area Ft x Ft (m x m) Max. Spacing Ft (m) Ordinary Temp. Rating (165°F/74°C)Top of Defl ector to Ceiling Inch (mm) Installation Type Minimum Spacing Ft (m)Flow GPM (L/min) Pressure PSI (bar) 12 x 12 (3,6 x 3,6) 12 (3,6) 13 (49) 7.0 (0,48) Smooth Ceilings ½ to 1 (13 to 25.4)Beamed Ceilings per NFPA 13D, 13R or 13 installed in beams ½ to 1 (13 to 25.4) Concealed 8 (2,4) 14 x 14 (4,3 x 4,3) 14 (4,3) 13 (49) 7.0 (0,48) 16 x 16 (4,9 x 4,9) 16 (4,9) 13 (49) 7.0 (0,48) 18 x 18 (5,5 x 5,5) 18 (5,5) 17 (64,3) 12.0 (0,83) 20 x 20 (6,1 x 6,1) 20 (6,1) 20 (75,73) 16.7 (1,14) For Ceiling types refer to NFPA 13, 13R or 13D Reliable Automatic Sprinkler Co., Inc. (800) 431-1588 Sales Offices(800) 848-6051 Sales Fax (914) 829-2042 Corporate Offices www.reliablesprinkler.com Internet Address Manufactured by Recycled Paper Revision lines indicate updated or new data. EG. Printed in U.S.A. 11/14 P/N 9999970261 The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Products manufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries. Ordering Information Specify: 1. Sprinkler Model 2. Cover Plate Finish 3. Thread-On or Push-On Feature Cover Plate Finishes(1) Standard Finishes Chrome White Paint Special Application Finishes(2) Bright Brass Finished Bronze Black Plating Black Paint Off White Satin Chrome (1) Other finishes and colors are available on special order. Consult factory for details. Coverplate custom paint is semi-gloss, unless specified otherwise. (2) For the perforated style cover- plate, consult factory for avail- ability on these and other cus-tom finishes.