HomeMy WebLinkAboutA17-0029_FireForce8 Vail Cascade Main Bldg Lower Level East_1496166300.pdf riGamewell
1 ° v - System Current Draw - FireForce8
Total Current
Standb 0.030 A
Alarm 2.335 A
Cl -Standby Current C2-Alarm Current
Device Qty Draw Standby Qty Draw Alarm
1.System Modules
Common Control Module(CCM) 1 x 0.03000 0.03000 1 x 0.05500 0.05500
NAC 1 and 2--Class B
Class B(NAC 1 + NAC 2) 1 x 0.00000 0.00000 1 x 0.06500 0.06500
NAC 3 and 4--Class B
Class B(NAC 3+ NAC 4) 1 x 0.00000 0.00000 1 x 0.06500 0.06500
External Load A+A- 24VDC 0 x 0.00000 0 x 0.00000
2.NAC#1
SCW15 9 x 0.00000 0.00000 9 x 0.06600 0.59400
SCW30 2 x 0.00000 0.00000 2 x 0.09400 0.18800
SPSCW15 4 x 0.00000 0.00000 4 x 0.06600 0.26400
SPSCW30 1 x 0.00000 0.00000 1 x 0.09400 0.09400
SPSCW75 1 x 0.00000 0.00000 1 x 0.15800 0.15800
0 x 0.00000 0 x 0.00000
0 x 0.00000 0 x 0.00000
0 x 0.00000 0 x 0.00000
NAC#1 Totals(Max 3.0 Amps): 0.00000 1.29800
3.NAC#2
SCW15 1 x 0.00000 0.00000 1 x 0.06600 0.06600
SCW30 2 x 0.00000 0.00000 2 x 0.09400 0.18800
SPSCW30 3 x 0.00000 0.00000 3 x 0.09400 0.28200
SPSCW75 2 x 0.00000 0.00000 2 x 0.15800 0.31600
0 x 0.00000 0 x 0.00000
0 x 0.00000 0 x 0.00000
0 x 0.00000 0 x 0.00000
0 x 0.00000 0 x 0.00000
NAC#2 Totals(Max 3.0 Amps): 0.00000 0.85200
4.NAC#3
SPSCW15 6 x 0.00000 0.00000 6 x 0.06600 0.39600
SPSW30 4 x 0.00000 0.00000 4 x 0.09400 0.37600
0 x 0.00000 0 x 0.00000
0 x 0.00000 0 x 0.00000
0 x 0.00000 0 x 0.00000
0 x 0.00000 0 x 0.00000
0 x 0.00000 0 x 0.00000
0 x 0.00000 0 x 0.00000
NAC#3 Totals(Max 3.0 Amps): 0.00000 0.77200
5.NAC#4
B200 SR-LF 5 x 0.00100 0.00500 5 x 0.09000 0.45000
SCWH177 2 x 0.00000 0.00000 2 x 0.28100 0.56200
0 x 0.00000 0 x 0.00000
0 x 0.00000 0 x 0.00000
0 x 0.00000 0 x 0.00000
0 x 0.00000 0 x 0.00000
0 x 0.00000 0 x 0.00000
0 x 0.00000 0 x 0.00000
NAC#4 Totals(Max 3.0 Amps): 0.00500 1.01200
6.Compatible Devices not listed
Other compatible devices _ 0 x 0.00000 _ 0 x 0.00000
Other compatible devices _ 0 x 0.00000 _ 0 x 0.00000
Other compatible devices 0 x 0.00000 0 x 0.00000
Total Standby Load: 0.030 Total Alarm Load: 2.335
ewel
r' I System Power Requirements
br M e•eY
FireForce8 Fire Alarm Control Panel
Protected Premises: Vail Cascade Main Bldg Lower Level East Date: 12/5/2016
Address: 1300 Westhaven Drive
City: Vail State: CO Zip: 81657
Prepared By: Acme Fire Aarm Company Phone: 970-625-5535
Address: PO Box 883 Email: clint@acmealarm.com
City: Rifle State: CO Zip: 81650
Primary Standby Load 0.03 Amps
Current load on the primary power supply during
non-alarm conditions.
Primary Alarm Load 2.34 Amps
Current load on the primary power supply during
alarm conditions.
Secondary Load Requirements 1.86 Amp Hours
Total Secondary Load from the calculation table below.
Current Draw Time (hours) I Total (AH)
Seconday Standby Load Required Standby Time 24.00
0.030 A 24 hours 0.72
Secondary Alarm Load Required Alarm Time(hours) 0.25
2.335 A 0.250 hours 0.58
Total Secondary Load 1.55
Derating factor x 1.2
Secondary Load Requirements 1.86 AH
Battery Selection 7 Amp Hours
Select batteries from the list below.
7.0 AH BAT-1270 Battery(12 volt)
Co Two fl Four(two 12VDC sets in parallel)
Page 1 of 2
Battery Distribution Chart
Shows amp-hour distribution of your selections.
Secondary Alarm Load •Spare Battery Capacity
10% OSecondary Standby Load
0 Secondary Alarm Load
Secondary Standby Load
13%
Comments
1. Batteries will fit in the FACP cabinet.
2. Selected battery size meets secondary load requirements.
3. The selected batteries (7AH) are within the charger range of this power supply(7-26AH).
Spare Battery Capacity 5.14 Battery Selection(AH)-Secondary Load Requirements(AH)
Secondary Standby Load 0.86 Secondary Standby Load(AH)*Derating Factor
Secondary Alarm Load 0.70 Secondary Alarm Load(AH)*Derating Factor
Page 2 of 2