HomeMy WebLinkAboutA17-0029_FireForce8 Vail Cascade Main Bldg Lower Level West_1496166300.pdf �GIr111
LvJf ° v - System Current Draw - FireForce8
byk.1
Total Current
Standb 0.030 A
Alarm 2.851 A
Cl -Standby Current C2-Alarm Current
Device Qty Draw Standby Qty Draw Alarm
1.System Modules
Common Control Module(CCM) 1 x 0.03000 0.03000 1 x 0.05500 0.05500
NAC 1 and 2--Class B
Class B(NAC 1 + NAC 2) 1 x 0.00000 0.00000 1 x 0.06500 0.06500
NAC 3 and 4--Class B
Class B(NAC 3+ NAC 4) 1 x 0.00000 0.00000 1 x 0.06500 0.06500
External Load A+A- 24VDC I 0 x 0.00000 0 x 0.00000
2.NAC#1
SCW15 4 x 0.00000 0.00000 4 x 0.06600 0.26400
SCW30 1 x 0.00000 0.00000 1 x 0.09400 0.09400
SPSCW15 5 x 0.00000 0.00000 5 x 0.06600 0.33000
SCW75 3 x 0.00000 0.00000 3 x 0.15800 0.47400
SPSWV75 5 x 0.00000 0.00000 5 x 0.15800 0.79000
0 x 0.00000 0 x 0.00000
0 x 0.00000 0 x 0.00000
0 x 0.00000 0 x 0.00000
NAC#1 Totals(Max 3.0 Amps): 0.00000 1.95200
3.NAC#2
SCW15 3 x 0.00000 0.00000 3 _ x 0.06600 0.19800
SPSCW15 4 x 0.00000 0.00000 4 _ x 0.06600 0.26400
SPSCW30 1 x 0.00000 0.00000 1 _ x 0.09400 0.09400
SPSCW75 1 x 0.00000 0.00000 1 _ x 0.15800 0.15800
0 x 0.00000 -1_ 0_ x 0.00000
0 x 0.00000 0 _ x 0.00000
0 x 0.00000 0 x 0.00000
0 x 0.00000 0 _ x 0.00000
NAC#2 Totals(Max 3.0 Amps): 0.00000 0.71400
4.NAC#3
SPSCW15 7 x 0.00000 0.00000 7 x 0.06600 0.46200
SPSCW75 1 x 0.00000 0.00000 1 x 0.15800 0.15800
SCW15 9 x 0.00000 0.00000 9 x 0.06600 0.59400
0 x 0.00000 0 x 0.00000
0 x 0.00000 0 x 0.00000
0 x 0.00000 0 x 0.00000
0 x 0.00000 0 x 0.00000
0 x 0.00000 0 x 0.00000
NAC#3 Totals(Max 3.0 Amps): 0.00000 1.21400
5.NAC#4
0 x 0.00000 0 x 0.00000
0 x 0.00000 0 x 0.00000
0 x 0.00000 0 x 0.00000
0 x 0.00000 0 x 0.00000
0 x 0.00000 0 x 0.00000
0 x 0.00000 _ 0 x 0.00000
0 x 0.00000 _ 0 x 0.00000
0 x 0.00000 _ 0 x 0.00000
NAC#4 Totals(Max 3.0 Amps): 0.00000 0.00000
6.Compatible Devices not listed
Other compatible devices _ 0 x 0.00000 _ 0 x 0.00000
Other compatible devices _ 0 x 0.00000 _ 0 x 0.00000
Other compatible devices 0 x 0.00000 0 x 0.00000
Total Standby Load: 0.030 1 Total Alarm Load: 2.851
ewel
r' I System Power Requirements
br M e•eY
FireForce8 Fire Alarm Control Panel
Protected Premises: Vail Cascade Main Bldg Lower Level West Date: 12/5/2016
Address: 1300 Westhaven Drive
City: Vail State: CO Zip: 81657
Prepared By: Acme Fire Aarm Company Phone: 970-625-5535
Address: PO Box 883 Email: clint@acmealarm.com
City: Rifle State: CO Zip: 81650
Primary Standby Load 0.03 Amps
Current load on the primary power supply during
non-alarm conditions.
Primary Alarm Load 2.85 Amps
Current load on the primary power supply during
alarm conditions.
Secondary Load Requirements 2.02 Amp Hours
Total Secondary Load from the calculation table below.
Current Draw Time (hours) I Total (AH)
Seconday Standby Load Required Standby Time 24.00
0.030 A 24 hours 0.72
Secondary Alarm Load Required Alarm Time(hours) 0.25
2.851 A 0.250 hours 0.71
Total Secondary Load 1.68
Derating factor x 1.2
Secondary Load Requirements 2.02 AH
Battery Selection 7 Amp Hours
Select batteries from the list below.
7.0 AH BAT-1270 Battery(12 volt)
Co Two fl Four(two 12VDC sets in parallel)
Page 1 of 2
Battery Distribution Chart
Shows amp-hour distribution of your selections.
Secondary Alarm Load •Spare Battery Capacity
13% OSecondary Standby Load
0 Secondary Alarm Load
Secondary Standby Load
13%
Comments
1. Batteries will fit in the FACP cabinet.
2. Selected battery size meets secondary load requirements.
3. The selected batteries (7AH) are within the charger range of this power supply(7-26AH).
Spare Battery Capacity 4.98 Battery Selection(AH)-Secondary Load Requirements(AH)
Secondary Standby Load 0.86 Secondary Standby Load(AH)*Derating Factor
Secondary Alarm Load 0.86 Secondary Alarm Load(AH)*Derating Factor
Page 2 of 2