HomeMy WebLinkAboutA17-0036_Scope of Work letter-Buffehr Creek_1501881180.pdf olti OF.10
ApAiroie.
u erior arm
'kW b
'114Z7r & Electronics
Vail Fire&Emergency Services
08/04/17
Security, Fire, CCTV, Access Control, Custom AudioNideo, and Automation
7/13/17
Vail Fire and Emergency Services
Mike Vaughan
42 W. Meadow Dr.
Vail, CO 81657 Approved based on
conversation with Contractor.
Re: Scope of Work Letter-1860 Meadow Ridge Rd
Dear Mike,
We've been contracted to replace the fire alarm panel at the Buffehr Creek Condos building. The
building is unsprinklered. The existing alarm panel is an addressable EST 10500 that is currently
damaged and requires replacement. The building ownership wants to replace the panel with a
non-proprietary alarm panel. Our proposal is to replace the alarm panel with a Silent Knight
5820XL. We will install multi-criteria smoke detectors in bedrooms (SK-ACCLIMATE) and
Smoke/Carbon Monoxide detectors outside bedrooms (SK-FIRE-CO). We will install one 135
degree fixed temp heat detector in each unit (SK-HEAT). This fully addressable system will be
programmed as follows:
• Common area smoke detectors and heat detectors will send general alarm and
dispatch fire department.
• Unit smoke detectors will sound temporal 3 in unit(in tandem)and will not dispatch
fire department.
• Unit carbon monoxide detector(s) will sound temporal 4 throughout unit and will
dispatch fire department.
• Unit heat detector will send general alarm and dispatch fire department.
Pull stations and notification devices will be replaced on a device for device basis.
Our installation will be performed in accordance with applicable NFPA 70, NFPA 72, [BC codes
and Town of Vail Standards.
Best Regards,
John Goss
NICET III Fire Alarm Systems#114260
Post Office Box 4910 • Edwards, Colorado 81632 • Phone(970)926-8788 • Fax(970)926-8790
www.superioralarmco.com o admin@superioralarmco.com