Loading...
HomeMy WebLinkAboutHydraulic Calcs_3.pdfCORPORATION VAIL VALLEY FIRE SPRINKLER CORP. 57 HEREFORD LANE EDWARDS, CO 81632 PH: (970) 914-5014 VILLAGE INN PLAZA UNIT 302 100 EAST MEADOW DR. VAIL, CO 81658 HYDRAULIC CALCULATIONS 4/22/2016 Hydraulic Calculations Location: 100 EAST MEADOWS DR., VAIL, CO 81658, Project Name: VILLAGE INN PLAZA UNIT 302 Drawing Name: 160403.cad Calculation Date: 4/22/2016 for Design Residential Area of Application: 602.94ft² (Actual 602.94ft²) Coverage per Sprinkler: 256.00ft² Type of sprinklers calculated: 4 1Remote Area Number: Occupancy Classification: No. of sprinklers calculated: Density:0.100gpm/ft² Pendent Volume of Dry or PreAction System: In-rack Demand: Hose Streams: Type of System: at Node:Type:Allowance at Source N/Aat Node:N/A gpm 1100.00 N/A (including Hose Streams where applicable):Total Water Required 89.109@208.23From Water Supply at Node 1: Water Supply Information: Name of Contractor:VAIL VALLEY FIRE SPRINKLER CO VAIL FIRE DEPTAuthority Having Jurisdiction: Address: Phone Number:Name of designer: 57 HEREFORD LANE, EDWARDS, CO 81632 (970) 914-5014 PAUL HUBBARD. Notes: 4/22/2016© M.E.P.CAD, Inc.Page 1AutoSPRINK® 12 v12.0.57.0 10:27:26AM1 Hydraulic Summary Report Description: Residential (1) Job Number: 160403 - Calculation #1 Node Flow(gpm) Total Hose Streams 100.00 Safety MarginRequiredAvailable Node Hose Flow Static Residual Flow Total Demand (gpm)(psi)(psi)(gpm)(psi)(gpm)(psi)(psi)@@Name 1 136.457 89.109 47.347721.41100.00 15.090150.000 208.23Water Supply Design EngineerJob Number Total Water Required (Including Hose Allowance) 208.23 Maximum Pressure Unbalance In Loops 0.000 Additional Hose Supplies 100.00 Hose Allowance At Source Supplies 333.37gal Residential 0.100gpm/ft² 256.00ft² 602.94ft² (Actual 602.94ft²) 4 Occupancy Area of Application Coverage Per SprinklerNumber Of Sprinklers Calculated Density Calculation #1 Job Suffix Volume capacity of Dry PipesVolume capacity of Wet Pipes 1.12 between nodes 1 and 2 Maximum Velocity Under Ground 26.53 between nodes 5 and 7 Maximum Velocity Above Ground 4.9 K-Factor 25.60 at 27.295 Most Demanding Sprinkler Data System VAIL, CO 81658 Job Site/Building VAIL FIRE DEPT100 EAST MEADOWS DR. AHJ 108221VILLAGE INN PLAZA UNIT 302 Job State Certification/License NumberJob Name: PAUL HUBBARD.160403 Contractor Contractor Number028 Name of Contractor: VAIL VALLEY FIRE SPRINKLER CO Address 1 57 HEREFORD LANE Address 2 EDWARDS, CO 81632 Contact Name Contact Title ExtensionPhone (970) 914-5014 FAX E-mail blazeinvail@aol.com Web-Site CLINT JANSSEN Address 3 Address 1 Address 2 Drawing Name 160403.cad System Flow Demand 108.23 Remote Area(s) Address 3 4/22/2016© M.E.P.CAD, Inc.Page 1AutoSPRINK® 12 v12.0.57.0 10:27:11AM Hydraulic Graph Water Supply Node: 1 Job Name: VILLAGE INN PLAZA UNIT 302 Remote Area Number: 1 Date: 4/22/2016 Summary Sheet N 1.85 © M.E.P.CAD, Inc.4/22/2016 Page 2AutoSPRINK® 12 v12.0.57.0 10:27:28AM Device (gpm) Actual Flow Minimum Flow (gpm)(K) K-Factor (psi) Pressure Summary Of Outflowing Devices Report Description: Residential (1) Job Number: 160403 - Calculation #1 Sprinkler 101 25.60 25.60 4.9 27.295 Sprinkler 102 26.21 25.60 4.9 28.604 Sprinkler 103 27.89 25.60 4.9 32.389 Sprinkler 104 28.54 25.60 4.9 33.923 Most Demanding Sprinkler Data © M.E.P.CAD, Inc.4/22/2016 Page 3AutoSPRINK® 12 v12.0.57.0 10:27:29AM Job Name: VILLAGE INN PLAZA UNIT 302 Remote Area Number: 1 Date: 4/22/2016 Node @ @ Supply Analysis Static (psi) Required Pressure (psi)(gpm) Total DemandAvailable (psi) Flow (gpm) Residual (psi)Name 15.0901 89.109208.23721.41 136.457150.000Water Supply Node Analysis NotesDischarge at Node (gpm) Pressure at Node (psi) Node TypeElevation (Foot)Node Number 0-0 108.2389.109Supply1 42-0 25.6027.295Sprinkler101 42-0 26.2128.604Sprinkler102 42-0 27.8932.389Sprinkler103 42-0 28.5433.923Sprinkler104 0-7 88.7672 3-1 73.6003 42-0 56.5604 43-0 49.1485 43-0 35.2366 43-0 36.5797 43-0 33.0718 43-0 29.6629 43-0 27.81410 © M.E.P.CAD, Inc.4/22/2016 Page 4AutoSPRINK® 12 v12.0.57.0 10:27:31AM Date: 4/22/2016 Job Name: VILLAGE INN PLAZA UNIT 302 Remote Area Number: 1 Pipe Information Node 1 Node 2 Nominal ID Actual ID Fittings & Devices C Factor Total(Pt) Elev(Pe) Friction(Pf) Fitting/Device (Equivalent Length) Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value. NotesFlow added this step (q) K-FactorElev 1 Elev 2 Total Flow (Q) Equiv. Length (Foot) (Foot)(Foot) (Foot) Length (Foot) Fitting (Foot) Total (psi) Pf Friction Loss Per Unit 1-0 43-0 2-0 -0.434 0.952 42-0 1-0101 10 ¾• • • • • Route 1 • • • • •(See Notes) 0.8110 27.29525.60 0.476082 Sprinkler, 25.60 4.9 E(1-0) 150 43-0 14-0 1.848 43-0 14-010 9 1 1.0550 27.814 0.13224325.60 150 2-0 43-0 14-2 6.917 43-0 12-29 7 1 (See Notes) 1.0550 29.66226.21 0.487238 Flow (q) from Route 2 51.81 E(2-0) 150 4-0 43-0 17-8 12.568 43-0 13-87 5 1¼(See Notes) 1.2910 36.57956.43 0.712398 Flow (q) from Route 3 108.23 EE(1-0), T(3-0) 150 38-0 42-0 64-2 0.434 6.979 43-0 26-25 4 2 (See Notes) 2.0670 49.148 0.108770108.23 EE(2-0), 4E(5-0), BV(6-0), PO(10-0) 120 7-11 3-1 46-10 16.890 0.151 42-0 38-114 3 4 (See Notes) 4.2600 56.560 0.003214108.23 LtE(7-11) 120 15-10 0-7 25-10 1.084 14.083 3-1 10-13 2 4 (See Notes) 4.2600 73.600 0.003214108.23 BFP(-12.000), 2LtE(7-11), PRV(-2.000), BOR 120 124-6 0-0 294-6 0.235 0.107 0-7 170-02 1 6 (See Notes) 6.2800 88.767 0.000365108.23 2LtE(14-2), 2E(22-1), T(47-3), GV(4-9), S 140 1 100.00 Hose Allowance At Source 208.23 Route 1Total(Pt) 89.109 2-0 43-0 3-0 -0.434 1.491 42-0 1-0102 9 ¾• • • • • Route 2 • • • • •(See Notes) 0.8110 28.60426.21 0.497158 Sprinkler, 26.21 4.9 T(2-0) 150 29.662 Total(Pt)Route 2 1-0 43-0 2-0 -0.434 1.115 42-0 1-0103 8 ¾• • • • • Route 3 • • • • •(See Notes) 0.8110 32.38927.89 0.557731 Sprinkler, 27.89 4.9 E(1-0) 150 © M.E.P.CAD, Inc.4/22/2016 Page 5AutoSPRINK® 12 v12.0.57.0 10:27:33AM1 Date: 4/22/2016 Job Name: VILLAGE INN PLAZA UNIT 302 Remote Area Number: 1 Pipe Information Node 1 Node 2 Nominal ID Actual ID Fittings & Devices C Factor Total(Pt) Elev(Pe) Friction(Pf) Fitting/Device (Equivalent Length) Fixed Pressure Losses, when applicable, are added directly to (Pf) and shown as a negative value. NotesFlow added this step (q) K-FactorElev 1 Elev 2 Total Flow (Q) Equiv. Length (Foot) (Foot)(Foot) (Foot) Length (Foot) Fitting (Foot) Total (psi) Pf Friction Loss Per Unit 43-0 14-0 2.165 43-0 14-08 6 1 1.0550 33.071 0.15492327.89 150 2-0 43-0 2-4 1.343 43-0 0-46 7 1 (See Notes) 1.0550 35.23628.54 0.570651 Flow (q) from Route 4 56.43 T(2-0) 150 36.579 Total(Pt)Route 3 2-0 43-0 3-0 -0.434 1.746 42-0 1-0104 6 ¾• • • • • Route 4 • • • • •(See Notes) 0.8110 33.92328.54 0.582121 Sprinkler, 28.54 4.9 T(2-0) 150 35.236 Total(Pt)Route 4 © M.E.P.CAD, Inc.4/22/2016 Page 6AutoSPRINK® 12 v12.0.57.0 10:27:33AM1 Date: 4/22/2016 Job Name: VILLAGE INN PLAZA UNIT 302 Remote Area Number: 1 Equivalent Pipe Lengths of Valves and Fittings (C=120 only) 1.51 Fittings Legend ALV Alarm Valve AngV Angle Valve b Bushing BalV Ball Valve BFP Backflow Preventer BV Butterfly Valve C Cross Flow Turn 90°cplg Coupling Cr Cross Run CV Check Valve DelV Deluge Valve DPV Dry Pipe Valve E 90° Elbow EE 45° Elbow Ee1 11¼° Elbow Ee2 22½° Elbow f Flow Device fd Flex Drop FDC Fire Department Connection fE 90° FireLock(TM) Elbow fEE 45° FireLock(TM) Elbow flg Flange FN Floating Node fT FireLock(TM) Tee g Gauge GloV Globe Valve GV Gate Valve Ho Hose Hose Hose HV Hose Valve Hyd Hydrant LtE Long Turn Elbow mecT Mechanical Tee Noz Nozzle P1 Pump In P2 Pump Out PIV Post Indicating Valve PO Pipe Outlet PRV Pressure Reducing Valve PrV Pressure Relief Valve red Reducer/Adapter S Supply sCV Swing Check Valve Spr Sprinkler St Strainer T Tee Flow Turn 90°Tr Tee Run U Union WirF Wirsbo WMV Water Meter Valve Z Cap 4.87 )(150 1.33 140 1.16 130 0.713 100Actual Inside Diameter Schedule 40 Steel Pipe Inside Diameter = Factor C Value Multiplier Value Of C Multiplying Factor © M.E.P.CAD, Inc.4/22/2016 Page 7AutoSPRINK® 12 v12.0.57.0 10:27:33AM1 Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523 Bulletin 006 Rev. IBulletin 006 Rev. I Model RFC30 (SIN RA0611) Model RFC43 (SIN RA0612) Model RFC49 (SIN RA0616) Residential Flat Concealed Sprinklers A Residential Flat Concealed Sprinkler engineered for a minimum design density of 0.05 gpm/ft2 with low GPM requirements. Features 1. Very low water flow requirements. 2. Cover plate attachment (Plain or Perforated) with ½” (13mm) Total adjustment. 3. Thread-On/Thread-Off or Push-On/Thread Off cover attachment option. 4. Smooth aesthetic ceiling profile. 5. Available in brass, chrome and black plated or painted finishes. Listings & Approval 1. Listed by Underwriters Laboratories, and certified by UL for Canada (cULus) UL Listing Categories Residential Automatic Sprinklers UL Guide Number VKKW Product Description Model RFC30, RFC43 and RFC49 Concealed Residen- tial Sprinklers are fast response residential fusible solder link automatic sprinklers. Residential sprinklers differ from standard sprinklers primarily in their response time and water distribution patterns. Model RFC30, RFC43 and RFC49 sprinklers discharge water in a hemispherical pattern below the sprinkler de- flector. Residential distribution patterns are higher and generally contain a finer droplet size than standard sprin- kler patterns. The combination of speed of operation and high dis- charge pattern required for residential sprinklers has demonstrated, in fire testing, an ability for controlling residential fires, and thereby providing significant evacu- ation time for occupants. The RFC30, RFC43 and RFC49 Sprinklers provide the best form of fire protection by combining an attractive ap- pearance and ½” (13mm) of cover adjustment for ease of installation. The small diameter cover plate is easily and positively attached and blends into the ceiling, con- cealing the most dependable fire protection available, an automatic sprinkler system. The RFC30, RFC43 and RFC49 are UL Listed Residen- tial Sprinklers to be installed in the residential portions of any occupancy in accordance with NFPA 13, 13R, & 13D. The RFC30, RFC43 and RFC49 can reduce the need for precise cutting of drop nipples. The threaded cover plate assembly can be adjusted without tools to fit ac- curately against the ceiling. The fire protection system need not be shut down to adjust or remove the cover plate assembly. Plain Cover Plate Perforated Cover Plate 2. Application and Installation The RFC30, RFC43 and RFC49, for residential instal- lations, use a 165°F (74°C) fusible solder link in a tun- ing fork style sprinkler frame with a drop-down deflector. This assembly is recessed into the ceiling and concealed by a flat cover plate. The cover plate is attached to the skirt, using 135°F (57°C) ordinary temperature classifica- tion solder. When the ceiling temperature rises, the solder holding the cover plate releases the cover allowing the deflector to drop into position and exposing the sprinkler inside to ceiling temperature. The subsequent operation of the solder link opens the waterway and causes the de- flector to drop into position to distribute the discharging water in a hemispherical pattern below the sprinkler de- flector. Any adjustment of thread engagement between the cover plate and cup will assure that the drop-down deflector is properly located below the ceiling. The resi- dential distribution pattern contains a finer droplet size than a standard sprinkler, and the pattern produces sig- nificantly higher wall wetting. After a 25/8 inch diameter hole is cut in the ceiling, the sprinkler is to be installed with the Model FC Wrench. When installing a sprinkler, the wrench is first positioned into the sprinkler/cup assembly and around the hexago- nal body of the sprinkler frame. The Wrench must bottom out against the cup in order to ensure proper, safe instal- lation. The sprinkler is then tightened into the pipe fitting. When inserting or removing the wrench from the sprin- kler/cup assembly, care should be taken to prevent dam- age to the sprinkler. DO NOT WRENCH ON ANY OTHER PART OF THE SPRINKLER/CUP ASSEMBLY. MODEL RFC30, RFC43 AND RFC49 CONCEALED SPRINKLERS MUST BE INSTALLED ONLY WITH 135°F RATED COV- ERS. Note: A leak tight ½” NPT (R1/2) sprinkler joint can be ob- tained with a torque of 8-18 ft-lbs (10,8 - 24,4 N-m). Do not tighten sprinklers over maximum recommended torque. It may cause leakage or impairment of the sprinklers. Cover assemblies provide up to 1/2” (13mm) of adjust- ment. Turn the cover clockwise until the flange is in con- tact with the ceiling. For the push-on/thread-off option, the cover assembly is pushed onto the cup and final ad- justment is made by turning the cover clockwise until the skirt flange makes full contact with the ceiling. Cover re- moval requires turning in the counter-clockwise direction. In ceilings that have a plenum space above the sprinkler, the plenum space may have neutral or neg- ative pressurization but must not be positively pres- surized. Inspect all sprinklers after installation to en- sure that the gap between the cover plate and ceiling and the 4 slots in the cup are all open and free from any air fl ow impediment. Model (SIN) Thread Size Inch (mm) Nominal Orifi ce Inch (mm) Sprinkler Temp Rating CCP Assembly Temp. Rating Max. Ambient Temp. K Factor Max. Pressure psi (bar)°F °C °F °C °F °C RFC 30 (RA0611)½” (15)21/64 (8,2) 165 74 135 57 100 38 3.0 (43.2) 175 (12) RFC 43 (RA0612)½” (15)3/8 (10) 165 74 135 57 100 38 4.3 (62) 175 (12) RFC 49 (RA0616)½” (15)7/16 (11) 165 74 135 57 100 38 4.9 (70.6) 175 (12) Note: 1 bar = 100 Kpa RFC 30 Max. Coverage area Ft x Ft (m x m) Max. Spacing Ft (m) Ordinary Temp. Rating (165°F/74°C)Top of Defl ector to Ceiling Inch (mm) Installation Type Minimum Spacing Ft (m)Flow GPM (L/min) Pressure PSI (bar) 12 x 12 (3,6 x 3,6) 12 (3,6) 9 (34,1) 9.0 (0,62) Smooth Ceilings ½ to 1 (13 to 25.4) Beamed Ceilings per NFPA 13D, 13R or13 installed in beams ½ to 1 (13 to 25.4)Concealed 8 (2,4) 14 x 14 (4,3 x 4,3) 14 (4,3) 10 (37,8) 11.0 (0,76) For Ceiling types refer to NFPA 13, 13R or 13D 3. Maintenance Model RFC30, RFC43 and RFC49 Concealed Sprin- klers should be inspected and the sprinkler system maintained in accordance with NFPA 25. Do not clean sprinklers with soap and water, ammonia or any other cleaning fluids. Remove dust by using a soft brush or gentle vacuuming. Remove any sprinkler cover plate as- sembly which has been painted (other than factory ap- plied) or damaged in any way. A stock of spare sprin- klers should be maintained to allow quick replacement of damaged or operated sprinklers. Prior to installation, sprinklers should be maintained in the original cartons and packaging until used to minimize the potential for damage to sprinklers that would cause improper opera- tion or non-operation. Model RFC30, RFC43 and RFC49 Residential Concealed Sprinkler Specifi cation Sprinklers shall be cULus Listed low flow residential con- cealed sprinklers with drop-down deflector and adjust- able flat cover plate engineered for a minimum design density of 0.05 gpm/ft2. Sprinkler frame and deflector shall be of bronze frame construction having a ½” NPT thread. Thermal element shall consist of an approved black-painted beryllium-nickel fusible solder link with symmetric lever mechanism, maintaining a Teflon-coated Belleville spring washer and machined brass cap water seal assembly containing no plastic parts. Sprinkler K- factor shall be nominal 3.0 (43.2), 4.3 (62), and 4.9 (70.6) having a 5/16”, 3/8” and 7/16” orifice. Temperature rating shall be Ordinary 165°F (74°C); cover plate temperature rating to be 135°F (57°C). Cover plate assembly shall consist of a brass cover plate and copper alloy retainer flange allowing a ½” cover plate adjustment. Any secure engagement between the cover plate and the cup will assure that the drop-down deflector is properly located below the ceiling. A plastic protective cap shall be provided and factory installed inside the sprinkler cup to protect the drop-down sprinkler deflector from dam- age, which could occur during construction before the cover plate is installed. Standard cover finish: [Chrome] [White] [Specialty – specify]. Residential concealed sprinklers shall be Reliable Model RFC30, SIN RA0611 (Bulletin 006), Model RFC43, SIN RA0612 (Bulletin 006) or Model RFC49, SIN RA0616 (Bulletin 006). RFC 43 Max. Coverage area Ft x Ft (m x m) Max. Spacing Ft (m) Ordinary Temp. Rating (165°F/74°C)Top of Defl ector to Ceiling Inch (mm) Installation Type Minimum Spacing Ft (m)Flow GPM (L/min) Pressure PSI (bar) 12 x 12 (3,6 x 3,6) 12 (3,6) 12 (4,5) 7.8 (0,54) Smooth Ceilings ½ to 1 (13 to 25.4) Beamed Ceilings per NFPA 13D, 13R or 13 installed in beams ½ to 1 (13 to 25.4) Concealed 8 (2,4) 14 x 14 (4,3 x 4,3) 14 (4,3) 13 (49) 9.1 (0,63) 16 x 16 (4,9 x 4,9) 16 (4,9) 13 (49) 9.1 (0,63) 18 x 18 (5,5 x 5,5) 18 (5,5) 18 (68) 17.5 (1,21) 20 x 20 (6,1 x 6,1) 20 (6,1) 21 (79) 23.8 (1,64) For Ceiling types refer to NFPA 13, 13R or 13D RFC 49 Max. Coverage area Ft x Ft (m x m) Max. Spacing Ft (m) Ordinary Temp. Rating (165°F/74°C)Top of Defl ector to Ceiling Inch (mm) Installation Type Minimum Spacing Ft (m)Flow GPM (L/min) Pressure PSI (bar) 12 x 12 (3,6 x 3,6) 12 (3,6) 13 (49) 7.0 (0,48) Smooth Ceilings ½ to 1 (13 to 25.4)Beamed Ceilings per NFPA 13D, 13R or 13 installed in beams ½ to 1 (13 to 25.4) Concealed 8 (2,4) 14 x 14 (4,3 x 4,3) 14 (4,3) 13 (49) 7.0 (0,48) 16 x 16 (4,9 x 4,9) 16 (4,9) 13 (49) 7.0 (0,48) 18 x 18 (5,5 x 5,5) 18 (5,5) 17 (64,3) 12.0 (0,83) 20 x 20 (6,1 x 6,1) 20 (6,1) 20 (75,73) 16.7 (1,14) For Ceiling types refer to NFPA 13, 13R or 13D Reliable Automatic Sprinkler Co., Inc. (800) 431-1588 Sales Offices(800) 848-6051 Sales Fax (914) 829-2042 Corporate Offices www.reliablesprinkler.com Internet Address Manufactured by Recycled Paper Revision lines indicate updated or new data. EG. Printed in U.S.A. 11/14 P/N 9999970261 The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Products manufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries. Ordering Information Specify: 1. Sprinkler Model 2. Cover Plate Finish 3. Thread-On or Push-On Feature Cover Plate Finishes(1) Standard Finishes Chrome White Paint Special Application Finishes(2) Bright Brass Finished Bronze Black Plating Black Paint Off White Satin Chrome (1) Other finishes and colors are available on special order. Consult factory for details. Coverplate custom paint is semi-gloss, unless specified otherwise. (2) For the perforated style cover- plate, consult factory for avail- ability on these and other cus-tom finishes.