HomeMy WebLinkAboutF16-0031_FP2_1478903093.pdf47 heads for Unit B
18 heads for lower level
17 heads for main level
12 heads for upper level
115.00 0.00
98.00 1299.00
Calculations are made after a 10 psi
reduction in water pressure
Test Results
Pressure Flow
125.00 0.00
108.00 1601.00
Water flow de-rate per Vail Fire
Flow 1601 gpm.
De-rate for month of June......... 81.16%
1601 x 81.16%..........................1299.00 GPM
stairs open to
above
BEDROOM #4
008
UNIT B MECH.
CRAWL SPACE-
5'-0" MAX CLG
HEIGHT
000
W.C.
009
BAR
002
FAMILY ROOM
001
SAUNA
007
BEDROOM #3
003
BATH #4
010
POWDER
012
CLOSET
011
BATHROOM #3
004
W.C.
005
CLOSET #3
006
UNIT B EXERCISE
ROOM
013
ELEVATOR
014
UNIT A
MECHANICAL
ROOM
034
EXERCISE ROOM
BATH
035
STORAGE
038
UNIT A STEAM
SHOWER
036
B.O. GWB @ 9' - 6" A.F.F.
DROPPED
EXPOSED STEEL
BEAM RE: STRUCT.
B.O. GWB @ 7' - 0" A.F.F.
B.O. GWB @ 9' - 6" A.F.F.
B.O. GWB @ 10' - 6 3/8" A.F.F.
B.O. GWB @ 9' - 6" A.F.F.
B.O. GWB @ 8' - 6" A.F.F.
B.O. GWB @ 8' - 6" A.F.F.
B.O. GWB @ 8' - 6" A.F.F.
B.O. GWB @ 9' - 6" A.F.F.
B.O. GWB @ 4' - 11 3/8" A.F.F.
B.O. GWB @ 8' - 6" A.F.F.
B.O. GWB @ 9' - 6" A.F.F.
B.O. GWB @ 8' - 6"
B.O. GWB @ 8' - 6"
B.O. GWB @ 10' - 1 3/8" A.F.F.
B.O. DECKING @ 10' - 2 3/4" A.F.F.
W.C.
040
B.O. GWB @ 9' - 6" A.F.F.
1A
2A
B
C
D
E
F
G
H
I
J
K
AA
BB
CC
BBB
AAA
6 16 16
5151 Bannock St.
Denver, CO
80216
303-291-1012
303-383-5023 FAX
firesprinkler@afssco.com
A FIRE SPRINKLER
DESIGN COMPANY
ACCEPTING THIS COPY IS DEEMED AS AGREEING TO THE FOLLOWING: THIS DRAWING COPY, ITS CONTENTS,
INFORMATION AND PRINCIPALS OF DESIGN ARE THE EXCLUSIVE PROPERTY OF THE FIRE PROTECTION
CONTRACTOR LISTED AND MILE HIGH DESIGN GROUP, LLC AND IS BEING SUBMITTED TO YOU WITH THE
UNDERSTANDING THAT IT IS NOT TO BE REPRODUCED, COPIED OR MODIFIED IN ANY MANNER; NEITHER SHALL
IT BE RELAYED IN WHOLE OR IN PART TO ANY OTHER INDIVIDUAL OR FIRM FOR ANY OTHER PROJECT OR
EXTENSION OF THIS PROJECT EXCEPT THRU WRITTEN AGREEMENT WITH THE FIRE PROTECTION CONTRACTOR
AND MILE HIGH DESIGN GROUP, LLC. ERRORS AS A RESULT OF THIS FILE BEING ELECTRONICALLY
TRANSMITTED ARE BEYOND THE CONTROL OF AND ARE NOT THE RESPONSIBILITY OF THE FIRE PROTECTION
CONTRACTOR OR MILE HIGH DESIGN GROUP. MILE HIGH DESIGN GROUP IS NOT RESPONSIBLE FOR
INSTALLATION OR INSPECTION OF WORK INSTALLED. THESE PLANS ARE DIAGRAMMATICAL ONLY. ON SITE
COORDINATION MUST BE ARRANGED WITH ALL OBSTRUCTIONS, i.e.: MECHANICAL, ELECTRICAL, AND
STRUCTURAL. ANY ALTERATIONS FROM ENGINEERED DRAWINGS MUST BE APPROVED BY MILE HIGH DESIGN
GROUP. MILE HIGH DESIGN GROUP IS NOT RESPONSIBLE FOR LAYOUT DESIGN ISSUES OR CONFLICTS WITH
ANY OBSTRUCTIONS. IF ADDITIONAL FIRE SPRINKLER PIPING AND/OR FIRE SPRINKLER HEADS ARE REQUIRED
THIS WILL BE THE RESPONSIBILITY OF THE FIRE SPRINKLER CONTRACTOR. ALL CHANGES MUST ME APPROVED
BY MILE HIGH DESIGN GROUP, LLC
THE OWNER IS RESPONSIBLE TO PROVIDE SUFFICIENT HEAT THROUGHOUT THIS BUILDING TO PREVENT
FREEZING OF WATER IN THE FIRE SPRINKLER SYSTEM -
SCALE: 1/4" = 1'-0"
PLAN
NORTH
FIRE SPRINKLER PLANS
1 2 3 4 5 6 7 8 9 10
LOWER LEVEL
This head should be a
175 head not 155
Why is this 175?
move this head so
it covers both
bath/sink are and
toilet room.
Vail Fire & Emergency Services
06/28/16