Loading...
HomeMy WebLinkAboutF16-0031_FP2_1478903093.pdf47 heads for Unit B 18 heads for lower level 17 heads for main level 12 heads for upper level 115.00 0.00 98.00 1299.00 Calculations are made after a 10 psi reduction in water pressure Test Results Pressure Flow 125.00 0.00 108.00 1601.00 Water flow de-rate per Vail Fire Flow 1601 gpm. De-rate for month of June......... 81.16% 1601 x 81.16%..........................1299.00 GPM stairs open to above BEDROOM #4 008 UNIT B MECH. CRAWL SPACE- 5'-0" MAX CLG HEIGHT 000 W.C. 009 BAR 002 FAMILY ROOM 001 SAUNA 007 BEDROOM #3 003 BATH #4 010 POWDER 012 CLOSET 011 BATHROOM #3 004 W.C. 005 CLOSET #3 006 UNIT B EXERCISE ROOM 013 ELEVATOR 014 UNIT A MECHANICAL ROOM 034 EXERCISE ROOM BATH 035 STORAGE 038 UNIT A STEAM SHOWER 036 B.O. GWB @ 9' - 6" A.F.F. DROPPED EXPOSED STEEL BEAM RE: STRUCT. B.O. GWB @ 7' - 0" A.F.F. B.O. GWB @ 9' - 6" A.F.F. B.O. GWB @ 10' - 6 3/8" A.F.F. B.O. GWB @ 9' - 6" A.F.F. B.O. GWB @ 8' - 6" A.F.F. B.O. GWB @ 8' - 6" A.F.F. B.O. GWB @ 8' - 6" A.F.F. B.O. GWB @ 9' - 6" A.F.F. B.O. GWB @ 4' - 11 3/8" A.F.F. B.O. GWB @ 8' - 6" A.F.F. B.O. GWB @ 9' - 6" A.F.F. B.O. GWB @ 8' - 6" B.O. GWB @ 8' - 6" B.O. GWB @ 10' - 1 3/8" A.F.F. B.O. DECKING @ 10' - 2 3/4" A.F.F. W.C. 040 B.O. GWB @ 9' - 6" A.F.F. 1A 2A B C D E F G H I J K AA BB CC BBB AAA 6 16 16 5151 Bannock St. Denver, CO 80216 303-291-1012 303-383-5023 FAX firesprinkler@afssco.com A FIRE SPRINKLER DESIGN COMPANY ACCEPTING THIS COPY IS DEEMED AS AGREEING TO THE FOLLOWING: THIS DRAWING COPY, ITS CONTENTS, INFORMATION AND PRINCIPALS OF DESIGN ARE THE EXCLUSIVE PROPERTY OF THE FIRE PROTECTION CONTRACTOR LISTED AND MILE HIGH DESIGN GROUP, LLC AND IS BEING SUBMITTED TO YOU WITH THE UNDERSTANDING THAT IT IS NOT TO BE REPRODUCED, COPIED OR MODIFIED IN ANY MANNER; NEITHER SHALL IT BE RELAYED IN WHOLE OR IN PART TO ANY OTHER INDIVIDUAL OR FIRM FOR ANY OTHER PROJECT OR EXTENSION OF THIS PROJECT EXCEPT THRU WRITTEN AGREEMENT WITH THE FIRE PROTECTION CONTRACTOR AND MILE HIGH DESIGN GROUP, LLC. ERRORS AS A RESULT OF THIS FILE BEING ELECTRONICALLY TRANSMITTED ARE BEYOND THE CONTROL OF AND ARE NOT THE RESPONSIBILITY OF THE FIRE PROTECTION CONTRACTOR OR MILE HIGH DESIGN GROUP. MILE HIGH DESIGN GROUP IS NOT RESPONSIBLE FOR INSTALLATION OR INSPECTION OF WORK INSTALLED. THESE PLANS ARE DIAGRAMMATICAL ONLY. ON SITE COORDINATION MUST BE ARRANGED WITH ALL OBSTRUCTIONS, i.e.: MECHANICAL, ELECTRICAL, AND STRUCTURAL. ANY ALTERATIONS FROM ENGINEERED DRAWINGS MUST BE APPROVED BY MILE HIGH DESIGN GROUP. MILE HIGH DESIGN GROUP IS NOT RESPONSIBLE FOR LAYOUT DESIGN ISSUES OR CONFLICTS WITH ANY OBSTRUCTIONS. IF ADDITIONAL FIRE SPRINKLER PIPING AND/OR FIRE SPRINKLER HEADS ARE REQUIRED THIS WILL BE THE RESPONSIBILITY OF THE FIRE SPRINKLER CONTRACTOR. ALL CHANGES MUST ME APPROVED BY MILE HIGH DESIGN GROUP, LLC THE OWNER IS RESPONSIBLE TO PROVIDE SUFFICIENT HEAT THROUGHOUT THIS BUILDING TO PREVENT FREEZING OF WATER IN THE FIRE SPRINKLER SYSTEM - SCALE: 1/4" = 1'-0" PLAN NORTH FIRE SPRINKLER PLANS 1 2 3 4 5 6 7 8 9 10 LOWER LEVEL This head should be a 175 head not 155 Why is this 175? move this head so it covers both bath/sink are and toilet room. Vail Fire & Emergency Services 06/28/16