HomeMy WebLinkAboutMaterial Submittal .pdf
MATERIAL SUBMITTAL
FOR
VILLAGE INN PLAZA #204
68 E MEADOW DRIVE
VAIL , CO
Prepared by:
Tyler Williams
Project Manager
Western States Fire Protection Co.
7026 S. Tucson Way
Centennial, CO 80112
Phone (303) 792-0022
Fax (303) 792-9049
Cell (720) 668-1160
Email: Tyler.Williams@wsfp.us
WSFP #CS2889
August 24, 2016
MATERIAL SUBMITTAL
FOR
VILLAGE INN PLAZA #204
68 E MEADOW DRIVE
VAIL , CO
Prepared by:
Tyler Williams
Project Manager
Western States Fire Protection Co.
7026 S. Tucson Way
Centennial, CO 80112
Phone (303) 792-0022
Fax (303) 792-9049
Cell (720) 668-1160
Email: Tyler.Williams@wsfp.us
WSFP #CS2889
August 24, 2016
The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523 Bulletin 176 Rev. CBulletin 176 Rev. C
Model F1
Residential Sprinklers for
Design Density of .10 gpm/ft2
Model F1 Res Sprinklers Listed to meet the minimum
design density as required by UL1626.
Types:
1. F1 Res 30 Pendent
2. F1 Res 30 Recessed/F2
3. F1 Res 30 Recessed/FP
4. F1 Res 30 CCP Pendent
5. F1 Res 49 Pendent
6. F1 Res 49 Recessed Pendent/F1
7. F1 Res 49 Recessed Pendent/FP
8. F1 Res 49 CCP Pendent
9. F1 Res 58 Pendent
10. F1 Res 58 Recessed Pendent/F1
11. F1 Res 58 Recessed Pendent/FP
12. F1 Res 58 CCP Pendent
13. F1 Res 44 & 58 HSW
14. F1 Res 44 & 58 HSW Recessed HSW/F2
15. F1 Res 58 HSWX
16. KRes58 HSWX
17. F1 Res 44 SWC
18. F1 Res 76 Pendent
19. F1 Res 76 Recessed Pendent/F1
20. F1 Res 76 Recessed Pendent/FP
21. F1 Res 76 CCP Pendent
F1 Res 30, 49, 58 & 76
Recessed Pendent/F1
The 3mm glass-bulb pendent sprinklers permit the ef-
ficient use of residential water supplies for sprinkler cover-
age in residential fire protection design.
Upon fire conditions, rising heat causes a sprinkler’s
heat-sensitive glass-bulb to shatter, releasing the water-
way for water flow onto the deflector, evenly distributing
the discharged water to control a fire.
Technical Data:
• Thermal Sensor: Nominal 3mm glass-bulb
• Sprinkler Frame : Brass Casting
• Sprinklers’ Pressure Rating : 175 psi
Factory Hydrostatically Tested to 500 psi
• Thread Size: ½” NPT (R1/2)
• K-Factor: 3.0 (Actual) - F1 Res 30 Pendent Sprinkler
4.9 (Actual) - F1 Res 49 Pendent Sprinkler
5.8 (Actual) - F1 Res 58 Pendent & HSW/HSWX
Sprinkler
7.6 (Actual) - F1 Res 76 Pendent Sprinkler
4.4 (Actual) - F1 Res 44 HSW Sprinkler
• Density: Minimum 0.10 gpm/ft2
F1 Res 30, 49, 58 & 76
Recessed Pendent/FP
F1 Res 30, 49, 58 & 76
CCP Pendent
F1 Res 44 & 58
Recessed HSW/F2Listings & Approvals
1. Listed by Underwriters Laboratories Inc. and
UL Certified for Canada (cULus)
2. NYC MEA 258-93-E
UL Listing Category
Residential Automatic Sprinkler
UL Guide Number
VKKW
Patents
US Patent No. 6,516,893 applies to the Model F1 Res 49
& 58 Pendent Sprinklers
US Patent No. 7,353,882 applies to Model F1 Res 44 &
58 HSW Sprinklers
US Patent No. 7,784,555 applies to Model F1 Res 44
SWC Sprinkler
Patent Pending - Model F1 Res 76 Pendent Sprinkler
Product Description
Model F1Res Pendent sprinklers (Figs. 1, 2, 3 & 4)
combine excellent durability, high sensitivity glass-bulb
and low profile decorative design.
F1 Res 44 SWC
F1 Res 58 HSWX
2.
K=7.6) that will provide lower pressure demands for
0.1 gpm/ft2 densities in NFPA 13 residential applica-
tions.
Example No. 1
Room Size= 12 ft x 20 ft (3.6 m x 6.1 m)
Coverage Area= 12 x 20 = 240 ft2 (22.3 m2)
Flow @ 0.10 gpm/ft2 density= 240 x 0.10 = 24 gpm
Using an F1 Res 49 Pendent Sprinkler, K=4.9
Pressure= (24/4.9)2 = 24 psi (1.65 bar)
The baseline flow for a 20 ft x 20 ft (6.1 m x 6.1 m) cover-
age area using the baseline density of 0.05 gpm/ft2 will
be 20 gpm @ 16.7 psi (75.7 L/min @ 1.14 bar). There-
fore, the minimum flow required is 24 gpm @ 24 psi (90.8
L/min @ 1.65 bar).
Example No. 2
Room Size= 8 ft x 20 ft (2.4 m x 6.1 m)
Coverage Area= 8 x 20 = 160 ft2 (14.9 m2)
Flow @ 0.10 gpm/ft2 density= 160 x 0.10 = 16 gpm
Using an F1 Res 49 Pendent Sprinkler, K=4.9
Pressure= (16/4.9)2 = 10.7 psi (0.74 bar)
The baseline flow for a 20 ft x 20 ft (6.1 m x 6.1 m) cover-
age area using the baseline density of 0.05 gpm/ft2 will
be 20 gpm @ 16.7 psi (75.7 L/min @ 1.14 bar). Therefore,
the minimum flow required is 20 gpm @ 16.7 psi (75.7
L/min @ 1.14 bar).
Example No. 3
Room Size= 10 ft x 16 ft (3.0 m x 4.91 m)
Coverage Area= 10 x 16 = 160 ft2 (14.9 m2)
Flow @ 0.10 gpm/ft2 density= 160 x 0.10 = 16 gpm
Using an F1 Res 76 Pendent Sprinkler, K=7.6
The baseline flow for a 16 ft x 16 ft coverage area is 21
gpm @ 7.6 psi (79.5 L/min @ 0.52 bar). Therefore, the
minimum flow and pressure is 21 gpm @ 7.6 psi (79.5
L/min @ 0.52 bar).
Example No. 4
Room Size= 14 ft x 18 ft (4.3 m x 5.5 m)
Coverage Area= 14 x 18 = 252 ft2 (23.6 m2)
Flow @ 0.10 gpm/ft2 density= 252 x 0.10 = 25.2 gpm
(94.6 L/min)
Using an F1 Res 76 Pendent Sprinkler, K=7.6
Pressure= (252/7.6)2 = 11 psi (0.76 bar)
The baseline flow and pressure of an 18 ft x 18 ft cover-
age area is 21 gpm @ 7.6 psi (79.5 L/min @ 0.52 bar).
Therefore, the minimum flow and pressure is 25.2 gpm @
11 psi (94.6 L/min @ 0.76 bar).
In general residential sprinklers require fl ows and
pressures as listed for 0.05 densities to achieve the
proper spray pattern so the fl ows and pressures at
0.05 density are the baseline fl ows and pressures.
Flows and pressures below the listed 0.05 density
shall not be used.
Application
Model F1 Res Sprinklers are used for Residential Fire Pro-
tection according to UL 1626 Standard. Be sure that orifice
size, temperature rating, deflector style and sprinkler type
are in accordance with the latest published standards of
The National Fire Protection Association or the approving
authority having jurisdiction.
When using F1 Residential Sprinklers for systems designed
to NFPA 13D or NFPA 13R, use listed area of coverage and
minimum flow and pressure requirements shown in Bulletin
135.
For systems designed to NFPA 13, use information in this
bulletin. The number of design sprinklers shall be the most
hydraulically demanding sprinklers as required by NFPA
13. Flows and pressures can not be below the baseline
flows and pressures.
NFPA 13
For residential sprinkler systems designed to NFPA 13, a
minimum density of 0.1 gpm/ft2 must be provided over the
“design area” that includes the four (4) hydraulically most
demanding sprinklers for the actual coverage areas being
protected by the 4 sprinklers. The minimum required dis-
charge from each of the four most hydraulically demanding
sprinklers shall be the greater of the following:
1. The flow rates given in the Reliable Residential
Sprinkler Technical Bulletins referenced in Table A
for NFPA 13D and 13R as a function of temperature
rating and maximum allowable coverage area (for
actual coverage areas less than or between those
indicated in the respective technical bulletin, it is re-
quired to use the minimum required flow for the next
largest coverage area); or
2. A minimum discharge density of 0.1 gpm/ft2 applied
over the “design area” consisting of the four most hy-
draulically demanding sprinklers for the actual cov-
erage areas being protected by the four sprinklers.
The maximum dimension of the actual coverage area
cannot be any greater than the maximum coverage
area indicated in the technical bulletins referenced
in Table A.
Design Note: Using the As = S x L method to de-
termine the sprinkler protection area of coverage in
accordance with NFPA 13, apply the 0.1 gpm/ft2 den-
sity to this area to determine the minimum required
flow. Compare this flow to the minimum 0.05 gpm/ft2
cULus Listed flow for the appropriate coverage area
in the technical bulletin for the specific residential
sprinkler. If the flow stated in the technical bulletin
is less than the calculated 0.1 gpm/ft2 density flow
required, the .1 density flow must then be used in the
equation Q=KP, solving for P, to establish the mini-
mum required pressure using the sprinkler K-factor.
Note: In many cases the listed flow of individual resi-
dential sprinklers may exceed the required minimum
0.05 gpm/ft2 density. Reliable has available resi-
dential sprinklers with larger K-factors (K=5.8 and
3.
Installation
Models F1 Res sprinklers are to be installed as shown.
Model F1, F2 and FP Escutcheons, illustrated herewith,
are the only recessed escutcheons to be used with Mod-
el F1 Res sprinklers. Use of any other recessed escutch-
eon will void all approvals and warranties. For installing
Model F1 Res Pendent sprinklers use only the Model D
sprinkler Wrench; for installing Models F1 Res Recessed
Pendent, CCP sprinklers use only the Model GFR2 sprin-
kler wrench; for installing Model F1 Res recessed HSW
sprinklers use only the Model GFR2 Sprinkler wrench.
Use of wrenches other than those specified may dam-
age these sprinklers.
Note: A ‘leak tight” sprinkler joint can be obtained with
the following torque:
• 3/4” NPT (R3/4) – 14-20 ft-lbs (19 - 27.1 N-m)
• ½” NPT (R1/2) – 8-18 ft-lbs (10.8 – 24.4 N-m)
Do not tighten sprinklers over maximum recom-
mended torque. It may cause leakage or impairment
of the sprinklers.
F1 escutcheon, 3/4” (19mm) adjustment
• Model F1 Res 30, 49, 58 &
76 Pendent
• Model F1 Res 30, 49, 58 & 76
Recessed Pendent / F1/F2
Note: See escutcheon table for dimensions.
Fig. 1 Fig. 2
**Baseline fl ows and pressures for 0.05 density
Defl ector - to - ceiling
Maximum 1” (25mm) to 4” (100mm)
Max. Sprinkler
Spacing
ft (m)
Flow
gpm (Lpm)
Pressure
psi (bar)
Sprinkler
Identifi cation
Number (SIN)
12 x 12 (3.6x3.6) 13 (49) 7.0 (0.48)
R3516
14 x 14 (4.3x4.3) 13 (49) 7.0 (0.48)
16 x 16 (4.9x4.9) 13 (49) 7.0 (0.48)
18 x 18 (5.5x5.5) 17 (64.3) 12.0 (0.83)
20 x 20 (6.1x6.1) 20 (75.7) 16.7 (1.14)
4.
Technical Data: F1 Res 49 Pendent and Recessed Pendent
Thread
Size
Nominal
Orifi ce
Inch
(mm)
Sprinkler
Temp.
Rating
Max.
Pressure
psi
(bar)
Max.
Ambient
Temp.
Actual
K
Factor
Sprinkler
Length
Inch
(mm)°F °C °F °C
1/2” NPT
(R1/2)7/16” (11)155
175
68
79 175 (12)100
150
38
66 4.9 2.25 (57)
Escutcheon*, F1 or F2, Data:
Type Adjustment
Inch (mm)
“A”
Inch (mm)
Face of fi tting to
ceiling
Inch (mm)
F1
3/4” (19.0)Min.= 3/4 (19.1)Max.=11/2 (38.1)
3/16 - 15/16
(4.7 - 24.0)
F2
1/2” (12.7)Min.= 15/16 (23.8)
Max.=11/2 (38.1)
3/16 - 11/16
(4.7 - 17.4)
* Note: Escutcheons F1 or F2 may be used with
Model F1 Res 49 & 58 Recessed Pendent Sprinkler
*Defl ector - to - ceiling
Maximum 4” (100mm) to 8” (203mm)
Max. Sprinkler
Spacing
ft (m)
Flow
gpm (Lpm)
Pressure
psi (bar)
Sprinkler
Identifi cation
Number (SIN)
12 x 12 (3.6x3.6) 15 (57) 9.4 (0.65)
R3516
14 x 14 (4.3x4.3) 16 (60.5) 10.6 (0.73)
16 x 16 (4.9x4.9) 17 (64.3) 12.0 (0.83)
18 x 18 (5.5x5.5) 19 (72) 15.0 (1.0)
20 x 20 (6.1x6.1) 22 (83.2) 20.2 (1.4)
*Note: The F1 Res 49 pendent and recessed pendent residential
sprinklers can be installed per NFPA 13 in beamed ceilings meeting the following criteria:
1. Maximum beam depth = 7” (178mm)
2. Beam spacing at or greater than 7.5 ft. (2.3m) on center.
Technical Data: F1 Res 58 Pendent and Recessed Pendent
Thread Size Nominal Orifi ce
Inch (mm)
Sprinkler Temp.
Rating Max. Pressure
psi (bar)
Max.
Ambient Temp.K
Factor
Sprinkler Length
Inch (mm) °F °C °F °C
½” NPT (R½) ½” (13)
155
175
68
79 175 (12)100
150
38
66 5.8 2.25 (57)
**Baseline fl ows and pressures for 0.05 density
Max. Sprinkler Spacing
ft (m)
Flow
gpm (Lpm)
Pressure
psi (bar)
Ceiling -to-Defl ector
Inch (mm)
Sprinkler Identifi cation
Number (SIN)
12 x 12 (3.6x3.6) 16 (61) 7.6 (0.53)
1-4
(25-100)R3513
14 x 14 (4.3x4.3) 16 (61) 7.6 (0.53)
16 x 16 (4.9x4.9) 16 (61) 7.6 (0.53)
18 x 18 (5.5x5.5) 19 (72) 10.8 (0.75)
20 x 20 (6.1x6.1) 22 (83.3) 14.4 (1.0)
**Calculate for a .10 density but in no case go below the baseline flows & pressures
Technical Data: F1Res 30 Pendent and Recessed Pendent (SIN R3511)
Thread
Size
Nominal Orifi ce
Inch (mm)
Max.
Pressure
psi (bar)
Sprinkler
Temp. Rating
Max.
Ambient Temp.
Actual
K
Factor
Sprinkler
Length
Inch (mm)°F °C °F °C
½” NPT
(R½)21/64” (8.2) 175 (12)
155
175
68
79 100 38 3.0 2.25 (57)
**Baseline fl ows and pressures for 0.05 density
Max. Coverage area
Ft x Ft (m x m)
Max.
Spacing
Ft (m)
Ordinary Temp. Rating
(155°F/68°C)
Intermediate Temp. Rating
(175°F/79°C)Top of Defl ector
to Ceiling
Inch (mm)
Minimum
Spacing
Ft (m)Flow
GPM (L/min)
Pressure
PSI (bar)
Flow
GPM (L/min)
Pressure
PSI (bar)
12 x 12 (3,6 x 3,6) 12 (3,6) 8 (30,3) 7.0 (0,48) 8 (30,3) 7.0 (0,48) 1 to 4 (25 to 100);½ recessed using
F2 escutcheon
8 (2,4)14 x 14 (4,3 x 4,3) 14 (4,3) 10 (37,8) 11 (0,76) 10 (37,8) 11 (0,76)
For Ceiling types refer to NFPA 13, 13R or 13D
**Calculate for a .10 density but in no case go below the baseline flows & pressures
5.
Technical Data: F1 Res 76 Pendent and Recessed Pendent
Thread
Size
Nominal
Orifi ce
Inch (mm)
Sprinkler
Temp.
Rating
Max.
Pressure
psi (bar)
Max.
Ambient
Temp.
K
Factor
Sprinkler
Length
Inch (mm)°F °C °F °C
3/4” NPT(R3/4)17/32 (13.5)155175 6879 175 (12)100150 3866 7.6 2.25 (57)
Escutcheon*, F1 or F2, Data:
Type Adjustment
Inch (mm)
“A”
Inch (mm)
Face of fi tting
to ceiling
Inch (mm)
F1 3/4 (19.0)Min.= 3/4 (19.1)
Max.=11/2 (38.1)3/16 - 15/16 (4.7 - 24.0)
F2 1/2 (12.7)Min.= 15/16 (23.8)
Max.=11/2 (38.1)3/16 - 11/16 (4.7 - 17.4)
*Calculate for a .10 density but in no case go
below the baseline flows & pressures
*Baseline fl ows and pressures for 0.05 density
Max. Sprinkler
Spacing
ft (m)
Flow
gpm (Lpm)
Pressure
psi (bar)
Sprinkler
Identifi cation
Number (SIN)
12 x 12 (3.6x3.6) 21 7.6 (0.53)
R7618
14 x 14 (4.3x4.3) 21 7.6 (0.53)
16 x 16 (4.9x4.9) 21 7.6 (0.53)
18 x 18 (5.5x5.5) 21 7.6 (0.53)
20 x 20 (6.1x6.1) 23 9.2 (0.63)
• Model F1 Res 30, 49, 58 &
76 Recessed Pendent / FP
• Model F1 Res 30, 49, 58 &
76 CCP Pendent*
Fig. 3 Fig. 4
NOTE: The F1 Res 76 will use a 1” x ¾” reducer.
FP push-on/thread-off
escutcheon* Not listed for corrosion resistance.
6.
Technical Data: F1 Res 49 CCP Pendent and Recessed Pendent / FP
Thread
Size
Nominal
Orifi ce
Inch
(mm)
Sprinkler
Temp. Rating
CCP
Assembly
Temp. Rating
Max.
Pressure
psi (bar)
Max.
Ambient
Temp.
K
Factor
Sprinkler
Length
Inch
(mm)°F °C °F °C °F °C
½” NPT
(R½)7/16” (11) 155 68 135 57 175 (12) 100 38 4.9 2.25 (57)
CCP Options Data:
“A”
Cover
Adjustment
Inch (mm)
“B”
CCP Height
Inch (mm)
1/2 (12.7)15/16 (24)
3/16 (4.7)3/4 (19)
*Baseline fl ows and pressures for 0.05 density
Max. Sprinkler
Spacing
ft (m)
Flow
gpm (Lpm)
Pressure
psi (bar)
Sprinkler
Identifi cation
Number (SIN)
12 x 12 (3.6x3.6) 13 (49) 7.0 (0.48)
R3516
14 x 14 (4.3x4.3) 13 (49) 7.0 (0.48)
16 x 16 (4.9x4.9) 14 (53) 8.2 (0.56)
18 x 18 (5.5x5.5) 18 (68.1) 13.5 (0.93)
20 x 20 (6.1x6.1) 20 (75.7) 16.7 (1.14)
FP Data “A”:
FP Position “A”
Inch (mm)
Max. Recessed 7/16 (11)
Min. Recessed 15/16 (24)
Note: Sprinklers shown in Fig. 3 and
Fig. 4 are not suitable for in-
stallation in ceilings which have positive pressure in the
space above.
Technical Data: F1 Res 58 CCP Pendent and Recessed Pendent/FP
Thread Size Nominal Orifi ce
Inch (mm)
Sprinkler
Temp. Rating
CCP Assembly
Temp. Rating Max. Pressure
psi (bar)
Max. Ambient
Temp.K
Factor
Sprinkler
Length Inch
(mm)°F °C °F °C °F °C
½” NPT (R½) ½ (13) 155 68 135 57 175 (12) 100 38 5.8 2.25 (57)
*Baseline fl ows and pressures for 0.05 density
Max. Sprinkler Spacing
ft (m)
Flow
gpm (Lpm)
Pressure
psi (bar)
Sprinkler Identifi cation
Number (SIN)
12 x 12 (3.6x3.6) 16 (61) 7.6 (0.53)
R3513
14 x 14 (4.3x4.3) 16 (61) 7.6 (0.53)
16 x 16 (4.9x4.9) 16 (61) 7.6 (0.53)
18 x 18 (5.5x5.5) 19 (72) 10.8 (0.75)
20 x 20 (6.1x6.1) 22 (83.3) 14.4 (1.0)
*Calculate for a .10 density but in no case go below the baseline flows & pressures
Technical Data: F1Res 30 CCP Pendent and Recessed Pendent/FP (SIN R3511)
Thread
Size
Nominal Orifi ce
Inch (mm)
Max. Pressure
psi (bar)
CCP Assembly
Temp. Rating
Max.
Ambient Temp.K
Factor
Sprinkler Length
Inch (mm)°F °C °F °C
½” NPT (R½)21/64” (8.2) 175 (12) 135 57 100 38 3.0 2.25 (57)
*Baseline fl ows and pressures for 0.05 density
Max. Coverage area
Ft x Ft (m x m)
Max. Spacing
Ft (m)
Ordinary Temp. Rating
(155°F/68°C)Top of Defl ector
to Ceiling
Inch (mm)
Minimum
Spacing
Ft (m)Flow
GPM (L/min)
Pressure
PSI (bar)
12 x 12 (3,6 x 3,6) 12 (3,6) 8 (30,3) 7.0 (0,48) 1 to 4 (25 to 100);
½ (13mm) recessed
using FP escutcheon
8 (2,4)14 x 14 (4,3 x 4,3) 14 (4,3) 11 (37,8) 13.4 (0,92)
For Ceiling types refer to NFPA 13, 13R or 13D
*Calculate for a .10 density but in no case go below the baseline flows & pressures
7.
*Calculate for a .10 density but in
no case go below the baseline flows
& pressures
F1 Res 44 & 58
Recessed HSW/F2
• Model F1 Res 44 & 58 HSW • Model F1 Res 44 & 58
Recessed HSW/F2
Technical Data: F1 Res 44 HSW & HSW/F2
Thread
Size
Nominal
Orifi ce
Inch (mm)
Sprinkler
Temp.
Rating
Max.
Pressure
psi (bar)
Max.
Ambient
Temp.
K
Factor
Sprinkler
Length
Inch (mm)°F °C °F °C
½” NPT
(R½)3/8 (10)155
175
68
79 175 (12)100
150
38
66 4.4 2.45 (62)
Escutcheon, F2, Data:
Type Adjustment
Inch (mm)
Face of Fitting to
wall
Inch (mm)
F2 1/2 (13)
3/16 - 11/16 (4.7 - 17.4)
*Baseline fl ows and pressures for 0.05 density
Max. Sprinkler
Spacing
ft (m)
“A”
Ceiling -to-
Defl ector
Inch (mm)
Sprinkler
Temp. Rating
°F (°C)
Flow
gpm (Lpm)
Pressure
psi (bar)
Sprinkler
Identifi cation
Number (SIN)
12 x 12 (3.6x3.6)
4 - 6
(101-152)
155 (68) 175 (79) 12 (45.4) 7.5 (0.52)
R3531
14 x 14 (4.3x4.3) 155 (68) 175 (79) 14 (53.0) 10.2 (0.71)
16 x 16 (4.9x4.9) 155 (68) 175 (79) 16 (60.6) 13.3 (0.92)
16 x 18 (4.9x5.5) 155 (68) 175 (79) 18 (68.1) 16.8 (1.16)
18 x 18 (5.5x5.5) 155 (68) 175 (79) 19 (72.0) 18.7 (1.29)
16 x 20 (4.9x6.1) 155 (68) 175 (79) 23 (87.1) 27.4 (1.89)
12 x 12 (3.6x3.6)
6 - 12
(152-305)
155 (68) 175 (79) 14 (53.0) 10.2 (0.71)
14 x 14 (4.3x4.3) 155 (68) 175 (79) 16 (60.6) 13.3 (0.92)
16 x 16 (4.9x4.9) 155 (68) 175 (79) 17 (64.4) 15.0 (1.04)
16 x 18 (4.9x5.5) 155 (68) 175 (79) 20 (75.7) 20.7 (1.43)
16 x 20 (4.9x6.1) 155 (68) 175 (79) 23 (87.1) 27.4 (1.89)
*Calculate for a .10 density but in no case go below the baseline flows & pressures
Technical Data: F1 Res 76 CCP Pendent and Recessed Pendent/FP
Thread Size Nominal Orifi ce
Inch (mm)
Sprinkler Temp.
Rating
CCP Assembly
Temp. Rating Max. Pressure
psi (bar)
Max. Ambient
Temp.K
Factor
Sprinkler
Length
Inch (mm)°F °C °F °C °F °C
¾” NPT (R3/4)17/32” (13.5)155
175
68
79 135 57 175 (12)
100
150
38
66 7.6 2.25 (57)
*Baseline fl ows and pressures for 0.05 density
Max. Sprinkler Spacing
ft (m)
Flow
gpm (Lpm)
Pressure
psi (bar)
Sprinkler Identifi cation
Number (SIN)
12 x 12 (3.6x3.6) 21 7.6 (0.53)
R7618
14 x 14 (4.3x4.3) 21 7.6 (0.53)
16 x 16 (4.9x4.9) 21 7.6 (0.53)
18 x 18 (5.5x5.5) 22 8.4 (0.58)
20 x 20 (6.1x6.1) 25 10.8 (0.74)
8.
Technical Data: F1 Res 44 SWC
Thread
Size
Nominal
Orifi ce
Inch (mm)
Sprinkler
Temp.
Rating
Cover
Temp.
Rating
Max.
Pressure
psi (bar)
Max.
Ambient
Temp.K
Factor
Sprinkler
Length
Inch (mm)°F °C °F °C °F °C
½” NPT
(R½)3/8 (10) 155 68 135 57 175 (12) 100 38 4.4 2.45 (62)
*Baseline fl ows and pressures for 0.05 density
Max.
Sprinkler Spacing
ft (m)
“A” Ceiling -to-
Defl ector
Inch (mm)
Flow
gpm (Lpm)
Pressure
psi (bar)
Sprinkler
Identifi cation
Number (SIN)
12 x 12 (3.6x3.6)
4 - 6
(101-152)
13 (49.2) 8.7 (0.60)
R3531
14 x 14 (4.3x4.3) 14 (53.0) 10.2 (0.71)
16 x 16 (4.9x4.9) 17 (64.3) 15.0 (1.1)
16 x 18 (4.9x5.5) 19 (71.8) 18.7 (1.13)
16 x 20 (4.9x6.1) 23 (87.1) 27.4 (1.89)
12 x 12 (3.6x3.6)
6 - 12
(152-305)
14 (52.9) 10.2 (0.71)
14 x 14 (4.3x4.3) 15 (56.7) 11.7 (0.81)
16 x 16 (4.9x4.9) 18 (68.1) 16.8 (1.16)
16 x 18 (4.9x5.5) 20 (75.6) 20.7 (1.43)
• Model F1 Res 44 SWC*
Fig. 5
*Calculate for a .10 density but in no case go below the baseline flows & pressures
* Not listed for corrosion resistance.
9.
Technical Data: F1 Res 58 HSW & HSW/F2
Thread
Size
Nominal
Orifi ce
Inch (mm)
Sprinkler
Temp.
Rating
Max.
Pressure
psi (bar)
Max.
Ambient
Temp.
K
Factor
Sprinkler
Length
Inch (mm)°F °C °F °C
½” NPT
(R½)½ (13)155
175
68
79 175 (12)100
150
38
66 5.8 2.45 (62)
Escutcheon, F2, Data:
Type Adjustment
Inch (mm)
Face of Fitting to
wall
Inch (mm)
F2 ½ (13)
3/16 - 11/16 (4.7 - 17.4)
*Baseline fl ows and pressures for 0.05 density
Max.
Sprinkler Spacing
ft (m)
“A”
Ceiling -to-
Defl ector
Inch (mm)
Sprinkler
Temp. Rating
°F (°C)
Flow
gpm (Lpm)
Pressure
psi (bar)
Sprinkler
Identifi cation
Number (SIN)
12 x 12 (3.6x3.6)
4 - 6
(101-152)
155 (68) 175 (79) 16 (60.6) 7.6 (0.53)
R3533
14 x 14 (4.3x4.3) 155 (68) 175 (79) 18 (68.2) 9.7 (0.67)
16 x 16 (4.9x4.9) 155 (68) 175 (79) 21 (79.5) 13.2 (0.91)
16 x 18 (4.9x5.5) 155 (68) 175 (79) 25 (94.7) 18.6 (1.28)
16 x 20 (4.9x6.1) 155 (68) 175 (79) 29 (109.8) 25 (1.73)
12 x 12 (3.6x3.6)
6 - 12
(152-305)
155 (68) 175 (79) 22 (83.3) 14.4 (1.0)
14 x 14 (4.3x4.3) 155 (68) 175 (79) 22 (83.3) 14.4 (1.0)
16 x 16 (4.9x4.9) 155 (68) 175 (79) 26 (98.4) 20.1 (1.39)
16 x 18 (4.9x5.5) 155 (68) 175 (79) 31 (117.4) 28.6 (1.97)
*Calculate for a .10 density but in no case go below the baseline flows & pressure
10.
Technical Data: F1Res 58 HSWX (SIN RA3533)
Thread
Size
Nominal
Orifi ce
Inch (mm)
Max.
Pressure
psi (bar)
Sprinkler
Temp. Rating
Max.
Ambient
Temp.
K
Factor
Sprinkler
Length
Inch
(mm)
Sprinkler
Identifi cation
Number (SIN)°F °C °F °C
Bulb ½” NPT
(R½)1/2” (13) 175 (12)
155
175
68
79
100
150
38
66 5.8 2.45 (62) RA3533
*Baseline fl ows and pressures for 0.05 density
Max.
Coverage area
Ft x Ft (m x m)
Max. Spacing
Ft (m)
Ordinary Temp. Rating
(155°F/68°C)
Intermediate Temp.
Rating
(175°F/79°C)
Top of Defl ector
to Ceiling
Inch (mm)
Minimum
Spacing
Ft (m)Flow
GPM (L/min)
Pressure
PSI (bar)
Flow
GPM (L/min)
Pressure
PSI (bar)
18 x 20 (5,5 x 6,1) 18 (5,5) 30 (114) 26.8 (1,85) 30 (114) 26.8 (1,85)
4 to 6 (100 to 152);½ (13) recessed
using F2 escutcheon
8 (2,4)
20 x 20 (6,1 x 6,1) 20 (6,1) 30 (114) 26.8 (1,85) 30 (114) 26.8 (1,85)
16 x 22 (4,9 x 7,3) 16 (4,9) 33 (125) 32.4 (2,23) 33 (125) 32.4 (2,23)
16 x 24 (4,9 x 7,3) 16 (4,9) 38 (144) 42.9 (2,96) 38 (144) 42.9 (2,96)
14 x 26 (4,3 x 7,9) 14 (4,3) 42 (160) 52.4 (3,75) 42 (160) 52.4 (3,75)
18 x 20 (5,5 x 6,1) 18 (5,5) 35 (133) 36.4 (2,5) 35 (133) 36.4 (2,5)
6 to 12 (152 to 305);
½ (13) recessedusing F2 escutcheon
16 x 22 (4,9 x 6,7) 16 (4,9) 38 (144) 42.9 (2,96) 38 (144) 42.9 (2,96)
16 x 24 (4,9 x 7,3) 16 (4,9) 42 (160) 52.4 (3,6) 42 (160) 52.4 (3,6)
14 x 26 (4,3 x 7,9) 14 (4,3) 46 (174) 62.9 (4,34) 46 (174) 62.9 (4,34)
For Ceiling types refer to NFPA 13, 13R or 13D
*Calculate for a 0.10 density but in no case go below the baseline floor and pressures.
• Model F1 Res 58 HSWX (Bulb)
• Model KRes58 HSWX (Link)
Fig. 6
Technical Data: KRes58 HSWX (RA3593)
Thread
Size
Nominal
Orifi ce
Inch (mm)
Max.
Pressure
psi (bar)
Max.
Ambient
Temp.
K
Factor
Sprinkler
Length
Inch
(mm)
Sprinkler
Identifi cation
Number (SIN)°F °C
Link ½” NPT
(R½)1/2” (13) 175 (12) 100 38 5.8 2.45 (62) RA3593
*Baseline fl ows and pressures for 0.05 density
Max. Coverage area
Ft x Ft (m x m)
Max. Spacing
Ft (m)
Ordinary Temp. Rating
(165°F/74°C)Top of Defl ector
to Ceiling
Inch (mm)
Minimum
Spacing
Ft (m)Flow
GPM (L/min)
Pressure
PSI (bar)
18 x 20 (5,5 x 6,1) 18 (5,5) 29 (109) 25 (1,72)
4 to 6 (100 to 152);½ (13) recessed
using F2 escutcheon
8 (2,4)
20 x 20 (6,1 x 6,1) 20 (6,1) 30 (114) 26.8 (1,85)
16 x 22 (4,9 x 7,3) 16 (4,9) 33 (125) 32.4 (2,23)
16 x 24 (4,9 x 7,3) 16 (4,9) 38 (144) 42.9 (2,96)
14 x 26 (4,3 x 7,9) 14 (4,3) 42 (160) 52.4 (3,75)
18 x 20 (5,5 x 6,1) 18 (5,5) 35 (133) 36.4 (2,5)
6 to 12 (152 to 305);
½ (13) Recessed
using F2 escutcheon
16 x 22 (4,9 x 6,7) 16 (4,9) 38 (144) 42.9 (2,96)
16 x 24 (4,9 x 7,3) 16 (4,9) 42 (160) 52.4 (3,6)
14 x 26 (4,3 x 7,9) 14 (4,3) 46 (174) 62.9 (4,34)
For Ceiling types refer to NFPA 13, 13R or 13D
*Calculate for a 0.10 density but in no case go below the baseline floor and pressures.
11.
Maintenance
Model F1 Res 30, 49, F1 Res 58 & F1 Res 76 Sprin-
klers should be inspected and the sprinkler system
maintained in accordance with NFPA 25, 13, 13D, and
13R. Do not clean sprinkler with soap and water, Am-
monia or any other cleaning fluids. Remove dust by
using a soft brush or gentle vacuuming. Remove any
sprinkler which has been painted (other than factory
applied) or damaged in any way. A stock of spare sprin-
klers should be maintained to allow quick replacement
of damaged or operated sprinklers. Prior to installation,
sprinklers should remain in the original cartons and
packaging until used. This will minimize the potential
for damage to sprinklers that could cause improper op-
eration or non-operation.
Model F1Res 30, 49 & 58 Pendent Sprinkler
Specifi cations
Sprinklers shall be [cULus Listed] [New York City
MEA Approved (258-93-E)] low flow residential pen-
dent sprinklers engineered to provide a minimum de-
sign density of 0.10 gpm/ft2 over the listed coverage
area. Listed flows as specified by the manufacturer’s
technical data sheets are to be used. Residential
sprinklers shall be installed in conformance with the
manufacturer’s installation guidelines and the appli-
cable installation standard. Where pendent residential
sprinklers are installed under sloped ceilings having
a pitch from [4/12] to [8/12], the sprinklers shall be
listed for such use. Deflector-to-ceiling distance list-
ing shall be 1” to 8” maximum. Sprinkler frame and de-
flector shall be of bronze frame construction having a
½” NPT thread. Water seal assembly shall consist of a
Teflon* coated Belleville spring washer with top-loaded
extruded or cold head cup with 3 mm glass bulb con-
taining no plastic parts, and having a temperature rat-
ing of [155°F (68°C)] [175°F (79°C)]. Sprinklers shall
have a nominal K-factor of 4.9 & 5.8. Standard finish:
[Bronze] [Chrome-plated] [White Polyester] [Special
finish– specify]. Residential pendent sprinklers shall be
Reliable Model F1 Res 49 & 58, SIN R3516 & R3513
(Bulletin 135).
*DuPont Registered Trademark
12.
Model F1 Res 30, 49 & 58 Recessed Pendent/F1,
Model F1 Res 30, 49 & 58 Recessed Pendent/F2,
Model F1 Res 30, 49 & 58 Recessed Pendent/FP
Sprinklers shall be [cULus Listed] [New York City MEA
Approved (258-93-E)] low flow residential recessed pen-
dent sprinklers engineered to provide a minimum design
density of 0.10 gpm/ft2 over the listed coverage area.
Listed flows as specified by the manufacturer’s technical
data sheets are to be used. Residential sprinklers shall
be installed in conformance with the manufacturer’s instal-
lation guidelines and the applicable installation standard.
Where pendent residential sprinklers are installed under
sloped ceilings having a pitch from [4/12] to [8/12], the
sprinklers shall be listed for such use. Deflector-to-ceiling
distance listing shall be 1” to 8” maximum. Sprinkler frame
and deflector shall be of bronze frame construction hav-
ing a ½” NPT thread. Water seal assembly shall consist of
a Teflon* coated Belleville spring washer with top-loaded
extruded or cold head cup with 3 mm glass bulb contain-
ing no plastic parts, and having a temperature rating of
[155°F (68°C)] [175°F (79°C)]. Sprinklers shall have a
nominal K-factor of 4.9 (70). Standard finish: [Bronze]
[Chrome-plated] [White Polyester] [Special finish– spec-
ify]. Recessed escutcheon assembly shall be a steel,
two-piece escutcheon [with ½” adjustment (Model F2)]
[with ¾” adjustment (Model F1)] [of push-on and thread
off design with ½” adjustment (Model FP)]. Standard finish
shall be [brass][bright chrome] [white painted]. Residen-
tial recessed pendent sprinklers shall be Reliable [Model
F1 Res 49 & 58 Recessed Pendent/F1] [Model F1 Res
49 & 58 Recessed Pendent/F2] [Model F1 Res 49 & 58
Recessed Pendent/FP] SIN R3516 & R3513 (Bulletin 135).
Model F1 Res 30, 49 & 58 CCP Pendent
(Concealed)
Sprinklers shall be [cULus Listed] [New York City MEA
Approved (258-93-E)] low flow residential concealed
sprinklers engineered to provide a minimum design den-
sity of 0.10 gpm/ft2 over the listed coverage area. Listed
flows as specified by the manufacturer’s technical data
sheets are to be used. Residential sprinklers shall be in-
stalled in conformance with the manufacturer’s installa-
tion guidelines and the applicable installation standard.
Where pendent residential sprinklers are installed under
sloped ceilings having a pitch from [4/12] to [8/12], the
sprinklers shall be listed for such use. Sprinkler frame and
deflector shall be of bronze frame construction having a
½” NPT thread. Water seal assembly shall consist of a
Teflon* coated Belleville spring washer with top-loaded
extruded or cold head cup with 3 mm glass bulb contain-
ing no plastic parts, and having a temperature rating of
155°F (68°C). Cover plate assembly shall consist of a
brass cover plate and copper alloy retainer flange. Meth-
od of attaching the cover plate to the sprinkler cup shall
be a push-on and thread-off design allowing a ½” cover
plate adjustment. Cover plate temperature rating shall be
135°F (57°C). A plastic protective cap shall be provided
and factory installed inside the sprinkler cup to protect
the sprinkler from damage, which could occur during
construction before the cover plate is installed. Standard
cover plate finish: [White] [Custom Color– specify]. ]. Con-
cealed pendent sprinklers shall be Reliable Model F1 Res
49 & 58 CCP, SIN R3516 & R3513 (Bulletin 135).
Model F1 Res 44, F1 Res 58 Horizontal
Sidewall, F1 Res 58 HSWX & KRes58 HSWX
Residential Sprinkler Specifi cations
Sprinklers shall be [cULus Listed] low flow residen-
tial horizontal sidewall sprinklers engineered to pro-
vide a minimum design density of 0.10 gpm/ft2 over
the listed coverage area. Listed flows as specified
by the manufacturer’s technical data sheets are to be
used. Residential sprinklers shall be installed in con-
formance with the manufacturer’s installation guide-
lines and the applicable installation standard. Where
horizontal sidewall residential sprinklers are installed
under sloped ceilings having a pitch from [4/12] to
[8/12], the sprinklers shall be listed for such use. Sprin-
kler frame and deflector shall be of bronze frame con-
struction having a ½” NPT thread. Water seal assem-
bly shall consist of a Teflon-coated Belleville spring
washer with top-loaded extruded or cold head cup
with 3 mm glass bulb containing no plastic parts, and
having a temperature rating of [155°F (68°C)] [175°F
(79°C)]. The solder element (Link) version, the water
seal consist of a cap with a bellville spring washer and
a temperature rating of 165°F (74°C). The recessed
assembly forthe HSWX (Bulb & Link) should be a steel
two pieces escutcheon with 1/2” adjustment (Model
F2) standard finish should be Bright Chrome and white
painted. The F1 Res 58 HSW is also available with low
lead frame. F1 Res 58 HSW and HSWX sprinklers shall
have a nominal K Factor of 5.8 and F1 Res 44 a nomi-
nal K factor of 4.4. Standard finish: [Bronze] [Chrome-
plated] [White Polyester] [Special finish– specify].
Residential horizontal sidewall sprinklers shall be Reli-
able Model F1 Res 44, F1 Res 58, F1 Res 58 HSWX &
Model KRes58 HSWX, SIN R3531, RA3533 & RA3593
(Bulletin 135).
*DuPont Registered Trademark
Model F1 Res 44 & 58 Recessed Horizontal
Sidewall Sprinkler
Use description for the Model F1 Res 58 horizontal
sidewall sprinkler with the following modifications: Re-
place “horizontal sidewall sprinkler” with “recessed hori-
zontal sprinkler.” Add: Recessed escutcheon assembly
shall be a steel, two-piece escutcheon with ½” adjust-
ment (Model F2). Standard finish shall be [brass][bright
chrome] [white painted] [Special finish– specify]. Resi-
dential recessed horizontal sidewall sprinklers shall be
Reliable Model F1 Res 58/F2, SIN R3513 (Bulletin 135).
Model F1 Res 76 Pendent
Sprinklers shall be [cULus Listed] low flow resi-
dential pendent sprinklers engineered to provide a
minimum design density of 0.10 gpm/ft2 over the list-
ed coverage area. Listed flows as specified by the
manufacturer’s technical data sheets are to be used.
Residential sprinklers shall be installed in conformance
with the manufacturer’s installation guidelines and the
applicable installation standard. Sprinkler frame and
deflector shall be of bronze frame construction having
a ¾” NPT thread. Water seal assembly shall consist of
a Teflon-coated Belleville spring washer with machined
or cold head cup with 3 mm glass bulb containing no
plastic parts, and having a temperature rating of [155°F
(68°C)] [175°F (79°C)]. Sprinklers shall have a nominal
K-factor of 7.6. Standard finish: [Bronze] [Chrome-plat-
ed] [White Polyester] [Special finish– specify]. Residen-
tial pendent sprinklers shall be Reliable Model F1 Res
76, SIN R7618 (Bulletin 135).
Model F1 Res 76 Recessed Pendent/F1,
Model F1 Res 76 Recessed Pendent/F2,
Model F1 Res 76 Recessed Pendent/FP
Sprinklers shall be [cULus Listed] low flow residen-
tial recessed pendent sprinklers engineered to provide
a minimum design density of 0.10 gpm/ft2 over the listed
coverage area. Listed flows as specified by the manu-
facturer’s technical data sheets are to be used. Residen-
tial sprinklers shall be installed in conformance with the
manufacturer’s installation guidelines and the applicable
installation standard. Sprinkler frame and deflector shall
be of bronze frame construction having a ¾” NPT thread.
Water seal assembly shall consist of a Teflon-coated Bel-
leville spring washer with machined or cold head cup with
3 mm glass bulb containing no plastic parts, and having
a temperature rating of [155°F (68°C)] [175°F (79°C)].
Sprinklers shall have a nominal K-factor of 7.6. Standard
finish: [Bronze] [Chrome-plated] [White Polyester] [Special
finish– specify]. Recessed escutcheon assembly shall be
a steel, two-piece escutcheon [with ½” adjustment (Mod-
el F2)] [with ¾” adjustment (Model F1)] [of push-on and
thread off design with ½” adjustment (Model FP)]. Stan-
dard finish shall be [brass][bright chrome] [white painted].
Residential recessed pendent sprinklers shall be Reliable
[Model F1 Res 76 Recessed Pendent/F1] [Model F1 Res
76 Recessed Pendent/F2] [Model F1 Res 76 Recessed
Pendent/FP] SIN R7618 (Bulletin 135).
Model F1 Res 76 CCP Pendent (Concealed)
Sprinklers shall be [cULus Listed] low flow residential
concealed sprinklers engineered to provide a minimum
design density of 0.10 gpm/ft2 over the listed coverage
area. Listed flows as specified by the manufacturer’s
technical data sheets are to be used. Residential sprin-
klers shall be installed in conformance with the manufac-
turer’s installation guidelines and the applicable installa-
tion standard. Sprinkler frame and deflector shall be of
bronze frame construction having a ¾” NPT thread. Water
seal assembly shall consist of a Teflon-coated Belleville
spring washer with machined or cold head cup with 3
mm glass bulb containing no plastic parts, and having a
temperature rating of 155°F (68°C). Cover plate assem-
bly shall consist of a brass cover plate and copper alloy
retainer flange. Method of attaching the cover plate to the
sprinkler cup shall be a push-on and thread-off design
allowing a ½” cover plate adjustment. Cover plate tem-
perature rating shall be 135°F (57°C). A plastic protec-
tive cap shall be provided and factory installed inside the
sprinkler cup to protect the sprinkler from damage, which
could occur during construction before the cover plate
is installed. Standard cover plate finish: [White] [Custom
Color– specify]. ]. Concealed pendent sprinklers shall be
Reliable Model F1 Res 76 CCP, SIN R7618 (Bulletin 135).
Finishes(1)
Standard Finishes
Sprinkler F1, F2, FP Escutcheons
Bronze
Chrome Plated
White Polyester Coated(2)
Brass
Bright Chrome Plated
White Painted
Special Application Finishes
Sprinkler F1,F2,FP Escutcheons
Electroless NickelPTFE(Teflon®)*(2)
Bright Brass
Black Plated
Black Paint
Off White Chrome Dull
Electroless NickelPTFE (Teflon®)*
Bright Brass
Black Plated
Black Paint
Off White Chrome Dull
(1) Other finishes and colors are available on special order.
Consult factory for details.
(2) cULus listed Corrosion Resistant.
Ordering Information
Specify:
1. Sprinkler Model
2. Sprinkler Type
3. Temperature Rating
4. Sprinkler Finish
5. Escutcheon Finish
13.
*DuPont Registered Trademark
The Reliable Automatic Sprinkler Co., Inc.(800) 431-1588 Sales Offices
(800) 848-6051 Sales Fax
(914) 829-2042 Corporate Offices
www.reliablesprinkler.com Internet Address
Manufactured by
Recycled
Paper
Revision lines indicate updated or new data.
EG. Printed in U.S.A. 03 /14 P/N 9999970322
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory
Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly
qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries.
• Automatic sprinklers
• Flush automatic sprinklers
• Recessed automatic sprinklers
• Concealed automatic sprinklers
• Adjustable automatic sprinklers
• Dry automatic sprinklers
• Intermediate level sprinklers
• Open sprinklers
• Spray nozzles
• Alarm valves
• Retarding chambers
• Dry pipe valves
• Accelerators for dry pipe valves
• Mechanical sprinkler alarms
• Electrical sprinkler alarm switches
• Water flow detectors
• Deluge valves
• Detector check valves
• Check valves
• Electrical system
• Sprinkler emergency cabinets
• Sprinkler wrenches
• Sprinkler escutcheons and guards
• Inspectors test connections
• Sight drains
• Ball drips and drum drips
• Control valve seals
• Air maintenance devices
• Air compressors
• Pressure gauges
• Identification signs
• Fire department connection
Reliable offers a wide selection of sprinkler components. Following are some of the many
precision-made Reliable products that guard life and property from fire around the clock.
Reliable...For Complete Protection