The Riser Manifolds described in thistechnical data sheet provide the nec-essary waterflow alarm, pressuregauge, and drain equipment in a singleassembly for use in NFPA 13D or 13Rresidential sprinkler systems as fol-
lows:
Figure 513D (13D)
1 Inch (DN25)Female Thread x Female Thread
Figure 513D/R (13D/R)
1-1/2 Inch (DN40)Male Thread x Female Thread
Male Thread x Male Thread
Figure 513D/R (13D/R)2 Inch (DN50)
Groove x GrooveMale Thread x Groove
The variety of sizes and end connec-tions allow cost effective and easytransition to check valves, controlvalves, and system piping. The RiserManifolds may be installed in either thehorizontal (flow switch on top) or verti-cal (flow going up).
The Figure 513D (13D) and 513D/R(13D/R) Riser Manifolds with a covertamper switch for the waterflow alarmswitch are UL Listed, ULC Listed, andFM Approved.
The Figure 513D (13D) and 513D/R(13D/R) Riser Manifolds without a
cover tamper switch for the waterflowalarm switch are UL Listed and FM
Approved.
175 psi (12,1 bar)
The manifold body of the Figure 513 is
ductile iron, whereas the manifoldbody of the Figure 13 is cast iron. The
two assemblies are completely inter-changeable in function, application,
and end-to-end laying length.
Red painted.
The Riser Manifolds may be installed
in either the horizontal (flow switch ontop) or vertical (flow going up). The
inlet of the Riser Manifold may be di-rectly connected to a shut-off control
valve.
Install the manifold body with
the flow arrow pointing in the down-stream position using threaded con-nections and/or listed mechanicalgrooved connections, as applicable.
Connect the drain line, and
then close the drain valve.
Refer to Figure 4 for wiringguidance. All wiring must be per-formed in accordance with the Author-
ity Having Jurisdiction and/or the Na-tional Electrical Code.
Place the system in service by
filling the system with water. When fill-ing the system, partially open the con-
trol valve to slowly fill the system.
After the system is fully pressurized,completely open the control valve.
Secure all supply valvesopen.
Tel: (800) 381-9312 / Fax: (800) 791-5500
4-1/2"
to the Waterflow Alarm Switches.
Cover Tamper Switches installed internal
ULC Listed Manifolds are equipped with
(114,3 mm)
10"
(254,0 mm)
Approximate weight, 7.5 lbs. (3,4 kg).1.
2.
NOTES:
3/4" NPT
(92,1 mm)
3-5/8"1 (73,0 mm)
2-7/8"
9-3/4"
(247,7 mm)
Waterflow
3 2
CH: Common Hardware3.
(88,9 mm)
3-1/2"
Paddle and Cover Tamper
VSR-SF modified with
QTY.DESCRIPTION
Female x Female NPT
1" Manifold Body,
Water Pressure Gauge
200 psi/1400 kPa
VSR-SF modified with
Waterflow Alarm Switch:
1
3
2
NO.
. . 1
. . . 1 N/A
2343
P/N
Paddle, UL/FM . . . . . . . . 1 971-096-01
Switch, ULC/FM 1 976-519-01. . . . . . . .
(Normally Closed)
Drain Valve
(136,5 mm)
5-3/8"
(288,9 mm)
11-3/8"
Male x Male NPT
Manifold
11-1/8" (282,6 mm)
(54,0 mm)
Male x Female NPT
Manifold
10" (254,0 mm)
NPT
2-1/8"
1"
(114,3 mm)
4-1/2"
Waterflow
3 2
to the Waterflow Alarm Switches.
Cover Tamper Switches installed internal
ULC Listed Manifolds are equipped with
Approximate weight, 8.7 lbs. (3,9 kg).1.
2.
NOTES:
CH: Common Hardware3.
(88,9 mm)
3-1/2"
QTY.DESCRIPTION
1-1/2" Manifold Body,Male x Female NPT
Water Pressure Gauge
300 psi/2000 kPa3
2
1
NO.
. . 1
. . . . . 1
2341
N/A
P/N
Switch, ULC/FM. . . . . . . . 1 976-519-02
. . . . . . . . .
Waterflow Alarm Switch:VSR-SF modified with
VSR-SF modified withPaddle and Cover Tamper
Paddle, UL/FM 971-096-001
1
(Normally Closed)
Drain Valve
Male x Male NPT . . . . . . . 1 N/A
The following inspection proceduremust be performed as indicated, in ad-dition to any specific requirements ofthe NFPA, and any impairment mustbe immediately corrected.
The owner is responsible for the in-
spection, testing, and maintenance oftheir fire protection system and de-
vices in compliance with this docu-ment, as well as with the applicable
standards of the National Fire Protec-tion Association (e.g., NFPA 25), in
addition to the standards of anyauthority having jurisdiction. The in-
stalling contractor or product manufac-turer should be contacted relative to
any questions.
It is recommended that automaticsprinkler systems be inspected,tested, and maintained by a qualifiedInspection Service in accordance withlocal requirements and/or nationalcodes.
Fully open the drain valve.
Make certain that drainage water willnot cause any damage or injury.
Verify that the residual (flow-ing) pressure indicated by the pres-
sure gauge is no less that originallyrecorded for the system when it was
first installed.
Close the drain valve.
Verify that the static (not flow-
ing) pressure indicated by the pres-sure gauge is no less that originally
recorded for the system when it wasfirst installed.
Temporarily install a test ori-fice in the drain line outlet.
Fully open the drain valve.Make certain that drainage water will
not cause any damage or injury.
Verify operation of the associ-ated alarms.
Close the drain valve.
Remove the test orifice fromthe drain line outlet.
Fully open the Inspector’s Test
Connection Valve. Make certain thatdrainage water will not cause any dam-
age or injury.
Verify operation of the associ-ated alarms.
Close the Inspector’s TestConnection Valve.
Optionally
Supply End
Grooved or
Male NPT
(57,2 mm)
(114,3 mm)
2-1/4"
2. ULC Listed Manifolds are equipped with
Cover Tamper Switches installed internal
to the Waterflow Alarm Switches.
. . . . . . . 1 N/AGroove x Groove
Male NPT x Groove
300 psi/2000 kPa
Water Pressure Gauge
Approximate weight, 11.0 lbs. (5,0 kg).
NOTES:
1.
3
2
5-7/16"
(138,1 mm)
1"
NPT
4-1/2"
. . 1 2341
(304,8 mm)
12"
N/A1. . . . .
Waterflow
DESCRIPTION
2" Manifold Body,1
NO. P/NQTY.
3 2
CH: Common Hardware3.
ULC/FM . . . . . . . . . . . . . . 1 976-520-01
. . . . . . . . . . . . . . .
Waterflow Alarm Switch:
VSC with Paddle,
VSC with Paddle and
Cover Tamper Switch,
UL/FM 976-357-011
13" (330,2 mm)
Male NPT x Groove
Groove x Groove,
Connection
(88,9 mm)
3-1/2"
1
(Normally Closed)
Drain Valve
INCOMING
OUTGOING
SINGLE
CONDUCTOR
TERMINAL
PLATE
LOOPED SECTION
UNINSULATED
CLAMPING
CONDUCTORS
SEPARATE
STRIPPED
ENDS
CLAMPING
TERMINALPLATE
SEVERED
An uninsulated section of a
single conductor is not
permitted to be looped around
the terminal and serve as two
separate connections. The
wire must be severed to serve
as two separate connections,
thereby providing supervision
of the connection in the event
that the wire becomes
dislodged from the terminal.
COM
NCNO
NO FLOW
CONTACTS SPDT (Form C)
5A @ 125 VACCONTACT RATING
2.5A @ 30 VDC
. . . . . . . . . .
. . . .
COM
NO NC
POWER
SIGNAL
LOCAL
DEVICE
NON-SUPERVISED
CIRCUITCONDITION
END OF LINE
RESISTOR
COM
SUPERVISED CIRCUIT
STYLE B/CLASS B
CONTROL
NO NC
PANEL
signaling unit, while the other contact is used to operate a local audible or visual annunciator.
Switch has two switches, one can be used to operate a central station, proprietary or remove
For supervised circuits, see "Switch Terminal Connections" above. The Waterflow Alarm
(SEE NOTE)
CONTACTS SHOWNWITH COVER IN PLACE
COM
. . . . . . . . . .
. . . .CONTACT RATING
NO
CONTACTS
3A @ 250 VAC
5A @ 125 VAC
NC
SPDT (Form C)
1mA @ 5 VDC min.
Products manufactured by Tyco Fire &Building Products (TFBP) are war-
ranted solely to the original Buyer forten (10) years against defects in mate-
rial and workmanship when paid forand properly installed and maintained
under normal use and service. Thiswarranty will expire ten (10) years
from date of shipment by TFBP. Nowarranty is given for products or com-
ponents manufactured by companiesnot affiliated by ownership with TFBP
or for products and components whichhave been subject to misuse, improper
installation,corrosion, or which havenot been installed, maintained, modi-
fied or repaired in accordance with ap-plicable Standards of the National Fire
Protection Association, and/or thestandards of any other Authorities
Having Jurisdiction. Materials foundby TFBP to be defective shall be either
repaired or replaced, at TFBP’s soleoption. TFBP neither assumes, nor
authorizes any person to assume for it,any other obligation in connection with
the sale of products or parts of prod-ucts. TFBP shall not be responsible for
sprinkler system design errors or inac-curate or incomplete information sup-
plied by Buyer or Buyer’s repre-sentatives.
In no event shall TFBP be liable, incontract, tort, strict liability or underany other legal theory, for incidental,indirect, special or consequential dam-
ages, including but not limited to laborcharges, regardless of whether TFBP
was informed about the possibility ofsuch damages, and in no event shall
TFBP’s liability exceed an amountequal to the sales price.
The foregoing warranty is made in lieu
of any and all other warranties, ex-press or implied, including warranties
of merchantability and fitness fora par-ticular purpose.
This limited warranty sets forth the ex-clusive remedy for claims based on
failure of or defect in products, materi-als or components, whether the claim
is made in contract, tort, strict liabilityor any other legal theory.
This warranty will apply to the full ex-
tent permitted by law. The invalidity, inwhole or part, of any portion of this
warranty will not affect the remainder.
Specify; Size (specify), Figure (specify
513D or 513D/R, (specify connectiontype inlet x outlet) Riser Manifold
(specify - without or with) a cover tam-per switch for the waterflow alarm
switch, P/N (specify).
1 Inch (DN25)
FT x FT. . . . . . . . . . . . . . . P/N 4085
1-1/2 Inch (DN40)
MT x FT . . . . . . . . . . . . . . P/N 40881-1/2 Inch (DN40)MT x MT . . . . . . . . . . . . . . P/N 4089
2 Inch (DN50)
G x G . . . . . . . . . . . . . . . . P/N 4093
2 Inch (DN50)MT x G . . . . . . . . . . . . . . . P/N 4094
1 Inch (DN25)
FT x FT. . . . . . . . . . . . . . . P/N 40471-1/2 Inch (DN40)MT x FT . . . . . . . . . . . . . . P/N 40571-1/2 Inch (DN40)
MT x MT . . . . . . . . . . . . . . P/N 4058
2 Inch (DN50)G x G . . . . . . . . . . . . . . . . P/N 40592 Inch (DN50)MT x G . . . . . . . . . . . . . . . P/N 4064
Specify: (description) for use with Fig-
ure 513D, 513D/R, 13D, or 13D/RRiser Manifold, P/N (Ref. Figure 1, 2or 2, as applicable).
data sheet
The information contained herein is produced in good faith and is believed to be reliable but is for guidance only. ARGCO and its agents cannot
assume liability or responsibility for results obtained in the use of its product by persons whose methods are outside or beyond our control. It is the
user's responsibility to determine the suitability of any of the products, methods of use, or preparation prior to use, mentioned in our literature. It is
the user's responsibility to observe and adapt such precautions as may be advisable for the protection of personnel and property in the handling and
use of any of our products.
FOR MORE INFORMATION CALL ARGCO AT 1-800-854-1015
OR LOG ONTO WWW.ARGCO.COM
PART #
65-20-105
65-20-110
65-20-115
65-20-120
65-20-125
65-20-130
A
2.07
2.36
2.62
3.17
3.54
4.25
SIZE
1/2
3/4
1
1-1/4
1-1/2
2
B
2.13
2.30
2.62
3.07
3.43
4.21
DIMENSIONS
B
A
MATERIAL
CAST BRASS
CAST BRASSCAST BRASSRUBBER
BRASS ROD
BRASS ROD
PART
CAPBODY
SEAT HOUSE
SEAT GASKET
PIN
LOCK BOLT
MATERIALS
Built for a tight seal on backflow
Water, oil & gas - 200 psi
1/2 to 2 IPS
Cast Brass Construction
NOT recommended for pulsating or vibrating service
nut & washer on gasket
Horizontal Swing Check Valve
Inline Check Valve
PART #
65-20-140
65-20-145
65-20-150
65-20-151
SIZE
1 IPS
1-1/4 IPS
1-1/2 IPS
2 IPS
Spring loaded, Buna-N Seat
Horizontal or Vertical installation
Body
End piece
Stem
Spring
Seat
Forged brass
Forged brass
Plastic
Stainless steel
Buna-N
MATERIALS
A
2.32
2.64
2.75
3.15
B
1.77
2.20
2.48
3.11A
B DIMENSIONS
Horizontal Swing Check Valve
MFG. #5400928 - REV D-1
12/10PRINTED IN USA PAGE 1 OF 3
PS10 SERIES
PRESSURE SWITCH
Installation
The Potter PS10 Series Pressure Actuated Switches are designed for the
Wiring Instructions
conduit wiring.
Testing
Wet System
Method 1
UL, cUL, and CSFM Listed, FM and LPC Approved, NYMEA
Accepted, CE Marked
Dimensions:
Conduit Entrance:
Enclosure:
Pressure Connection:
Factory Adjustment:
Differential:
Maximum System Pressure:
Switch Contacts:
Service Use:
Method 2
Testing:
Note:
Wet System With Excess Pressure
Testing:
Dry System
Testing:
Note:
Tamper
Ordering Information
PS10-1 Pressure switch with one set 1340103
SPDT contacts
PS10-2 Pressure switch with two sets 1340104
SPDT contacts
PRESSURE SWITCH
MFG. #5400928 - REV D-1
12/10PRINTED IN USA PAGE 2 OF 3
PS10 SERIES
PRESSURE SWITCH
Typical Sprinkler Applications
Switch Clamping Plate TerminalDimensions
Low Pressure Signal Connection
Fig. 2
Fig. 4 Fig. 5
Fig. 3
Fig. 1
PRESSURE SWITCH
MFG. #5400928 - REV D-1
12/10PRINTED IN USA PAGE 3 OF 3
PS10 SERIES
PRESSURE SWITCH
One Conduit Wiring
Fig. 9
Removing KnockoutsSwitch Operation
Fig. 8
indication.
PRESSURE SWITCH
SAMMYS® FOR WOOD
Part No. Model
Rod
Size
Mount
Direction
UL Max
Pipe Size
UL Test
Load (lbs)
UL Min Wood
Thickness
FM Max
Pipe Size
FM Test
Load (lbs)
FM Min Wood
Thickness
8007957 GST 10 3/8” Vertical CPVC 1-1/2” 300 1-1/2”
8020957 SWG 10 3/8” Horizontal CPVC 1-1/2” 300 1-1/2”
8008957 GST 20 3/8” Vertical 2-1/2” 850 1-1/2” 4” 1475 1-1/2”
8068925 GST 20-SS 3/8” Vertical 2-1/2” 850 1-1/2”
8010957 GST 30 3/8” Vertical 4” 1500 1-1/2” 4” 1475 1-1/2”
8009925 GST 25-380 3/8” Vertical 4” 1500 1-1/2”
8022925 SWG 25-380 3/8” Horizontal 3-1/2” - 4”* 1500 1-1/2”
8021957 SWG 20 3/8” Horizontal 2-1/2” - 3”** 1050 1-1/2”
8073925 SWG 20-SS 3/8” Horizontal 2-1/2” 850 1-1/2”
8139957 SH-GST 20 3/8” 17° Angle off Vertical 3” 1050 1-1/2”4” 1475 1-1/2”
8141957 SH-GST 30 3/8” 17° Angle off Vertical 4” 1500 1-1/2”4” 1475 1-1/2”
14 For the most up to date information, visit www.sammysuperscrew.com
SAMMYS® FOR STEEL
Part No. Model
Rod
Size
Mount
Direction
UL Max
Pipe Size
UL Test
Load (lbs)
UL Min. Steel
Thickness
FM Max
Pipe Size
FM Test
Load (lbs)
FM Min. Steel
Thickness
8038957 DSTR 1 3/8” Vertical 4” 1500 .035” 4” 1475 .105”
8037957 DSTR 1-1/2 3/8” Vertical 4” 1500 .035” 4” 1475 .105”
8039957 DSTR 516 3/8” Vertical 4” 1500 .037” 4” 1475 .105”
8045957 DST 516 3/8” Vertical 4” 1500 .188” 4” 1475 .188”
8046957 TEK 50 3/8” Vertical 4” 1500 .250” 4” 1475 .188”
8055957 SWDR 1 3/8” Horizontal 4” 1500 .037” 4” 1475 .060”
8056957 SWDR 516 3/8” Horizontal 4” 1500 .037” 4” 1475 .060”
8054957 SWDR 1-1/2 3/8” Horizontal 4” 1500 .037” 4” 1475 .060”
8137957 SH-DSTR 1 3/8” 17° Angle off Vertical 4” 1500 .035” 4” 1475 .105”
8150922 XP 20 3/8” Vertical 2-1/2” 850 .027”
2” 940 .029”
4” 1475 .105”
8153922 XP 35 3/8” Vertical 3-1/2” 1250 .060”
2” 940 .029”
4” 1475 .105”
8294922 SXP 20 3/8” Vertical or up to 45°2” 750 .027” 2” 635 .029”
8295922 SXP 35 3/8” Vertical or up to 89°3-1/2” 1250 .060” 2” 635 .029”
8293957 SWXP 35 3/8” Horizontal 3-1/2” 1250 .060”
SAMMYS® FOR CONCRETE
Part No. Model
Rod
Size
Mount
Direction
UL Max
Pipe Size
UL Test
Load (lbs)
UL Min
PSI
FM Max
Pipe Size
FM Test
Load (lbs)
FM Min
PSI
8059957 CST 20 3/8” Vertical 4” 1475 3000
8061957 SWC 20 3/8” Horizontal 4” 1475 3000
8150922 XP 20 3/8” Vertical 2-1/2” 850 Pre-Pour Structural @ 3000psi
8150922 XP 20 3/8” Vertical 2-1/2” 850
3)
TRUSS-T HANGER®
Part No. Model
Rod
Size
Mount
Direction
UL Load
Rating (lbs)
UL Test
Load (lbs)Listed Application
8296900 HD38TC 3/8” Top Chord 1200 6075 Maximum 4” Schedule 40 pipe
8297900 HD38BC 3/8” Bottom Chord 1200 6075 Maximum 4” Schedule 40 pipe
8198900 HD12CZP 1/2” Bottom Chord 1200 6075 Maximum 8” Schedule 40 Pipe
8298900 HD12TC 1/2” Top Chord 1200 6075 Maximum 8” Schedule 40 Pipe
8299900 HD12BC 1/2” Bottom Chord 1200 6075 Maximum 8” Schedule 40 Pipe
APPROVALS APPROVALS APPROVALS APPROVALSPipe Hanger
Pipe Hanger
Pipe Hanger
Pipe Hanger
PIPE HANGER
*SWG 25-380 Maximum pipe size in composite wood joist allowed by UL is 3-1/2”
*SWG 25-380 Maximum pipe size in wood timber or joist allowed by UL is 4”
**SWG 20 Maximum pipe size in composite wood joist allowed by UL is 2-1/2”**SWG 20 Maximum pipe size in wood timber or joist allowed by UL is 3”
UL compliance with NEC Standards.
UL and FM tests were performed in compliance with NFPA 13 Standards.
8022925 SWG 25-380 3/8”Horizontal 3-1/2” - 4”*1500 1-1/2”