HomeMy WebLinkAboutF17-0013_REVISED AREA 6-7-2017_1497036840.pdfMERIDIAN INTERMOUNTAIN 331 METCALF ROAD # 6 AVON, COLORADO 970-748-8888 Job Name : ASHTON-HURST Building : Location : System : BONUS ROOM Contract : Data File : AREA 1 6-7-2017.WXF Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 MERIDIAN INTERMOUNTAIN Page 1 ASHTON-HURST Date 6-7-2017 HYDRAULIC CALCULATIONS for Project name:ASHTON-HURST Location: Drawing no: Date:6-7-2017 Design Remote area number:BONUS ROOM Remote area location: Occupancy classification: Density:.1 - Gpm/SqFt Area of application: - SqFt Coverage per sprinkler:130 - SqFt Type of sprinklers calculated: No. of sprinklers calculated:3 In-rack demand: - GPM Hose streams:0 - GPM Total water required (including hose streams):39.9779 - GPM @ 89.2251 - Psi Type of system: Volume of dry or preaction system: - Gal Water supply information Date: Location: Source: Name of contractor:MERIDIAN INTERMOUNTAIN Address:331 METCALF ROAD # 6 / / AVON, COLORADO Phone number:970-748-8888 Name of designer: Authority having jurisdiction: Notes: (Include peaking information or gridded systems here.) Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 MERIDIAN INTERMOUNTAINPage 2 ASHTON-HURSTDate 6-7-2017 12243648E60R72U84S96S108E120R132P144156168180100 200 300 400 500 600 700 800 900FLOW ( N ^ 1.85 )City Water Supply:Demand:C1C2C1 - Static Pressure : 150 C2 - Residual Pressure: 13 C2 - Residual Flow : 675 D1 - Elevation : 21.655 D2 - System Flow : 39.978 D2 - System Pressure : 89.225 Hose ( Demand ) : _______D3 - System Demand : 39.978 Safety Margin : 60.041 D1D2Water Supply Curve CComputer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 MERIDIAN INTERMOUNTAIN Page 3 ASHTON-HURST Date 6-7-2017 13 HS11  |13 13.5| HS22 13.5 HS33 13 1 2 M21 26.5 |26.5|40 13.5||40 40 40 3 M21M20M5 M10TORBORTEST 40 40 40 Flow Diagram Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 MERIDIAN INTERMOUNTAINPage 4 ASHTON-HURSTDate 6-7-2017 Fitting Legend Abbrev.Name ½¾11¼1½22½33½456810121416182024 Ball B Ball Milw BB-SC100 2.25 2 2.5 2.25 10 E NFPA 13 90' Standard Elbow 1 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61 Fsp Flow Switch Potter VSR Fitting generates a Fixed Loss Based on Flow N *CPVC 90'Ell Harvel-Spears 7789111213000000000000 S NFPA 13 Swing Check 0 0 5 7 9 11141619222732455565 T NFPA 13 90' Flow thru Tee 3 4 5 6 8 10121517202530355060718191101121 Zil Wilkins 975XL Fitting generates a Fixed Loss Based on Flow Units Summary Diameter Units Inches Length Units Feet Flow Units US Gallons per Minute Pressure Units Pounds per Square Inch Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters. Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors of 120 except as noted with *. The fittings marked with a * show equivalent lengths values supplied by manufacturers based on specific pipe diameters and CFactors and they require no adjustment. All values for fittings not marked with a * will be adjusted in the calculation for CFactors of other than 120 and diameters other than Sched 40 per NFPA. Fittings Used SummaryComputer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 MERIDIAN INTERMOUNTAIN Page 5 ASHTON-HURST Date 6-7-2017 Node Elevation K-Fact Pt Pn Flow Density Area Press No. Actual Actual Req. HS1 143.0 4.9 7.04 na 13.0 0.1 130 7.0 HS2 143.0 4.9 7.57 na 13.49 0.1 130 7.0 HS3 143.0 4.9 7.58 na 13.49 0.1 130 7.0 1 144.0 7.01 na 2 144.0 7.58 na 3 144.0 7.79 na M21 144.0 8.58 na M20 144.0 9.26 na M5 144.0 21.82 na M10 144.0 30.26 na TOR 144.0 30.82 na BOR 93.0 58.23 na TEST 93.0 89.23 na The maximum velocity is 10.21 and it occurs in the pipe between nodes M20 and M5 Pressure / Flow Summary - STANDARD Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 MERIDIAN INTERMOUNTAIN Page 6 ASHTON-HURST Date 6-7-2017 Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv ******* Notes ****** Point Qt Pf/Ft Eqv. Ln. Total Pf Pn HS1 13.00 1.025 2E 5.4 4.000 7.039 K Factor = 4.90 to 150.0 0.0 5.400 -0.433 1 13.0 0.0434 0.0 9.400 0.408 Vel = 5.05 0.0 13.00 7.014 K Factor = 4.91 HS2 13.49 1.025 2E 5.4 4.000 7.575 K Factor = 4.90 to 150.0 0.0 5.400 -0.433 2 13.49 0.0465 0.0 9.400 0.437 Vel = 5.25 0.0 13.49 7.579 K Factor = 4.90 HS3 13.49 1.025 2E 5.4 8.370 7.582 K Factor = 4.90 to 150.0 0.0 5.400 -0.433 3 13.49 0.0465 0.0 13.770 0.640 Vel = 5.25 0.0 13.49 7.789 K Factor = 4.83 1 13.00 1.025 1T 6.75 6.250 7.014 to 150.0 0.0 6.750 0.0 2 13.0 0.0435 0.0 13.000 0.565 Vel = 5.05 2 13.49 1.265 1T 5.935 11.280 7.579 to 150.0 0.0 5.935 0.0 M21 26.49 0.0581 0.0 17.215 1.001 Vel = 6.76 0.0 26.49 8.580 K Factor = 9.04 3 13.49 1.265 3N 24.0 11.490 7.789 to 150.0 2T 11.87 35.870 0.0 M21 13.49 0.0167 0.0 47.360 0.791 Vel = 3.44 M21 26.49 1.505 1T 8.704 4.000 8.580 to 150.0 0.0 8.705 0.0 M20 39.98 0.0535 0.0 12.705 0.680 Vel = 7.21 0.0 39.98 9.260 K Factor = 13.14 M20 39.98 1.265 6N 48.0 35.000 9.260 to 150.0 3T 17.804 65.804 0.0 M5 39.98 0.1246 0.0 100.804 12.561 Vel = 10.21 M5 0.0 1.505 4E 17.409 123.000 21.821 to 150.0 2T 17.409 34.818 0.0 M10 39.98 0.0535 0.0 157.818 8.439 Vel = 7.21 M10 0.0 1.505 2E 8.704 1.750 30.260 to 150.0 0.0 8.705 0.0 TOR 39.98 0.0535 0.0 10.455 0.559 Vel = 7.21 TOR 0.0 1.505 2E 8.704 25.000 30.819 to 150.0 1S 9.792 18.498 25.088 * * Fixed Loss = 3 BOR 39.98 0.0535 1Fsp 0.0 43.498 2.326 Vel = 7.21 BOR 0.0 1.598 11N 99.0 325.000 58.233 to 150.0 1Zil 0.0 114.299 13.450 * * Fixed Loss = 13.45 TEST 39.98 0.0399 1T 11.656 439.299 17.542 Vel = 6.40 1Ball 3.643 0.0 Final Calculations - Hazen-Williams - 2007 Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 MERIDIAN INTERMOUNTAIN Page 7 ASHTON-HURST Date 6-7-2017 Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv ******* Notes ****** Point Qt Pf/Ft Eqv. Ln. Total Pf Pn 39.98 89.225 K Factor = 4.23 Final Calculations - Hazen-Williams Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087