F17-0022_0 VVMC Central Wing Equip Sub_1499705340.pdf
2617 W Holden Pl, Denver CO 80204 | Phn 303-629-0221, Fax 303-623-7830 AUTOMATIC FIRE SPRINKLER SYSTEM EQUIPMENT SUBMITTAL FOR VAIL VALLEY MEDICAL CENTER CENTRAL WING RENOVATION 180 S. FRONTAGE ROAD VAIL, CO 81657 06/08/17 Vail Fire & Emergency Services 07/10/17 Vail Fire & Emergency Services 07/10/17 TABLE OF CONTENTS Bookmark/Section Description 0 Cover sheet - Table of Contents 1 Fire Stop caulking 2 Hangers 3 Pipe 4 Fittings 5 Valves (Not Used) 6 Backflow preventer (Not Used) 7 Electrical (Not Used) 8 Sprinkler heads 9 Equipment (No Used) Vail Fire & Emergency Services 07/10/17 Vail Fire & Emergency Services 07/10/17 September 2015 PRODUCT DATA SHEET Metacaulk® 1000 Firestopping Sealant 1. Product Description Metacaulk® 1000 is a one component, general purpose fire rated sealant and smoke seal for construction joints and through-penetrations. Metacaulk® 1000 is a water based, extremely intumescent, non-sag caulking grade sealant that is easy to apply as well as to retrofit. It cures to an elastomeric seal that is suitable where dynamic movement is expected. In the event of a fire, Metacaulk® 1000 will prevent the spread of flames, smoke, hot gases and water through joint openings and through- penetrations. No dilution or mixing is required for use. No special skills are necessary for installation. Metacaulk® 1000 is applied with a conventional caulking gun, bulk loading gun or can be troweled from the pail. For large applications, it can be pumped directly from the pail. Metacaulk® 1000 systems are rated for 1, 2, 3 and 4 hours in accordance with the ASTM E814 (UL1479),UL 2079 and ULC-S115-95 test standards. Metacaulk® 1000 is protected in a wet stage as well as in a dry stage against mold growth with a combination of biocides. Use Metacaulk® 1000 for various applications: Top of the Wall Construction Joints Deflection Track Wall Systems Up to 2" (51 mm) PVC\CPVC (Open) Up to 3" (76 mm)PVC\CPVC & ABS (Closed) Crosslinked Polyethylene (PEX) tubing Steel, Copper, Cast Iron and EMT Pipe Flexible Conduit Fiberglass Insulated Pipe Armaflex Insulated Pipe Telephone, Communication and Power Cables HVAC Ductwork Color Red Cure Time 3 t o 4 weeks (at 77˚F/ 25˚C) Density 10.5 +/- 0.5 lbs./gal. 1.25 kg/L Elastomeric Yes Freeze-Thaw Excellent Skin Over Time 30 min. (at 77˚ F/ 25˚C) pH Value 6.5 to 7 Volume Coverage: for 10.3 oz. tube (304ml) 18 cu. in. (295 cc) for 5 gallon (18.9 liter) 1155 cu. in. (5000 cu. cm/L) VOC Negligible ASTM E 84, UL 723 Tunnel Test Flame Spread 0 Smoke Index 0 Sound Transmission Class STC 62* *Tested in a UL 411 wall assembly/section to ASTM E90. 3. Applications Metacaulk® 1000 can be used in interior applications as a general purpose fire rated sealant and smoke seal for construction joints on both vertical and horizontal surfaces. Metacaulk® 1000 is also an excellent fire rated acoustical sealant and can be used in areas under constant For a complete list of product applications or for additional technical information, call RECTORSEAL for the latest updated information. Metacaulk® 1000 Features • Water Based • Excellent Freeze-Thaw • Flexible Set • Highly Intumescent • Paintable • VOC Compliant • Safe and Easy to Use • Minimum 3 Year Shelf Life 2. Material Properties Asbestos Fillers None Solvents None Hazardous Ingredients None Application Caulking Gun or Trowel Activation of Intumescence: Expansion Begins 375˚ F (190˚C) Expansion Greatest 575˚ (302˚C) to 1100˚ F(593˚ C) For list of systems see metacaulk.com Vail Fire & Emergency Services 07/10/17 10. LIMITED WARRANTY RectorSeal makes the Limited Express Warranty that when the instructions for storage and handling of our products are followed we warrant our products to be free from defects. THIS LIMITED EXPRESS WARRANTY IS EXPRESSLY IN LIEU OF ANY OTHER EXPRESS OR IMPLIED WARRANTIES, INCLUDING ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PAR- TICULAR PURPOSE, AND OF ANY OTHER OBLIGATION ON THE PART OF RECTORSEAL. The sole remedy for breach of the Limited Express Warranty shall be the refund of the purchase price. All other liability is negated and disclaimed, and RectorSeal shall not be liable for incidental or consequential damages. Suggestions and recommendations covering the use of our products are based on our past experience and laboratory findings. However, as we have no control as to the methods and conditions of application, we only assume responsibility for the uniformity of our products within manufacturing tolerances. I-15 METACAULK® 1000 8. Limitations Metacaulk® 1000 is not designed to be used in areas under continuous immersion or in areas which would be continuously wet. Metacaulk® 1000 should not be used against hot uninsulated surfaces above 300˚ F (149˚ C). 9. Cautions FOR CHEMICAL EMERGENCY, SPILL, LEAK, FIRE, EXPOSURE OR ACCIDENT, CALL CHEMTREC-DAY OR NIGHT 1-800- 424-9300. PRECAUTIONS: Do not take internally. May be harmful if swallowed. May cause eye and skin irritation if prolonged or repeated contact occurs. Wash after handling. FIRST AID: For any overexposure, get immediate medical attention after first aid is given. Eyes- Flush 15 minutes with clean water. Skin-Wash with soap and water. Inhalation-Remove to fresh air. Ingestion-Only if conscious, give large amounts of water and INDUCE VOMITING. FIRE AND SPILLS: Use water fog, CO2, foam, or dry chemicals. Wipe up spills to prevent footing hazard. Clean up with scrapers and water. STORAGE AND HANDLING: Store away from heat sources. Keep container closed. Do not reuse empty container. KEEP OUT OF REACH OF CHILDREN. For additional information, refer to Material Safety Data Sheet. For additional technical service, call: 1-800-231-3345 fax: 1-800-452-2824 www.rectorseal.com www.metacaulk.com vibration or movement. Metacaulk® 1000 can also be used on various penetrations such as EMT, telephone & power cables, insulated pipes, etc. in concrete floors and walls , gypsum walls as well as wood floors. Use Metacaulk® 1000 to prevent the spread of fire and smoke through joints in fire rated gypsum wallboard partitions, concrete block or concrete walls and/ or concrete or corrugated steel deck floor/ceiling assemblies. 4. Installation Data Install Metacaulk® 1000 using standard caulking techniques or trowel from pails. Metacaulk® 1000 may also be pumped from the pails. When damming materials are needed, use only materials approved for the specific application. TYPICAL TOP OF WALL INSTALLATION Step 1) Cut and fit the gypsum wallboard to the contour of the steel decking leaving a maximum 3/4" (19 mm) relief gap. Step 2) Pack the flute openings and relief gap with required amount of fiberglass insulation and recess to required depth. Step 3) Gun, trowel or pump the sealant as required to the specified depth. Properly tool sealant surface flush with the wall. Consult UL Directory for complete instructions and system listings. 5. Testing Data For specific test criteria, refer to the UL's Fire Resistance Directory or Warnock Hersey International Listing Directory or call RECTORSEAL Metacaulk® 1000 was tested at positive pressure with a minimum 0.01 (2.5 Pa) inches water and in accordance with ASTM E814 (UL 1479), UL 2079 and ULC-S115-95. Complies to Required Environmental Exposure Testing of Accelerated Aging and High Humidity as per UL 1479 Fire Test of Through-Penetration Firestops. FBC System Compatible indicates that this product has been tested, and is monitored on an ongoing basis, to assure its chemical compatibility with FlowGuard Gold®, BlazeMaster® and Corzan® pipe and fittings. FBC, FlowGuard Gold®, BlazeMaster® and Corzan® are licensed trademarks of the Lubrizol corporation. 6. Storage & Handling Metacaulk® 1000 should be stored between 35˚F (2˚C) and 120˚ F (49˚ C). to obtain a minimum 3 year shelf life. NOTE: Do not dilute, no mixing is required. Best if protected from freezing. If freezing occurs, thaw completely before using. Keep products stored under protective cover in original containers. 7. Availability Metacaulk® 1000 is available in 10.3 oz. (304 ml), 30 oz.(887 ml) caulking tubes and 20.2 oz. (597 ml) sausage pack and in 5 gallon (18.9 L) pails. Vail Fire & Emergency Services 07/10/17 System No. C-AJ-1235 July 15, 2014 ANSI/UL1479 (ASTM E814) CAN/ULC S115 F Rating — 2 and 3 Hr (See Item 3B) F Rating — 2 and 3 Hr (See Item 3B) T Rating — 0 Hr FT Rating — 0 Hr L Rating At Ambient — Less Than 1 CFM/sq ft FH Rating — 2 and 3 Hr (See Item 3B) L Rating At 400 F — Less Than 1 CFM/sq ft FTH Rating — 0 Hr L Rating At Ambient — Less Than 1 CFM/sq ft L Rating At 400 F — Less Than 1 CFM/sq ft 1. Floor or Wall Assembly — Min 4-1/2 in. (114 mm) thick reinforced normal weight (140-150 pcf or 2200-2400 kg/m3) concrete. Floor may also be constructed of any min 6 in. (152 mm) thick UL Classified hollow-core Precast Concrete Units*. Wall may also be constructed of any UL Classified Concrete Blocks*. Max diam of opening is 26 in. (660 mm). If the firestop system is installed within a hollow-core hollow-core precast concrete unit, max diam of opening shall be 7 in. (178 mm). See Concrete Block (CAZT) and Precast Concrete Units (CFTV) categories in the Fire Resistance Directory for names of manufacturers. 1A. Metallic Sleeve — (Not shown, Optional) — Nom 8 in. (203 mm) diam (or smaller) Schedule 10 (or heavier) steel sleeve cast or grouted into floor or wall assembly, flush with floor or wall surfaces. The use and the max diam of the steel sleeve is dependent upon the type and max diam of the through penetrant (Item 3) and type and min fill material thickness as tabulated in Item 3B. Vail Fire & Emergency Services 07/10/17 2. Through Penetrants — One metallic pipe, conduit or tubing to be installed either concentrically or eccentrically within the firestop system. The annular space between the pipe, conduit or tubing and the periphery of the opening shall be min 0 in. (point contact) to a max 1-7/8 in. (48 mm). Pipe, conduit or tubing to be rigidly supported on both sides of floor or wall assembly. The following types and sizes of metallic pipes, conduits or tubing may be used: A. Steel Pipe — Nom 24 in. (610 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe. B. Iron Pipe — Nom 24 in. (610 mm) diam (or smaller) cast or ductile iron pipe. C. Conduit — Nom 4 in. (102 mm) diam (or smaller) steel electrical metallic tubing (EMT) or nom 6 in. (152 mm) diam (or smaller) steel conduit. D. Copper Tubing — Nom 6 in. (152 mm) diam (or smaller) Type L (or heavier) copper tubing. E. Copper Pipe — Nom 6 in. (152 mm) diam (or smaller) Regular (or heavier) copper pipe. 3. Firestop System — The firestop system shall consist of the following: A. Packing Material — Min 4 pcf (64 m3) mineral wool batt insulation firmly packed into opening or min 1 in. (25 mm) diam backer rod friction fitted into the opening as a form. Packing material to be recessed from top surface of floor or from both surfaces of wall as required to accommodate the required thickness of fill material. When the floor is constructed of hollow-core precast concrete units, packing material shall be recessed from both surfaces of floor to accommodate the required thickness of fill materials. In floors, the packing material may be removed after the fill material cures. B. Fill, Void or Cavity Material* — Sealant — Fill material applied within the annulus, flush with top surface of floor or with both surfaces of wall. At the point contact location between through penetrant and concrete, a min 3/8 in. (10 mm) diam bead of fill material shall be applied at the concrete/through penetrant interface on the top surface of floor and on both surfaces of wall. When the floor is constructed of hollow-core precast concrete units, fill material shall be installed symmetrically on both sides of floor, flush with both floor surfaces. The F Rating of the firestop system is dependent upon the use and the max diam of the steel sleeve, type and max diam of the through penetrant and type and min fill material thickness as tabulated below: Use of Steel Sleeve Max Diam of Steel Sleeve In. Type of Through Penetrant Max Diam of Through Penetrant In. Type of Fill Mtl Min Fill Mtl Thkns In. F Rating Hr Not permitted - Steel or Iron Pipe 24 (610) FS1900, Metacaulk 1000, Metacaulk 350i, Biostop 350i or Biostop 500+ 1 (25) 3 Permitted 8 (203) Steel or Iron Pipe 6 (152) FS1900, Metacaulk 1000, Metacaulk 350i, Biostop 350i or Biostop 500+ 1 (25) 3 Permitted 8 (203) Copper Pipe, 6 (152) FS1900, Metacaulk 1000, Metacaulk 350i, Biostop 350i or Biostop 500+ 1 (25) 3 Copper Tube or Steel Conduit Permitted 6 (152) Steel EMT 4 (102) FS1900, Metacaulk 1 (25) 3 Vail Fire & Emergency Services 07/10/17 1000, Metacaulk 350i, Biostop 350i or Biostop 500+ Permitted 6 (152) Steel or Iron Pipe 4 (102) FS1900, Metacaulk 1000, Metacaulk 350i, Biostop 350i or Biostop 500+ 1/2 (13) 2 Permitted 6 (152) Copper Pipe, 4 (102) FS1900, Metacaulk 1000, Metacaulk 350i, Biostop 350i or Biostop 500+ 1/2 (13) 2 Copper Tube or Steel Conduit Permitted 6 (152) Steel EMT 4 (102) FS1900, Metacaulk 1000, Metacaulk 350i, Biostop 350i or Biostop 500+ 1/2 (13) 2 Not permitted - Steel or Iron Pipe 24 (610) FS900/FS900+, Biostop BF 150+, Metacaulk MC 150+ 1/2 (13) 3 Permitted 8 (203) Steel or Iron Pipe 6 (152) FS900/FS900+, Biostop BF 150+, Metacaulk MC 150+ 1/2 (13) 3 Permitted 8 (203) Copper Pipe, 6 (152) FS900/FS900+, Biostop BF 150+, Metacaulk MC 150+ 1/2 (13) 3 Copper Tube or Steel Conduit Permitted 6 (152) Steel EMT 4 (102) FS900/FS900+, Biostop MC 150+, Metacaulk MC 150+ 1/2 (13) 3 RECTORSEAL — FlameSafe® FS1900, Flamesafe® FS900, FlameSafe® FS900+, Metacaulk MC 150+, Metacaulk 1000, Metacaulk 350i, Biostop BF 150+, Biostop 350i or Biostop 500+.. * Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada), respectively. Vail Fire & Emergency Services 07/10/17 System No. W-L-5148 December 20, 2001 F Ratings — 1 and 2 Hr (See Item 1) T Ratings — 0 and 3/4 Hr (See Item 1) 1. Wall Assembly — The 1 or 2 hr fire-rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300 or U400 Series Wall or Partition Designs in the UL Fire Resistance Directory and shall include the following construction features: A. Studs — Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. lumber spaced 16 in. OC. Steel channel studs to be min 3-1/2 in. wide and spaced max 24 in. OC. B. Gypsum Board* — Nom 5/8 in. thick, 4 ft wide with square or tapered edges. The gypsum board type, number of layers, fastener type and sheet orientation shall be as specified in the individual Wall and Partition Design. Max diam of opening is 6-1/2 in. The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly. The T Rating for a 1 hr wall is 0 hr, T Rating for a 2 hr wall is ¾ hr. 2. Through Penetrant — One metallic pipe to be installed either concentrically or eccentrically within the firestop system. Pipe to be rigidly supported on both sides of wall assembly. The following types and sizes of metallic pipes may be used: A. Steel Pipe — Nom 4 in. diam (or smaller) Schedule 10 (or heavier) steel pipe. B. Iron Pipe — Nom 4 in. diam (or smaller) cast or ductile iron pipe. C. Copper Tubing — Nom 4 in. diam (or smaller) Type L (or heavier) copper tube D. Copper Pipe — Nom 4 in. diam (or smaller) Regular (or heavier) copper pipe. 3. Tube Insulation - Plastics+ — Nom 3/4 in. thick acrylonitrile butadiene/polyvinyl chloride (AB/PVC) flexible foam furnished in the form of tubing. The annular space between the pipe or tube insulation and the periphery of the opening Vail Fire & Emergency Services 07/10/17 shall be min 0 in. (point contact) to a max 7/8 in. See Plastics+ (QMFZ2) category in the Plastics Recognized Component Directory for names of manufacturers. Any Recognized Component tube insulation material meeting the above specifications and having a UL 94 Flammability Classification of 94-5VA may be used. 4. Fill, Void or Cavity Materials* - Caulk — Min 5/8 in. thickness of caulk applied within annular space flush with each surface of wall. A min 1/2 in. diam bead of caulk shall be applied to the pipe insulation/gypsum board interface at the point contact location on both sides of wall. RECTORSEAL — Metacaulk 1000 *Bearing the UL Classification Mark Vail Fire & Emergency Services 07/10/17 OFFICE/MANUFACTURING FACILITY 1375 SAMPSON AVE. CORONA, CA 92879 PH: 951.737.5599 FAX: 951.737.0330 CUSTOMER SERVICE 800.786.5266 www.tolco.com 70 wwwwww..ttoollccoo..ccoomm ® a brand of Revision 8/15/2005 Size Range Secures 3/8" thru 7/8" hanger rod Material Carbon Steel Function Secures channel to hanger rod for vertical seismic bracing. Approvals — Underwriters Laboratories Listed in the USA (UL) and Canada (cUL). Included in our Seismic Restraints Catalog approved by the State of California Office of Statewide Health Planning and Development (OSHPD). For additional load, spacing and placement information relating to OSHPD projects, please refer to the TOLCO Seismic Restraint Systems Guidelines Finish Electro Galvanized Note Available in HDG finish or Stainless Steel materials. Order By Figure number Fig. 98 - Rod Stiffener Fig. 99 - All Thread Rod Cut to Length Size Range Secures 3/8" thru 7/8" rod in 1" increments Material Carbon Steel Maximum Temperature 750°F Finish Plain Note Available in Electro-Galvanized and HDG finish or Stainless Steel materials. Order By Figure number, rod diameter, rod length and finish Fig. 100 - All Thread Rod Full Lengths Size Range Secures 3/8" thru 7/8" rod in 10 lengths Material Carbon Steel Maximum Temperature 750°F Finish Plain Note Available in Electro-Galvanized and HDG finish or Stainless Steel materials. Order By Figure number, rod diameter and finish Dimensions · Weights Rod Max. Rec. Load Lbs. Size For Service Temps 650°F 750°F 3/8 610 540 1/2 1130 1010 5/8 1810 1610 3/4 2710 2420 7/8 3770 3360 Dimensions · Weights Max Rec. Load Lbs. Rod For Service Temps Approx. Size 650°F 750°F Wt./100 1/4 240 215 12 3/8 610 540 29 1/2 1130 1010 53 5/8 1810 1610 84 3/4 2710 2420 123 7/8 3770 3360 169 1 4960 4420 222 11/4 8000 7140 360 11/2 11630 10370 510 Component of State of California OSHPD Approved Seismic Restraints System Vail Fire & Emergency Services 07/10/17 Main Office/Manufacturing Facility · 1375 Sampson Ave. · Corona, CA 92879 · Ph: 909.737.5599 · Fax: 909.737.0330 Customer Service · 800.786.5266 www.tolco.com 86 wwwwww..ttoollccoo..ccoom m Revision 5/24/2001 ™ ® a brand of Fig. 200 - “Trimline” Adjustable Band Hanger Size Range — 1/2" thru 8" pipe Material — Carbon Steel, Mil. Galvanized to G90 specifications Function — For fire sprinkler and other general piping purposes. Knurled swivel nut design permits hanger adjustment after installation. Features — · (1/2" thru 2") Flared edges ease installation for all pipe types and protect CPVC plastic pipe from abrasion. Captured design keeps adjusting nut from separating with hanger. Hanger is easily installed around pipe. · (21/2" thru 8" Spring tension on nut holds it securely in hanger before installation. Adjusting nut is easily removed. Approvals — Underwriters’ Laboratories listed (1/2" thru 8") in the USA (UL) and Canada (cUL) for steel and CPVC plastic pipe and Factory Mutual Engineering Approved (3/4" thru 8"). Conforms to Federal Specifications WW-H-171E, Type 10 and Manufacturers Standardization Society SP-69, Type 10. Maximum Temperature — 650°F Finish — Mil. Galvanized. For Stainless Steel materi- als, order TOLCO™ Fig. 200WON. Order By — Figure number and pipe size Dimensions · Weights Pipe Rod Size Max. Rec. Approx. Size Inch Metric A B Load Lbs. Length 1/2 3/8 8mm or 10mm 31/8 25/8 400 11 3/4 3/8 8mm or 10mm 31/8 2 1/2 400 11 1 3/8 8mm or 10mm 33/8 25/8 400 12 11/4 3/8 8mm or 10mm 33/4 27/8 400 13 11/2 3/8 8mm or 10mm 37/8 27/8 400 14 2 3/8 8mm or 10mm 41/2 3 400 15 21/2 3/8 10mm 55/8 41/8 600 27 3 3/8 10mm 57/8 4 600 29 31/2 3/8 10mm 73/8 51/4 600 34 4 3/8 10mm 73/8 5 1000 35 5 1/2 12mm 91/8 6 1/4 1250 66 6 1/2 12mm 101/8 63/4 1250 73 8 1/2 12mm 131/8 8 3/4 1250 136 Vail Fire & Emergency Services 07/10/17 www.powers.com 1 General InformatIon TECH MANUAL – MECHANiCAL ANCHors ©2015 PoWErs VoLUME 1 – 9/2015 – rEV. H Section contentS Mechanical anchors snAke+ inTernal Thread Version • Unified coarse thread (UNC) anchor MaTerials • Zinc plated carbon steel body anchor size range (TYP.) • 1/4",3/8 " and 1/2" diameters suiTable base MaTerials • Normal-weight concrete • Sand-lightweight concrete • Concrete oversteel deck C R A C K E D C O N C R E T E T E N S I O N Z O N E Q U AL I F I C A T I O N S E I S M I C R E G I O N Code listed ICC-eS eSr-2272 concreTe This ProductAvailable In ® Powers DesignAssist ® Real-TimeAnchor Design Software www.powersdesignassist.com general inforMaTion snAke+® Internally Threaded Screw Anchor ProdUct descriPtion The snake+ anchor is an internally threaded, self-tapping screw anchor designed for performance in cracked and uncracked concrete. suitable base materials include normal-weight concrete, sand-lightweight concrete and concrete over steel deck. The snake+ screw anchor is installed into a drilled hole with a power tool and a snake+ setting tool. After installation a steel element is threaded into the anchor body. GenerAl APPlicAtions And Uses • Suspending conduit, cable trays and strut • Interior applications/low level corrosion environment • Tension zone areas • Pipe supports • Seismic and wind loading applications • Fire sprinklers • Suspended lighting FeAtUre And BeneFits + Cracked concrete approved alternative to a dropin anchor + Designed for use in holes drilled with standard ANSI carbide drill bits + Anchor design allows for shallow embedment and mechanically interlocks with base material + Internally threaded anchor for easy adjustment and removability of threaded rod or bolt + Fast anchor installation with a powered impact wrench + Hammer not used for installation APProvAls And listinGs • International Code Council, Evaluation Service (ICC-ES), ESR-2272 for concrete. Code compliant with the 2015IBC, 2015IRC, 2012 IBC, 2012 IRC, 2009 IBC, 2009 IRC, 2006 IBC, and 2006 IRC. • Tested in accordance with ACI 355.2 and ICC-ES AC193 for use in structural concrete under the design provisions ofACI 318 (Strength Design method using Appendix D) • Evaluated and qualified by an accredited independent testing laboratory for recognition in cracked and uncracked concrete including seismic and wind loading (Category 1 anchor) • Evaluated and qualified by an accredited independent testing laboratory for reliability against brittle failure, e.g. hydrogen embrittlement • Evaluated and qualified by an accredited independent testing laboratory for supplemental recognition in redundant fastening applications • FM Global (Factory Mutual) - File No. 3038104 (see report for sizes) www.approvalguide.com - Pipe hanger components for automatic sprinkler systems GUide sPeciFicAtions Csi Divisions: 03 16 00 - Concrete Anchors and 05 05 09 - Post-installed Concrete Anchors. internally threaded anchors shall be snake+ as supplied by Powers Fasteners, inc., Brewster, NY. Anchors shall be installed in accordance with published instructions and the Authority Having Jurisdiction. MaTerial sPecificaTions Anchor Component Specification Anchor Body Case hardened carbon steel Plating Zinc plating according to AsTM B633, sC1, Type iii (Fe/Zn 5) Minimum plating requirements for Mild service Condition General Information......................1 Material Specifications .................1 Installation Specifications ............2 Installation Instructions................3 Performance Data..........................4 Installation Specifications ............8 Ordering Information ....................9 Vail Fire & Emergency Services 07/10/17 www.powers.com 2 TECH MANUAL – MECHANiCAL ANCHors ©2015 PoWErs VoLUME 1 – 9/2015 – rEV. H InStallatIon SpeCIfICatIonS Mechanical anchors insTallaTion sPecificaTions Installation Information for Snake+ Screw Anchor for Single Point Applications1 Anchor Property/ Setting Information Notation Units Nominal Anchor Size 1/4" 3/8" 1/2" Nominal outside anchor diameter da(do)3 i n. (mm) 0.375 (9.5) 0.500 (12.7) 0.750 (19.1) internal thread diameter (UNC) d in. (mm) 0.250 (6.4) 0.375 (9.5) 0.500 (12.7) Minimum diameter of hole clearance in fixture for steel insert element (following anchor installation) dh in. 5/16 7/16 9/16 Nominal drill bit diameter dbit in. 3/8 ANsi 1/2 ANsi 3/4 ANsi Minimum hole depth ho in. (mm) 2 (51) 2 (51) 2-1/2 (64) overall anchor length ℓanch in. (mm) 1-1/4 (32) 1-1/4 (32) 1-11/16 (43) Minimum nominal embedment depth2 hnom in. (mm) 1-5/8 (41) 1-5/8 (41) 2-3/16 (55) Effective embedment hef in. (mm) Not Applicable4 1.10 (28) 1.54 (39) Maximum impact wrench power (torque) Tscrew ft.-lb. (N-m) 120 (163) 345 (468) 345 (468) Maximum tightening torque of steel insert element (threaded rod or bolt) Tmax ft.-lb. (N-m) 4 (6) 8 (11) 36 (49) Anchors Installed in Concrete Construction2 Minimum member thickness2 hmin in. (mm) Not Applicable4 4 (102) 4 (102) Critical edge distance2 cac in. (mm) Not Applicable4 3 (76) 4(102) Minimum edge distance2 cmin in. (mm) Not Applicable4 3 (76) 4 (102) Minimum spacing distance2 smin in. (mm) Not Applicable4 3 (76) 4 (102) Anchors Installed in the Topside of Concrete-Filled Steel Deck Assemblies5 Minimum member topping thickness hmin,deck in. (mm) Not Applicable4 3-1/4 (83) Not applicable Critical edge distance cac,deck,top in. (mm) Not Applicable4 3 (76) Not applicable Minimum edge distance cmin,deck,top in. (mm) Not Applicable 4 3 (76) Not applicable Minimum spacing distance smin,deck,top in. (mm) Not Applicable4 3 (76) Not applicable 1. The information presented in this table is to be used in conjunction with the design criteria of ACI 318 Appendix D. 2. For installations through the soffit of steel deck into concrete, see installation detail. Anchors in the lower flute may be installed with a maximum 1-inch offset in either direction from center of the flute. In addition, anchors shall have an axial spacing along the flute equal to the greater of 3hef or 1.5 times the flute width. 3. The notation in parenthesis is for the 2009 IBC. 4. The 1/4-inch diameter anchor is limited to redundant fastening design only. 5. For 3/8-inch diameters installed in the topside of concrete-filled steel deck assemblies, steel installation detail. Dimensional Sketch for Snake+ Screw Anchor Installed with Steel Insert Element Do not exceed Tmax Do not exceed Tmax Vail Fire & Emergency Services 07/10/17 www.powers.com 3 InStallatIon InStruCtIonS TECH MANUAL – MECHANiCAL ANCHors ©2015 PoWErs VoLUME 1 – 9/2015 – rEV. H Mechanical anchors insTallaTion insTrucTions Min. 3-1/4" Max.3" Min. 4-1/2" (Typ) SAND-LIGHTWEIGHT CONCRETE OR NORMAL WEIGHT CONCRETEOVER STEEL DECK (MINIMUM 2,500 PSI) Snake+ Anchor(Typ) 1. 3/8-inch diameter anchors may be placed in the topside of steel deck profiles provided the minimum topping thickness, minimum spacing distance and minimum edge distance are satisfied. Min. 3" Max. 3" Min. 4-1/2" Min. 4-1/2" (Typ) Min. 12" (Typ) Upper Flute (Valley) 1" Clearance Min. STRUCTURAL SAND-LIGHTWEIGHT CONCRETE OR NORMAL WEIGHT CONCRETE OVER STEEL DECK (MINIMUM 3,000 PSI) Snake+Anchor (Typ) 1. Anchors may be placed in the upper flute or lower flute of the steel deck profiles provided in minimum hole clearance is satisfied. Anchors in the lower flute may be installed with a maximum 1-inch offset in either direction from the center of the flute. The offset distance may be increased proportionally for profiles with lower flute widths greater than those shown provided the minimum lower flute edge distance is also satisfied. Vail Fire & Emergency Services 07/10/17 www.powers.com 4 TECH MANUAL – MECHANiCAL ANCHors ©2015 PoWErs VoLUME 1 – 9/2015 – rEV. H performanCe Data Mechanical anchors PerforMance daTa Tension Design Information (For use with load combinations taken from ACI 318 Section 9.2)1,2 Design Characteristic Notation Units Nominal Anchor Diameter 3/8 inch 1/2 inch Anchor category 1,2 or 3 - 1 1 Nominal embedment depth hnom in. (mm) 1-5/8 (41) 2-3/16 (55) STEEL STRENGTH IN TENSION4 Minimum specified yield strength of steel insert element fy ksi (N/mm2) AsTM A36 36.0 (248) AsTM A193, Grade B7 105.0 (724) - Minimum specified ultimate strength of steel insert element futa 11 ksi (N/mm2) AsTM A36 58.0 (400) AsTM A193, Grade B7 125.0 (862) - Effective tensile stress area of steel insert element Ase, n (Ase)11 in2 (mm2) 0.0775 (50) 0.1419 (92) steel strength in tension Nsa lb (kN) AsTM A36 4.495 (20.0) 8,230 (37.0) AsTM A193, Grade B7 9,685 (43.1) - reduction factor for steel strength3,4 f - 0.65 CONCRETE BREAKOUT STRENGTH IN TENSION8 Effective embedment hef in. (mm) 1.10 (28) 1.54 (39) Effectiveness factor for uncracked concrete kucr - 24 30 Effectiveness factor for cracked concrete kcr - 17 24 Modification factor for cracked and uncracked concrete5 ψc,n - Cracked concrete = 1.0 Uncracked concrete = 1.0 Critical edge distance cac in. (mm) 3 (76) 4 (102) reduction factor for concrete breakout strength3 f - Condition B = 0.65 PULLOUT STRENGTH IN TENSION (NON-SEISMIC APPLICATIONS)8 Characteristic pullout strength, uncracked concrete (2,500 psi)6 Np,uncr lb (kN) see note 7 see note 7 Characteristic pullout strength,cracked concrete (2,500 psi)6 Np,cr lb(kN) see note 7 1,665 (7.4) reduction factor for pullout strength3 f - 0.65 (Condition B) PULLOUT STRENGTH IN TENSION FOR SEISMIC APPLICATIONS8 Characteristic pullout strength, seismic (2,500 psi)6,9 Np,eq lb(kN) see note 7 1,665 (7.4) reduction factor for pullout strength3 f - Condition B = 0.65 PULLOUT STRENGTH IN TENSION FOR SOFFIT OF SAND-LIGHT WEIGHT AND NORMAL-WEIGHT CONCRETE OVER STEEL DECK Characteristic pullout strength, uncracked concrete over steel deck6,10 Np,deck,uncr lb (kN) 1,515 (6.7) 1,625 (7.2) Characteristic pullout strength, cracked concrete over steel deck6,10 Np,deck,cr lb (kN) 1,075 (4.8) 1,300 (5.8) Characteristic pullout strength, cracked concrete over steel deck, seismic6,9,10 Np,deck,eq lb (kN) 1,075 (4.8) 1,300 (5.8) reduction factor for pullout strength, concrete over steel deck3 f - Condition B = 0.65 1. The data in this table is intended to be used with the design provisions of ACI 318 Appendix D; for anchors resisting seismic load combinations the additional requirements of Section D.3.3 shall apply. 2. Installation must comply with published instructions and details. 3. All values offwere determined from the load combinations of ACI 318 Section 9.2. If the load combinations of ACI 318 Appendix C are used, the appropriate value offmust be determined in accordance with ACI 318-11 Section D.4.4. For reinforcement that meets ACI 318 Appendix D requirements for condition A, see ACI 318-11 D.4.3 for appropriateffactor. 4. It is assumed that the threaded rod or bolt used with the Snake+ anchor will be a steel element as defined by ACI 318 Section D.1. However, the anchor steel is considered a brittle steel element in tension as defined by ACI 318. D.1. Tabulated values for steel strength in tension must be used for design. 5. For all design cases useψc,n = 1.0. Select appropriate effectiveness factor for cracked concrete (kcr) or uncracked concrete (kuncr). 6. For all design cases useψc,p = 1.0. For concrete compressive strength greater than 2,500 psi, Npn = (Pullout strength value from table)*(specified concrete compressive strength/2500)0.5. For concrete over steel deck the value of 2,500 must be replaced with the value of 3,000. 7. Pullout strength will not control design of indicated anchors. Do not calculate pullout strength for indicated anchor size and embedment. 8. Anchors are permitted to be used in sand-lightweight concrete provided that Nb and Npn are multiplied by a factor of 0.60 (not required for steel deck). 9. Reported values for characteristic pullout strength in tension for seismic applications are based on test results per ACI 355.2, Section 9.5. 10.Values for Np, deck are for sand-lightweight concrete (f’c, min = 3,000 psi) and additional lightweight concrete reduction factors need not be applied. In addition, evaluation for the concrete breakout capacity in accordance with ACI 318 Section D.5.2 is not required for anchors installed in the flute (soffit). 11.The notation in brackets is for the 2006 IBC. Vail Fire & Emergency Services 07/10/17 www.powers.com 5 performanCe Data TECH MANUAL – MECHANiCAL ANCHors ©2015 PoWErs VoLUME 1 – 9/2015 – rEV. H Mechanical anchors Shear Design Information (For use with load combinations taken from ACI 318 Section 9.2)1,2 Design Characteristic Notation Units Nominal Anchor Diameter 3/8 inch 1/2 inch Anchor category 1,2 or 3 - 1 1 Nominal embedment depth hnom in. (mm) 1-5/8 (41) 2-3/16 (55) STEEL STRENGTH IN SHEAR4 steel strength in shear5 Vsa lb (kN) AsTM A36 770 (3.4) 1,995 (8.9) AsTM A193, Grade B7 1,655 (7.4) - reduction factor for steel strength3 f - 0.60 CONCRETE BREAKOUT STRENGTH IN SHEAR6 Nominal outside anchor diameter da(do)10 in. (mm) 0.500 (12.7) 0.750 (19.1) Load bearing length of anchor (hef or 8do, whichever is less) ℓe - 1.10 (28) 1.54 (39) reduction factor for concrete breakout strength3 f - Condition B = 0.70 PRYOUT STRENGTH IN SHEAR6 Coefficient for pryout strength (1.0 for hef < 2.5 in, 2.0 for hef ≥ 2.5 in.) kcp - 1.0 1.0 Effective embedment hef in. (mm) 1.10 (28) 1.54 (39) reduction factor for pullout strength3 f - Condition B = 0.70 STEEL STRENGTH IN SHEAR FOR SEISMIC APPLICATIONS steel strength in shear, seismic7 Vsa,eq lb (kN) AsTM A36 770 (3.4) 1,995 (8.9) AsTM A193, Grade B7 1,655 (7.4) - reduction factor for pullout strength3 f - Condition B = 0.60 STEEL STRENGTH IN SHEAR FOR SOFFIT OF SAND-LIGHT WEIGHT AND NORMAL-WEIGHT CONCRETE OVER STEEL DECK9 steel strength in shear, concrete over steel deck8 Vsa,deck lb (kN) AsTM A36 770 (3.4) 1,995 (8.9) AsTM A193,Grade B7 1,655 (7.4) - steel strength in shear, concrete over steel deck, seismic8 Vsa,deck,eq lb (kN) AsTM A36 770 (3) 1,995 (8.9) AsTM A193, Grade B7 1,665 (7.4) - reduction factor for pullout strength3 f - Condition B = 0.60 1. The data in this table is intended to be used with the design provisions of ACI 318 Appendix D; for anchors resisting seismic load combinations the additional requirements of ACI 318 D.3.3 shall apply. 2. Installation must comply with published instructions and details. 3. All values offwere determined from the load combinations of IBC Section 1605.2. or ACI 318 Section 9.2. If the load combinations of ACI 318 Appendix C are used, the appropriate value offmust be determined in accordance with ACI 318-11 D.4.4. For reinforcement that meets ACI 318 Appendix D requirements for Condition A, see ACI 318-11, D.4.3 for the appropriateffactor. 4. It is assumed that the threaded rod or bolt used with the Snake+ anchor will be a ductile steel element as defined by ACI 318 D.1. 5. Tabulated values for steel strength in shear must be used for design. These tabulated values are lower than calculated results using equation D-29 in ACI 318-11 (DC-20 in ACI 318-08 and ACI 318-05) and ACI 318 D.6.1.2. 6. Anchors are permitted to be used in sand-lightweight concrete provided that Vb is multiplied by a factor of 0.60 (not required for steel deck).. 7. Tabulated values for steel strength in shear are for seismic applications and based on test results in accordance with ACI 355.2 Section 9.6. 8. Tabulated values for Vsa,deck are for sand-lightweight concrete (f’c,min = 3,000 psi) and additional lightweight concrete reduction factors need not be applied. In addition, evaluation for the concrete breakout capacity in accordance with ACI 318 D.6.2 and the pryout capacity in accordance with ACI 318 D.6.3 are not required for anchors installed in the deck soffit (flute). 9. Shear loads for anchors installed through steel deck into concrete may be applied in any direction. 10.The notation in parenthesis is for the 2006 IBC. Vail Fire & Emergency Services 07/10/17 www.powers.com 6 TECH MANUAL – MECHANiCAL ANCHors ©2015 PoWErs VoLUME 1 – 9/2015 – rEV. H performanCe Data Mechanical anchors Factored Design Strength (ØNn And ØVn) Calculated In Accordance With ACI 318 Appendix D: 1- Tabular values are provided for illustration and are applicable for single anchors installed in normal- weight concrete with minimum slab thickness, ha = hmin, and with the following conditions: - ca1 is greater than or equal to the critical edge distance, cac (table values based on ca1 = cac). - ca2 is greater than or equal to 1.5 times ca1. 2- Calculations were performed according to ACi 318-11 Appendix D. The load level corresponding to thecontrolling failure mode is listed. (e.g. For tension: steel, concrete breakout and pullout; For shear: steel,concrete breakout and pryout). Furthermore, the capacities for concrete breakout strength in tensionand pryout strength in shear are calculated using the effective embedment values, hef, for the selectedanchors as noted in the design information tables. Please also reference the installation specifications formore information. 3- strength reduction factors (ø) were based on ACi 318 section 9.2 for load combinations. Condition B is assumed. 4- Tabular values are permitted for static loads only, seismic loading is not considered with these tables. 5- For designs that include combined tension and shear, the interaction of tension and shear loads must be calculated in accordance with ACi 318 Appendix D. 6- interpolation is not permitted to be used with the tabular values. For intermediate base materialcompressive strengths please see ACi 318 Appendix D. For other design conditions including seismicconsiderations please see ACi 318 Appendix D. Ca1 Ca2 ha Tension and Shear Design Strengths Installed in Cracked Concrete ® NominalAnchorSize (in.) NominalEmbed.hnom (in. ) SteelInsertElement (ThreadedRod orBolt) Minimum Concrete Compressive Strength, f’c (psi) 2,500 3,000 4,000 6,000 8,000 fNn Tension (lbs.) fVn Shear (lbs.) fNn Tension (lbs.) fVn Shear (lbs.) fNn Tension (lbs.) fVn Shear (lbs.) fNn Tension (lbs.) fVn Shear (lbs.) fNn Tension (lbs.) fVn Shear (lbs.) 3/8 1-5/8 AsTM A36 635 500 700 500 805 500 985 500 1,140 500 AsTM A193Grade B7 635 685 700 750 805 870 985 1,065 1,140 1,075 1/2 2-3/16 AsTM A36 1,080 1,295 1,185 1,295 1,370 1,295 1,675 1,295 1,935 1,295 ■ - Anchor Pullout/Pryout Strength Controls ■ - Concrete Breakout Strength Controls ■ - Steel Strength Controls Tension and Shear Design Strengths Installed in Uncracked Concrete ® NominalAnchorSize (in.) NominalEmbed.hnom (in. ) SteelInsertElement (ThreadedRod orBolt) Minimum Concrete Compressive Strength, f’c (psi) 2,500 3,000 4,000 6,000 8,000 fNn Tension (lbs.) fVn Shear (lbs.) fNn Tension (lbs.) fVn Shear (lbs.) fNn Tension (lbs.) fVn Shear (lbs.) fNn Tension (lbs.) fVn Shear (lbs.) fNn Tension (lbs.) fVn Shear (lbs.) 3/8 1-5/8 AsTM A36 900 500 985 500 1,140 500 1,395 500 1,610 500 AsTM A193Grade B7 900 970 985 1,060 1,140 1,075 1,395 1,075 1,610 1,075 1/2 2-3/16 AsTM A36 1,865 1,295 2,040 1,295 2,355 1,295 2,885 1,295 3,335 1,295 ■ - Anchor Pullout/Pryout Strength Controls ■ - Concrete Breakout Strength Controls ■ - Steel Strength Controls Vail Fire & Emergency Services 07/10/17 www.powers.com 7 performanCe Data TECH MANUAL – MECHANiCAL ANCHors ©2015 PoWErs VoLUME 1 – 9/2015 – rEV. H Mechanical anchors redUndAnt FAsteninG APPlicAtions For an anchoring system designed with redundancy, the load maintained by an anchor that experiences failure or excessive deflection can be transmitted to neighboring anchors without significant consequences to the fixture or remaining resistance of the anchoring system. in addition to the requirements for anchors, the fixture being attached shall be able to resist the forces acting on it assuming one of the fixing points is not carrying load. it is assumed that by adhering to the limits placed on n1, n2 and n3 below, redundancy will be satisfied. Anchors qualified for redundant applications may be designed for use in normal weight and sand-lightweight cracked and uncracked concrete. Concrete compressive strength of 2,500 psi shall be used for design. No increase in anchor capacity is permitted for concrete compressive strengths greater than 2,500 psi. The anchor installation is limited to concrete with a compressive strength of 8,500 psi or less. redundant applications shall be limited to structures assigned to seismic Design Categories A or B only. redundant applications shall be limited to support of nonstructural elements. n2 = At Number of AnchoragePoints n1 Vail Fire & Emergency Services 07/10/17 www.powers.com 8 TECH MANUAL – MECHANiCAL ANCHors ©2015 PoWErs VoLUME 1 – 9/2015 – rEV. H InStallatIon SpeCIfICatIonS Mechanical anchors insTallaTion sPecificaTions Installation Information for Snake+ Screw Anchor in Redundant Fastening Applications Anchor Property/ Setting Information Notation Units Nominal Anchor Size 1/4" 3/8" 1/2" Nominal drill bit diameter dbit in. 3/8" ANsi 1/2" ANsi 3/4" ANsi Nominal embedment depth hnom in. (mm) 1-5/8 (41) 1-5/8 (41) 2-3/16 (55) Effective embedment hef in. (mm) 1.10 (28) 1.10 (28) 1.54 (39) Minimum hole depth ho in. (mm) 2 (51) 2 (51) 2-1/2 (64) Minimum concrete member thickness hmin in. (mm) 3 (76.2) 3 (76.2) 3 (76.2) overall anchor legnth ℓanch in. (mm) 1-1/4 (32) 1-1/4 (32) 1-11/16 (43) Minimum edge distance, redundant fastening1 cmin = cac i n.(mm) 4 (102) 4 (102) 4 (102) Minimum spacing distance, redundant fastening1 smin in. (mm) 8 (203) 8 (203) 8 (203) Maximum tightening torque of steel insert element (threaded rod or bolt) Tmax ft.-lb. (N-m) 4 (6) 8 (11) 36 (49) Maximum impact wrench power (torque) Tscrew ft.-lb. (N-m) 120 (163) 345 (468) 345 (468) 1. Tabulated minimum spacing and edge distances are applicable only for redundant fastening applications. Redundant Fastening Design Information for Snake+ Anchors1,2,3 Anchor Property/ Setting Information Notation Units Nominal Anchor Size 1/4" 3/8" 1/2" Anchor category 1,2 or 3 - 1 1 1 Nominal embedment depth hnom in. (mm) 1-5/8 (41) 1-5/8 (41) 2-3/16 (55) CHARACTERISTIC STRENGTH (RESISTANCE) INSTALLED IN CONCRETE4,5 resistance, cracked or uncracked concrete (2,500psi) Fra lb (kN) Number ofanchorage points Number ofanchorage points Number ofanchorage points n1 ≥ 4 n1 ≥ 3 n1 ≥ 4 n1 ≥ 3 n1 ≥ 4 n1 ≥ 3 550 (2.5) 360 (1.6) 675 (3.0) 450 (2.0) 675 (3.0) 450 (2.0) Effective tensile stress area fra - 0.65 CHARACTERISTIC STRENGTH (RESISTANCE) FOR SAND-LIGHTWEIGHT AND NORMAL WEIGHT CONCRETE OVER STEEL DECK4 resistance, cracked or uncracked concrete over steel deck (2,500 psi) Fra lb (kN) Number of anchorage points Number of anchorage points Number of anchorage points n1 ≥ 4 n1 ≥ 3 n1 ≥ 4 n1 ≥ 3 n1 ≥ 4 n1 ≥ 3 550 (2.5) 360 (1.6) 675 (3.0) 450 (2.0) 675 (3.0) 450 (2.0) strength reduction factor3 fra - 0.65 1. The data in this table is intended to be used with the design provisions of this product; loads may be applied in any direction. 2. Installation must comply with published instructions and details. 3. All values offwere determined from the load combinations of IBC Section 1605.2.1, or ACI 318 Section 9.2. 4. It is assumed that the threaded rod or bolt used with the Snake+ anchor has minimum specified properties as listed in the table above or an equivalent steel element. 5. Anchors are permitted to be used in structural sand-lightweight concrete, provided the resistance value is multiplied by 0.6. Vail Fire & Emergency Services 07/10/17 www.powers.com 9 orDerInG InformatIon TECH MANUAL – MECHANiCAL ANCHors ©2015 PoWErs VoLUME 1 – 9/2015 – rEV. H Mechanical anchors Ultimate Tension Load Capacities for Snake+ in Normal-Weight Uncracked Concrete1,2,3,4 Nominal Anchor Diameter in. MinimumEmbedmentDepth in.(mm) Minimum Concrete Compressive Strength f’c = 2,500 psi (17.2 MPa) f’c = 3,000 psi (20.7 MPa) f’c = 6,000 psi (41.4 MPa) Tension lbs. (kN) Shear lbs. (kN) Tension lbs. (kN) Shear lbs. (kN) Tension lbs. (kN) Shear lbs. (kN) 1/4 1-5/8(41) 2,130 (9.5) 1,045 (4.6) 2,335 (10.4) 1,045 (4.6) - - 3/8 1-5/8 (41) 2,165 (9.7) 1,045 (4.6) 2,370 (10.6) 1,045 (4.6) 3,190 (14.2) 1,045 (4.6) 1/2 2-3/16 (55) 5,590 (24.9) 2,050 (9.1) 6,125 (27.3) 2,050 (9.1) 7,240 (32.0) 2,050 (9.1) 1. Tabulated load values are for anchors installed in concrete. Concrete compressive strength must be at the specified minimum at the time of installation. 2. Ultimate load capacities must be reduced by a minimum safety factor of 4.0 or greater to determine allowable working load. 3. The tabulated load values are applicable to single anchors in uncracked concrete installed at critical spacing distance between anchors and at critical edge distance. 4. Ultimate shear capacity is controlled by steel strength of ASTM A36 element (or equivalent). ordering inforMaTion Carbon Steel Snake+ Screw Anchor Cat. No. Anchor Size Embedment Internal Thread Depth Std. Box1 Std. Ctn. 6400sD 1/4" 1-5/8" 11/32" 100 1,000 6401sD 3/8" 1-5/8" 23/32" 50 500 6403sD 1/2" 2-1/2" 15/16" 50 300 1. Each box comes with one free setting tool Setting Tool for Snake+ Screw Anchor Cat. No. Anchor Size Std. Ctn. 6402sD 1/4" 1 6407sD 3/8" 1 6404sD 1/2" 1 Vail Fire & Emergency Services 07/10/17 Schedule 10 and Schedule 40 A company 1819 Clarkson Road Chesterfield, MO 63017 (800) 325-4467 FAX: (636) 537-2645 www.bullmoosetube.com e-mail: info@bullmoosetube.com For additional information, contact your salesperson today at (800) 325-4467 or (636) 537-2600 in the USA, or from Canada call (800) 882-4666 All information contained herein is accurate as known at the time of publication. Bull Moose Tube reserves the right to change product specifications without notice and without incurring obligation. 02/03 FM Approved and UL Listed Sprinkler Pipe Bull Moose Tube Company is a recognized producer of quality pipe products. Our Schedule 10 and Schedule 40 are FM Approved and UL Listed (for U.S. and Canada), even though these products do not require separate approvals and listings. Bull Moose Tube made the decision to have them approved and listed for your peace of mind. Our Sch. 10 and Sch. 40 have been through the same rigorous testing as our other fine pipe products. Bull Moose Tube’s Sch. 10 and Sch. 40 pipes are made to ASTM A135 and ASTM A795. These products are typically supplied with our protective coating but can be supplied without the coating so they can be hot-dip galvanized to meet FM requirements for use in dry systems in accordance with the zinc coating specifications of ASTM A795 or ASTM A53. Schedule 10 Pipe Nominal Pipe Size (in) O.D. (in) I.D. (in) Nom. Wall (in) Weight/Ft Bundle Size 1 1-1/4 1-1/2 2 2-1/2 3 4 1.315 1.660 1.900 2.375 2.875 3.500 4.500 1.097 1.442 1.682 2.157 2.635 3.260 4.260 0.109 0.109 0.109 0.109 0.120 0.120 0.120 1.40 lbs/ft 1.81 lbs/ft 2.08 lbs/ft 2.64 lbs/ft 3.53 lbs/ft 4.33 lbs/ft 5.62 lbs/ft 91 61 61 37 30 19 19 Schedule 40 Pipe Nominal Pipe Size (in) O.D. (in) I.D. (in) Nom. Wall (in) Weight/Ft Bundle Size 1 1-1/4 1-1/2 2 1.315 1.660 1.900 2.375 1.049 1.380 1.610 2.067 0.133 0.140 0.145 0.154 1.68 lbs/ft 2.27 lbs/ft 2.72 lbs/ft 3.65 lbs/ft 70 51 44 30 PIPE PREPARATION For proper operation, all pipe surfaces should be cleaned prior to installation. In order to provide a leak-tight seat for the gasket, pipe surfaces should be free from indentations and projections from the end of the pipe to the groove. All loose paint, scale, dirt, chips, grease, and rust must be removed prior to installation. Failure to take these important steps may result in improper coupling assembly, causing leakage. Also, check the manufacturer’s instructions for the specific fitting used. Vail Fire & Emergency Services 07/10/17 * Schedule 10 pipe can not be threaded or cut-grooved. Youngstown Tube Company 401 Andrews Avenue Youngstown, Ohio 44505 1-866-The-Tube www.youngstowntube.com Project: Contractor: Submitted By: Date Submitted: "Quality by the Foot" Schedule 10 Sprinkler Pipe Youngstown Tube manufactures Schedule 10 pipe in sizes 1 ¼" thru 6" using only high quality domestic steel coils. This ensures a uniform superior product for roll grooving, welding or plain end uses. Youngstown Tube's schedule 10 pipe is produced under ASTM A135/A795 Type E, Grade A, NH standards. Every piece is Eddy-Current tested and conforms to internal SPC testing and recording. Youngstown Tube Schedule 10 steel sprinkler pipe is coated with a waterbased black enamel coating, YTC Guard® antimicrobial coating and a continuous color coded white stencil, and stored indoors ready for immediate shipment. Approvals: UL Listed, CUL Listed, FM Approved Youngstown Tube schedule 10 pipe meets the rigorous testing and certification processes of Underwriters Laboratory and Factory Mutual for steel sprinkler pipe with working pressures of 300 psi or less. It also meets the requirements of NFPA 13 and can be used in wet, dry, deluge and preaction systems. Schedule 10 * Pipe Size Pipe OD Pipe ID Nominal Wall Weight per Foot Standard Length Pieces per Bundle Feet per Bundle Weight per Bundle UL Untreaded CRR 1 ¼ 1.660 1.442 .109 1.81 21 61 1,281 2,319 8.5 1 ½ 1.900 1.682 .109 2.08 21 44 924 1,921 6.8 2 2.375 2.157 .109 2.64 21 37 777 2,051 5.5 2 ½ 2.875 2.635 .120 3.53 21 37 777 2,742 4.1 3 3.500 3.260 .120 4.33 21 24 504 2,182 3.0 4 4.500 4.260 .120 5.61 21 19 399 2,238 1.8 6 6.625 6.357 .134 9.29 21 10 210 1,951 1.16 Page 1 of 1 Youngstown Tube Company Schedule 10 5/14/2010 http://www.youngstowntube.com/submit/sch10_page.html Vail Fire & Emergency Services 07/10/17 Youngstown Tube Company 401 Andrews Avenue Youngstown, Ohio 44505 1-866-The-Tube www.youngstowntube.com Project: Contractor: Submitted By: Date Submitted: "Quality by the Foot" Schedule 40 Sprinkler Pipe Youngstown Tube manufactures Schedule 40 pipe in sizes 1" thru 2" using only high quality domestic steel coils. This ensures a uniform superior product for threading, roll grooving, welding or plain end uses. Youngstown Tube's schedule 40 pipe is produced under ASTM A135/A795 Type E, Grade A, NH standards. Every piece is Eddy-Current tested and conforms to internal SPC testing and recording. Youngstown Tube Schedule 40 steel sprinkler pipe is coated with a waterbased black enamel coating, YTC Guard® antimicrobial coating and a continuous color coded red stencil, and stored indoors ready for immediate shipment. Approvals: UL Listed, CUL Listed, FM Approved Youngstown Tube schedule 40 pipe meets the rigorous testing and certification processes of Underwriters Laboratory and Factory Mutual for steel sprinkler pipe with working pressures of 300 psi or less. It also meets the requirements of NFPA 13 and can be used in wet, dry, deluge and preaction systems. Schedule 40 Pipe Size Pipe OD Pipe ID Nominal Wall Weight per Foot Standard Length Pieces per Bundle Feet per Bundle Weight per Bundle UL Threaded CRR 1 1.315 1.049 .133 1.68 21 61 1,281 2,152 1.00 1 ¼ 1.660 1.380 .140 2.27 21 61 1,281 2,907 1.00 1 ½ 1.900 1.610 .145 2.72 21 44 924 2,511 1.00 2 2.375 2.067 .154 3.65 21 37 777 2,836 1.00 Page 1 of 1 Youngstown Tube Company Schedule 40 5/14/2010 http://www.youngstowntube.com/submit/sch40_page.html Vail Fire & Emergency Services 07/10/17 Page 40 D.I. THREADED FITTINGS For fire protection services request submittal GRS 1.3 DUCTILE IRON 90 DEG. ELBOW NOMINAL ITEM MAX. WEIGHT SIZE CODE WORKING EACH (INCH) # P.S.I. A B PIECE 1 DB90033 500 1.50 1.50 0.62 1 1/4 DB90044 500 1.75 1.75 0.90 1 1/2 DB90055 500 1.94 1.94 1.20 2 DB90066 500 2.25 2.25 1.85 DIMENSIONS DUCTILE IRON STRAIGHT TEE NOMINAL ITEM MAX. WEIGHT SIZE CODE WORKING EACH (INCH) # P.S.I. A B PIECE 1 DT333 500 1.50 1.50 0.85 1 1/4 DT444 500 1.75 1.75 1.22 1 1/2 DT555 500 1.94 1.94 1.55 2 DT666 500 2.25 2.25 2.45 DIMENSIONS DUCTILE IRON RED.90 DEG. ELBOW NOMINAL ITEM MAX. WEIGHT SIZE CODE WORKING EACH (INCH) # P.S.I. A B PIECE 1X1/2 DB90031 500 1.26 1.36 0.44 1X3/4 DB90032 500 1.37 1.45 0.52 1 1/4X1/2 DB90041 500 1.34 1.53 0.64 1 1/4X3/4 DB90042 500 1.45 1.62 0.72 1 1/4X1 DB90043 500 1.58 1.67 0.75 1 1/2X1 DB90053 500 1.65 1.80 0.92 1 1/2X1 1/4 DB90054 500 1.82 1.88 1.08 2X1/2 DB90061 500 1.49 1.88 1.08 2X3/4 DB90062 500 1.60 1.97 1.24 2X1 DB90063 500 1.73 2.02 1.40 2X1 1/4 DB90064 500 1.90 2.10 1.52 2X1 1/2 DB90065 500 2.02 2.16 1.65 DIMENSIONS DUCTILE IRON COUPLING NOMINAL ITEM MAX. DIMENSION WEIGHT SIZE CODE WORKING EACH (INCH) # P.S.I. A PIECE 1 DCL033 500 1.67 0.40 1 1/4 DCL044 500 1.93 0.57 1 1/2 DCL055 500 2.15 0.75 2 DCL066 500 2.53 1.15 DUCTILE IRON RED. COUPLING NOMINAL ITEM MAX. DIMENSION WEIGHT SIZE CODE WORKING EACH (INCH) # P.S.I. A PIECE 1X1/2 DRC031 500 1.69 0.39 1X3/4 DRC032 500 1.69 0.53 DUCTILE IRON 45 DEG. ELBOW NOMINAL ITEM MAX. WEIGHT SIZE CODE WORKING EACH (INCH) # P.S.I. A B PIECE 1 DB45033 500 1.12 1.12 0.46 1 1/4 DB45044 500 1.29 1.29 0.73 1 1/2 DB45055 500 1.43 1.43 0.92 2 DB45066 500 1.68 1.68 1.50 DIMENSIONS DUCTILE IRON THREADED FITTINGS ARE UL, ULC LISTED AND FACTORY MUTUAL APPROVED FOR 500 PSI SERVICE. DUCTILE IRON PER ASTM A 536 GRADE 65-45- 12. DIMENSIONS CONFORM TO ANSI B16.3 CLASS 150. THREADS ARE NPT PER ANSI/ASME B1.20.1 NOTICE: DUCTILE IRON FITTINGS HAVE HIGHER TENSILE STRENGTH THEN THAT OF STEEL PIPE. THEREFORE, OVER TIGHTENING CAN CAUSE DAMAGE TO PIPE THREADS WHICH MAY CAUSE LEAKAGE. DUCTILE IRON FITTINGS SHOULD BE TIGHTENED THREE TURNS BEYOND HAND TIGHT, BUT NO MORE THAN FOUR TURNS. A Vail Fire & Emergency Services 07/10/17 Page 41 DUCTILE IRON REDUCING TEE NOMINAL ITEM MAX. WEIGHT SIZE CODE WORKING EACH (INCH) # P.S.I. A B C PIECE 1X1X1/2 DT331 500 1.26 1.26 1.36 0.64 1X1X3/4 DT332 500 1.37 1.37 1.45 0.73 1X1/2X1 DT313 500 1.50 1.36 1.50 0.71 1X3/4X1 DT323 500 1.50 1.45 1.50 0.76 1X1X1 1/4 DT334 500 1.67 1.67 1.58 0.98 1X1X1 1/2 DT335 500 1.80 1.80 1.65 1.16 1 1/4X1X1/2 DT431 500 1.34 1.26 1.53 0.82 1 1/4X1X3/4 DT432 500 1.45 1.37 1.62 0.90 1 1/4X1X1 DT433 500 1.58 1.50 1.67 1.00 1 1/4X1X1 1/4 DT434 500 1.75 1.67 1.75 1.08 1 1/4X1X1 1/2 DT435 500 1.88 1.80 1.82 1.42 1 1/4X1 1/4X1/2 DT441 500 1.34 1.34 1.53 0.86 1 1/4X1 1/4X3/4 DT442 500 1.45 1.45 1.62 0.92 1 1/4X1 1/4X1 DT443 500 1.58 1.58 1.67 0.95 1 1/4X1 1/4X1 1/2 DT445 500 1.88 1.88 1.82 1.45 1 1/4X1 1/4X2 DT446 500 2.10 2.10 1.90 1.75 1 1/2X1X1/2 DT531 500 1.41 1.34 1.66 0.95 1 1/2X1X3/4 DT532 500 1.52 1.37 1.75 1.14 1 1/2X1X1 DT533 500 1.65 1.50 1.80 1.17 1 1/2X1X1 1/4 DT534 500 1.82 1.67 1.88 1.34 1 1/2X1X1 1/2 DT535 500 1.94 1.80 1.94 1.45 1 1/2X1 1/4X1/2 DT541 500 1.41 1.34 1.66 1.05 1 1/2X1 1/4X3/4 DT542 500 1.52 1.45 1.75 1.15 1 1/2X1 1/4X1 DT543 500 1.65 1.58 1.80 1.25 1 1/2X1 1/4X2 DT546 500 2.16 2.10 2.02 1.90 1 1/2X1 1/2X1/2 DT551 500 1.41 1.41 1.16 1.15 1 1/2X1 1/2X3/4 DT552 500 1.52 1.52 1.75 1.24 1 1/2X1 1/2X1 DT553 500 1.65 1.65 1.80 1.30 1 1/2X1 1/2X1 1/4 DT554 500 1.82 1.82 1.88 1.48 1 1/2X1 1/2X2 DT556 500 2.16 2.16 2.02 1.98 2X1X2 DT636 500 2.25 2.02 2.25 2.15 2X1 1/4X2 DT646 500 2.25 2.10 2.25 2.30 2X1 1/2X1/2 DT651 500 1.49 1.41 1.88 1.50 2X1 1/2X3/4 DT652 500 1.60 1.52 1.97 1.62 2X1 1/2X1 DT653 500 1.73 1.65 2.02 1.64 2X1 1/2X1 1/4 DT654 500 1.90 1.82 2.10 1.80 2X1 1/2X1 1/2 DT655 500 2.02 1.94 2.16 2.00 2X1 1/2X2 DT656 500 2.25 2.16 2.25 2.35 2X2X1/2 DT661 500 1.49 1.49 1.88 1.60 2X2X3/4 DT662 500 1.60 1.60 1.97 1.68 2X2X1 DT663 500 1.73 1.73 2.02 1.85 2X2X1 1/4 DT664 500 1.90 1.90 2.10 2.04 2X2X1 1/2 DT665 500 2.02 2.02 2.16 2.18 2X2X2 1/2 DT556 500 2.60 2.60 2.39 3.61 2 1/2X2X3/4 DT762 500 1.74 1.60 2.32 2.28 DIMENSIONS DUCTILE IRON CAP NOMINAL ITEM MAX. DIMENSION WEIGHT SIZE CODE WORKING EACH (INCH) # P.S.I. A PIECE 1 DCP003 500 1.16 0.32 1 1/4 DCP004 500 1.28 0.43 1 1/2 DCP005 500 1.33 0.60 2 DCP006 500 1.45 0.91 DUCTILE IRON CROSS NOMINAL ITEM MAX. WEIGHT SIZE CODE WORKING EACH (INCH) # P.S.I A B PIECE 1 DX033 500 1.50 1.50 0.98 1 1/4 DX044 500 1.75 1.75 1.50 1 1/2 DX055 500 1.94 1.94 1.90 2 DX066 500 2.25 2.25 2.95 1 1/4X1 DX043 500 1.58 1.67 1.27 1 1/2X1 DX053 500 1.65 1.80 1.48 2X1 DX063 500 1.73 2.02 2.10 DIMENSIONS DT667 DUCTILE IRON BUSHINGS NOMINAL ITEM SIZE CODE (INCH) # DIMENSIONS 1x1/2 DBUSH31 0.75 0.25 1.42 OUT 1x3/4 DBUSH32 0.75 0.25 1.42 OUT 1 1/4x1 DBUSH43 0.80 0.28 1.76 OUT 1 1/2x1 DBUSH53 0.83 0.31 2.00 OUT 1 1/2x1 1/4 DBUSH54 0.83 0.31 2.00 OUT 2x1 DBUSH63 0.88 0.41 1.95 IN 2x1 1/4 DBUSH64 0.88 0.34 2.48 OUT 2x1 1/2 DBUSH65 0.88 0.34 2.48 OUT 0.22 0.17 0.28 0.44 0.30 0.66 0.72 0.61 DIMENSIONS A B C STYLE WT. EACH D.I. THREADED FITTINGS For fire protection services request submittal GRS 1.3 OUTSIDE HEAD INSIDE HEAD Vail Fire & Emergency Services 07/10/17 FireLock® Style 005 rigid coupling has a unique, patented angle-pad design which allows the housings to offset while clamping the grooves. By permitting the housings to slide on the angled bolt pads, rigidity is obtained. Support and hanging requirements correspond to NFPA 13 Sprinkler Systems. Angle-pad design permits assembly by removing one nut/bolt and swinging the housing over the gasket. This reduces components to handle during assembly. Style 005 FireLock coupling are designed and recommended for use ONLY on fire protection systems. Vic-Plus™ Gasket System: In North America, Victaulic® offers a gasket system which requires no field lubrication on wet pipe systems that are hydrostatically tested. The Vic-Plus™ System (patented) is dry, clean, and non-toxic. It reduces assembly time substantially and eliminates the mess and chance of over- lubrication. Please refer to the latest copy of the Victaulic Field Installation Handbook (I-100) for supplemental lubrication requirements and dry pipe fire protection system notes. LISTING/APPROVALS The information provided below is based on the latest listing and approval data at the time of publication. Listings/Approvals are subject to change and/or additions by the approvals agencies. Contact Victaulic for performance on other pipe and the latest listings and approvals. Related Working Pressure – psi Related Working Pressure – psi Related Working Pressure – psi PipeSch. Size Inches UL ULC FM PipeSch. Size Inches UL ULC FM PipeSch. Size Inches UL ULC FM 5 1 ¼ – 3 175 175 175 EL 1 ¼ – 2 300 N/A N/A MT 1 ¼ – 2 300 N/A N/A 10, 40 1 ¼ – 4 350 350 350 ET 1 ¼ – 2 300 N/A N/A STF 1 ¼ – 4 N/A N/A 300 5 – 8 300 300 300 EZ 4 – 6 300# N/A 300 Steady Thd. 1 ¼ – 2 N/A N/A 300 BLT 1 ¼ – 2 300 300 N/A FF 1 ¼ – 4 N/A N/A 300 TF 3 – 8 N/A N/A 300 DF 1 ¼ – 4 300 300 300 GAL - 7 1 ¼ – 2 300 N/A N/A WLS 1 ¼ – 2 300 300 N/A DT 1 ¼ – 2 300 300 N/A MLT 1 ¼ – 2 300 N/A N/A XL 1 ¼ – 3 300 300 300 EF 1 1⁄ – 4 175@ N/A 175 MF 1 ¼ – 4 300 N/A 300* * FM approved for service in 1 ½ – 4" pipe. # UL Listed for service up to 4" pipe only. @ UL Listed for service up to 3" only. 10.02_1 FireLock® Rigid Coupling STYLE 005 WITH VIC-PLUS™ GASKET SYSTEM (NORTH AMERICA ONLY) 10.02 IPS CARBON STEEL PIPE - FIRE PROTECTION PRODUCTS JOB/OWNER CONTRACTOR ENGINEER System No. __________________________ Submitted By ________________________ Spec Sect ____________ Para__________ Location ____________________________ Date ________________________________ Approved ___________________________ Date________________________________ www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2006 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA. REV_I SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS § LPC and VdS Approved,see notes on page 4 PATENTED Exaggerated for clarity Vail Fire & Emergency Services 07/10/17 DIMENSIONS Size Max. Work Pressure § * Max. EndLoad * Allow. PipeEnd Sep. † Bolt/Nut@ No – Size Dimensions – Inches/mm Approx.Wgt. Each Nominal Size Inches/mm Actual Outside Diameter Inches/mm PSI kPa Lbs. N Inchesmm Inches Lbs. kg 1 ¼ 1.660 350 755 0.05 2 – 3⁄8 x 2 ¼ 2.75 4.50 1.88 1.2 32 42.4 2413 3370 1.2 70 114 148 0.5 1 ½ 1.900 350 990 0.05 2 – 3⁄8 x 2 ¼ 3.00 4.75 1.88 1.2 40 48.3 2413 4415 1.2 76 121 148 0.5 2 – 3⁄8 x 2 ½ 3.50 5.25 1.88 1.6 50 60.3 2413 6900 1.7 89 133 148 0.7 2 ½ 2.875 350 2270 0.07 2 – 3⁄8 x 2 ½ 4.00 5.75 1.88 1.9 65 73.0 2413 10110 1.7 102 146 148 .09 76.1 mm 3.000 350 2475 0.07 2 – 3⁄8 x 2 ½ 4.13 5.75 1.88 1.9 76.1 2413 11010 1.7 105 146 148 0.9 2 – 3⁄8 x 2 ½ 4.63 6.13 1.88 2.1 80 88.9 2413 14985 1.7 118 156 148 1.0 2 – 3⁄8 x 2 ½ 5.75 7.25 2.13 3.1 100 114.3 2413 24770 4.1 146 184 54 1.4 108.0 mm 4.250 300 4255 0.16 2 – 3⁄8 x 2 ½ 5.63 7.25 2.13 3.1 108.0 2068 18940 4.1 143 184 54 1.4 2 – ½ x 3 6.88 9.00 2.13 4.5 125 141.3 2068 32445 4.1 175 229 54 2.0 133.0 mm 5.250 300 6495 0.16 2 – ½ x 2 ¾ 6.63 9.00 2.13 4.5 133.0 2068 28900 4.1 168 229 54 2.0 139.7 mm 5.500 300 7125 0.16 2 – ½ x 2 ¾ 6.88 9.00 2.13 4.8 139.7 2068 31715 4.1 175 229 54 2.2 2 – ½ x 3 8.00 10.00 2.13 5.0 150 168.3 2068 46020 4.1 203 254 53 2.3 159.0 mm 6.250 300 9200 0.16 2 – ½ x 2 ¾ 7.63 10.00 2.13 5.5 159.0 2068 40955 4.1 194 254 54 2.5 165.1 mm 6.500 300 9955 0.16 2 – ½ x 3 8.15 10.00 2.13 5.5 165.1 2068 44295 4.1 207 254 54 2.5 8 8.625 300 17525 0.19 2 – 5⁄8 x 4 ¼ 10.50 13.14 2.63 11.3 200 219.1 2068 78000 4.8 267 334 67 5.1 * Working Pressure and End Load are total, from all internal and external loads, based on standard weight (ANSI) steel pipe, standard roll or cut grooved in accordance with Victaulic specifications. Contact Victaulic for perfor- mance on other pipe. WARNING: FOR ONE TIME FIELD TEST ONLY, the Maximum Joint Working Pressure may be increased to 1 1/2 times the figures shown. † The allowable pipe separation dimension shown is for system layout purposes only. Style 005 couplings are con- sidered rigid connections and will not accommodate expansion or contraction of the piping system. @ Number of bolts required equals number of housing segments. Metric thread size bolts are available (color coded gold) for all coupling sizes upon request. Contact Victaulic for details. § Style 005 couplings are VdS and LPC Approved to 12 Bar/175 psi. Rated for wet and dry sprinkler systems at 350 psi/2413 kPa for 1 ¼ – 4"/32 – 100 mm sizes and 300 psi /2068 kPa for 4 ¼ – 8"/108 – 200 mm sizes; Schedule 10 roll grooved or Schedule 40 cut or roll grooved steel pipe. Style 005 is rigid and does not accommodate expansion, contraction or angular deflection. X Z Y 10.02_2 FireLock® Rigid Coupling STYLE 005 WITH VIC-PLUS™ GASKET SYSTEM (NORTH AMERICA ONLY) 10.02 IPS CARBON STEEL PIPE - FIRE PROTECTION PRODUCTS www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2006 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA. REV_I Vail Fire & Emergency Services 07/10/17 MATERIAL SPECIFICATIONS Housing: Ductile iron conforming to ASTM A-536, grade 65-45-12. Ductile iron conforming to ASTM A-395, grade 65-45-15, is available upon special request. Housing Coating: Orange enamel (North America); red enamel (Europe) • Optional: Hot dipped galvanized Gasket: • Grade “E” EPDM – Type A Vic-Plus™ Gasket System Δ (Violet color code). FireLock products have been Listed by Underwriters Laboratories Inc. and Approved by Factory Mutual Research for wet and dry (oil free air) sprinkler services up to the rated working pressure using the Grade “E” Type A Vic-Plus™ Gasket System, requiring no field lubrication for most installation conditions. • Grade “L” Silicone Recommended for dry heat, air without hydrocarbons to +350°F and certain chemical services. For dry services, Victaulic continues to recommend the use of Grade “E” Type A FlushSeal® Gasket. Contact Victaulic for details. Bolts/Nuts: Heat-treated plated carbon steel, trackhead meeting the physical and chemical requirements of ASTM A-449 and physical requirements of ASTM A-183. Δ Standard gasket and FlushSeal gasket approved for dry pipe systems to –40°F/–40°C. Based on “typical” pipe surface conditions, supplemental lubricant is recommended for services installed below 0°F/–18°C and for all dry pipe systems or systems to be subjected to air tests prior to being filled with water. Supplemental lubrication may also be required on pipe with raised or undercut weld seams or pipe that has voids and/or cracks at the weld seams. Victaulic continues to recommend the use of FlushSeal gaskets for dry services. 10.60_3 FireLock® Rigid Coupling STYLE 005 WITH VIC-PLUS™ GASKET SYSTEM (NORTH AMERICA ONLY) 10.02 IPS CARBON STEEL PIPE - FIRE PROTECTION PRODUCTS www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2006 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA. REV_I Vail Fire & Emergency Services 07/10/17 WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details. This product shall be manufactured by Victaulic or to Victaulic specifications. All products to be installed in accordance with current Victaulic installation/assembly instructions. Victaulic reserves the right to change product specifications, designs and standard equipment without notice and without incurring obligations. NOTE WARNING: Depressurize and drain the piping system before attempting to install, remove, or adjust any Victaulic piping products. GENERAL NOTES INSTALLATION Reference should always be made to the I-100 Victaulic Field Installation Handbook for the product you are installing. Handbooks are included with each shipment of Victaulic products for complete installation and assembly data, and are available in PDF format on our website at www.victaulic.com. 10.02 FireLock® Rigid Coupling STYLE 005 WITH VIC-PLUS™ GASKET SYSTEM (NORTH AMERICA ONLY) 10.02 IPS CARBON STEEL PIPE - FIRE PROTECTION PRODUCTS For complete contact information, visit www.victaulic.com 10.02 1538 REV I UPDATED 9/2006 VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2006 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA. WCAS-697KR4 Vail Fire & Emergency Services 07/10/17 FireLock® products comprise a unique system specifically designed for fire protection services. FireLock full-flow elbows and tees are a CAD-developed, hydrodynamic design that has a shorter center-to-end dimension than standard fittings. A noticeable bulge allows the water to make a smoother turn to maintain similar flow characteristics as standard full flow fittings. FireLock fittings are designed for use exclusively with Style 005 and Style 009 FireLock couplings. Use of other couplings or flange adapters may result in bolt pad interference. Victaulic FireLock fittings pressure ratings conform to the ratings of Victaulic FireLock Style 005 couplings. Fitting: Ductile iron conforming to ASTM A-536, grade 65-45-12. Fitting Coating: Orange enamel. • Optional: Hot dipped galvanized. MATERIAL SPECIFICATIONS 10.03_1 FireLock® Fittings 10.03 IPS CARBON STEEL PIPE – FIRE PROTECTION PRODUCTS JOB/OWNER CONTRACTOR ENGINEER System No. __________________________ Submitted By ________________________ Spec Sect ____________ Para__________ Location ____________________________ Date________________________________ Approved ___________________________ Date________________________________ www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2009 VICTAULIC COMPANY. ALL RIGHTS RESERVED. REV_H See Victaulic publication 10.01 for details VNIIPO Vail Fire & Emergency Services 07/10/17 DIMENSIONS C to E C to E NO. 001 C to E NO. 003 C to E C to E NO. 002 T NO. 006 Size No. 001 90° Elbow No. 003 45° Elbow No. 002 Straight Tee No. 006 Cap Nominal Size Inches mm ActualOutside Diameter Inches mm C to E Inches mm Approx. Weight Each Lbs. kg C to E Inches mm Approx. Weight Each Lbs. kg C to E Inches mm Approx. Weight Each Lbs. kg Thickness “T” Inches mm Approx. Weight Each Lbs. kg 1 1 1.660 — — — — — — 0.8 0.3 32 42.4 21 0.1 1 1 1.900 — — — — — — 0.82 0.4 40 48.3 — — — — — — 21 0.2 2 2.375 2.75 1.7 2.00 1.8 2.75 2.4 0.88 0.6 50 60.3 70 0.8 51 0.8 70 1.1 22 0.3 2 1 2.875 3.00 3.1 2.25 2.2 3.00 3.6 0.88 1.0 65 73.0 76 1.4 57 1.0 76 1.6 22 0.5 76.1 mm 3.000 3.00 3.30 2.25 2.4 — — — — 76.1 76 1.5 57 1.1 3 3.500 3.38 4.0 2.50 3.1 3.38 5.3 0.88 1.2 80 88.9 86 1.8 64 1.4 86 2.4 22 0.5 108 mm 4.250 4.00 5.7 3.00 5.1 4.00 7.5 — — 108.0 102 2.6 76 2.3 102 3.4 4 4.500 4.00 6.7 3.00 5.6 4.00 8.7 1.00 2.4 100 114.3 102 3.0 76 2.5 102 3.9 25 1.1 5 5.563 4.88 12.6 3.25 8.3 4.88 15.7 1.00 4.1 125 141.3 124 5.7 83 3.8 124 7.1 25 1.9 159 mm 6.250 5.50 12.6 3.50 9.2 5.50 17.9 — — 158.8 140 5.7 89 4.2 140 8.0 6 6.625 5.50 18.3 3.50 11.7 5.50 22.7 1.00 5.9 150 168.3 140 8.3 89 5.3 140 10.3 25 2.7 8 8.625 6.81 25.5 4.25 20.4 6.94 38.7 1.13 12.7 200 219.1 173 11.6 108 9.3 176 17.6 29 5.8 10.03_2 FireLock® Fittings 10.03 IPS CARBON STEEL PIPE – FIRE PROTECTION PRODUCTS www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2009 VICTAULIC COMPANY. ALL RIGHTS RESERVED. REV_H Vail Fire & Emergency Services 07/10/17 FLOW DATA Size Frictional Resistance Equivalent Feet/meters of Straight Pipe † Nominal Size Inches mm Actual Outside Diameter Inches mm Elbows No. 002 Straight Tee No. 00190° Elbow No. 00345° Elbow Branch Run 1 1 1.660 1.5 0.8 3.7 1.5 32 42.4 0.5 0.2 1.1 0.5 1 1 1.900 2.2 1.1 5.5 2.2 40 48.3 0.7 0.3 1.7 0.7 2 2.375 3.5 1.8 8.5 3.5 50 60.3 1.1 0.5 2.6 1.1 2 1 2.875 4.3 2.2 10.8 4.3 65 73.0 1.3 0.7 3.3 1.3 76.1 mm 3.000 4.5 2.3 11.0 4.5 76.1 1.4 0.7 3.4 1.4 3 3.500 5.0 2.6 13.0 5.0 80 88.9 1.5 0.8 4.0 1.5 108 mm 4.250 6.4 3.2 15.3 6.4 108.0 2.0 0.9 4.7 2.0 4 4.500 6.8 3.4 16.0 6.8 100 114.3 2.1 1.0 4.9 2.1 5 5.563 8.5 4.2 21.0 8.5 125 141.3 2.6 1.3 6.4 2.6 159 mm 6.250 9.4 4.9 25.0 9.6 158.8 2.9 1.5 7.6 2.9 6 6.625 10.0 5.0 25.0 10.0 150 168.3 3.0 1.5 7.6 3.0 8 8.625 13.0 5.0 33.0 13.0 200 219.1 4.0 1.5 10.1 4.0 † The flow data listed is based upon the pressure drop of Schedule 40 pipe. 10.03_3 FireLock® Fittings 10.03 IPS CARBON STEEL PIPE – FIRE PROTECTION PRODUCTS www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2009 VICTAULIC COMPANY. ALL RIGHTS RESERVED. REV_H Vail Fire & Emergency Services 07/10/17 500 Series Mechanical Tee, Threaded 6 Size Hole Diameter Max Working Dimensions Run x Branch +1/8, -0 / +3.2, -0 Pressure A B C Weight Packaging Part Number IN / mm IN / mm PSI / bar IN / mm IN / mm IN / mm LB / KG Master Bulk 65MT3020004 2 x 1/2 1-1/2 500 2.52 4.96 2.80 3.1 21 _ 50 x 15 38 35 64.0 126.0 71.0 1.4 65MT3020006 2 x 3/4 1-1/2 500 2.52 4.96 2.80 3.1 21 – 50 x 20 38 35 64.0 126.0 71.0 1.4 65MT3020010 2 x 1 1-1/2 500 2.52 4.96 2.80 3.0 21 – 50 x 25 38 35 64.0 126.0 71.0 1.4 65MT3020012 2 x 1-1/4 1-3/4 500 2.76 4.96 2.80 3.5 18 – 50 x 32 45 35 70.0 126.0 71.0 1.6 65MT3020014 2 x 1-1/2 1-3/4 500 2.76 4.96 2.87 3.6 18 – 50 x 40 45 35 70.0 126.0 73.0 1.6 65MT3024004 2-1/2 x 1/2 1-1/2 500 2.76 5.20 2.80 3.0 18 – 65 x 15 38 35 70.0 132.0 71.0 1.4 65MT3024006 2-1/2 x 3/4 1-1/2 500 2.76 5.20 2.80 3.0 18 – 65 x 20 38 35 70.0 132.0 71.0 1.4 65MT3024010 2-1/2 x 1 1-1/2 500 2.76 5.20 2.80 3.0 18 – 65 x 25 38 35 70.0 132.0 71.0 1.4 65MT3024012 2-1/2 x 1-1/4 1-3/4 500 2.99 5.20 3.03 3.5 16 – 65 x 32 45 35 76.0 132.0 77.0 1.6 65MT3024014 2-1/2 x 1-1/2 2 500 2.99 5.20 3.27 3.6 16 – 65 x 40 51 35 76.0 132.0 83.0 1.6 65MT3030010 3 x 1 1-1/2 500 3.07 5.91 2.80 3.3 14 – 80 x 25 38 35 78.0 150.0 71.0 1.5 65MT3030012 3 x 1-1/4 1-3/4 500 3.27 5.91 3.03 3.8 14 – 80 x 32 45 35 83.0 150.0 77.0 1.7 65MT3030014 3 x 1-1/2 2 500 3.50 5.91 3.27 4.1 14 – 80 x 40 51 35 89.0 150.0 83.0 1.9 65MT3030020 3 x 2 2-1/2 500 3.50 5.91 3.78 4.9 10 – 80 x 50 64 35 89.0 150.0 96.0 2.2 65MT3040010 4 x 1 1-1/2 500 3.54 7.09 2.80 3.6 22 – 100 x 25 38 35 90.0 180.0 71.0 1.6 65MT3040012 4 x 1-1/4 1-3/4 500 3.78 7.09 3.03 4.0 22 – 100 x 32 45 35 96.0 180.0 77.0 1.8 65MT3040014 4 x 1-1/2 2 500 4.02 7.09 3.27 4.2 22 – 100 x 40 51 35 102.0 180.0 83.0 1.9 " 4" x 3" 65MT ! # SMITH COOPER INTERNATIONAL • TOLL FREE 1-800-766-0076 • FAX (323) 890-4456 • www.smithcooper.com ® ® NOTES: 1. All bolts and gaskets identified by SCI logo. 2. 100% Magnetic particle inspection of each bolt. Each bolt has a minimum tensile strength of 110,000 psi. 3. Gaskets are pre-lubricated. 4. Gasket Grade E EPDM (green stripe): • Temperature range: -30˚F (-34˚C) to +230˚F (+110˚C). 5. Gasket Grade T Nitrile (orange stripe) available: • Temperature range: -20˚F (-29˚C) to +180˚F (+82˚C). 6. See Installation Instructions on Page 17. 7. Smith Cooper Warranty (see page 16) only applies to assemblies made up using gaskets, housings, and bolts with the logo. Fig. 65MT – Mechanical Tee, Threaded Vail Fire & Emergency Services 07/10/17 9 500 Series Threaded Strap Tee Size Hole Diameter Max Working Dimensions Run x Branch +1/8, -0 / +3.2, -0 Pressure A B C Weight Packaging Part Number IN / mm IN / mm PSI / bar IN / mm IN / mm IN / mm LB / KG Master Bulk 65MU3012004 1-1/4 x 1/2 1-1/4 300 1.65 3.54 2.28 3.1 50 – 32 x 15 32 20.7 42.0 90.0 58.0 1.4 65MU3012006 1-1/4 x 3/4 1-1/4 300 1.85 3.54 2.28 3.1 50 – 32 x 20 32 20.7 47.0 90.0 58.0 1.4 65MU3012010 1-1/4 x 1 1-1/4 300 2.13 3.54 2.28 3.0 50 – 32 x 25 32 20.7 54.0 90.0 58.0 1.4 65MU3014004 1-1/2 x 1/2 1-1/4 300 1.77 3.54 2.28 3.1 48 – 40 x 15 32 20.7 45.0 90.0 58.0 1.4 65MU3014006 1-1/2 x 3/4 1-1/4 300 1.97 3.54 2.28 3.1 48 – 40 x 20 32 20.7 50.0 90.0 58.0 1.4 65MU3014010 1-1/2 x 1 1-1/4 300 2.24 3.54 2.28 3.0 48 – 40 x 25 32 20.7 57.0 90.0 58.0 1.4 65MU3020004 2 x 1/2 1-1/4 300 2.01 3.74 2.28 3.1 45 – 50 x 15 32 20.7 51.0 95.0 58.0 1.4 65MU3020006 2 x 3/4 1-1/4 300 2.20 3.74 2.28 3.1 45 – 50 x 20 32 20.7 56.0 95.0 58.0 1.4 65MU3020010 2 x 1 1-1/4 300 2.48 3.74 2.28 3.0 45 – 50 x 25 32 20.7 63.0 95.0 58.0 1.4 65MU3024004 2-1/2 x 1/2 1-1/4 300 2.26 4.29 2.28 3.0 36 – 65 x 15 32 20.7 57.5 109.0 58.0 1.4 65MU3024006 2-1/2 x 3/4 1-1/4 300 2.46 4.29 2.28 3.0 36 – 65 x 20 32 20.7 62.5 109.0 58.0 1.4 65MU3024010 2-1/2 x 1 1-1/4 300 2.74 4.29 2.28 3.0 36 – 65 x 25 32 20.7 69.5 109.0 58.0 1.4 " 65MU ! # SMITH COOPER INTERNATIONAL • TOLL FREE 1-800-766-0076 • FAX (323) 890-4456 • www.smithcooper.com ® NOTES: 1. All bolts and gaskets identified by SCI logo. 2. 100% Magnetic particle inspection of each bolt. Each bolt has a minimum tensile strength of 110,000 psi. 3. Gaskets are pre-lubricated. 4. Gasket Grade E EPDM (green stripe): • Temperature range: -30˚F (-34˚C) to +230˚F (+110˚C). 5. Gasket Grade T Nitrile (orange stripe) available: • Temperature range: -20˚F (-29˚C) to +180˚F (+82˚C). 6. See Installation Instructions on Page 17. 7. Smith Cooper Warranty (see page 16) only applies to assemblies made up using gaskets, housings, and bolts with the logo. ® Fig. 65MU – Strap Tee, Threaded Vail Fire & Emergency Services 07/10/17 The Style 750 Reducing Coupling permits direct reduction on the piping run. Designed to replace two couplings and a reducing fitting, the Style 750 features a special reducing gasket for pressure responsive sealing. A steel washer which prevents telescoping of the smaller pipe inside the larger pipe during vertical systems assembly is available upon request. Housing: Ductile iron conforming to ASTM A-536, grade 65-45-12. Ductile iron conforming to ASTM A-395, grade 65-45-15, is available upon special request. Housing Coating: Orange enamel • Optional: Hot dipped galvanized and others Gasket: (Specify choice*): • Grade “E” EPDM (All other sizes) EPDM (Green color code). Temperature range –30°F to +230°F/–34°C to +110°C. Recommended for cold and hot water service within the specified temperature range plus a variety of dilute acids, oil-free air and many chemical services. UL classified in accordance with ANSI/NSF 61 for cold +86°F/+30°C and hot +180°F/+82°C potable water service. NOT RECOMMENDED FOR PETROLEUM SERVICES. • Grade “T” nitrile Nitrile (Orange color code). Temperature range –20°F to +180°F/–29°C to +82°C. Recommended for petroleum products, air with oil vapors, vegetable and mineral oils within the specified temperature range. Not recommended for hot water services over +150°F/+66°C or for hot dry air over +140°F/+60°C. * Services listed are General Service Recommendations only. It should be noted that there are services for which these gaskets are not recommended. Reference should always be made to the latest Victaulic Gasket Selection Guide for specific gasket service recommendations and for a listing of services which are not recommended. • Optional: Assembly Washer: Galvanized, carbon steel Bolts/Nuts: Heat-treated plated carbon steel, trackhead meeting the physical and chemical requirements of ASTM A-449 and physical requirements of ASTM A-183. MATERIAL SPECIFICATIONS 06.08_1 Reducing Coupling STYLE 750 06.08 CARBON STEEL PIPE – GROOVED COUPLINGS JOB/OWNER CONTRACTOR ENGINEER System No. __________________________ Submitted By ________________________ Spec Sect ____________ Para__________ Location ____________________________ Date________________________________ Approved ___________________________ Date________________________________ www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2007 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA. REV_I Exaggerated for clarity SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS VNIIPO Vail Fire & Emergency Services 07/10/17 DIMENSIONS X Z Y X Z Y Size Max. Work Pressure * Max. End Load * Allow. Pipe End Sep. † Deflect. Fr. CL† Bolt/Nut@ No - Size Dimensions – Inches/mm Approx. Wgt. Each Nominal Size Inches/mm psi kPa Lbs. N Inches/ mm PerCplg. Deg. PipeIn./Ft. mm/m Inches X Y Z Lbs. kg 2 × 1 350 500 0 – 0.07 0˚ – 57' 0.20 2 – 3/8 x 2 3.38 5.28 1.88 2.7 50 25 2410 2225 0 – 1.8 17 85 134 48 1.2 1 1 350 1000 0 – 0.07 0˚ – 57' 0.20 2 – 3/8 x 2 3.38 5.28 1.88 2.0 40 2410 4450 0 – 1.8 17 85 134 48 1.0 2 1 × 2 500 2215 0 – 0.07 0˚ – 47' 0.16 2 – 3/8 x 2 4.00 5.93 1.88 3.1 65 50 3450 9850 0 – 1.8 14 102 151 48 1.4 76.1 mm × 2 350 1550 0 – 0.07 0˚ – 47' 0.16 2 – 1 x 2 3 4.38 6.63 1.88 4.6 50 2410 6900 0 – 1.8 14 111 168 48 2.1 3 × 2 350 1550 0 – 0.07 0˚ – 39' 0.13 2 – 1 x 2 3 4.75 7.13 1.88 4.9 80 50 2410 6900 0 – 1.8 11 121 181 48 2.2 2 1 500 3250 0 – 0.07 0˚ – 39' 0.13 2 – 1 x 2 3 4.75 7.13 1.88 4.3 65 3450 14460 0 – 1.8 11 121 181 48 2.0 88.9 mm × 76.1 mm 350 2275 0 – 0.07 0˚ – 39' 0.13 2 – 1 x 2 3 4.75 7.13 1.88 4.2 2410 10125 0 – 1.8 11 121 181 48 1.9 4 × 2 350 1550 0 – 0.13 1˚ – 19' 0.28 2 – 5/8 x 3 1 6.25 8.90 2.25 8.1 100 50 2410 6900 0 – 3.2 25 159 226 57 3.7 2 1 350 2275 0 – 0.13 1˚ – 19' 0.28 2 – 5/8 x 3 1 6.25 8.90 2.25 8.6 65 2410 10125 0 – 3.2 25 159 226 57 3.9 3 500 4810 0 – 0.13 1˚ – 19' 0.28 2 – 5/8 x 3 1 6.00 8.90 2.25 6.7 80 3450 21400 0 – 3.2 25 152 226 57 3.0 114.3 mm × 76.1 mm 350 2475 0 – 0.13 1˚ – 19' 0.28 2 – 5/8 x 3 1 6.25 8.90 2.25 6.9 2410 11014 0 – 3.2 25 159 226 57 3.1 5 × 4 350 5565 0 – 0.13 1˚ – 3' 0.22 2 – 3 x 4 1 7.18 10.70 2.13 11.2 125 100 2410 24765 0 – 3.2 19 182 272 54 5.1 6 × 4 350 5565 0 – 0.13 0˚ – 52' 0.18 2 – 3 x 4 1 8.63 11.90 2.25 16.7 150 100 2410 24765 0 – 3.2 15 181 302 57 7.6 5 350 8500 0 – 0.13 0˚ – 52' 0.18 2 – 3 x 4 1 8.31 11.90 2.25 12.9 125 2410 37825 0 – 3.2 15 211 302 57 5.9 165.1 mm × 4 350 5565 0 – 0.13 0˚ – 55' 0.19 2 – 3 x 4 1 8.63 11.90 2.25 15.2 100 2410 24765 0 – 3.2 16 219 302 57 6.9 8 × 6 350 12000 0 – 0.13 0˚ – 38' 0.13 2 – 7/8 x 5 10.81 14.88 2.50 22.4 200 150 2410 53400 0 – 3.2 11 275 378 64 10.2 219.1 mm × 165.1 mm 350 1625 0 – 0.13 0˚ – 38' 0.13 2 – 7/8 x 5 10.75 14.88 2.50 23.2 2410 0 – 3.2 11 273 378 64 10.5 10 × 8 350 20450 0 – 0.13 0° – 25' 0.9 2 – 1 x 5 1 13.12 17.26 2.62 31.4 273 219.1 2410 0 – 3.2 8 333 438 67 14.2 Style 750 Reducing couplings should not be used with end caps (#60) in systems where a vacuum may be developed. Contact Victaulic for details. * Working Pressure and End Load are total, from all internal and external loads, based on standard weight (ANSI) steel pipe, standard roll or cut grooved in accordance with Victaulic specifications. Contact Victaulic for performance on other pipe. Maximum working pressure rating based on larger pipe size. Maximum End Load rating based on smaller pipe size. WARNING: FOR ONE TIME FIELD TEST ONLY, the Maximum Joint Working Pressure may be increased to 1 1 times the figures shown. † Allowable Pipe End Separation and Deflection figures show the maximum nominal range of movement available at each joint for standard roll grooved pipe. Figures for standard cut grooved pipe may be doubled. These figures are maximums; for design and installation purposes these figures should be reduced by: 50% for 3 – 3 1"/20 – 90 mm; 25% for 4"/100 mm and larger. @ Number of bolts required equals number of housing segments. Metric thread size bolts are available (color coded gold) for all coupling sizes upon request. Contact Victaulic for details. WARNING: Depressurize and drain the piping system before attempting to install, remove, or adjust any Victaulic piping products. 06.08_2 Reducing Coupling STYLE 750 06.08 CARBON STEEL PIPE – GROOVED COUPLINGS www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2007 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA. REV_I Vail Fire & Emergency Services 07/10/17 FLOW DATA Size Equiv. Pipe Length Nominal Size Inches/mm Sm. Dia. Feet/m 2 × 1 5.9 50 25 1.8 1 1 2.0 40 0.6 2 1 × 2 1.9 65 50 0.6 76.1 mm × 2 1.9 50 0.6 3 × 2 5.5 80 50 1.7 2 1 3.8 65 1.2 88.9 mm × 76.1 mm 3.8 1.2 4 × 2 6.0 100 50 1.8 2 1 6.0 65 1.8 3 6.0 80 1.8 114.3 mm × 76.1 mm 6.0 1.8 5 × 4 3.0 125 100 0.9 6 × 4 6.0 150 100 1.8 5 4.5 125 1.4 165.1 mm × 4 6.0 100 1.8 8 × 6 7.3 200 150 2.2 219.1 mm × 165.1 mm 7.3 2.23 10 × 8 8.7 273 219.1 2.65 Size Equiv. Pipe Length Nominal Size Inches/mm Sm. Dia. Feet/m 1 × 2 2.7 25 50 0.8 1 1 × 2 1.9 40 50 0.6 2 × 2 1 1.0 50 65 0.3 76.1 mm 1.0 0.3 3 3.5 80 1.1 4 3.0 100 0.9 2 1 × 3 2.5 65 80 0.8 4 3.0 100 0.9 76.1 mm × 88.9 mm 2.5 0.8 114.3 mm 3.0 0.9 3 × 4 2.5 80 100 0.8 4 × 5 3.3 100 125 1.0 6 4.6 150 1.4 165.1 mm 4.6 1.4 5 × 6 2.3 125 150 0.7 6 × 8 6.0 150 200 1.8 165.1 mm × 219.1 mm 5.4 1.65 8 × 10 6.3 219.1 273 19.2 HEAD LOSS The head loss across Style 750 Reducing coupling is very small and is essentially the same as for standard short body reducing pipe fittings. Equivalent lengths of standard weight steel pipe are shown in the tables. All data is based on water flowing at ambient temperature. FLOW REDUCING FLOW EXPANDING 06.08_3 Reducing Coupling STYLE 750 06.08 CARBON STEEL PIPE – GROOVED COUPLINGS www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2007 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA. REV_I Vail Fire & Emergency Services 07/10/17 WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details. This product shall be manufactured by Victaulic or to Victaulic specifications. All products to be installed in accordance with current Victaulic installation/assembly instructions. Victaulic reserves the right to change product specifications, designs and standard equipment without notice and without incurring obligations. NOTE Reference should always be made to the I-100 Victaulic Field Installation Handbook for the product you are installing. Handbooks are included with each shipment of Victaulic products for complete installation and assembly data, and are available in PDF format on our website at www.victaulic.com. INSTALLATION WCAS-6UPKD7 06.08 Reducing Coupling STYLE 750 CARBON STEEL PIPE – GROOVED COUPLINGS 06.08 For complete contact information, visit www.victaulic.com 06.08 1536 REV I UPDATED 6/2008 VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2007 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA. Vail Fire & Emergency Services 07/10/17 Project InformatIon: aPProval StamP: Project: Date: Phone: Architect / Engineer: Contractor: Address: Notes 1: Notes 2: Gruvlok Couplings, Fittings, Flanges, Clamps Rev. 06.09.06-006 ® For the latest UL/ULC Listed and FM Approved pressure ratings, versus pipe schedule, go to www.anvilstar.com or contact your local AnvilStar representative Submittal Sheet Material SpecificationS gaSketS: Materials Properties as designated in accordance with ASTM D-2000 Grade “E” EPDM (Green color code) -40°F to 150°F (Service Temperature Range) (-40°C to 66°C) Recommended for water service, diluted acids, alkalies solutions, salts, oil-free air and many chemical services not involving hydrocarbons, oils or gases. NOT FOR USE WITH HYDROCARBONS. Other________________________________________________ HouSing: Ductile Iron conforming to ASTM A-536, Grade 65-45-12. u-Bolt & nutS: Plated U-bolt conforming to ASTM A-307 with plated hex nuts conforming to ASTM A-563. coatingS: Plain Other (Specify): ___________ For other Coating requirements contact an AnvilStar Representative. luBrication: Standard Gruvlok Gruvlok Xtreme™ (Required for dry pipe systems and freezer applications.) Other (Specify): ___________ The Gruvlok Fig. 7044 Branch outlet is for direct connection of sprinkler heads and drop nipples. Just cut a hole, saddle up and fasten it with the U-bolt. The branch outlet provides an economical, quick, and easy outlet at any location along a pipe. Specially engineered to conform to the pipe o.D., the Fig. 7044 provides a leak tight reliable seal in both positive pressure and vacuum conditions. Ductile iron housings with Grade e gasket and carbon steel U-bolt (3⁄" dia.) with flanged nuts. The maximum working pressure for all sizes is 7 PSI (2. bar). 7044 Branch Outlet PAGe oF 2 For Listing/Approval Details and Limitations visit our Web Site www.anvilintl.com or contact an Anvil®/AnvilStar Sales Representative. Print... Return Next Page undefined undefined undefined undefined undefined undefined undefined undefined Vail Fire & Emergency Services 07/10/17 SMITH-COOPER INTERNATIONAL" · TOLL FREE 1-800-766-0076 · FAX (323) 890-4456 · www.smithcooper.com 147 COOPLET" Weld Outlets & Adapter Nipples Vail Fire & Emergency Services 07/10/17 SMITH-COOPER INTERNATIONAL" · TOLL FREE 1-800-766-0076 · FAX (323) 890-4456 · www.smithcooper.com 148 PIPE NAME Manufacturer Dyna-Thread߰,"Central-Thread߰,"XL߰","XL-II߰","Dyna-Flow߰," Super"40߰,"Super-Flo߰,"TL߰,"Central"7"߰,"BLT"߰ Allied"Tube"and"Conduit"Corp. Eddylite߰,"Eddy"Flow߰,"Eddy"Thread"40߰ Bull"Moose"Tube"Co. Gal-7߰ IDOD"Systems"Co. EZ-Flow߰ Northwest"Pipe"Company WLS߰,"Mega"Flow߰,"Mega-Thread߰,"MLT߰,"GL߰ Wheatland"Tube"Company Steady"Flow߰,"Steady"Thread߰ Welded"Tube"Corp. Fire-Flo߰,"Ez-Thread߰ Youngstown"Tube"Co. Tex-Flow߰ Tex-"Tube"International Fire"Line"Flow߰,"Rapid"Thread߰,"Rapid-Thread"Light߰ Western"International"Forest"Products"Inc. COOPLET߰"Weld"Outlets"are"UL"Listed"and"FM"Approved"for" use"on"Sch"10,"Sch"40"and"the"following"sprinkler"pipes Weld Outlet Speci#cations · "Branded"COOPLET߰"Weld"Outlets"are"UL"Listed"and"FM"Approved"at"300"psi · COOPLET߰"Weld"Outlets"(Threaded)"conform"to"ASTM"A106,"ASME"B1.20.1 · COOPLET߰"Grooved"Weld"Outlets"are"made"from"Sch."40"Pipe · COOPLET߰"Grooved"Weld"Outlets"size"on"size"are"UL"Listed"Only · All"Grooves"are"cut"grooved"are"A53,"AWWA"C606"(cut"grooved"speci#cations"on"page"60) COOPLET" Weld Outlets & Adapter Nipples · COOPLET߰"Adapter"Nipples"conform"to"ASTM"A106,"ASME"B1.20.1,"ASME"B36.10"and" AWWA"C606 · All"Grooves"are"cut"grooved"(cut"grooved"speci#cations"on"page"60) Adapter Nipple Speci#cations Vail Fire & Emergency Services 07/10/17 SMITH-COOPER INTERNATIONAL" · TOLL FREE 1-800-766-0076 · FAX (323) 890-4456 · www.smithcooper.com C O O P L E T S߰ $ Size IN Pipe Run Size Part Number A IN C IN Packing Weight LB Inner Master 1/2 1"to"1-1/2 61FT1004010 1.063 0.750 50 400 0.1 1/2 2"to"2-1/2 61FT1004020 1.063 0.750 50 400 0.1 1/2 3"to"8 61FT1004030 1.063 0.750 50 400 0.1 3/4 1"to"1-1/2 61FT1006010 1.125 0.875 50 300 0.2 3/4 2"to"2-1/2 61FT1006020 1.125 0.875 50 300 0.2 3/4 2-1/2 61FT1006024 1.125 0.875 50 300 0.2 3/4 3"to"8 61FT1006030 1.125 0.875 50 300 0.2 1 1-1/4"to"1-1/2 61FT1010012 1.250 1.125 50 200 0.2 1 2"to"2-1/2 61FT1010020 1.250 1.125 50 200 0.2 1 2-1/2 61FT1010024 1.250 1.125 50 200 0.2 1 3"to"4 61FT1010030 1.250 1.125 50 200 0.2 1 5"to"8 61FT1010060 1.250 1.125 50 200 0.2 1-1/4 1-1/2 61FT1012014 1.375 1.500 70 140 0.3 1-1/4 2 61FT1012020 1.375 1.500 70 140 0.3 1-1/4 2-1/2 61FT1012024 1.375 1.500 70 140 0.3 1-1/4 3"to"4 61FT1012030 1.375 1.500 70 140 0.3 1-1/4 5"to"8 61FT1012060 1.375 1.500 70 140 0.3 1-1/2 2 61FT1014020 1.625 1.625 50 100 0.5 1-1/2 2-1/2 61FT1014024 1.625 1.625 50 100 0.5 1-1/2 3 61FT1014030 1.625 1.625 50 100 0.5 1-1/2 4"to"5 61FT1014040 1.625 1.625 50 100 0.5 1-1/2 6"to"8 61FT1014060 1.625 1.625 50 100 0.5 2 2-1/2 61FT1020024 1.750 2.000 25 50 0.8 2 3 61FT1020030 1.750 2.000 25 50 0.8 2 4"to"5 61FT1020040 1.750 2.000 25 50 0.8 2 6"to"8 61FT1020060 1.750 2.000 25 50 0.8 2-1/2 3 61FT1024030 2.215 2.500 15 30 1.4 2-1/2 4 61FT1024040 2.215 2.500 15 30 1.4 2-1/2 6 61FT1024060 2.215 2.500 15 30 1.4 2-1/2 8 61FT1024080 2.215 2.500 15 30 1.4 3 4 61FT1030040 2.500 3.000 8 16 2.4 3 6 61FT1030060 2.500 3.000 8 16 2.3 3 8 61FT1030080 2.500 3.000 8 16 2.3 4 6 61FT1040060 3.000 4.000 4 8 4.1 4 8 61FT1040080 3.000 4.000 4 8 4.0 Fig. 61FT1 ± Threaded Weld Outlet COOPLET" Weld Outlets - 300$ UL/FM & Vail Fire & Emergency Services 07/10/17 SMITH-COOPER INTERNATIONAL" · TOLL FREE 1-800-766-0076 · FAX (323) 890-4456 · www.smithcooper.com C O O P L E T S߰ Size IN Pipe Run Size Part Number A IN C IN Packing Weight LB Inner Master 1-1/4 1-1/2 61CG1012014 3.00 1.38 40 80 0.5 1-1/4" 2 61CG1012020 3.00 1.38 40 80 0.5 1-1/4 2-1/2 61CG1012024 3.00 1.38 40 80 0.5 1-1/4 3 61CG1012030 3.00 1.38 40 80 0.5 1-1/4 4"to"5 61CG1012040 3.00 1.38 40 80 0.5 1-1/4 6"to"8 61CG1012060 3.00 1.38 40 80 0.5 1-1/2 2 61CG1014020 3.00 1.61 25 50 0.6 1-1/2 2-1/2 61CG1014024 3.00 1.61 25 50 0.6 1-1/2 3 61CG1014030 3.00 1.61 25 50 0.6 1-1/2 4"to"5 61CG1014040 3.00 1.61 25 50 0.6 1-1/2 6"to"8 61CG1014060 3.00 1.61 25 50 0.6 2 2-1/2 61CG1020024 3.00 2.00 16 32 0.8 2" 3 61CG1020030 3.00 2.00 16 32 0.8 2 4"to"5 61CG1020040 3.00 2.00 16 32 0.8 2 6 61CG1020060 3.00 2.00 16 32 0.8 2 8 61CG1020080 3.00 2.00 16 32 0.8 2-1/2 3 61CG1024030 3.00 2.50 12 24 1.3 2-1/2 4"to"5 61CG1024040 3.00 2.50 12 24 1.3 2-1/2 6 61CG1024060 3.00 2.50 12 24 1.3 2-1/2 8 61CG1024080 3.00 2.50 12 24 1.3 3 4 61CG1030040 3.00 3.00 6 12 1.8 3 6 61CG1030060 3.00 3.00 6 12 1.8 3 8 61CG1030080 3.00 3.00 6 12 1.7 4 6 61CG1040060 4.00 4.00 4 8 3.5 4 8 61CG1040080 4.00 4.00 4 8 3.4 6 8 61CG1060080 4.00 6.00 - 2 6.5 COOPLET" Weld Outlets - 300$ UL/FM Fig. 61CG1 ± Grooved Weld Outlet $ & Size IN Pipe Run Size Part Number A IN C IN Packing Weight LB Inner Master 1-1/4 1-1/4 61CG1012012 3.00 1.38 40 80 0.5 1-1/2 1-1/2 61CG1014014 3.00 1.61 25 50 0.6 2 2 61CG1020020 3.00 2.00 16 32 0.8 2-1/2 2-1/2 61CG1024024 3.00 2.50 12 24 1.3 3 3 61CG1030030 3.00 3.00 6 12 1.8 4 4 61CG1040040 4.00 4.00 4 8 3.5 6 6 61CG1060060 4.00 6.00 - 2 6.5 8 8 61CG1080080 4.00 8.00 - 2 11.6 Fig. 61CG1* ± Grooved Weld Outlet (size on size) *Size on Size Grooved Weld Outlets are UL Listed Only Note: All Grooves are Cut Grooved (Cut grooved specifications on page 60). Vail Fire & Emergency Services 07/10/17 Vail Fire & Emergency Services 07/10/17 Vail Fire & Emergency Services 07/10/17 NIBCO INC. WORLD HEADQUARTERS • 1516 MIDDLEBURY ST. • ELKHART, IN 46516-4740 • USA • PH: 1.800.234.0227 TECH SERVICES PH: 1.888.446.4226 • FAX: 1.888.336.4226 • INTERNATIONAL OFFICE PH: +1.574.295.3327 • FAX: +1.574.295.3455 www.nibco.com 6 AHEAD OF THE FLOW® www.nibco.com Brass Ball Valves Two-Piece Body • Full Port • Blowout-Proof Stem • PTFE Seats ¹⁄₄"-2" 600 PSI/41߰4 Bar Non-Shock Cold Working Pressure 2¹⁄₂"-4" 400 PSI/27߰6 Bar Non-Shock Cold Working Pressure T-FP-600A Threaded MATERIAL LIST PART SPECIFICATION 1߰ Body Forged Brass2 CU > 57% 2߰ End Cap Forged Brass2 CU > 57% 3߰ Ball Seat PTFE 4߰ Ball Brass, Chrome Plated 5߰ Stem Brass 6߰ O-Ring (Stem Seal)* Fluorocarbon (FKM) 7߰ Stem Packing PTFE 8߰ Packing Nut Brass 9߰ Lever Handle1 Steel, Plated 10߰ Lock Washer* Stainless Steel 11߰ Handle Nut1 Stainless Steel Note: * Parts 6 and 10 are applicable of S-FP-600A only߰ 1 Due to Standard Approvals, Lever Handles and Nuts are not interchangeable between Solder and Threaded߰ 2 For Material Certification, contact NIBCO Technical Services߰ DIMENSIONS—WEIGHTS—QUANTITIES Dimensions T-FP-600A S-FP-600A T-FP-600A S-FP-600A T-FP-600A S-FP-600A Port Size A A B B C C D T-FP-600A S-FP-600A T-FP-600A S-FP-600N In߰ mm߰ In߰ mm߰ In߰ mm߰ In߰ mm߰ In߰ mm߰ In߰ mm߰ In߰ mm߰ In߰ mm߰ Lbs߰ Kg߰ Lbs߰ Kg߰ Ctn߰ Qty߰ Ctn߰ Qty߰ Z\v 8 1߰76 45 — — 1߰73 44 — — 3߰54 90 — — ߰39 10 ߰33 ߰15 — — 18 — C\, 10 1߰76 45 1߰75 44 1߰73 44 1߰58 40 3߰54 90 3߰78 96 ߰39 10 ߰30 ߰14 ߰38 ߰17 18 18 Z\x 15 2߰05 52 2߰01 51 1߰92 49 1߰78 45 3߰54 90 3߰78 96 ߰59 15 ߰44 ߰20 ߰40 ߰18 18 18 C\v 20 2߰36 60 2߰74 70 2߰09 53 2߰13 54 3߰78 96 3߰98 101 ߰75 19 ߰66 ߰30 ߰67 ߰30 12 12 1 25 2߰76 70 3߰35 85 2߰56 65 2߰52 64 4߰53 115 4߰41 112 ߰98 25 1߰10 ߰50 1߰12 ߰51 6 6 1Z\v 32 3߰31 84 3߰78 96 2߰95 75 2߰65 67 4߰53 115 5߰04 128 1߰26 32 1߰57 ߰71 1߰49 ߰67 4 4 1Z\x 40 3߰66 93 4߰42 112 3߰35 85 3߰12 79 5߰51 140 6߰22 158 1߰57 40 2߰40 1߰09 2߰38 1߰08 2 2 2 50 4߰18 106 5߰34 136 3߰68 93 3߰41 87 5߰51 140 6߰22 158 1߰97 50 3߰37 1߰53 3߰62 1߰64 2 2 2Z\x 65 5߰38 137 6߰28 160 4߰76 121 4߰76 121 8߰66 220 8߰66 220 2߰56 65 7߰60 3߰45 6߰36 2߰88 3 3 3 75 6߰04 153 7߰15 182 5߰08 129 5߰08 129 8߰66 220 8߰66 220 2߰95 75 9߰36 4߰24 8߰32 3߰77 2 2 4 100 7߰39 188 — — 5߰87 149 — — 9߰61 244 — — 3߰89 99 16߰85 7߰64 — — 1 — S-FP-600A C x C T-FP-600A NPT x NPT S-FP-600A Solder Revised 1/1/2014 CSA CERTIFIED TO ASME B16߰44 AND CR91-002 (THREADED Z\v"-4") • UL LISTED (THREADED Z\v"-4") • FM APPROVED (THREADED Z\v"-2") Threaded CSA (Z\v" - 4"): • CR91-002: Z\x psig, 2 psig, and 5 psig (these are specific approved categories) • ASME B13߰44: 125 psig (maximum) • Temperature is -4° F to 194° F Threaded FM (1/4" - 2"): • 175wwp Threaded UL, Gas and Oil (Z\v" - 4"): • YQNZ, Compressed Gas Shutoff Valves: 250 psi • YRBX, Flammable Liquid Shutoff Valves: 250 psi • YRPV, Gas Shutoff Valves: 250 psi • YSDT, LP-Gas Shutoff Valves: 250 psi • MHKZ, Manual Valves: 250 psi NOT FOR USE WITH POTABLE DRINKING WATER APPLICATIONS AFTER JANUARy 3, 2014߰ NOT FOR USE WITH POTABLE DRINKING WATER APPLICATIONS AFTER JANUARy 3, 2014߰ Vail Fire & Emergency Services 07/10/17 mirage® standard and Qr concealed pendent sprinkler vk462 and hp sprinkler vk463 (k5.6) technical data January 27, 2012 the viking corporation, 210 n industrial park drive, hastings mi 49058 telephone: 269-945-9501 technical services: 877-384-5464 Fax: 269-818-1680 email: techsvcs@vikingcorp.com 1. description Viking Mirage® Standard and Quick Response Concealed Pendent Sprinkler VK462 and HP Sprinkler VK463 are thermosensitive glass-bulb spray sprinklers designed for installation on concealed pipe systems where the appearance of a smooth ceiling is desired. The sprinkler is pre-assembled with a threaded adapter for installation with a low-pro- file cover assembly that provides up to ½” (12.7 mm) of vertical adjustment. The two- piece design allows installation and testing of the sprinkler prior to installation of the cover plate. The “push-on”, “thread-off” design of the concealed cover plate assembly allows easy installation of the cover plate after the system has been tested and the ceiling finish has been applied. The cover assembly can be removed and reinstalled, allowing temporary removal of ceiling panels without taking the sprinkler system out of service or removing the sprinkler. 2. listings and approvals cUlus listed: Category VNIV Fm approval: Class 2015 nYc approved: MEA 89-92-E, Volume 32 vds approved: Certificate G4080021 lpcB approved: Ref. No. 096e/12 ce certified: Standard EN 12259-1, EC-certificate of conformity 0832-CPD-2032 Refer to Approval Chart 1 on page 54c and Design Criteria on page 54d for cULus Listing requirements, and refer to Approval Chart 2 and Design Criteria on page 54e for FM Approval requirements that must be followed. 3. technical data Specifications: Available since 2006. Minimum Operating Pressure: 7 psi (0.5 bar)* maximum Working pressure: sprinkler vk463 is rated for use with water working pressures ranging from the minimum 7 psi (0.5 bar) up to 250 psi (17.2 bar) for high-pressure systems. high-pressure (hp) sprinklers can be identified by locating “250” stamped on the deflector. sprinkler vk462 is rated to a maximum 175 psi (12 bar) wwp. Factory tested hydrostatically to 500 psi (34.5 bar) Thread size: 1/2” (15 mm) NPT Nominal K-Factor: 5.6 U.S. (80.6 metric†) Glass-bulb fluid temperature rated to -65°F (-55°C) Patents Pending *cULus Listing, FM Approval, and NFPA 13 installs require a minimum of 7 psi (0.5 bar). The minimumoperatingpressureforLPC�andCEinimum operating pressure for LPC� and CE Approvals ONLY is 5 psi (0.35 bar). †Metric K-factor measurement shown is when pressure is measured in �ar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0. material standards: Sprinkler �ody: �rass UNS-C84400 Deflector: Copper UNS-C19500 for Sprinkler VK462 Phosphor �ronze UNS-C51000 for Sprinkler VK463 Deflector Pins: Stainless Steel Alloy �ulb: Glass, nominal 3 mm diameter Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400 �utton: �rass UNS-C36000 Screws: 18-8 Stainless Steel �elleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with Teflon Tape Yoke: Phosphor �ronze UNS-C51000 Cover Adapter: Cold Rolled Steel UNS-G10080, Finish: Clear Chromate over Zinc Plating Form No. F_103005 Replaces page 54a-f, dated April 8, 2011. (Revised VdS Approval.) viking technical data may be found on the viking corporation’s Web site at http://www.vikinggroupinc.com. the Web site may include a more recent edition of this technical data page. Sprinkler 54a Vail Fire & Emergency Services 07/10/17 technical data January 27, 2012 the viking corporation, 210 n industrial park drive, hastings mi 49058 telephone: 269-945-9501 technical services: 877-384-5464 Fax: 269-818-1680 email: techsvcs@vikingcorp.com mirage® standard and Qr concealed pendent sprinkler vk462 and hp sprinkler vk463 (k5.6) cover assembly materials: Cover: Copper UNS-C11000 �ase: �rass UNS-C26000 or UNS-C26800 Springs: Nickel Alloy Solder: Eutectic ordering information: (Also refer to the current Viking price list.) Viking Mirage® Standard and Quick Response Concealed Pendent Sprinklers and Cover Plate Assemblies must be ordered separately: sprinkler: �ase Part No. 13503A or HP �ase Part No. 13667A Specify sprinkler temperature rating by adding the appropriate suffix for the temperature rating to the base part number: Temperature Suffix: 155 °F (68 °C) = �, 175 °F (79 °C) = D, 200 °F (93 °C) = E For example, sprinkler VK463 with a 155 °F (68 °C) temperature rating = 13667A�. cover plate assembly: �ase Part No. 13504 (2-3/4” diameter), �ase Part No. 13642 (3-5/16“ diameter), or �ase Part No. 15394 (square cover plate, 3-5/16” diameter) Specify finish and temperature rating of the cover plate assembly by adding the appropriate suffixes for the finish and the cover temperature rating to the base part number: Finish Suffix: Polished Chrome = F, �rushed Chrome = F-/�, �right �rass = �, Antique �rass = �-/A, �rushed �rass = �-/�, �rushed Copper = E-/�, Painted White = M-/W, Painted Ivory = M-/I, Painted �lack = M-/� Temperature Suffix: 135 °F (57 °C) UL (139 °F (59 °C) FM and LPC�) = A, 165 °F (74 °C) = C For example, cover 13504 with a Polished Chrome finish and a 165 °F (74 °C) temperature rating = 13504FC. Note: Square cover plate 15394 cULus Listing is for the 135 °F (57 °C) temperature rated cover plate only. Refer to the Approval Chart. available Finishes and temperature ratings: Refer to Table 1. accessories: (Also refer to the “Sprinkler Accessories” section of the Viking data book.) sprinkler Wrenches**: A. Heavy Duty Wrench Part No. 14047W/� (available since 2006), or �. Head Cabinet Wrench Part No. 14031*** (available since 2006) C. Optional Concealed Cover Plate Installer Tool Part No. 14412 for cover 13504, or Part No. 14867 for the large diameter cover (available since 2007) **Requires a ½” ratchet (not available from Viking). ***Optional for removal of the protective cap. Ideal for sprinkler cabinets. sprinkler cabinet: Part No. 01731A (available since 1971) 4. installation Refer to appropriate NFPA Installation Standards. 5. operation During fire conditions, when the temperature around the sprinkler approaches its operating temperature, the cover plate detaches. Continued heating of the exposed sprinkler causes the heat-sensitive liquid in the glass bulb to expand and the bulb to shatter, releasing the yoke, pip-cap and sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern to extinguish or control the fire. 6. inspections, tests and maintenance Refer to NFPA 25 for Inspection, Testing and Maintenance requirements. 7. availaBilitY Viking Sprinklers VK462 and VK463 are available through a network of domestic and international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation. 8. gUarantee For details of warranty, refer to Viking’s current list price schedule or contact Viking directly. Sprinkler 54b Vail Fire & Emergency Services 07/10/17 mirage® standard and Qr concealed pendent sprinkler vk462 and hp sprinkler vk463 (k5.6) technical data January 27, 2012 the viking corporation, 210 n industrial park drive, hastings mi 49058 telephone: 269-945-9501 technical services: 877-384-5464 Fax: 269-818-1680 email: techsvcs@vikingcorp.com taBle 1: availaBle sprinkler temperatUre ratings and Finishes sprinkler temperature classification sprinkler nominal temperature rating1 maximum ambient ceiling temperature2 temperature rating of cover assembly (required) Bulb color Ordinary 155 °F (68° C) 100 °F (38 °C) 135 °F (57 °C) cULus 139 °F (59 °C) FM and LPC� Red Intermediate 175 °F (79 °C) 150 °F (65 °C) 165 °F (74 °C) Yellow Intermediate 200 °F (93 °C) 150 °F (65 °C) 165 °F (74 °C) Green cover plate Finishes: Polished Chrome, �rushed Chrome, �right �rass, Antique �rass, �rushed �rass, �rushed Copper, Painted White, Painted Ivory, or Painted �lack Footnotes 1 The sprinkler temperature rating is stamped on the sprinkler deflector. 2 �ased on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction. Refer to specific installation standards. approval chart 1 (Ul) mirage® concealed pendent sprinklers vk462 and vk463 sprinkler Base part no.1 sin npt thread size nominal k-Factor maximum Water Working pressure listings and approvals4 (refer also to design criteria on page 54d.) inch mm U.s. metric2 cUlus5 nYc vds7 lpcB standard response applications 13503A VK462 1/2” 15 5.6 80.6 175 psi (12 bar) -- -- AY1, CZ1 AY1, �Z1 AY1, CZ18 Quick response applications 13503A VK462 1/2” 15 5.6 80.6 175 psi (12 bar) AV1, �X1 AV1, �W16 -- -- -- 13667A VK463 1/2” 15 5.6 80.6 250 psi (17.2 bar)3 AV1, �X1 AV1, �W16 -- -- -- sprinkler temperature ratings A - 155 °F (68 °C) � - 175 °F (79 °C) and 200 °F (93 °C) C - 200 °F (93 °C) cover plate assembly temperature ratings9 V - 135°F(57°C)cULusListedcover13504135 °F (57 °C) cULus Listed cover 135041, 136421 (large diam- eter), or 153941 (square cover plate) W - 165 °F (74 °C) cover 135041 or 136421 (large diameter) X - 165°F(74°C)cover13504165 °F (74 °C) cover 135041, or 136421 (large diameter) Y - 135 °F (57 °C) cover 135041 LPCB Approved as 139 °F (59 °C) Z - 165 °F (74 °C) cover 135041 cover plate assembly Finishes10 1 - Polished Chrome, �rushed Chrome, �right �rass, Antique �rass, �rushed �rass, �rushed Copper, Painted White, Painted Ivory, or Painted �lack Footnotes 1 Part number shown is the base part number. For complete part number, refer to current Viking price list schedule. 2 Metric K-factor measurement shown is when pressure is measured in �ar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0. 3 The Water Working Pressure rating is stamped on the deflector. 4 This chart shows the listings and approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer for any additional approvals. 5 Listed by Underwriter’s Laboratories for use in the U.S. and Canada. 6 Accepted for use, City of New York Department of �uildings, MEA Number 89-92-E, Vol. 32. 7 VdS Approved, standards VdS 2344:2005-12, VdS 2100-25:2008-01, and EN 12259-1:1999 + A1:2001 + A2:2004 + A3:2006, Certificate G4080021. 8 Certified, Standard EN 12259-1, EC-certificate of conformity 0832-CPD-2032. 9 The 135/139 °F cover has an orange label. The 165 °F (74 °C) cover has a white label. 10Painted finish consists of Polyester �aked Enamel. Other paint colors are available on request with the same listings as the standard paint colors. Listings and approvals apply for any paint manufacturer. Contact Viking for additional information. note: Custom colors are indicated on a label inside the cover assembly. Refer to Figure 1. Sprinkler 54c Vail Fire & Emergency Services 07/10/17 technical data January 27, 2012 the viking corporation, 210 n industrial park drive, hastings mi 49058 telephone: 269-945-9501 technical services: 877-384-5464 Fax: 269-818-1680 email: techsvcs@vikingcorp.com mirage® standard and Qr concealed pendent sprinkler vk462 and hp sprinkler vk463 (k5.6) Sprinkler 54d Figure 1: identification of custom paint color for concealed covers Figure 2: square cover assembly 15394 design criteria - Ul (Also refer to Approval Chart 1 on page 54c.) cUlus listing requirements: Mirage® Concealed Pendent Sprinklers VK462 and VK463 are cULus Listed as quick response for installation in accordance with the latest edition of NFPA 13 for standard coverage pendent spray sprinklers as indicated below. For hazard occupancies up to and including Ordinary Hazard, Group II. Protection areas and maximum spacing shall be in accordance with the tables provided in NFPA 13. Maximum spacing allowed is 15 ft. (4.6 m). Minimum spacing allowed is 6 ft. (1.8 m) unless baffles are installed in accordance with NFPA 13. Minimum distance from walls is 4 in. (102 mm). Maximum distance from walls shall be no more than one-half of the allowable distance between sprinklers. The distance shall be measured perpendicular to the wall. The sprinkler obstruction rules contained in NFPA 13 for standard coverage pendent spray sprinklers must be followed. note:concealedsprinklersmustbeinstalledinneutralornegativepressureplenumsonly.ote: concealed sprinklers mustbeinstalledinneutralornegativepressureplenumsonly.ust be installed in neutral or negative pressure plenums only. • • • • • • vds approval requirements: a) The sprinkler can be installed in a concrete ceiling (massive ceiling) or in a false ceiling made of light materials. b) This sprinkler is deflector fixed type and can be only activated by heat. The housing is not tight. c) Follow installation guidelines of current standards, CEA4001VdS and EN12845. These sprinklers can only be installed in LH and OH occupan- cies, except in OH4. notes: Due to the design the sprinkler type ‘Domed-CCP’ shall not be installed in false ceilings in which the false ceiling space is protected by a water extinguishing system. Due to the design the sprinkler type ‘Domed-CCP’ shall not be installed in false ceilings in which during a fire the pressure above the false ceiling may be assumed to be higher than the pressure below the false ceiling. The criterion for the dropping of the cover relevant for this approval is heat. Steps of installation: Prepare the sprinkler key. Remove the plastic cover. Hold the sprinkler with the wrench and fasten it. Replace the plastic cover and do not remove until the cover is installed. 1. 2. 3. 4. important: always refer to Bulletin Form no. F_091699 - care and handling of sprinklers. also refer to page sr1-3 or Qr1-3 for general care, installation, and maintenance information. viking sprinklers are to be installed in accordance with the latest edition of viking technical data, the appropriate standards of nFpa, lpcB, apsad, vds or other similar organizations, and also with the provisions of governmental codes, ordinances, and stan- dards, whenever applicable. Vail Fire & Emergency Services 07/10/17 mirage® standard and Qr concealed pendent sprinkler vk462 and hp sprinkler vk463 (k5.6) technical data January 27, 2012 the viking corporation, 210 n industrial park drive, hastings mi 49058 telephone: 269-945-9501 technical services: 877-384-5464 Fax: 269-818-1680 email: techsvcs@vikingcorp.com Sprinkler 54e design criteria - Fm (Also refer to Approval Chart 2 above.) Fm approval requirements: Viking Concealed Pendent Sprinkler VK462 is FM Approved as a standard response non-storage concealed pendent sprinkler as indicated in the FM Approval Guide. For specific application and installation requirements, reference the latest applicable FM Loss Prevention Data Sheets (including Data Sheet 2-0). FM Global Loss Prevention Data Sheets contain guidelines relating to, but not limited to: minimum water supply requirements, hydraulic design, ceiling slope and obstructions, minimum and maximum allowable spacing, and deflector distance below the ceiling. note: the Fm installation guidelines may differ from cUlus and/or nFpa criteria. important: always refer to Bulletin Form no. F_091699 - care and handling of sprinklers. also refer to page sr1-3 for general care, installation, and maintenance information. viking sprinklers are to be installed in ac- cordance with the latest edition of viking technical data, the appropriate standards of nFpa, Fm global, lpcB, apsad, vds or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. approval chart 2 (Fm) mirage® standard response concealed pendent sprinkler vk462 sprinkler Base part no.1 sin npt thread size nominal k-Factor maximum Water Working pressure Fm approvals3 (refer also to design criteria below.) inch mm U.s. metric2 13503A VK462 1/2” 15 5.6 80.6 175 psi (12 bar) AW1, �X1 sprinkler temperature ratings A - 155 °F (68 °C) � - 175 °F (79 °C) and 200 °F (93 °C) cover plate assembly temperature ratings4 W - 139°F(59°C)cover13504139 °F (59 °C) cover 135041, 136421 (large diameter), or 153941 (square cover plate) X - 165°F(74°C)cover13504165 °F (74 °C) cover 135041, 136421 (large diameter), or 153941 (square cover plate) cover plate assembly Finishes5 1 - Polished Chrome, �rushed Chrome, �right �rass, Antique �rass, �rushed �rass, �rushed Copper, Painted White, Painted Ivory, or Painted �lack Footnotes 1 Part number shown is the base part number. For complete part number, refer to current Viking price list schedule. 2 Metric K-factor measurement shown is when pressure is measured in �ar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0. 3 This chart shows the FM Approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer for any additional approvals. 4 The 139 °F (59 °C) cover has an orange label. The 165 °F (74 °C) cover has a white label. 5 Painted finish consists of Polyester �aked Enamel. Otherpaintcolorsareavailableonrequestwiththesamelistingsasthestandardpaintcolors.Other paint colors are available on request with the same listings as the standard paint colors. Listings and approvals apply for any paint manufacturer. Contact Viking for additional information. note: Custom colors are indicated on a label inside the cover assembly. Refer to Figure 1. Vail Fire & Emergency Services 07/10/17 technical data January 27, 2012 the viking corporation, 210 n industrial park drive, hastings mi 49058 telephone: 269-945-9501 technical services: 877-384-5464 Fax: 269-818-1680 email: techsvcs@vikingcorp.com mirage® standard and Qr concealed pendent sprinkler vk462 and hp sprinkler vk463 (k5.6) Form No. F_103005 Sprinkler 54f Figure 4: sprinkler dimensions and cover installation Figure 3: sprinkler installation and correct Use of Wrenches Replaces page 54a-f, dated April 8, 2011. (Revised VdS Approval.) Vail Fire & Emergency Services 07/10/17 microfast® quick response pendent sprinkler Vk302 (k5.6) tecHnical data Form No. F_033314 17.06.02 Rev 17.1 Page 1 of 6 the Viking corporation, 210 n industrial park drive, Hastings mi 49058 telephone: 269-945-9501 technical services: 877-384-5464 fax: 269-818-1680 email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com 1. description The Viking Microfast® Quick Response Pendent Sprinkler VK302 is a small thermo- sensitive glass bulb spray sprinkler available with various finishes and temperature ratings to meet design requirements. The special Polyester and Electroless Nickel PTFE (ENT) coatings can be used in decorative applications where colors are desired. In addition, these coatings have been investigated for installation in corrosive atmos- pheres and are listed/approved as corrosion resistant as indicated in the Approval Charts. (Note: fm Global approves ent finish as corrosion resistant. FM Global has no approval classification for Polyester coatings as corrosion resistant.) 2. listinGs and approVals culus listed: Category VNIV fm approved: Class Series 2000 Vds approved: Certificates G414009 and G414010 lpcB approved ce certified: Standard EN 12259-1:1999, A3:2006 Certificate of Constancy of Performance 0832-CPR-S0021 cccf approved: Approved by the China Certification Center for Fire Products (CCCF) Refer to Approval Chart 1 and Design Criteria cULus Listing requirements, and refer to Approval Chart 2 and Design Criteria for FM Approval requirements that must be followed. 3. tecHnical data Specifications: Minimum Operating Pressure: 7 psi (0.5 bar) Rated to 175 psi (12 bar) water working pressure Factory tested hydrostatically to 500 psi (34.5 bar) Thread size: 1/2” NPT, 15 mm BSP Nominal K-Factor: 5.6 U.S. (80.6 metric**) Glass-bulb fluid temperature rated to -65 °F (-55 °C) Overall Length: 2-1/4” (58 mm) *cULus Listing, FM Approval, and NFPA 13 installs require a minimum of 7 psi (0.5 bar). The minimum operating pressure for LPCB and CE Approvals ONLY is 5 psi (0.35 bar). material standards: Frame Casting: Brass UNS-C84400 or QM Brass Deflector: Phosphor Bronze UNS-C51000 or Copper UNS-C19500 Bulb: Glass, nominal 3 mm diameter Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape Screw: Brass UNS-C36000 Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400 For Polyester Coated Sprinklers: Belleville Spring-Exposed For ENT Coated Sprinklers: Belleville Spring-Exposed, Screw and Pipcap - ENT plated. ordering information: (Also refer to the current Viking price list.) Order Quick Response Pendent Sprinklers by first adding the appropriate suffix for the sprinkler finish and then the appropriate suffix for the temperature rating to the sprinkler base part number. Finish Suffix: Brass = A, Chrome = F, White Polyester = M-/W, Black Polyester = M-/B, and ENT = JN Temperature Suffix: 135 °F (57 °C) = A, 155 °F (68 °C) = B, 175 °F (79 °C) = D, 200 °F (93 °C) = E, 286 °F (141 °C) = G For example, sprinkler VK302 with a Brass finish and a 155 °F (68 °C) temperature rating = Part No. 12979AB available finishes and temperature ratings: Refer to Table 1. accessories: (Also refer to the current Viking price list.) Replaces Form No. F_033314 Rev 16.4 (Added PN for CCCF approved sprinkler.) Vail Fire & Emergency Services 07/10/17 microfast® quick response pendent sprinkler Vk302 (k5.6) tecHnical data Form No. F_033314 17.06.02 Rev 17.1 Page 2 of 6 the Viking corporation, 210 n industrial park drive, Hastings mi 49058 telephone: 269-945-9501 technical services: 877-384-5464 fax: 269-818-1680 email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com sprinkler Wrenches: A. Standard Wrench: Part No. 10896W/B (available since 2000). B. Wrench for Recessed Pendent Sprinklers: Part No. 13655W/B** (available since 2006) C. Optional Protective Sprinkler Cap Remover/Escutcheon Installer Tool*** Part No. 15915 (available since 2010) **A ½” ratchet is required (not available from Viking). ***Allows use from the floor by attaching a length of 1” diameter CPVC tubing to the tool. Ideal for sprinkler cabinets. Refer to Bulletin F_051808. sprinkler cabinets: A. Six-head capacity: Part No. 01724A (available since 1971) B. Twelve-head capacity: Part No. 01725A (available since 1971) 4. installation Refer to appropriate NFPA Installation Standards. 5. operation During fire conditions, the heat-sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the pip cap and sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern to extinguish or control the fire. 6. inspections, tests and maintenance Refer to NFPA 25 for Inspection, Testing and Maintenance requirements. 7. aVailaBility The Viking Microfast® Quick Response Pendent Sprinkler VK302 is available through a network of domestic and international dis- tributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation. 8. Guarantee For details of warranty, refer to Viking’s current list price schedule or contact Viking directly. figure 1: standard sprinkler Wrench 10896W/B protective sprinkler cap Wrench flat protective sprinkler clip Vail Fire & Emergency Services 07/10/17 microfast® quick response pendent sprinkler Vk302 (k5.6) tecHnical data Form No. F_033314 17.06.02 Rev 17.1 Page 3 of 6 the Viking corporation, 210 n industrial park drive, Hastings mi 49058 telephone: 269-945-9501 technical services: 877-384-5464 fax: 269-818-1680 email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com taBle 1: aVailaBle sprinkler temperature ratinGs and finisHes sprinkler temperature classification sprinkler nominal temperature rating1 maximum ambient ceiling temperature2 Bul b color Ordinary 135 °F (57 °C) 100 °F (38 °C) Orange Ordinary 155 °F (68 °C) 100 °F (38 °C) Red Intermediate 175 °F (79 °C) 150 °F (65 °C) Yellow Intermediate 200 °F (93 °C) 150 °F (65 °C) Green High 286 °F (141 °C) 225 °F (107 °C) Blue sprinkler finishes: Brass, Chrome, White Polyester, Black Polyester, and ENT corrosion-resistant coatings3: White Polyester, and Black Polyester. ENT in all temperature ratings except 135 °F (57 °C) footnotes 1 The sprinkler temperature rating is stamped on the deflector. 2 Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction. Refer to specific installation standards. 3 The corrosion-resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Charts. These tests cannot and do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are com- patible with or suitable for the proposed environment. For automatic sprinklers, the coatings indicated are applied to the exposed exterior surfaces only. Note that the spring is exposed on sprinklers with Polyester and ENT coatings. For ENT coated automatic sprinklers, the waterway is coated. figure 2: Wrench 13655W/B for recessed pendent sprinklers carefully slide the wrench sideways around the protective cap, ensuring engagement with the sprinkler wrench flats sprinkler wrench 13655W/B** for recessed pendent sprinklers ** a 1/2” ratchet is required (not available from Viking) Vail Fire & Emergency Services 07/10/17 microfast® quick response pendent sprinkler Vk302 (k5.6) tecHnical data Form No. F_033314 17.06.02 Rev 17.1 Page 4 of 6 the Viking corporation, 210 n industrial park drive, Hastings mi 49058 telephone: 269-945-9501 technical services: 877-384-5464 fax: 269-818-1680 email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com approval chart 1 (ul) the Viking microfast® quick response pendent sprinkler Vk302 maximum 175 psi (12 Bar) WWp Base part number1 sin sprinkler style thre ad size nominal k-f actor overall length listings and approvals3 (refer also to design criteria.) npt Bsp u.s. metric2 inches mm culus4 Vds lpcB 7 12979 VK302 Pendent 1/2” 15 mm 5.6 80.6 2-1/4 58 A1Z, B1Y, D2, C2X A1 A1Z, B1Y D1Z, C1Y -- -- 19780 VK302 Pendent 1/2” -- 5.6 80.6 2-1/4 58 -- -- -- -- -- D3 21354 VK302 Pendent -- 15 mm 5.6 80.6 2-1/4 58 -- -- -- -- -- D3 NOTICE - Product Below - Limited Availability (Contact Local Viking Office) 06662B VK302 Pendent 1/2” 15 mm 5.6 80.6 2-1/4 58 A1Z, B1Y, D2, C2X -- -- -- -- -- 18021 VK302 Pendent 1/2” 15 mm 5.6 80.6 2-1/4 58 A1X, B1Y A1 A1X, B1Y D1X, C1Y8 D1X, C1Y9 -- approved temperature ratings A - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), 286 °F (141 °C) B - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), and 200 °F (93 °C) C - 155 °F (68 °C), 175 °F (79 °C), and 200 °F (93 °C) D - 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), 286 °F (141 °C) approved finishes 1 - Brass, Chrome, White Polyester5,6, Black Polyes- ter5,6 2 - ENT5 3 - Chrome approved escutcheons X - Standard surface-mounted escutcheon or the Viking Micromatic® Model E-1 Recessed Escutcheon Y - Standard surface-mounted escutcheon or the Viking Microfast® Model F-1 Adjustable Escutcheon, or recessed with the Viking Micro- matic® Model E-1, E-2, or E-3 Recessed Escutcheon Z - Standard surface-mounted escutcheon or the Viking Microfast® Model F-1 Adjustable Escutcheon footnotes 1 Base part number shown. For complete part number, refer to Viking’s current price schedule. 2 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0. 3 This table shows the listings and approvals available at the time of printing. Other approvals may be in process. 4 Listed by Underwriters Laboratories Inc. for use in the U.S. and Canada. 5 cULus Listed as corrosion-resistant. 6 Other colors are available on request with the same Listings and Approvals as the standard colors. 7 CE Certified, Standard EN 12259-1, EC-certificate of conformity 0832-CPD-2001. 8 CE Certified, Standard EN 12259-1, EC-certificates of conformity 0832-CPD-2001 and 0832-CPD-2003. 9 MED Certified, Standard EN 12259-1, EC-certificates of conformity 0832-MED-1003 and 0832-MED-1008. desiGn criteria - ul (Also refer to Approval Chart 1 above.) culus listing requirements: The Viking Microfast® Quick Response Pendent Sprinkler VK302 is cULus Listed as indicated in the Approval Chart for installation in accordance with the latest edition of NFPA 13 for standard spray sprinklers. • Designed for use in Light and Ordinary occupancies. • The sprinkler installation rules contained in NFPA 13 for standard spray pendent sprinklers must be followed. important: always refer to Bulletin form no. f_091699 - care and Handling of sprinklers. also refer to form no. f_080614 for general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the latest edition of Viking technical data, the appropriate standards of nfpa, lpcB, apsad, Vds or other similar organizations, and also with the provisions of governmental codes, ordinances, and stan- dards, whenever applicable. Vail Fire & Emergency Services 07/10/17 microfast® quick response pendent sprinkler Vk302 (k5.6) tecHnical data Form No. F_033314 17.06.02 Rev 17.1 Page 5 of 6 the Viking corporation, 210 n industrial park drive, Hastings mi 49058 telephone: 269-945-9501 technical services: 877-384-5464 fax: 269-818-1680 email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com approval chart 2 (fm) the Viking microfast® quick response pendent sprinkler Vk302 maximum 175 psi (12 Bar) WWp Base part number1 sin spr inkler style thread size nominal k-factor overall length fm approvals3 (refer also to design criteria.) npt Bsp u.s. metric2 inches mm 12979 VK302 Pendent 1/2” 15 mm 5.6 80.6 2-1/4 58 A1Z, B1Y, D2X, C2 NOTICE - Product Below - Limited Availability (Contact Local Viking Office) 06662B VK302 Pendent 1/2” 15 mm 5.6 80.6 2-1/4 58 A1Z, B1Y, D2X, C2 18021 VK302 Pendent 1/2” 15 mm 5.6 80.6 2-1/4 58 A1Z, B1Y approved temperature ratings A - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), 286 °F (141 °C) B - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), and 200 °F (93 °C) C - 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), 286 °F (141 °C) D - 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C) approved finishes 1 - Brass, Chrome, White Polyester4, and Black Polyester4 2 - ENT5 approved escutcheons X - Standard surface-mounted escutcheon or the Viking Micromatic® Model E-1 Recessed Escutcheon Y - Standard surface-mounted escutcheon or the Viking Microfast® Model F-1 Adjustable Escutcheon, or recessed with the Viking Micromatic® Model E-1 or E-2 Recessed Escutcheon Z - Standard surface-mounted escutcheon or the Viking Microfast® Model F-1 Adjustable Escutcheon footnotes 1 Base part number shown. For complete part number, refer to Viking’s current price schedule. 2 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0. 3 This table shows the FM Approvals available at the time of printing. Other approvals may be in process. 4 Other colors are available on request with the same Approvals as the standard colors. 5 FM approved as corrosion resistant. desiGn criteria - fm (Also refer to Approval Chart 2 above.) fm approval requirements: The Viking Microfast® Quick Response Pendent Sprinkler VK302 is FM Approved as quick response non-storage pendent sprinklers as indicated in the FM Approval Guide. For specific application and installation requirements, reference the latest applicable FM Loss Prevention Data Sheets (including Data Sheet 2-0). FM Global Loss Prevention Data Sheets contain guidelines relating to, but not limited to: minimum water supply requirements, hydraulic design, ceiling slope and obstructions, minimum and maximum allowable spacing, and deflector distance below the ceiling. note: the fm installation guidelines may differ from culus and/or nfpa criteria. important: always refer to Bulletin form no. f_091699 - care and Handling of sprinklers. also refer to page f_080614 for general care, installation, and maintenance information. Viking sprinklers are to be installed in ac- cordance with the latest edition of Viking technical data, the appropriate standards of nfpa, fm Global, lpcB, apsad, Vds or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. Vail Fire & Emergency Services 07/10/17 microfast® quick response pendent sprinkler Vk302 (k5.6) tecHnical data Form No. F_033314 17.06.02 Rev 17.1 Page 6 of 6 the Viking corporation, 210 n industrial park drive, Hastings mi 49058 telephone: 269-945-9501 technical services: 877-384-5464 fax: 269-818-1680 email: techsvcs@vikingcorp.com Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com figure 4: sprinkler dimensions with the model e-1 and e-2 recessed escutcheons figure 3: sprinkler dimensions with a standard escutcheon and the model f-1 adjustable escutcheon 1/2” (15 mm) npt 2-1/4” (57 mm) 1-3/4” (45 mm) 2” (51 mm) max. 2-1/8” (54 mm) 1-1/2” (38 mm) min. installed with a standard 1/8” surface-mounted escutcheon installed with a microfast model f-1 adjustable escutcheon ceiling opening size: 2-5/16” (59 mm) minimum 2-1/2” (64 mm) maximum note: at maximum, adapter is exposed 1/2” (13 mm) from face of ceiling 1-3/4” (45 mm) max. 2-1/8” (54 mm) 1-1/8” (29 mm) min. 2”” (51 mm) max. 1-1/8” (29 mm) min. 2-1/8” (54 mm) ceiling opening size: 2-5/16” (59 mm) minimum 2-1/2” (64 mm) maximum installed with a model e-1 recessed escutcheon installed with a model e-2 thread-on recessed escutcheon Replaces Form No. F_033314 Rev 16.4 (Added PN for CCCF approved sprinkler.) Vail Fire & Emergency Services 07/10/17 MICROFAST® QUICK RESPONSE HORIZONTAL SIDEWALL SPRINKLER VK305 (K5.6) TECHNICAL DATA The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Page 1 of 6 Form No. F_060914 Rev 14.2 1. DESCRIPTION The Viking Microfast® Quick Response Horizontal Sidewall Sprinkler VK305 is a small thermosensitive glass bulb spray sprinkler available with various finishes and tempera- ture ratings to meet design requirements. The special Polyester and Electroless Nickel PTFE (ENT) coatings can be used in decorative applications where colors are de- sired. In addition, these coatings have been investigated for installation in corrosive atmospheres and are listed/approved as corrosion resistant as indicated in Approval Charts. 2. LISTINGS AND APPROVALS cULus Listed: Category VNIV FM Approved: Class 2020 Refer to Approval Chart 1 and Design Criteria for cULus Listing requirements, and refer to Approval Chart 2 and Design Criteria for FM Approval requirements that must be followed. 3. TECHNICAL DATA Specifications: Minimum Operating Pressure: 7 psi (0.5 bar) Rated to 175 psi (12 bar) water working pressure Factory tested hydrostatically to 500 psi (34.5 bar) Nominal K-Factor: 5.6 U.S. (80.6 metric*) * Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0. Overall Length: 2-3/4” (68 mm) Material Standards: Frame Casting: Brass UNS-C84400 or QM Brass Deflector: Copper UNS-C19500 Bulb: Glass, nominal 3 mm diameter Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape Screw: Brass UNS-C36000 Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400 For Polyester Coated Sprinklers: Belleville Spring-Exposed For ENT Coated Sprinklers: Belleville Spring - Exposed, Screw and Pip cap - ENT plated. Ordering Information: (Also refer to the current Viking price list.) Order Viking Microfast® Quick Response Horizontal Sidewall Sprinkler VK305 by first adding the appropriate suffix for the sprin- kler finish and then the appropriate suffix for the temperature rating to the sprinkler base part number. Finish Suffix: Brass = A, Chrome = F, White Polyester = M-/W, Black Polyester = M-/B, and ENT = JN Temperature Suffix: 135 °F / 68 °C = A, 155 °F / 68 °C = B, 175 °F / 79 °C = D, 200 °F / 93 °C = E, and 286 °F / 141 °C = G For example, sprinkler 12997 with a Brass finish and a 155 °F / 68 °C temperature rating = Part No. 12997AB Available Finishes And Temperature Ratings: Refer to Table 1. Accessories: (Also refer to the “Sprinkler Accessories” section of the Viking data book.) Sprinkler Wrenches: A. Standard Wrench: Part No. 10896W/B (available since 2000). B. Wrench for recessed and/or wax coated sprinklers: Part No. 13655W/B** (available since 2006) **A ½” ratchet is required (not available from Viking). Sprinkler Cabinets: A. Six-head capacity: Part No. 01724A (available since 1971) B. Twelve-head capacity: Part No. 01725A (available since 1971) Viking Technical Data may be found on The Viking Corporation’s Web site at http://www.vikinggroupinc.com. The Web site may include a more recent edition of this Technical Data Page. (Added 12121) Vail Fire & Emergency Services 07/10/17 MICROFAST® QUICK RESPONSE HORIZONTAL SIDEWALL SPRINKLER VK305 (K5.6) TECHNICAL DATA The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Page 2 of 6 Form No. F_060914 Rev 14.2 4. INSTALLATION Refer to appropriate NFPA Installation Standards. 5. OPERATION During fire conditions, the heat-sensitive fusible link disengages, the pip cap and spring are released, and the waterway is opened. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern to extinguish or control the fire. 6. INSPECTIONS, TESTS AND MAINTENANCE Refer to NFPA 25 for Inspection, Testing and Maintenance requirements. 7. AVAILABILITY Viking Microfast® Quick Response Horizontal Sidewall Sprinkler VK305 is available through a network of domestic and interna- is available through a network of domestic and interna- tional distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation. 8. GUARANTEE For details of warranty, refer to Viking’s current list price schedule or contact Viking directly. Figure 1: Standard Sprinkler Wrench 10896W/B Wrench Flat Vail Fire & Emergency Services 07/10/17 MICROFAST® QUICK RESPONSE HORIZONTAL SIDEWALL SPRINKLER VK305 (K5.6) TECHNICAL DATA The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Page 3 of 6 Form No. F_060914 Rev 14.2 Figure 2: Wrench 13655W/B for Recessed Sprinklers Step 1: Carefully slide the wrench sideways around the deflector, ensuring en- gagement with the sprinkler wrench flats. Sprinkler wrench 13655W/B** must be used for installing wax coated sprinklers. ** A 1/2” ratchet is required (not available from Viking) Step 2: Carefully press the wrench onto the sprinkler wrench flats. TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES Sprinkler Temperature Classification Sprinkler Nominal Temperature Rating1 Maximum Ambient Ceiling Temperature2 Bulb Color Ordinary 135 °F (57 °C) 100 °F (38 °C) Orange Ordinary 155 °F (68 °C) 100 °F (38 °C) Red Intermediate 175 °F (79 °C) 150 °F (65 °C) Yellow Intermediate 200 °F (93 °C) 150 °F (65 °C) Green High 286 °F (141 °C) 225 °F (107 °C) Blue Sprinkler Finishes: Brass, Chrome, White Polyester, Black Polyester, and ENT Corrosion-Resistant Coatings3: White Polyester, Black Polyester, and ENT Footnotes 1 The sprinkler temperature rating is stamped on the deflector. 2 Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction. Refer to specific installation standards. 3 The corrosion-resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Charts. These tests cannot and do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are compat- ible with or suitable for the proposed environment. For automatic sprinklers, the coatings indicated are applied to the exposed exterior surfaces only. For ENT coated sprinklers, the waterway is coated. Note that the spring is exposed on sprinklers with Polyester, and ENT coatings. Vail Fire & Emergency Services 07/10/17 MICROFAST® QUICK RESPONSE HORIZONTAL SIDEWALL SPRINKLER VK305 (K5.6) TECHNICAL DATA The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Page 4 of 6 Form No. F_060914 Rev 14.2 Approval Chart 1 (UL) Microfast® Quick Response Horizontal Sidewall Sprinkler VK305 For Light or Ordinary Hazard Occupancies Maximum 175 PSI (12 Bar) WWP Deflector must be located 4” to 12” (102 mm to 305 mm) below the ceiling. Base Part Number1 SIN Sprinkler Style Thread Size Nominal K-Factor Overall Length Listings and Approvals3 (Refer also to Design Criteria on page 43x.) NPT BSP U.S. metric2 Inches mm cULus4 LPCB 12997 VK305 HSW 1/2” 15 mm 5.6 80.6 2-11/16 68 A1Y, B1X, C2W, D2Z -- -- -- NOTICE - Product Below - Limited Availability (Contact Local Viking Office) 12121 VK305 HSW 1/2” 15 mm 5.6 80.6 1-11/16 68 A1Y, B1X, C2W, D2Z -- -- -- Approved Temperature Ratings A - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), and 286 °F (141 °C) B - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), and 200 °F (93 °C) C - 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), and 286 °F (141 °C) D - 155 °F (68 °C), 175 °F (79 °C), and 200 °F (93 °C) Approved Finishes 1 - Brass, Chrome, White Poly-ester5,6, and Black Polyester5,6 2 - ENT5 Approved Escutcheons W - Installed with standard surface-mounted escutcheons X - Installed with standard surface-mounted escutcheons or the Viking Microfast® Model F-1 Adjustable Escutcheon, or recessed with the Viking Micromatic® Model E-1, E-2, or G-1 Recessed Escutcheon Y - Installed with standard surface-mounted escutcheons or the Viking Microfast® Model F-1 Adjustable Escutcheon Z - Installed with standard surface-mounted escutcheons or recessed with the Viking Micromatic Model E-1 Footnotes 1 Base part number shown. For complete part number, refer to Viking’s current price schedule. 2 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0. 3 This table shows the listings and approvals available at the time of printing. Other approvals may be in process. 4 Listed by Underwriters Laboratories Inc. for use in the U.S. and Canada. 5 cULus Listed as corrosion-resistant. 6 Other colors are available on request with the same Listings and Approvals as the standard colors. DESIGN CRITERIA - UL (Also refer to Approval Chart 1.) cULus Listing Requirements: Quick Response Horizontal Sprinkler VK305 is cULus Listed as indicated in Approval Chart 1 for installation in accordance with the latest edition of NFPA 13 for sidewall standard spray sprinklers. • Designed for use in Light and Ordinary Hazard occupancies. • Locate with the deflector 4” to 12“ (102 mm to 305 mm) below the ceiling. • Protection areas and maximum spacing shall be in accordance with the tables provided in NFPA 13. • Minimum spacing allowed is 6 ft. (1.8 m). • Align the top of the deflector parallel with the ceiling. • Locate no less than 4” (102 mm) from end walls. • Maximum distance from end walls shall be no more than one-half of the allowable distance between sprinklers. The distance shall be measured perpendicular to the wall. • The sprinkler installation and obstruction rules contained in NFPA 13 for sidewall standard spray sprinklers must be followed. IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page QR1-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in accor- dance with the latest edition of Viking technical data, the appropriate standards of NFPA, LPCB, APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. Vail Fire & Emergency Services 07/10/17 MICROFAST® QUICK RESPONSE HORIZONTAL SIDEWALL SPRINKLER VK305 (K5.6) TECHNICAL DATA The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Page 5 of 6 Form No. F_060914 Rev 14.2 Approval Chart 2 (FM) Quick Response Sidewall Sprinklers Maximum 175 PSI WWP Base Part Number1 SIN Thread Size Nominal K-Factor Overall Length FM Approvals3,4 (Refer also to Design Criteria below.) NPT BSP U.S. metric2 Inches mm 12997 VK305 1/2” 15 mm 5.6 80.6 2-11/16 68 A1Y, B1X NOTICE - Product Below - Limited Availability (Contact Local Viking Office) 12121 VK305 1/2” 15 mm 5.6 80.6 2-11/16 68 A1Y, B1X Approved Temperature Ratings A - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), and 286 °F (141 °C) B - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), and 200 °F (93 °C) Approved Finishes 1 - Brass Approved Escutcheons X - Installed with standard surface-mounted escutcheons or the Viking Microfast® Model F-1 Adjustable Escutcheon, or recessed with the Viking Micromatic® Model E-1, E-2, E-3, or G-1 Recessed Escutcheon Y - Installed with standard surface-mounted escutcheons or the Viking Microfast® Model F-1 Adjustable Escutcheon Footnotes 1 Base part number shown. For complete part number, refer to Viking’s current price schedule. 2 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0. 3 This table shows the FM Approvals available at the time of printing. Other approvals may be in process. 4 Viking vertical sidewall sprinklers may be installed pendent or upright. DESIGN CRITERIA - FM (Also refer to Approval Chart 2 above.) FM Approval Requirements: Horizontal Sidewall Sprinkler VK305 is FM Approved as a quick response Non-Storage sidewall sprinkler as indicated in the FM Approval Guide. For specific application and installation requirements, reference the latest applicable FM Loss Prevention Data Sheets (including Data Sheet 2-0). FM Global Loss Prevention Data Sheets contain guidelines relating to, but not limited to: minimum water supply requirements, hydraulic design, ceiling slope and obstructions, minimum and maximum allowable spacing, and deflector distance below the ceiling. NOTE: The FM installation guidelines may differ from cULus and/or NFPA criteria. IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page QR1-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in ac- cordance with the latest edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB, APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. Vail Fire & Emergency Services 07/10/17 MICROFAST® QUICK RESPONSE HORIZONTAL SIDEWALL SPRINKLER VK305 (K5.6) TECHNICAL DATA The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Page 6 of 6 Form No. F_060914 Rev 14.2 Figure 4: Sidewall Sprinkler VK305 Dimensions with the Model E-1 and E-2 Recessed Escutcheons (Added 12121) Figure 3: Sidewall Sprinkler Dimensions with a Standard Escutcheon and the Model F-1 Adjustable Escutcheon 2-3/4” (68 mm) 2-7/16” (62 mm) 1-7/8” (48 mm) Installed with a Standard 1/8” Surface-Mounted Escutcheon Installed with a Microfast Model F-1 Adjustable Escutcheon Wall Opening Size: 2-5/16” (58.7 mm) minimum 2-1/2” (63.5 mm) maximum 2-5/8” (67 mm) 2-1/8” (54 mm) 1-5/8” (41 mm) Installed with the Threaded Model E-2 Recessed Escutcheon Wall Opening Size: 2-5/16” (58.7 mm) minimum 2-1/2” (63.5 mm) maximum 2-1/8” (54 mm) 2-1/4” (57 mm) Maximum Minimum 2-1/8” (54 mm) 2-5/8” (67 mm) Maximum 1-3/4” (45 mm) Minimum Installed with the Micromatic Model E-1 Recessed Escutcheon Minimum Maximum Vail Fire & Emergency Services 07/10/17 microfast® and microfastHP® quick resPonse uPrigHt and conventional sPrinklers tecHnical data December 4, 2013 the viking corporation, 210 n industrial Park drive, Hastings mi 49058 telephone: 269-945-9501 technical services: 877-384-5464 fax: 269-818-1680 email: techsvcs@vikingcorp.com 1. descriPtion Viking Microfast® and MicrofastHP® Quick Response Upright and Conventional (Old Style) Sprinklers are small, thermosensitive, glass-bulb spray sprinklers available in several different finishes, temperature ratings, and K-Factors to meet design require- ments. The special Polyester, Polytetrafluoroethylene (PTFE), and Electroless Nickel PTFE (ENT) coatings can be used in decorative applications where colors are desired. In addition, these coatings have been investigated for installation in corrosive atmos- pheres and are listed/approved as corrosion resistant as indicated in the Approval Charts. (Note: fm global approves the ent coating as corrosion resistant. FM Global has no approval classification for PTFE and Polyester coatings as corrosion resistant.) 2. listings and aPProvals culus listed: Category VNIV fm approved: Classes 2002 and 2020 nYc approved: Calendar Number 219-76-SA and MEA 89-92-E, Volume 16 aBs certified: Certificate 04-HS407984B-PDA vds approved: Certificates G4060054, G4060056, G4880046, G4930039, and G4980020 lPc approved: Ref. No. 096e/03, TE30401, and TE30872 ce certified: Standard EN 12259-1, EC-certificate of conformity 0832-CPD-2001, 0832-CPD-2003, 0786-CPD-40131, 0786-CPD-40171, and 0786-CPD-40278 med certified: Standard EN 12259-1, EC-certificate of conformity 0832-MED-1003 and 0832-MED-1008 note: Other International approval certificates are available upon request. Refer to Approval Chart 1 and Design Criteria on pages 51c-d for cULus Listing requirements, and refer to Approval Chart 2 and Design Criteria on page 51e for FM Approval requirements that must be followed. 3. tecHnical data specifications: Available since 1987. Minimum Operating Pressure: 7 psi (0.5 bar)* maximum Working Pressure: sprinklers vk315 and vk340 are rated for use with water working pressures ranging from the minimum 7 psi (0.5 bar) up to 250 psi (17 bar) for high-pressure systems. High-pressure (HP) sprinklers can be identified by locating “250” stamped on the de- flector. all other Part nos. not mentioned above are rated to a maximum 175 psi (12 bar) wwp. Factory tested hydrostatically to 500 psi (34.5 bar) Testing: U.S.A. Patent No. 4,831,870 Thread size: Refer to the Approval Charts Nominal K-Factor: Refer to the Approval Charts Glass-bulb fluid temperature rated to -65 °F (-55 °C) Overall Length: Refer to the Approval Charts *cULus Listing, FM Approval, and NFPA 13 installs require a minimum of 7 psi (0.5 bar). The minimum operating pressure for LPCB and CE Approvals ONLY is 5 psi (0.35 bar). material standards: Frame Casting: Brass UNS-C84400 or QM Brass for Sprinklers 12978, 06766B, 07060, and 12281. Brass UNS-C84400 for all other sprinklers. Deflector: Brass UNS-C23000 or Copper UNS-C19500 for Sprinklers 12978, 06764B, and 12281. Copper UNS-C19500 for Sprinklers 06665B, 07060, and 14817. Brass UNS-C26000 for all other Sprinklers. Bushing (for Sprinklers 06719B, 06717B, and 12286): Brass UNS-C36000 Bulb: Glass, nominal 3 mm diameter Form No. F_080488 viking technical data may be found on the viking corporation’s Web site at http://www.vikinggroupinc.com. the Web site may include a more recent edition of this technical data Page. Sprinkler 51a Replaces page 51a-e, dated June 28, 2013. (Changed 06931 to VK3271) Vail Fire & Emergency Services 07/10/17 tecHnical data December 4, 2013 the viking corporation, 210 n industrial Park drive, Hastings mi 49058 telephone: 269-945-9501 technical services: 877-384-5464 fax: 269-818-1680 email: techsvcs@vikingcorp.com microfast® and microfastHP® quick resPonse uPrigHt and conventional sPrinklers Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape Screw: Brass UNS-C36000 Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400 For PTFE Coated Sprinklers: Belleville Spring-Exposed, Screw-Nickel Plated, Pip Cap-PTFE Coated For Polyester Coated Sprinklers: Belleville Spring-Exposed For ENT Coated Sprinklers: Belleville Spring-Exposed, Screw and Pipcap - ENT plated. ordering information: (Also refer to the current Viking price list.) Order Microfast® and MicrofastHP® Quick Response Upright and Conventional Sprinklers by first adding the appropriate suffix for the sprinkler finish and then the appropriate suffix for the temperature rating to the sprinkler base part number. Finish Suffix: Brass = A, Chrome = F, White Polyester = M-/W, Black Polyester = M-/B, and Black PTFE = N, ENT = JN Temperature Suffix (°F/°C): 135°/57° = A, 155°/68° = B, 175°/79° = D, 200°/93° = E, and 286°/141° = G For example, sprinkler VK300 with a 1/2” thread, Brass finish and a 155 °F/68 °C temperature rating = Part No. 12978AB available finishes and temperature ratings: Refer to Table 1. accessories: (Also refer to the “Sprinkler Accessories” section of the Viking data book.) sprinkler Wrench: Standard Wrench: Part No. 10896W/B (available since 2000) sprinkler cabinets: A. Six-head capacity: Part No. 01724A (available since 1971) B. Twelve-head capacity: Part No. 01725A (available since 1971) 4. installation Refer to appropriate NFPA Installation Standards. 5. oPeration During fire conditions, the heat-sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the pip cap and sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern to extinguish or control the fire. 6. insPections, tests and maintenance Refer to NFPA 25 for Inspection, Testing and Maintenance requirements. 7. availaBilitY The Viking Microfast® and MicrofastHP® Quick Response Upright and Conventional Sprinklers are available through a network of domestic and international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation. 8. guarantee For details of warranty, refer to Viking’s current list price schedule or contact Viking directly. Sprinkler 51b taBle 1: availaBle sPrinkler temPerature ratings and finisHes sprinkler temperature classification sprinkler nominal temperature rating1 maximum ambient ceiling temperature2 Bulb color Ordinary 135 °F (57 °C) 100 °F (38 °C) Orange Ordinary 155 °F (68 °C) 100 °F (38 °C) Red Intermediate 175 °F (79 °C) 150 °F (65 °C) Yellow Intermediate 200 °F (93 °C) 150 °F (65 °C) Green High 286 °F (141 °C) 225 °F (107 °C) Blue sprinkler finishes: Brass, Chrome, White Polyester, Black Polyester, Black PTFE, and ENT corrosion-resistant coatings3: White Polyester, Black Polyester, and Black PTFE. ENT in all temperature ratings except 135 °F (57 °C) footnotes 1 The sprinkler temperature rating is stamped on the deflector. 2 Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction. Refer to specific installation standards. 3 The corrosion-resistant coatings have passed the standard corrosion test required by the approving agencies indicated on pages 51c-e. These tests cannot and do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are compatible with or suitable for the proposed environment. For automatic sprinklers, the coatings indicated are applied to the exposed exterior surfaces only. Note that the spring is exposed on sprinklers with Polyester, ENT, and PTFE coatings. For ENT coated automatic sprinklers, the waterway is coated. Vail Fire & Emergency Services 07/10/17 microfast® and microfastHP® quick resPonse uPrigHt and conventional sPrinklers tecHnical data December 4, 2013 the viking corporation, 210 n industrial Park drive, Hastings mi 49058 telephone: 269-945-9501 technical services: 877-384-5464 fax: 269-818-1680 email: techsvcs@vikingcorp.com approval chart 1 (ul) microfast® and microfastHP® quick response upright and conventional sprinklers maximum 175 Psi (12 bar) WWP Base Part number1 sin thread size nominal k-factor overall length listings and approvals3 (refer also to design criteria on page 51d.) nPt BsP u.s. metric2 inches mm culus4 nYc8 vds lPcB upright-standard orifice 12978 VK300 1/2” 15 mm 5.6 80.6 2-3/16 56 A1, B4 See Footnote 7. -- -- -- -- 07060 VK345 -- 15 mm 5.6 80.6 2-3/16 56 -- -- A2 A2 B212 B215 conventional-standard orifice 06766B VK310 1/2” 15 mm 5.6 80.6 2-3/16 56 A2 A2 -- A2 B212 B215 upright-large orifice 06665B VK350 3/4” -- 8.0 115.2 2-5/16 59 A1, B4 A1 A2 A2 B212 -- 14817 VK350 -- 20 mm 8.0 115.2 2-5/16 59 A1, B4 A1 A2 A2 B212 -- 06764B16 VK350 1/2” 15 mm 8.0 115.2 2-5/16 59 A1, B4 A1 A2 -- A213 -- conventional-large orifice 06768B VK354 3/4” 20 mm 8.0 115.2 2-5/16 59 A1 A2 -- A2 B212 -- upright-small orifice11 06717B11 VK325 1/2” 15 mm 2.8 40.3 2-3/16 56 A1 A1 -- -- -- -- 06719B11 VK327 1/2” 15 mm 4.2 57 2-3/16 56 A1 A1 -- -- -- -- 06931B11 VK3271 -- 10 mm 4.2 57 2-3/16 56 -- -- A2 -- C314 -- maximum 250 Psi (17 bar) WWP upright-standard orifice Base Part number1 sin thread size nominal k-factor overall length listings and approvals3 (refer also to design criteria on page 51d.) nPt BsP u.s. metric2 inches mm culus4 nYc9 vds lPcB 12281 VK315 1/2” 15 mm 5.6 80.6 2-3/16 56 A1 A1 -- -- -- -- upright-small orifice10 1228611 VK340 1/2” 15 mm 2.8 40.3 2-3/16 56 A1 A1 -- -- -- -- approved temperature ratings A - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), and 286 °F (141°C) B - 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), and 286 °F (141°C) C - 155 °F (68 °C) approved finishes 1 - Brass, Chrome, White Polyester5,6, Black Polyester5,6, and Black PTFE5 2 - Brass, Chrome, White Polyester5,6, and Black Polyester5,6 3 - Brass and Chrome 4 - ENT5 footnotes 1 Base part number is shown. For complete part number, refer to Viking’s current price schedule. 2 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0. 3 This table shows the listings and approvals available at the time of printing. Check with the manufacturer for any additional approvals. 4 Listed by Underwriters Laboratories Inc. for use in the U.S. and Canada. 5 cULus Listed as corrosion resistant. 6 Other colors are available on request with the same Listings and Approvals as the standard colors. 7 Meets New York City requirements, effective July 1, 2008. 8 Accepted for use, City of New York Board of Standards and Appeals, Calendar Number 219-76-SA. 9 Accepted for use, City of New York Department of Buildings, MEA 89-92-E, Vol. 16. 10 Listings and Approvals limited to Light Hazard Occupancies where allowed by the installation standards being applied, with hydraulically calculated wet systems only. exception: 4.2K sprinklers may be installed on hydraulically calculated dry pipe systems where piping is corrosion resistant or internally galvanized. 11The sprinkler orifice is bushed. 12 Certified, Standard EN 12259-1, EC-certificate of conformity 0832-CPD-2001 and 0832-CPD-2003. 13 Certified, Standard EN 12259-1, EC-certificate of conformity 0786-CPD-40278. 14 Certified, Standard EN 12259-1, EC-certificate of conformity 0786-CPD-40131. 15 MED Certified, Standard EN 12259-1, EC-certificate of conformity 0832-MED-1003 and 0832-MED-1008. 16 The 1/2” NPT Large Orifice Sprinkler is Listed and Approved for retrofit only Sprinkler 51c Vail Fire & Emergency Services 07/10/17 tecHnical data December 4, 2013 the viking corporation, 210 n industrial Park drive, Hastings mi 49058 telephone: 269-945-9501 technical services: 877-384-5464 fax: 269-818-1680 email: techsvcs@vikingcorp.com microfast® and microfastHP® quick resPonse uPrigHt and conventional sPrinklers Sprinkler 51d figure 1: standard sprinkler Wrench 10896W/B design criteria - ul (Also refer to Approval Chart 1 on page 51c) culus listing requirements: Microfast® and MicrofastHP® Quick Response Upright and Conventional Sprinklers are cULus Listed as indicated in Approval Chart 1 for installation in accordance with the latest edition of NFPA 13 for standard spray sprinklers, or old style (conventional) sprinklers. Designed for use in Light and Ordinary Hazard occupancies (exception: small orifice sprinklers are limited to Light Hazard where allowed by the installation standards being applied, with hydraulically calculated wet systems only). The sprinkler installation rules contained in NFPA 13 for standard spray upright sprinklers must be followed. For conventional sprinklers, refer to the installation guidelines for old style (conventional) sprinklers. • • imPortant: always refer to Bulletin form no. f_091699 - care and Handling of sprinklers. also refer to page qr1-3 for general care, installation, and maintenance information. viking sprinklers are to be installed in accor- dance with the latest edition of viking technical data, the appropriate standards of nfPa, lPcB, aPsad, vds or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. Vail Fire & Emergency Services 07/10/17 microfast® and microfastHP® quick resPonse uPrigHt and conventional sPrinklers tecHnical data December 4, 2013 the viking corporation, 210 n industrial Park drive, Hastings mi 49058 telephone: 269-945-9501 technical services: 877-384-5464 fax: 269-818-1680 email: techsvcs@vikingcorp.com Sprinkler 51e design criteria - fm (Also refer to Approval Chart 2 above.) fm approval requirements: The sprinklers indicated in Approval Chart 2 are FM Approved as quick response non-storage upright sprinklers as indicated in the FM Approval Guide. For specific application and installation requirements, reference the latest applicable FM Loss Prevention Data Sheets (including Data Sheet 2-0). FM Global Loss Prevention Data Sheets contain guidelines relating to, but not limited to: minimum water supply requirements, hydraulic design, ceiling slope and obstructions, minimum and maximum allowable spacing, and deflector distance below the ceiling. note: the fm installation guidelines may differ from culus and/or nfPa criteria. imPortant: always refer to Bulletin form no. f_091699 - care and Handling of sprinklers. also refer to page qr1-3 for general care, installation, and maintenance information. viking sprinklers are to be installed in ac- cordance with the latest edition of viking technical data, the appropriate standards of nfPa, fm global, lPcB, aPsad, vds or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. approval chart 2 (fm) microfast® quick response upright sprinklers maximum 175 Psi (12 bar) WWP Base Part number1 sin thread size nominal k-factor overall length fm approvals3 (refer also to design criteria below.) nPt BsP u.s. metric2 inches mm standard orifice 12978 VK300 1/2” 15 mm 5.6 80.6 2-3/16 56 A2, B3 07060 VK345 -- 15 mm 5.6 80.6 2-3/16 56 A2 large orifice 06665B VK350 3/4” -- 8.0 115.2 2-5/16 59 A2, B3 14817 VK350 -- 20 mm 8.0 115.2 2-5/16 59 A2, B3 06764B7 VK350 1/2” 15 mm 8.0 115.2 2-5/16 59 A2, B3 small orifice4 06717B6 VK325 1/2” 15 mm 2.8 40.3 2-3/16 56 A1 approved temperature ratings A - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), and 286 °F (141°C) B - 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), and 286 °F (141°C) approved finishes 1 - Brass and Chrome 2 - Brass, Chrome, White Polyester5, and Black Polyester5 3 - ENT8 footnotes 1 Base part number is shown. For complete part number, refer to Viking’s current price schedule. 2 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0. 3 This table shows the FM Approvals available at the time of printing. Check with the manufacturer for any additional approvals. 4 FM Approved as quick response non-storage pendent sprinklers. For specific application and installation requirements, reference the latest appli- cable FM Loss Prevention Data Sheets (including Data Sheet 2-0). 5 Other colors are available on request with the same Approvals as the standard colors. 6 The sprinkler orifice is bushed. 7 The 1/2” NPT Large Orifice Sprinkler is Listed and Approved for retrofit only 8 FM approved as corrosion resistant. Vail Fire & Emergency Services 07/10/17