Loading...
HomeMy WebLinkAboutF17-0035_1487BuffehrCreek-ScopeLetter_1501279560.pdf274 CENTER DRIVE GLENWOOD SPRINGS, CO 81601 (970) 618-3294 (970) 945-9504 FAX Fire Protection Systems Design · Fabrication · Installation Commercial · Industrial · Residential · Institutional Special Hazards · High Tech · Defense · Hangars Retrofit · Service · Inspection · Maintenance July 21st, 2017 Mike Vaughan Vail Fire And Emergency Services 2399 North Frontage Road West Vail, CO 81657 Re: Wallace Residence 1487 Buffehr Creek Road Vail, CO. 81657 Mike, This letter is to explain the scope of work on the above mentioned project. The existing fire sprinkler system is to be modified to allow for remodel. Elevator; Re-locate Feed Riser from lower level to main level on inside Stair wall to adjacent wall. Re-rout piping to heads under lower stair. Kitchen; Re-locate Feed Riser closest to stairs to adjacent wall. This Riser feeds 4) ¾” Branch lines. Kitchen / Dining; Re-locate Feed Riser from existing wall into new column. This Riser feeds 3) ¾” Branch lines. Living; Re-locate Feed Riser from existing wall into new column. This Riser feeds 2) ¾” Branch lines. All existing pipe is Copper. New pipe will be Copper to match. New pipe will be same size as existing. Some ¾” lines may be upsized to 1” for simplification of material needed. Changes will not impact the hydraulic demand of the system and will be made per NFPA 13D and Vail Fire requirements. Additional re-model work is going on, but no Sprinkler Head locations will need to be modified. If you have any questions or need additional information please contact me at your convenience. Thanks, Steve Allen Project Manager Cell Phone: 720-219-0574 Approved for changes Vail Fire & Emergency Services 07/28/17