HomeMy WebLinkAboutPEC160009_E2.1_1465853400.pdf1 2 3 A B C A.1 B.1 C.1 1.1 2.1 3.1 4 D 1. EXTERIOR LIGHTING SHALL BE CONTROLLED BY LIGHTING CONTROL PANEL (LCP). NOTES: LIGHTING CONTROL PANEL (LCP). RE: A/E1.0 FOR LIGHTING CONTROL PANEL DIAGRAM. PROVIDE WATTSTOPPER ULTRASONIC LINE VOLTAGE CEILING SENSOR. PROVIDE WATTSTOPPER PASSIVE INFRARED WALL SWITCH. PROVIDE ELECTRICAL CONNECTION TO AUTOMATIC PLUMBING FIXTURES. PROVIDE 4-SQUARE JUNCTION BOX, WITH BLANK COVER, FOR FUTURE POSSIBLE BASEBOARD HEATER. PROVIDE 3/4" CONDUIT FROM JUNCTION BOX TO ELECTRICAL PANEL WITH PULL STRING. JUNCTION BOX FOR FUTURE HEAT CONTROL/THERMOSTAT. PROVIDE 1/2" RACEWAY, WITH PULL STRING TO HEATER LOCATION. FLAG NOTES: SCALE: RESTROOM ELECTRICAL PLAN 1/4" = 1'-0" PANEL 'P1' W1 W1 W1 W1 W2 W2 S1 S1 S1 S1 S1 LUMINAIRE SCHEDULE TYPE DESCRIPTION MOUNTING LUMENS LAMPS INPUT WATTS VOLT MANUFACTURER CATALOG NUMBER SPECIFIC NOTES QTY TYPE W1 4FT WALL MOUNTED LED VANDAL RESISTANT SURFACE FIXTURE, VERIFY FINISH WITH ARCHITECT SURFACE 2080 -- LED AS SUPPLIED, 3500K 30 UNV PHILIPS LPLS4L30-35K-UNV-F1 W2 2FT WALL MOUNTED LED VANDAL RESISTANT SURFACE FIXTURE, VERIFY FINISH WITH ARCHITECT SURFACE 2200 -- LED AS SUPPLIED, 3500K 30 UNV PHILIPS LPLS2L30-35K-UNV-F1 S1 5" ROUND, LOW PROFILE, SURFACE MOUNTED LED DOWNLIGHT SURFACE 650 -- LED AS SUPPLIED, 2700K 9.5 120 PHILIPS S5R827K7AL GENERAL NOTES: A. THE LUMINAIRE SCHEDULE CAN NOT BE USED INDEPENDENTLY OF THE DRAWINGS AND SPECIFICATIONS TO OBTAIN LUMINAIRE COSTS. THE INDIVIDUAL ESTABLISHING LUMINAIRE COSTS SHALL NOT QUOTE PRICING WITHOUT FIRST SEEING APPLICABLE ELECTRICAL DRAWINGS AND ELECTRICAL DIVISION SPECIFICATIONS. THE CONTRACTOR IS REPONSIBLE FOR PROVIDING NECESSARY DRAWINGS AND SPECIFICATIONS TO THE INDIVIDUAL QUOTING LUMINAIRE PRICING. B. REFER TO DRAWINGS FOR FIXTURES REQUIRING EMERGENCY BATTERY BACKUP OPTION (SHOWN BY HATCH IN/OVER SYMBOL). MINIMUM LIGHT OUTPUT FOR EM BALLAST SHALL BE 600 LUMENS. C. ALL FLUORESCENT LAMPS ARE TO BE 3500° KELVIN COLOR TEMPERATURE SPECIFIC NOTES: (1) (2) (3) (4) 1 1 OS OS 2 2 2 S O S O 3 3 3 MECHANICAL EQUIPMENT SCHEDULE MARK DESCRIPTION VOLT / PHASE HP WATTS FLA DISCONNECT/ FUSE SIZE FEEDER SPECIFIC NOTES BB-1 BASEBOARD HEATER 120/1 -- 500 4.2 1P MOTOR RATED SWITCH (2#12 & 1#12G) 3/4"C WH-1 INTANTANEOUS WATER HEATER 240/1 -- 13000 54 2P MOTOR RATED SWITCH (3#4 & 1#10G) 1"C GENERAL NOTES: A. SEE SPECIFICATIONS FOR ELECTRICAL DIVISION AND MECHANICAL DIVISION MOTOR STARTER COORDINATION. B. PROVIDE PHASE PROTECTION FOR ALL THREE PHASE MOTORS ABOVE 7-1/2 HP. C. PROVIDE ALL EXTERIOR DISCONNECTS WITH NEMA 3R RATING. D. WHEN EQUIPMENT IS LISTED WITH ONLY A HORSEPOWER RATING THE DISCONNECT AND FEEDER ARE SIZED PER THE N.E.C. SPECIFIC NOTES: (1) (2) (3) (4) BB 1 BB 1 WP WP +48" +48" +48" +48" WH 1 WH 1 J J J J 4 4 4 4 4 J 4 CONTROLLED BY LCP J J 5 5 5 6 6 6 J J C SHEET NUMBER PROJECT NUMBER: 1 5431 2 3 4 5 6 7 A B C D E C O P Y R I G H T D E S I G N W O R K S H O P, I N C. F 8 9 1 2 3 4 5 6 7 8 9 100% DESIGN DEVELOPMENT DOCUMENTS COPYRIGHT 2016 B ANZE G EAUDIN (970) 949-6108 (303) 278-3820 (970) 221-5691 (505) 323-9070 (307) 739-3944 Vail: Denver: Fort Collins: Albuquerque: Jackson: www.bgce.com DESIGN DATE # DESCRIPTION ISSUE DATE: REVIEWED: DRAWN: WORKSHOP REVISIONS REDEVELOPMENT 2900 MANNS RANCH ROAD VAIL, COLORADO W W W . D E S I G N W O R K S H O P . C O M Landscape Architecture  Land Planning Urban Design  Tourism Planning Facsimile (970) 920-1387 (970) 925-8354 Aspen, CO 81611 120 E. Main St. Asheville  Aspen  Austin  Beijing  Chicago  Denver  Dubai  Houston  Lake Tahoe  Los Angeles February 12, 2016 BOOTH CREEK PARK 1309 ELKHORN DRIVE. VAIL, COLORADO. 81657 970.479.2158 E2.1 RESTROOM ELECTRICAL PLAN BAS MAS PEC APPROVED 3/14/2016 12:00:00 AM